L.B. White COMBO-MCS User Manual

Page 1
Owner's Manual and Instructions
SmartBox™Controller
For Use with GUARDIAN®Electronic Ignition F orced Air Heaters
with Smart Sense
and Infraconic Manual or Spark Ignition Radiant Heaters
Automatic Variable Rate Heat
MODEL
COMBO-MCS
Patent Pending
Congratulations!
The SmartBox™incorporates the benefits from the most experienced manufacturer of agricultural animal confinement building heating products using state-of-the-art technology.
We,atL.B.White,thank you for your confidence in our products and welcome any suggestions or comments you may have...call us, toll-free, at 1-800-345-7200.
ATTENTION ALL USERS
The SmartBox™has been designed and developed by L.B.White Co. as a variable rate heat controller for managing heat to demand within the animal confinement facility. It works in conjuction with L.B.White Smart Sense™forced air and radiant heaters and an existing room controller with on/off capability.
150-28782
Page 2
Table of Contents
SECTION PAGE
GeneralInformation ...................................................................3
Features ............................................................................3
TechnicalSpecifications ...............................................................3
ComponentIdentification,PartNumber,andFunction.......................................4
WiringDiagram.......................................................................5
Locating and Mounting the SmartBox
SensorLocation ......................................................................6
Interconnection ......................................................................7
Connecting the Electrical Power Supply to the SmartBox
ConnectingPowertotheHeaters ....................................................7
Wiring from the SmartBox
Connecting the Building Controller Heating Contacts to the SmartBox™....................8
Wiring the SmartBox™toRadiantHeaters .............................................8
Set-up and Programming the SmartBox
TouchPadControlandDisplay.......................................................9
BasicRoomControlTypicalSet-Up ...................................................9
TemperatureControlParameters.....................................................9
A.ManualOverride ............................................................9
B.TemperatureCurve ..........................................................9
InitialStart-Up ...................................................................10
Initial SmartBox
HomeScreens...................................................................10
ManualModeorTemperatureCurveSelection ........................................10
SetClock .......................................................................11
TemperatureSensors ............................................................11
CalibratingTemperatureSensors ...................................................12
DefiningtheTemperatureCurve ....................................................13
Set-upofRoomControl ...........................................................13
Set-upofSystemTemperatureCurve ................................................13
ScreenDisplays..................................................................14
Maintenance/Cleaning ...............................................................15
ServiceInstructions ..................................................................15
Fuses ..........................................................................15
Relays..........................................................................16
TouchPadDisplay ................................................................16
Transformers ....................................................................16
ProgrammableController ..........................................................17
ForcedAirSignalConditioner .......................................................17
RadiantSignalConditioner ........................................................18
TroubleshootingandOperationSequence................................................19
WarrantyPolicy .....................................................................23
ReplacementPartsandService ........................................................23
Set-Up ..........................................................10
...................................................5
................................7
to the Forced Air Heater’s Smart Sense™GasControlValve.......7
.................................................9
2
Page 3
Forced Air
Radiant
General Information
This manual will instruct you in the installation and operation of the SmartBox™. Have a qualified installer review this manual with you so that you fully understand the controller and how it functions.
When calling for technical service assistance, or for other specific information, always have the model number and serial number available.
The SmartBox reducing fuel consumption and improving animal productivity and health. This configuration provides control of both forced air and radiant heaters.
The SmartBox temperature control of the forced air heaters. The SmartBox™operates the radiant heaters independent of the room controller
maintains precise temperature thereby
interfaces to the room controller for
Operator interface touch pad.
-- Sets manual operation
-- Allows setting the clock at initial set-up
-- Activates and operates sensors
-- Provides for installing and changing the temperature management curve.
Handles up to 10 temperature set points with up to
225 days per period.
-- Linearly ramps from one set point temperature to the next over the duration days for that period
Separate temperature control zones
-- Up to four temperature sensors for forced air heaters.
-- One separate sensor for radiant heaters
-- Zone 1 can handle two forced air heaters
-- Zone 2 interfaces with a proportional zone control
for either spark or manual ignition heaters.
-- Maximum capacity: 24, I-17 LP/NG radiant heaters.
-- Zone control #s: Manual ignition 28564
Spark Ignition 28580
Contact your local L. B. White distributor or the L. B. White Co., Inc. for assistance, or if you have any questions about the use of this product or its application.
The L. B. White Co., Inc. has a policy of continuous product improvement. It reserves the right to change specifications and design without notice.
Features
Heat Enable
-- Used with Zone 1 (forced air heaters) only.
-- Connected to the room controller in a manner to allow operation only when the room controller determines a need for heat.
-- Minimizes interference between the heating and ventilation systems.
Indicator Lights
-- Heat Zone On: Green Light
-- Sensor Failure: Red Light a. Identifies sensor malfunction. b. If one sensor fails in a zone controlled by
two sensors, the remaining sensor allows
continued operation.
-- Cycle Complete: Amber Light
Control Reset Switch
-- Allows the producer to reset the controller back to day 1 for the start of a new cycle.
-- Position the switch to OFF and then to ON to
reset.
Technical Specifications
SmartBox
Enclosure
Dimensions(LxWxHin.) 141/2x111/8x6
Inputs 120 /60 /1, 30 amps power required
Up to two 20k NTC temperature probes per zone
Two 25 amp 120 /60/1 relays for heater power
F
Outputs
Net weight (lbs.) 11.5
: 0-15 vdc control signal for the variable rate gas control valves; 500 mA.
