LAARS TL80-199 User Manual

Installation, Operation and Maintenance Instructions Document 2095D
Installation, Operation and Maintenance Instructions for
Mighty-Stack
Gas-Fired Water Heater with Storage Tank
Model TL80-199
These instructions are to be stored next to the water heater for reference purposes.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H2022800D
Page 2
LAARS Heating Systems Company
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction .................................................. 3
1B. Warranty Information.................................... 3
1C. Unpacking .................................................... 3
1D. Heater Identification ..................................... 3
1E. Dimensions .................................................. 3
1F. Identifying Important Components ............... 3
1G. Placing the Water Heater ............................. 3
1H. Gas Supply Piping ........................................ 5
1I. Combustion Air Supply................................. 6
1J. General Venting Instructions ........................ 7
1K. Vertical Venting — Category I ...................... 7
1L. Horizontal Venting — Category III................ 8
1M. Water Piping ................................................. 9
1N. Electrical Wiring ......................................... 11
1P. Filling the Storage Water Tank ................... 11
SECTION 2. Operating Instructions
2A. Starting the System .................................... 14
2B. Starting the System After
Extended Shut-Down .................................15
2C. Shut-Down Procedure................................ 15
2D. Extended Shut-Down —
Cold Weather Areas ................................... 15
SECTION 3. Maintenance and Service
3A. Regular Maintenance ................................. 17
3B. Recommended Annual Inspection .............17
3C. Cleaning the Heat Exchanger .................... 17
3D. Operating Sequence .................................. 17
3E. Cleaning the Pilot and Main Burners ......... 18
3F. Electrical Troubleshooting .......................... 18
3G. Parts Listing ............................................... 20
Mighty Stack Water Heater
Page 3
SECTION 1. General Information
WARNING
To install this unit correctly, you must follow the
procedures listed in this manual. If you do not do this, the warranty offered by Laars will be voided.
Follow the requirements of the local jurisdiction which has authority over the installation. In the United States, also follow the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54.
In Canada, the installation must conform with the latest edition of CAN/CGA B149.1 or .2 installation codes for gas burning appliances, and/or local codes.
Where the recommendations made in this manual are different from the national or local codes, the national or local codes should take precedence.
Do not make any changes to the water heater, or to its gas controls, gas orifices, wiring or draft inducer. Any modifications may void the warranty. If the unit must be modified because of special conditions, consult a factory representative before beginning any changes.
1A. Introduction
This manual provides information necessary for the installation, operation, and maintenance of the Laars Mighty-Stack Model TL80 water heater. This unit includes a blower for induced-draft venting, and has an advanced hot-surface proven-pilot ignition system.
The model designation is listed on the rating plate, which is attached to the top of the water heater.
Please read all application and installation procedures completely before doing the installation. If you have any problems or questions regarding this equipment, consult the Laars factory, or local factory representative. Experience has shown that most operating problems are caused by improper installation.
1B. Warranty Information
The Laars Mighty-Stack Model TL80 water heater is covered by a limited warranty. A copy of the warranty is printed on the back cover of this manual. The owner should fill out the warranty registration card and return it to Laars.
All warranty claims must be made to an authorized Laars representative or directly to the factory. Claims must include the serial number and model of the unit. (This information is listed on the rating plate.) The claim must also include the
installation date and the name of the installer. Shipping costs are not included in the warranty coverage.
1C. Unpacking
Some accessory items are shipped in separate packages. Check to be sure you have received all of the packages which are listed on the packing slip. Inspect each item for damage immediately upon delivery. If there are any shortages or damage, tell the carrier right away. Any claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether the damage is visible or concealed.
1D. Heater Identification
To identify the unit, see the rating plate. Here is an explanation of the coding system:
12345678 9 101112 TL80–199N or PS,HK C
or I or D
Table 1. Heater Identification.
1st to 4th characters – series name (TL80) 5th character – dash (–) 6th through 8th characters – input rate (BTU/hr) x 1000 9th character – fuel
N = natural gas
P = propane
10th character - altitude (feet)
S = 0-2000 for natural gas, 0-5000 for propane
H = 2001-5000 for natural gas
I = 5001-10,000 for natural gas and propane
11th character - Heat Exchanger Type
K = Copper
12th character - Pump Type
C = Wet Rotor (Taco) D = Sealed Rotor (B&G)
1E. Dimensions
Figure 1 shows the dimensions of this unit.