NEMA -4X
: 24 VDC PWM Control Signal, 900 mA
3
Page 4
Component Identification, Part Number, and Function
Fuse for Forced Air heaters: 572812 Fuse for Incoming Power and Radiant Brooders: 572918
Fuse holder with 1/4 in. male tabs:572809 Fuse holder with 3/16 male tabs: 572808
Green
26392
Amber
572813
Red:(571333
Forced Air Heaters : 572771 Radiant Brooders : 572913
Control Reset Switch (570456)
Powers up the SmartBox™for heating zone and allows the producer to reset the control back to day 1 for start of new cycle. Position from On to Off, then back to On.
Fuses
Used for protection of the programmable controller and the variable rate gas control valves.
Fuse Holders
Secures the fuse into position within the electrical circuit.
Indicator Lights
: (
: (
) Indicates which heat zone is in operation
) Indicates heat cycle complete
) SmartBox™temperature sensor failure
Relays (572811)
Used for sending of power to the heaters in a specific heat zone.
Sensor (572815) Not Illustrated
Used for monitoring temperature within the confinement space. Interfaces to the programmable controller to allow operation of the Smart Sense™variable rate gas control valves.
Signal Conditioners
Used to process the electrical signal from the programmable controller for operation of the variable rate gas control valves.
Touch Pad / Display (572914)
Used for set up of the SmartBox™for system operation : temperature , heating days, etc
Programmable Controller (572917)
Micro-processor used for the operation of the SmartBox system and operation of the signal conditioners.
Transformers Used for reducing incoming 115 VAC to 24
VAC for powering of programmable controller and signal conditioners. Radiant Brooders (UPPER): 572912 Forced Air Heaters (LOWER): 570230
FIG. 1 FIG. 2
TOUCH PAD AND DISPLAY
RELAYS
TRANSFORMERS
PROGRAMMABLE CONTROLLER
FUSES
RADIANT FORCED AIR
SIGNAL CONDITIONERS
4
Page 5
Location
Mounting
Wiring Diagram
L
-- Locate in a corridor or control room on the wall adjacent to or close to the existing room controller. See Fig.3.
-- This area should be dry and not exposed to water washdown.
-- The temperature in this area must be between 32F and 104F.
FIG. 3
Locating and Mounting
-- Use mounting tabs and screws provided with the SmartBox™at all corners of the box back. See Fig.4.
-- Use proper hardware to secure the SmartBox the wall surface
-- Provide sufficient clearance to allow complete opening of the SmartBox™cover.
FIG. 4
to
5
Page 6
Sensor Location
Each SmartBox™ controls two zones of heat.:
-- Zone 1: Two forced air heaters
-- Zone 2: Radiant heaters
Use only the L.B.White SmartBox
sensors provided wi th th e SmartBox™, or o rde r repl ace men ts as needed. Do not use sensors from other controller syst e ms as thes e a re not com p a tibl e w i th the L.B.White SmartBox
.
See below for proper SmartBox™sensor location.
One SmartBox™sensor may be used for each zone of heat. However two or more sensors are used for optimum temperature management.
FIG. 5
FAN(S)
ROOM CONTROLLER
SmartBox™ SYSTEM DIAGRAM FORCED AIR AND RADIANT HEATERS
ZONE1
ZONE2 CYCLE SENSOR
RESET
120 VAC
POWER SUPPLY
SmartBox
ENABLE
GUARDIAN WITH Smart Sense
SmartBox™ SENSOR(S) LOCATED WITHIN 6 IN. OF
EXISTING ROOM SENSOR AND AT SAME HEIGHT
GUARDIAN
GUARDIAN WITH
w/ SMARTSENSE™
Smart Sense
ROOM CONTROL SENSORS
ZONE PANEL
RADIANT SENSOR
120 VAC
POWER SUPPLY
SmartBox™ SENSOR(S) LOCATED WITHIN 6 IN. OF
EXISTING ROOM SENSOR AND AT SAME HEIGHT
120 VAC TO SPARK IGNITION
INFRACONICS ONLY (ZONE 2)
CONTROL SIGNAL TO ZONE PANEL VARIABLE RATE SOLENOID VALVE (USE MINIMUM 18 GAUGE WIRING))
USE 18 GAUGE WIRE FROM THE SmartBox™TO EACH TEMPERATURE SENSOR LOCATION. UP TO 4-FORCED AIR AND 1 RADIANT ZONE
6
Page 7
A
All wiring must be done by a qualified electrician in
accordance with local, state, and national electrical codes.
Do not drill holes
at the top of the control box.
Install the appropriate sized water tight connectors.
Connecting the 120 VAC Power Supply to the SmartBox™.
Connecting 120 VAC Power to the Heaters
Wiring from SmartBox™to the forced air heater’s Smart Sense™ variable rate gas control valve
WARNING
Electrical Shock Hazard
Disconnect the electrical supply before installation of
the SmartBox
.
Failure to follow this warning may result in personal
injury or death.
Unlatch the control box cover, and open the control
panel.
Select locations on either the side or the bottom where
a wiring access holes may be drilled.
Interconnection
a. Connect the Smart Sense™ gas control valve wiring
for Zone 1 at the brown SmartBox shown in Fig.8.
FIG. 8
leads as
Use customer supplied minimum 18 gauge conductor
and the appropriate wiring terminals for connecting the Smart Boxto the heater’s variable gas control valve, to the room controller contacts, and the temperature sensors.
Refer to the following instructions for wiring
connections. Refer to the white flags on the SmartBox™leads for interconnections.
Connect to hot, neutral, and ground leads as shown in Fig.6.
FIG. 6
b. Route the wiring from these leads through the
gas inlet hole at the heater’s case. See Fig.9.
c. Attach 1/4 in. insulated female terminals to
these wires and connect to either terminal on the valve. See Fig. 9.
FIG. 9
CONNECT WIRING TO TERMINALS ( NOT POLARITY SENSITIVE)
ROUTE WIRING THROUGH HOLE
d. See Fig.10 for typical connections. Each SmartBox
zone can control two heaters.
FIG. 10
Connect leads in SmartBox™to heating Zones 1 and 2. See Fig.7.
FIG. 7
FORCED AIR
USED FOR SPARK IGNITION RADIANT HEATERS ONLY. DO NOT USE FOR MANUAL IGNITION RADIANT HEATERS
WIRING FROM Smart Box™ To FORCED AIR Smart Sense™
VARIABLE RATE GAS CONTROL VALVE
VALV E
VOLTS TO VALVE
HEATER 1 GAS VALVE
HEATER 2 GAS VALVE
7
Page 8
C
Connecting the building controller’s heating contacts to the
SmartBox™(for contact closure) for Zone 1 forced air heaters.
(Zone 2 is for radiant heaters and operates independent of the room controller. This does not require contact closure wiring)
These are
not powered contacts.
Wiring from SmartBox™to the radiant heaters.
Connecting the SmartBox™temperature sensors (Zone 1 has 4 sensors, Zone 2 has 1 sensor)
See page 6 for sensor location.
Use onl y the L.B. White SmartBox™se nsors, part num ber 572815, provided with the SmartBox™, or order replacements as needed. Do not use sensors from room controllers as these are not compatible with the L.B.White SmartBox
.
FIG. 13
Connect to the red leads as shown in Fig.11.
-- Remove the wiring from the heat contacts (one for each zone) in the room controller.
-- Connect these same contacts to the SmartBox Enable wiring Zone 1, and to common Zone 1.
- This allows each SmartBoxzone to operate within the temperature parameters of the room controller.
FIG. 11
FIG. 14
COMBO SmartBox
PROPORTIONAL CONTROL VALVE CONNECTOR BLOCK
2
1
-
+
BLUE
BLUE
GROUND
The SmartBoxoperates the variable rate proportional
solenoid control used for the radiant heaters, and operates independent from the room controller.
Separate installation and operation instructions
accompany the appropriate control for manual igntion or spark ignition radiant heaters.
See Fig.12 for connection of the SmartBoxto the
proportional control valve for radiant heaters. Fig13 identifies the proportional valve and Fig.14 illustrates a typical connection from the SmartBox
to the valve.
FIG. 12
Connect 18 gauge (minimum) wiring between the gray leads as shown in Fig.14 and the SmartBox™sensor.
Solder the connection between the SmartBoxsensor and the conductor. Wrap this connection with electrical tape.
FIG. 14
8
Page 9
Set Up and Programming
TOUCH PAD CONTROL AND DISPLAY
BASIC ROOM CONTROL-TYPICAL SET-UP
As an Example:
Note: The actual average room temperature is what will
become the Set-point for the variable rate forc
ed air heating.
TEMPERATURE CONTROL PARAMETERS
A. Manual Mode
Note:
B. Temperature Curve:
The touch pad control is an interface device used to program and operate the control. See Fig. 16 as an example.
FIG. 16
SOFT KEYS
DOWN UP
The following can be programmed from the touch pad:
-- Setting for manual operation.
-- Setting the clock at initial start-up or resetting in the event of a power failure of more than 24 hours.
-- Enabling or disabling room sensors
-- Correlating the SmartBox
controller sensors
-- Setting the initial temperature set points for each zone.
-- Setting the initial temperature curve, if one is used.
-- With the system in operation, temperature and day points can be edited to make changes as needed.
sensors to room
There are up and down keys to adjust parameters.
There are three soft keys used to access and program
entries:
-- Designation for the function of each soft key is indicated at the bottom of the display screen within the three boxes. Designations change depending on operating mode.
The SmartBox
controller that has an on/off heat control in order to provide variable rate heating for the forced air heaters. The SmartBox of the room controller.
interfaces with an existing room
operates radiant heaters independently
There is a desired room air temperature -not to be
exceeded- typically called:
-- DRT (Daily Required Temperature) or
-- Set Point
The typical swine room control will operate a minimum
ventilation fan plus additional stages of ventilation.
-- If DRT /Set Point is exceeded by room temperature the ventilation fan will increase in speed to full output.
-- At some point, if this increased airflow is not sufficient to cool the room back to the desired DRT/Set Point, then additional stages of ventilation are activated.
To avoid the situation of heaters causing room air
temperature to increase above the DRT/Set Point thereby causing increased ventilation to remove the heated air, the settings for heat “on” and “off” are set to avoid overshoot and the accompanying waste of fuel.
-- DRT/Set Point is 82 F
-- Heater “on” offset is -3F: heater comes on at 79F.
-- Heater “off” differential is -1F, the heater goes off at 81F. This is below the DRT/set point and intended to minimize overshoot.
With settings given such as in the previous example:
-- You will typically see 5-6 degrees variation in room temperature. This variation will be eliminated with variable heat control.
-- The actual average room temperature due to heating is about 2F lower than the stated DRT/Set-point temperature, in this example 80F.
There are two ways of utilizing the temperature control:
the operator based on appearance and performance of the animal. room controller temperature setting and the SmartBox temperature setting must be aligned.
curve of temperature vs. days that is used to adjust the
room temperature environment as the animal ages.