1F. Identifying Important Components
Figure 2 shows the switches, sensors and control components on this unit.
1G. Placing the Water Heater
This water heater is designed for indoor use only. The enclosure is not designed for outdoor installation.
1. Choose a convenient indoor location. Be sure
that any leaking water from the connections will
not damage the area near the appliance. If the
unit must be installed on an upper floor of a
multistory structure, ensure that any leaking
Page 4
LAARS Heating Systems Company
Dimensions shown in inches (mm).
Figure 1. Dimensions.
Figure 2. Component Locations.
Mighty Stack Water Heater
water will not damage areas below the appliance. If a suitable location can not be found, install a drain pan under the appliance. Make sure the drain pan is properly piped to an adequate drain.
2. Place the water heater as close as possible to the vent or chimney.
3. For minimum clearances around the water heater, refer to Table 2. Maintain the minimum distances from all combustible surfaces (see Figure 4). The unit can be installed in a closet. Pay special attention to the air supply opening to the closet.
It is recommended that at least 12 inches
(305mm) is allowed around the entire unit for maintenance, inspection, and plumbing access.
Page 5
Left Right
Side Side Rear Front Flue* Top
inches 6 6 2 2 6 18
mm 152 152 51 51 152 457
*One inch (25 mm) clearance using type B double wall vent pipe when vented vertically.
Table 2. Minimum Clearances from
Combustible Surfaces.
4. This product may be installed on combustible flooring. Do not install directly on carpeting.
5. Be sure that the parts in the gas ignition system are protected from water when the water heater is operating or being serviced. Arrange water lines in the area so that water cannot drip or spray onto the water heater.
6. If the product is to be installed in a location where vibration or tipping is a concern, the unit may be secured to a fixed vertical surface. The TL80 is equipped with slots in the cabinet that can accommodate a strap up to 1½" wide. To secure the unit to a wall, place a strap around the tank (not the tank enclosure), as shown in Figure
3. Allow the strap to pass through the slots provided in the cabinet. Secure the strap as necessary to the wall.
Figure 3. Strap Location.
1H. Gas Supply Piping
Please review these instructions before installing
the water heater.
1. Check that the water heater is fitted for the proper type of gas by checking the rating plate.
2. Laars water heaters are normally equipped to operate below a 2000 foot altitude. Water heaters equipped to operate at higher altitudes have appropriate information on the rating plate.
Figure 4. Installation in Closet.
3. Use the figures in Table 3 to provide adequate gas piping from the gas meter to the water heater.
4. A sediment trap (drip leg) must be provided ahead of the gas controls (see Figure 5). A manual gas shutoff valve must also be provided for service, convenience and safety. This should be installed about 5 feet (1.5 m) above the floor. Check the local codes.
5. Turn off the water heater before you do any pressure testing on the gas lines.
Page 6
Figure 5. Gas Supply Piping.
LAARS Heating Systems Company
If you will be testing at a pressure greater than 1/2" psig (3.5 kPa) –
Disconnect the gas line before the water heater and before the shutoff valve for the water heater.
If you will be testing at a pressure equal to or less than 1/2 psig (3.5 kPa) –
Turn off the manual shut off valve ahead of the water heater gas controls.
6. Provide gas to the water heater at the pressure shown in Table 4. The gas valve regulator is preset at the factory, and normally requires no further adjustment.
Distance from Gas Meter Pipe Size
0' – 200' (0 – 60 m) 1¼"
NOTE: These figures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but maintain a 1/2" minimum diameter. A “normal” number of Tees and elbows have been taken into allowance.
Table 3. Gas Piping Size.
Water Column
Natural Gas Propane (LP)
inches kPa inches kPa
Minimum Supply
Pressure*
Maximum Supply
Pressure**
Manifold Gas
Pressure
* Listed for purposes of inlet adjustment
** The gas supply should not exceed this pressure.
6 1.5 11 2.7
10 2.5 14 3.4
4 1.0 9 2.2
Note: When measuring the inlet supply pressure, the water heater and all other gas appliances sharing the water heater gas supply line must be firing at maximum capacity. Low gas pressure could be caused by an undersized gas meter or an obstructed gas supply line.
7. Before operating the water heater, the complete gas supply system and all connections must be tested for leaks using a soap solution.
Caution
Some solutions used for leak testing may cause corrosion or stress cracking. (These include soap and water.) To prevent this, rinse the piping with water after testing.