: Temperature is adjusted as needed by
To operate in the manual mode, the
there is a defined temperature
9
Page 10
I
INITIAL START-UP
INITIAL SET-UP
The following instructions guide you through a step by step process for setting the various paramete
rs.
HOME SCREENS
MANUAL MODE OR TEMPERATURE CURVE SELECTION
Connect to a 120 VAC power supply. Set the reset switch
to the ON position. It will take about 30 seconds for the
touch pad to display the following screen.
FIG. 17
-- Display # 2 shows the actual room temperature for each zone plus the day in the temperature curve cycle. See Fig.20.
FIG. 20
FORCED AIR TEMP.
RADIANT TEMP.
If at any time during set-up you want to start over, press the up/down keys and the center soft key simultaneously to get back to the Home Screen. Press the right soft key PARAMETERS, then press right soft key NEXT to scroll to the area you want to change.
Simultaneously press the up/down keys and center soft
key. The following screen is displayed. See Fig.18.
FIG. 18
FORCED AIR TEMP.
RADIANT TEMP.
Press right soft key NEXT.
-- Display # 3 shows Set Point for both heating zones and schedule day. See Fig.21.
FIG. 21
Once you have decided which display you want, press the
left soft key DONE to get back to the Home Screen selection.
To continue from the Home Screen, press the right soft key
PARAMETERS. The following screen will be displayed.
To access Home Screens, press left soft key SET HOME
SCREEN. See Fig.18.
There are three home screen displays:
-- Display #1 shows schedule day. See Fig.19. Then press right soft key NEXT.
FIG. 19
10
FIG. 22
This is the manual temperature override selection,
allowing you to set and hold a specific temperature. Once the selection has been made, the SmartBox will hold this temperature.
Page 11
Press the center soft key EDIT. The following screen will be
ENABLE (Manual Mode)
Zone 1 is now in manual override. After ensuring the room controller and Smart Box
set points are
aligned, no further action is needed.
DISABLE (Operating on Temperature Curve)
to operate within the
temperature curve.
--
SET CLOCK (To run the temperature curve the clock must be
set)
TEMPERATURE SENSORS
displayed.
FIG. 23
Press the right soft key NEXT to continue. The screen shown in Fig.26 will be displayed.
FIG. 26
Using the up/down keys, select either “‘ENA” to enable the
manual override or “dSA” to disable the override.
E
-- If enable is selected, press the right soft
key NEXT and then up/down keys to set the temperature that will be maintained by the SmartBox
-- Once the temperature has been selected , press the
left soft key DONE.
--
. See Fig.24.
FIG. 24
Press the right soft key NEXT to continue set-up. The
screen shown in Fig.27 will be displayed.
FIG. 27
Press the center soft key EDIT to set the clock.
-- Starting with the Month, use the up/down keys to select Month, day, year, hour, (Note; AM or PM) and Minutes.
-- Press left soft key DONE to return to SET CLK.
Press the right soft key NEXT to continue set-up.
FIG. 25
-- Selecting disable deactivates the manual override, allowing the SmartBox
-- Press the right soft key NEXT. The following screen will be displayed. Complete the same enabling
or disabling process for Zone 2 as you previously did
for Zone 1.
The following screen is displayed. There are four
temperature sensors for Zone 1(forced air) and one temperature sensor for Zone 2 (radiant). This screen gives
you the option for either using all sensor for the forced air zones, or the single radiant sensor. YOU MUST USE AT LEAST ONE SENSOR.
FIG. 28
11
Page 12
Press the center soft key EDIT.
CALIBRATING TEMPERATURE SENSORS
Press the up/down keys to enable (ENA) or disabled (dSA)
Zone 1 Temperature Sensor 1. See Fig. 29. Make the same selections for sensors 2 through 4 for Zone 1.
FIG. 29
Once all have been selected for Zone 1, Temperature
Sensor 1 through 4, , press the right soft key NEXT to access Zone 2, Temperature Sensor 1. Enable the sensor using the up/down keys. When completed, press the left soft key DONE.
To continue set-up, press right soft key NEXT. The following
screen is displayed.
-- Before making any adjustments, you must allow the temperature between the room controller sensors and the SmartBox
-- Once temperatures have stabilized, use the up/down keys to enter room temperature sensor offset.
Press the right soft key NEXT to set temperature offset for
Zone 1, Temperature Sensors 1 through 4. Complete the same process for Zone 2, Temperature Sensor 1. Use the up/down keys accordingly.
-- Example: If the room controller reads 70 F and the SmartBox by pressing the up key.
Press the leftsoft key DONE, then press NEXT. The
following screen is displayed
reads 69 F, set the offset temperature 1F
sensors to stabilize.
FIG. 32
C
This selection allows correlation between the room controller’s sensors and the SmartBoxsensors.
FIG. 30
Press the center soft key EDIT. The following screen is
displayed.
FIG. 31
Press the center soft key EDIT to view the heat load
percent in Zone 1. See Fig. 33. To view Zone 2, press right center soft key NEXT
FIG. 33
Press the up/down keys and center soft key
simultaneously to exit the set-up mode and to return you back to the Home Screen. Now determine your temperature curve.
12
Page 13
D
DEFINING THE TEMPERATURE CURVE
Period DRT Day SmartBox™Set Point
Forced Air Radiant
1 76 F 1 74 F 88 F
2 76 F 7 74 F 85 F
3 76 F 21 74 F 74 F * 4 72 F 35 70 F 60 F 5 70 F
48 68 F 60 F 6 68 F 65 66 F 60 F 7 66 F 70 64 F 60 F 8 64 F 80 62 F 60 F 9 62 F 120 60 F 60 F
10 62 F
180 60 F 60 F
* Typically the radiant heaters will shut off
after 2-3 weeks o
f operation.
SET-UP OF ROOM CONTROL
SET-UP OF SYSTEM TEMPERATURE CURVE
The SmartBox™has the capacity for 10 time and
temperature control periods.
-- An example is the following:
Note: For each Period, the Days must be equal to or
greater than the previous period. Example: Period 3 cannot start at Day 6.
-- Determine the 10 temperature/day period curve.
-- Enter the temperature curve.(See the previous table example)
-- Set heat “on” offset to -3F (73F)
-- Set the heat “off” differential to 3F (76F), same as the DRT
- The SmartBox temperature exceeds DRT or Set-point.
- This allows the SmartBox operate in the range of 73F to 76F.
will turn heating off before
to be enabled to
FIG. 35
To enter the temperature, press the center soft key EDIT.
The following screen is displayed.
FIG. 36
Use the up/down keys to set the Start Temperature for
Zone 1. Press the right soft key NEXT and use the up/down keys to set Zone 2 Start Temperature.
Press the left soft key DONE.
Press the up/down keys and the center soft key
simultaneously to enter the set-up mode. The following screen is displayed.
FIG. 34
Press the right soft key PARAMETERS.
Continue to press the right soft key NEXT to arrive at the
Temperature Curve Input section. See Fig.35.
Press the right soft key NEXT. The following screen is
displayed.
FIG. 37
Press the center soft key EDIT. The following screen is
displayed.
FIG. 38
13
Page 14
Press the up/down keys to set the Period 2 day as
Set up is complete.
SCREEN DISPLAYS
*
*
* Percentage of operation of variable rate gas control valves
determined with the Temperature Curve.
Press the right soft key NEXT. The following screen is
displayed. Enter the desired set point for Period 2 Zone 1 using the up/down keys.
FIG. 39
Press the right soft key NEXT and enter the set point for
Period 2 Zone 2 using the up/down keys.
Press the left hand soft key DONE.
Repeat this this same process for Periods 3 through 10,
setting the number of days and set points.
Press the left soft key DONE.
Simultaneously press the middle soft key and up/down
S
keys to return to the Home Screen.
-- Z1 OR EN (Zone 1 Override Enabled)
-- Z1 TSP OR ( Zone 1 Temperature Set Point Override)
-- Z1 OR ENA or dSA (Zone 1 enabled or disabled)
-- Z2 OR EN (Zone 2 Overide Enabled)
-- Z2 TSP OR (Zone 2 Temperature Set Point Override)
-- STRT DAY (Start Day)
-- Time
-- SCHD DAY (Schedule Day)
-- ACT Period (Actual Period)
-- RMNG HRS (Remaining Hours)
-- Z1 ACTSP (Zone 1 Actual Set point)
-- Z2 ACTSP (Zone 2 Actual Set Point)
-- Z1 T1, T2,T3 etc (Zone 1 Temperature Sensor 1, etc.)
-- Z2 T1 ( Zone 2 Temperature Sensor 1)
-- Z1 T Avg (Zone 1 Temperature Sensor Average)
-- Z2 T Avg (Zone 2 Temperature Sensor Average)
-- SCHED ER (Schedule Error)
-- HTG STS (Heating Status)
-- Z1 Htg Ld (Zone 1 Heating Load Forced Air)
-- Z2 Htg Ld (Zone 2 Heating Load Radiant)
-- P1 T SP(Period 1 through 10 Temperature Set Point)
-- P-1 Z11 (Set Point for Period 1,Zone 1)
-- P-1 Z-2 (Set Point for Period 2 Zone 2)
-- P2 Day (Period 2 Day through Period 10 Day)
-- Sen Dis (Sensor Disabled)
-- Z1 T1 through T4 (Zone 1 Temperature Sensor 1-4 Disabled)
-- Z 2 T2 (Zone 2 Temperature Sensor 2 Disabled)
-- TMP OF SET( Temperature off set)
-- OF ST T1 (or T2) (Off set Temperature Sensor 1 or 2)
-- Status
-- Set Clk (Set Clock)
-- Month
-- Day
-- Year
-- Hour
-- Minutes
14
Page 15
Maintenance/Cleaning Instructions
Don’t use water or chemicals when cleaning.
WARNING
Electrical Shock Hazard
Fuse A
Fuse B
Fuse C:
WARNING
Electrical Shock Hazard
1. Ensure all water tight connectors on the SmartBox are securely tightened. Check the interior of the box for any water/condensation which might have entered. Replace the connector if necessary.
3. Peridically check all wiring, associated terminals, and
electrical components within the controller for corrosion, frayed or cut insulation, tight connections, etc. Repair or replace as necessary.
2. Periodically check the SmartBox fits tightly around the cabinet, and that the cover gasket is in good condition. (No cuts, nicks etc. ).
to ensure its cover
Do not disassemble or attempt to repair any
components of the SmartBox™.
All component parts must be replaced if defects are
found.
Failure to follow this warning will result in shock,
causing injury, or death.
4. Use a soft rag to clean the exterior to prevent dust/dirt from entering the box when opening for
D
service.
Service Instructions
1. Open the box cover and loosen the panel screws for
access to control components.
2 Disconnect the appropriate electrical leads and
remove the mounting screws for the component being replaced.
3. For reassembly, reverse the service procedure. Ensure all electrical connections are tight.
4. The SmartBox checking components, you will need a volt ohm meter cable of measuring these voltages.
operates on AC and DC volts. When
Disconnect the electrical supply before servicing the
SmartBox™.