1I. Combustion Air Supply
The water heater location must provide enough
air for proper combustion and ventilation of the surrounding area. See the latest edition of ANSI standard Z233.1 or in Canada, CAN/CGA-B149.1 or .2, and any local codes that may be applicable.
In general, these requirements specify that if the
unit is installed in a confined space, there must be at least two permanent air supply openings. One opening should be within 12 inches (305mm) of the ceiling, and the other should be within 12 inches (305mm) of the floor.
Table 4. Gas Pressure Measurement.
Mighty Stack Water Heater
Page 7
For installation in U.S.A.:
Water Heater Outside Air Inside Air
Size Area
199 50 sq in. 199 sq in.
323 sq cm 1284 sq cm
The area indicated is for one of two openings; one at floor level and one at ceiling, so the total net free area would be double the figures indicated. For special conditions, refer to NFPA54 ANSI Z223.1.
Outside air supply – Combustion air is supplied directly through an outside wall.
††
Inside air supply – Combustion air is supplied from inside the building.
NOTE: Check with louver manufacturers for Net Free Area of Louvers. Correct for screen resistance to the New Free Area if a screen is used.
Table 5. Minimum Recommended Air Supply
to Water Heater Room.
Area
††
Outside Air Supply: When combustion air is
supplied directly through an outside wall, each opening should have a minimum free area of one square inch per 4,000 BTUH input of the total input rating of all appliances in the enclosed area.
Inside Air Supply: When combustion air is
supplied from inside the building, each opening should have a minimum free area of one square inch (6.5 sq cm) per 1,000 BTUH input of the total input rating of all appliances in the enclosed area. These openings should never be less than 100 square inches (645 sq cm).
For installation in Canada:
NOTE: In Canada, follow Canadian Standard
CAN/CGA-B149 or local codes.
Exhaust Fans or Vents: Any equipment which
exhausts air from the room around the unit can deplete the combustion air supply. Such equipment can also reverse the action of the venting system. This could cause flue products to accumulate in the space where the water heater is installed. Additional air must be supplied to compensate for any exhaust effect.
The information in Table 5 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
If a blower or fan is used to supply air to the water heater room, the installer should make sure it does not create drafts which could cause nuisance shutdowns. If a blower is necessary to provide adequate combustion air to the water heater, a switch or equivalent must be wired into the water heater control circuit to prevent the water heater from firing unless the blower is operating.
The water heater must be protected from any source of corrosive chemical fumes including those emitted by trichlorethylene, perchlorethylene, chlorine, etc.
1J. General Venting Instructions
WARNING
This water heater must be vented in accordance with Part 7, Venting of Equipment, of the latest edition of the National Fuel Gas code, ANSI Z223.1 and all applicable local building codes. In Canada, follow CAN/CGA B149 Installation codes. Improper venting of this appliance can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
Here are some general rules to follow when
venting this unit:
• Place the water heater as close as possible to the vent or chimney.
• The vent collar on the water heater must be fastened directly to an unobstructed vent pipe. Use rustproof sheet metal screws no longer than 1/2" (13 mm).
• Do not weld the vent pipe to the water heater collar. The weight of the stack must not rest on the water heater. The top of the water heater must be easily removable for normal service and inspection of the unit.
• The water heater vent must not be connected to a fireplace, wood stove or other equipment which burns solid fuel.
• Avoid terminating the water heater vent near any air-conditioning or air-supply fans. These fans can pick up the exhaust flue products from the water heater and return them to the building. This can create a health hazard.
• Avoid using an oversized vent pipe or using extremely long runs of the pipe. This may cause excessive cooling and condensation of flue gases.
1K. Vertical Venting – Category I
This unit can be vented into a masonry chimney,
provided several conditions are met (see Figure 6).
• The chimney must have an appropriate tile lining. The lining should be the correct size, should be constructed correctly, and must be clean.
• Check the chimney passage way to be sure that it is clear and free of obstructions.
• If the chimney must be rebuilt, follow nationally­recognized standards. (See the National Building Code or ANSI/NFPA 211.)
Page 8
Figure 6. Chimney Venting.
LAARS Heating Systems Company
the latest edition of ANSI Z223.1/NFPA 54. See “Sizing of Category I Venting Systems” and “Appendix G.” In Canada, follow the instructions in the CAN/CGA-B149 installation code.
An unused chimney can be used as a raceway for a single-wall vent pipe (see Figure 7). Never run a vent pipe through a flue that has another appliance attached to it.