Failure to follow this warning may result in electrical
shock, causing personal injury or death.
There are three 250V fuses in the box. See Fig.40.
incoming power supply.
signal conditioner to the variable rate gas solenoid on the zone panel.
signal conditioner to the variable rate Smart Sense™ gas control valve.
: 3.0 amp fuse connected to the 120 VAC
: 3.0 amp fuse connected from the radiant
1.5 amp fuse connected from the forced air
5. DO NOT overtighten the small wiring connection screws used on the programmable controller or the touch pad display. Overtightening will strip threads. Snug the screws in.
FUSES
FIG. 40
A B C
15
Page 16
Terminal Function
RELAYS
Upper transfo mer
Lower transformer
Both transformers must supply 24VAC for complete system operation.
Two relays are mounted in the SmartBox™, each responsible for supplying power to a maximum of two heaters.
Upper relay: Supplies power to Zone 2 heaters.
Lower relay: Supplies power to Zone 1 heaters.
Refer to Fig. 41 and following table for connection of wiring and voltage checks.
The relays have numbers adjacent to the male 1/4 in. male connectors for reference.
T
2 Power supply neutral 4 Neutral for heater 6 120 VAC power to heater 8 120 VAC power to relay 0 Ground for relay 1 24 VAC input for relay coil
TOUCH PAD /DISPLAY
closure (sends 115 VAC from terminal 8 to terminal 6)
FIG. 41
ZONE 2 RELAY
2
0
4
6
1
8
ZONE 1 RELAY
2
0
4
6
1
8
The touch pad/display allows the user to set up the SmartBox
for system operation, heating days,
temperature, etc.
In the event the pad is being programmed and erratic displays are observed, or no display, the display pad must be replaced.
Loosen the small screws securing the brown leads to the back of the touch pad. See Fig.42.
Remove the sheet metal screws adjacent to the front of the touch pad.
TRANSFORMERS
There are two transformers with 120 VAC input voltages.
controller and to the radiant heater signal conditioner.
signal conditioner for use in operating the variable rate gas control valves.
- 24 VAC to the programmable
- 24 VAC output to the forced air
FIG. 42
FIG. 43
UPPER TRANSFORMER
LOWER TRANSFORMER
16
Page 17
The controller requires 24 VAC for operation which can
Replacement
or
If transferring the blocks with wiring intact, refer to the following:
LED BLINK RATE
STATUS
be checked at the terminals shown in Fig 44. (Without 24 VAC, the controller will not operate the SmartBox
)
FIG. 44
LED
24 VAC INPUT FROM UPPER TRANSFORMER
The controller also includes an LED which provides operation status. When power is applied, the LED may appear in one of the conditions given in the following table:
:
OFF Not applicable No power to controller,
ON ON steady
Not blinking
Very slow blink (continuous)
Slow blink (continuous)
1 second ON 1 second OFF
0.5 second ON
0.5 second OFF
low voltage, or controller damaged
Controller is receiving power but its internal processor has malfunctioned.
Normal operation
Sensor failure
PROGRAMMABLE CONTROLLER
a. Remove all individual wires from the terminal
blocks and reconnect to the replacement controller
b.Remove the terminal blocks with the wiring intact
from original controller and transfer the blocks to the replacement controller
a. Use a thin bladed screw driver to evenly raise the
block from its alignment pins on the replacement controller.
b.Insert the screwdriver blade no more than 1/8 in. to
prevent damage to the alignment pins.
c. Insert the screwdriver blade at one end of the
terminal block and rotate the blade about 1/4 turn.
d. Move to the other end of the terminal block and
do the same. See Fig.45. Repeat the process until the block is evenly raised about 1/4 in. from the alignment pins.
e. Once the block has been elevated, grasp the
block at its center and carefully pull the block straight up.
f. Complete these same steps for removal of the
blocks with wiring from the original controller.
g. Remove respective blocks from replacement
controller using this process.
h.Transfer the blocks with wiring to the replacement:
-- Position the block onto the respective alignment pins.
-- Press straight down to firmly seat the block.
-- Repeat the process for all blocks.
FIG. 45
This signal conditioners receives 24 VAC from the lower transformer in the SmartBox
, in addition to a 4-20 mA input signal from the programmable controller.
The conditioner sends anywhere from 0-15 VDC to the heater’s variable rate Smart Sense™gas control for operation, based upon the 4-20 mA signal supplied from the programmable controller.
See Fig.46 for reference to terminals on the conditioner when checking voltage and connection of wiring.
FORCED AIR SIGNAL CONDITIONER
FIG.46
24 VAC INPUT FROM LOWER TRANSFORMER
0-15 VDC OUTPUT TO GAS CONTROL
4-20 mA INPUT FROM CONTROLLER
17
Page 18
RADIANT SIGNAL CONDITIONER
This conditioner receives 24 VAC from the upper transformer in the SmartBox™, in addition to a 4-20 mA input signal from the programmable controller.
The conditioner then sends control signal of 0-15 VDC to the zone control panel’s variable rate solenoid valve for operation, based upon the 4-20 mA signal supplied from the programmable controller.
See Fig.47 for reference to terminals on the conditioner when checking voltage and connection of wiring.
NOT USED
4-20 mA INPUT
ROM CONTROLLER
F
GROUND
24 VAC INPUT FROM UPPER TRANSFORMER
FIG.47
0-15 VDC OUTPUT TO THE PROPORTIONAL GAS SOLENOID VALVE
18
Page 19
DO NO T SERVICE UNL ESS Y OU HAV E BEE N
PROPERLY TRAINED.