(b) Vent Termination
A listed vent terminal must complete the vertical run where it exits the chimney. This must be designed for the type of pipe being used. The vent pipe must extend at least 3 feet (1 m) above the highest point where it passes through the roof. In addition, the vent cap must be at least 2 feet (0.6 m) higher than any part of a building within a horizontal distance of 10 feet (3m). Clearance to any combustible materials must be maintained as listed (see Figure 8).
• When the water heater and a boiler are to be connected to the same chimney, each unit must have its own vent connector. The two connectors must enter the chimney at least 6" (152 mm) apart.
(a) Vent Connections
Use type B double wall or type C single wall gas
vent pipe (26 gauge, minimum thickness) from the water heater to the chimney. Laars recommends installation of a riser with a minimum of 12" (305 mm) height above the water heater. The vent system should be sloped up toward the chimney at a rate of 1/ 4" per foot (1 cm per 50 cm). The vent connector must be strong enough to support the weight of the material used. This will maintain the clearances and prevent physical damage and separation of the joints.
NOTE: Always provide a minimum clearance of
6 inches (152 mm) between a Type C vent pipe and any combustible materials.
Warning
Single-wall vent pipe must never pass through interior walls, or through floors or ceilings! Failure to comply with this warning could result in a fire, causing property damage, personal injury, or death!
1L. Horizontal Venting – Category III
When a vent system is horizontal or cannot meet the requirements of Category I, it can develop positive pressure. This type of system must be installed in accordance with the instructions in this section, and with the instructions supplied by the vent manufacturer.
(a) Vent Connections
The vent system must be gas tight. All seams and joints must be sealed with silicone sealant or adhesive tape having a minimum temperature rating of 400°F (204°C). (See Table 6 for a list of approved sealing materials.)
When installing the vent system, all applicable national and local codes must be followed! If you install thimbles, firestops or other protective devices, and they penetrate any combustible or noncombustible construction, be sure to follow all applicable national and local codes.
If a vertical vent is installed, follow the code requirements for Category 1, Fan Assisted Appliances. Follow the requirements as indicated in
Figure 7. Vertical Venting.
Mighty Stack Water Heater
Figure 8. Vertical Vent Termination.
Page 9
For best results, a horizontal vent system should be as short and straight as possible. The materials used in the vent connectors should be as listed in Table 7.
Description Manufacturer Product
High Temperature
RTV Dow Corning Trade Mate
2" (51 mm) wide
aluminum foil tape, Venture Product #3243
backed with adhesive
2" (51 mm) wide
aluminum foil tape 3M Product #433
backed with adhesive
Table 6. Vent Sealing Material.
In USA: Up to a maximum of Use UL type 304, 316 or 40 feet (12 m) of equiv­29-4C stainless steel, alent pipe run (including 26 gauge minimum. required elbows). In Canada: Use “BH” vent type complying with ULC S-636 Standard.
Table 7. Vent Connector Materials.
The water heater vent collar must be fastened to vent pipe of the same diameter, with rustproof metal screws no longer than 1/2" (13 mm) and sealed with high temperature 500°F (260°C) silicone sealant. For larger diameter vent pipes, use a sealed reducer fastened directly to the water heater collar and seal all joints as indicated in Figure 9. Allow the sealant to cure for 24 hours before operating the water heater.
The entire vent system must not exceed the size specified in Table 8.
The following criteria must be observed:
• Attach a vertical pipe at least 12 inches (305 mm) high to the water heater outlet before the horizontal run if run exceeds 5 feet (1.5m) (see Figure 9).
• Support the vent run at 3-foot (1 m) intervals with overhead hangers.
• Pitch down the vent run, toward the vent terminal (hood), at a rate of 1/4 inch per foot (1cm per 50 cm).
• Do not locate any joint screws at the bottom of the vent run.
No. of Horizontal Run
Diameter Elbows Length*
4" (102 mm) 4 20' (6 m)
*For each elbow eliminated, add 5 feet (1.5 m) of allowable vent.
Table 8. Horizontal Venting Configuration.
Outside wall
Vent
system
Thimble
Water
heater
Figure 9. Horizontal Venting.
*12" Min.
(305 mm)
Sheet metal
screws
Caulk entire joint
including the screws
Boiler venting detail
* When horizontal run exceeds 5 ft. (1.5 m)
Loading...
+ 19 hidden pages