Use the green LED on the programmable c ontroller for assistance in troubleshooting if problems occur. A blink pattern of 1 second ON, 1 second OFF indicates normal operation.
• Digital Multimeter
Problems Page
Sequence of Operation
spark iggnition radiant
heaters only
Troubleshooting Instructions
WARNING
Electrical Shock Hazard
READ THIS ENTIRE SECTION BEFORE BEGINNING TO TROUBLESHOOT PROBLEMS.
Troubleshooting this system may require operating the
unit with line voltage present. Use extreme caution when working on the SmartBox
.
Failure to follow this warning may result in personal
injury or death.
The troubleshooting flow charts on the following pages provide systematic procedures for isolating problems. The charts are intended for use by a QUALIFIED SERVICE
D
PERSON.
Components should be replaced only after each step has been completed.
The troubleshooting flow charts pertain to forced air, and radiant heaters, (spark and manual ignition). Unless otherwise noted, the troubleshooting is the same for all heaters, regardless if forced air or radiant.
TEST EQUIPMENT REQUIRED
- for measuring AC and DC voltage and
resistance.
INITIAL PREPARATION
Check all internal wiring for loose connections and
worn/damaged insulation.
a. 120 VAC is supplied to SmartBox™. b. Call for heat occurs from building controller. c. Building controller closes heating contacts
enabling SmartBox operation.
d. 120 VAC is sent to both transformers and to both
relays.
e. Upper transformer reduces 120 VAC to 24 VAC which
is sent to the programmable controller and radiant heat signal conditioner.
-- Green LED on blinks 1 second ON, 1 second Off (Normal operation)
f. Lower transformer reduces the 120 VAC to 24VAC
and sends it to the forced air signal conditioners.
g. Programmable controller sends 24 VAC to both
relays.
-- 24 VAC is used to close the relay coil.
-- Relays send out 120 VAC for power supply to heaters.
h. Programmable controller sends out 4-20 mA signal to
the signal conditioners.
i. Signal conditioners use the 4-20 mA signal to change
the received 24VAC into 0-15 VDC output (forced air) and 0-24 VDC (radiant).
-- Forced air signal conditioner sends the 0-15 VDC to the forced air heater’s variable rate gas control
-- Radiant signal conditioner sends the 0-24 VDC to the proportional solenoid valve.
j. Ignition of gas occurs at a specific rate.
-- Room warms to desired temperature.
k. Building controller and SmartBox
simultaneously to monitor temperature until heat demand is satisfied.
operation for forced air heater
-- Forced air or
-- Heaters start the ignition cycle
work
Green LED on controller is steady ON
. . . . . . . . . . . . . .20
Green LED on controller is OFF. No display at touch pad, indicator lights are out, heaters do not operate
. .20
Green LED on controller is blinking 0.5 seconds ON,
0.5 seconds OFF. Red sensor failure light is on . . . . .21
Forced air or spark ignition heaters do not start, but
zone light is ON. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Zone 1 forced air or Zone 2 radiant heaters do not start. Zone 1 or 2 LED os OFF, but touch pad is
functional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Heaters start and operate properly, but zone
LED is off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Heaters in zone start, but heat output does not change is response to SmartBox
setting . . . . . . . . . .22
SmartBox™ Zone 1 (forced air) does not operate
concurrently with room controller . . . . . . . . . . . . . . . .22
19
Page 20
Green LED on
programmable
controller is
steady ON
Green LED on
programmable
controller is
OFF.
No display at
touch pad, all
indicator lights
are off.
Heaters d
o not
operate.
Problem 2
Yes
Problem 1
Is
upper transformer
delivering 24 VAC to
Yes
Is upper
transformer
Yes
controller?
programmable
power fuse?
receiving 120
VAC from main
No
Verify 24 VAC between the two
yellow leads, (Terminals 10 and 6)
of the transformer. If absent,
No
needed.
Defective electrical wire or
connection. Repair or replace as
replace the transformer.
OFF and then
Cycle the power to the
Smart Box
controller.
steady ON, replace the
ON. If the LED remains
fuse in Smart Box
Is main power supply
delivering 120 VAC to
Yes
?
Is 120 VAC
delivered to
Smart Box
transformers?
No
No
Check breakers in building.
continuity.
by checking voltage to
and from fuse or check
Replace the fuse. Verify
Check power outlet for
Check power cord for tight
defects, corrosion, etc.
connections and continuity.
No
controller?
18 VDC from
Is touch pad receiving
controller.
controller terminals 5 and 6 (brown). If
Check for 18VDC at the programmable
present at the programmable controller,
VDC is absent, trace the wires back to the
Check across brown wires at touch pad. If 18
repair or replace wiring between the touch
pad and the programmable controller. If
absent, replace the programmable controller.
20
G
Page 21
Green LED on
programmable
controller is
blinking 0.5
seconds ON,
0.5 seconds
OFF
Red sensor
failure light is
o
n.
Problem 3
Forced air or spark
ignition radiant
heaters do not start,
zone light is ON.
Problem 4
Zone 1 forced air or
Zone 2 radiant
heaters do not start,
Zone 1 or 2 LED is
OFF. Touch pad
display is fun
ctional
Problem 5
OFF and then
Cycle the power to the
ON. If the LED remains in
SmartBox
this blink pattern, replace
the programmable controller.
Yes
No
Have sensors
continuity across
been checked for
the sensor leads?
Yes
sensor.
oberved, replace the
Check continuity across
sensor leads. Reading
overload or infinity is
20 k ohm. If a reading of
should be in the range of
for troubleshooting.
not functioning, there is a
at the heater but heater is
If 120 VAC is being received
fault in the heater. Refer to
the heater’s Owner’s Manual
Yes
Is 120 VAC
delivered at
heaters?
No
Yes
heaters?
out 120 VAC to
Is relay sending
Yes
Repair or replace.
outlets, and electrical
connections to the heater.
Check power supply wiring ,
No
relay is not sending 120 VAC,
from programmable controller.
If 24 VAC is present at relay, but
Ensure relay is receiving 24 VAC
replace the relay.
controller is defective.
If good, the programmable
check wiring and connections.
from programmable controller,
If 24 VAC is not received at relay
tight at
connectors
Are all sensor
secure and water
?
in the
SmartBox
appropriate leads
sensor leads.
No
corrosion, etc.
Verify proper connection of zone
Ensure good, tight connections, no
sensors to SmartBox
Press right soft key VIEW to determine
No
supply?
VAC power
power from 120
Is relay receiving
needed.
Check electrical connections,
wiring, etc. Repair or replace as
tripped circuit breaker, defective
FORCED AIR HEATERS ONLY
Verify room controller is calling for heat
which sensor (T1 or T2) is inoperative.
the touch pad.
FORCED AIR AND RADIANT: Verify
temperature set-point for the zone, using
21
Page 22
Heaters start but
heat ouptut does
not change in
response to
SmartBox
setting.
Problem 7
Radiant heaters:
Forced Air Heaters:
Radiant Heaters
Forced Air
Radiant:
SmartBox
Zone 1
(forced air) does not
operate concurrently
with room controller.
Problem 8
Heaters start
and operate
properly, but
zone light is
OFF
Problem 6
Check for
gas supply
blockages in
Yes
proportional valve
receiving 1-15 VDC
the radiant heater’s
Is the Smart Sense™
forced air gas valve or
Yes
continuity?
the SmartBox
Have the variable
been checked for
rate output fuses of
from fuse?
No
for the specific heater to a
higher temperature (at least 10F) over room
temperature.
A. Set the SmartBox
No
defective, replace.
Check the fuses. If
Measure across terminals at
: Loosen the proportional gas
valve to obtain reading
B. Verify increase in VDC to gas valve.
valve’s housing screw and pull back the connector
block sufficiently to allow voltage meter probes to
be inserted at the valve terminals.
: Terminals 3 and 4 (brown wires)
Terminals 10 and 11 (blue wires).
C. If no increase in VDC (should be 13-15 VDC) at
gas control, then check the output at the
respective signal conditioner terminals:
If 13-15 VDC is measured at output but not at
valve, check all wiring and terminals between
the signal conditioner and variable rate valve.
D. If no reading is given at the output of the forced
air or radiant signal conditioner, then the signal
conditioner for that zone of heaters is defective
and must be replaced.
LED.
absent, repair wiring
between controller and
If present replace LED. If
Verify 24 VDC to zone LED.
controller and LED.
between programmable
Zone LED is defective or
poor electrical connecton
sensors
Are SmartBox
Yes
Are sensors
Yes
sensors?
same height as
the room control
positioned to the
properly?
positioned
No
No
Reposition the sensors. Refer
cold spots, etc.
away from drafts, air inlets,
Ensure all sensors are located
to sensor location
instructions in this manual.
Ensure the
radiant sensor bracket is
installed and that the sensor
to 3/16 in. from the end of
is located properly within its
housing. It should be 1/8 in.
and inside the sensor housing.
and the
Check temperature curve for
both the SmartBox
room controller. Verify the
temperatures match.
22
Page 23
Warranty Policy
L.B. White Co., Inc. warrants that the component parts are free from defects in material and workmanship, when properly installed, operated, and maintained in accordance with the Installation and Maintenance Instructions, safety guides and labels contained with each unit. If, within 12 months from the date of purchase by the end user, any component is found to be defective, L.B. White Co., Inc. will at its option, repair or replace the defective part or heater, with a new part or heater, F.O.B., Onalaska, Wisconsin.
L.B. White Co., Inc. warrants that replacement parts purchased from the company and used on the appropriate L. B. White equipment are free from defects both in material and workmanship for 12 months from the date of purchase by the end user. Warranty is automatic if a component is found defective within 12 months of the date code marked on the part. If the defect occurs more than 12 months later than the date code but within 12 months from the date of purchase by the end user, a copy of a bill of sale will be required to establish warranty qualification.
The warranty set forth above is the exclusive warranty provided by L.B. White, and all other warranties, including any implied warranties or merchantability or fitness for a particular purpose, are expressly disclaimed. In the event any implied warranty is not hereby effectively disclaimed due to operation of law, such implied warranty is limited in
Smart Box
A warranty card on file at L.B. White will automatically qualify a unit and its component parts for warranty consideration. If a warranty card is not on file, a copy of the bill of sale will be required to establish warranty qualification. If neither is available, the warranty period will be 12 months from date of shipment from L B. White.
Parts
duration to the duration of the applicable warranty stated above. The remedies set forth above are the sole and exclusive remedies available hereunder. L.B. White will not be liable for any incidental or consequential damages directly or indirectly related to the sale, handling or use of the equipment, and in any event L.B. White's liability in connection with the equipment, including for claims based on negligence or strict liability, is limited to the purchase price.
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Contact your local L.B. White dealer for replacement parts and service or call the L.B. White Co., Inc. at 1-800-345-7200 for assistance. Be sure that you have your model number and serial number when calling.
Replacement Parts and Service
23
Loading...