Install a relay for
each output stage
which will be active
Use these three buttons
to adjust the settings
In AUTO, the lead stage will automatically
rotate among the active outputs. Press to
INCREMENT for manual rotation.
Each Stage
Output has
one set of
N.O. contacts
The green LEAD stage
light indicates which
stage will be activated
first on a system call
The red OUTPUT lights
indicate when the relays
are energized and the
N.O. contacts are
continuous.
The System
Output is
SPDT
Each output can be switched
ON, AUTO, or OFF. In AUTO,
the output will be controlled
based on system requirements.
120 VAC Power Input
GND must be connected
Sensor, Shutdown/Setback,
Prove/DHW, and Outdoor
input terminals
Page 4
12345678
ON
Switch 1
System Output
Switch 5
Rotation
Switches 6 and 7
Input Type
5
First On/Last Off
Lead stage rotates
every 24 hours
5
First On/First Off
First stage on is
the first stage
turned off
Temperature
67
External Set Point
Available for temperature
systems only, 4-20mA
signal changes Set Point
67
ON
ON
ON
ON
Switch 8
Set Point or Reset
8
Set Point
Set Point control
for temperature
8
Outdoor Reset
Hydronic heating
control with
outdoor reset
ON
ON
1
System Pump
SYSTEM relay is on
based on outside
temp, Shutdown,
and DHW priority
1
Combustion Air
Damper/Prove
SYSTEM relay is
on when any
OUTPUT is on
ON
ON
Switches 2, 3, and 4
Stage Type
2Stage Lo/Lo/Hi/Hi
On load increase
sequence on Lo
stages first, then Hi
stages
2
On/Off Stages
Each stage is
either on or off
2 Stage Lo/Hi
On load increase
sequence Lo to Hi
then next Lo to Hi
34
234
2
3 Stages
On load increase
sequence Lo, Mid,
Hi
34
234
4 Stages
On load increase
sequence Lo,
LoMid, HiMid, Hi
234
ON
ON
ON
ON
ON
ON
Page 5
temperature is from 20 to 120°F.
the enclosure.
the metal front panel).
- System relay output type - Combustion Air Damper, or System Pump operation
- Stage type - On/Off, Lo/Hi, 3 Stage or 4 Stage
- Rotation Sequence - First On/Last Off or First On/First Off
- Input type - Temperature or External Set Point
- Operation - Set Point or Outdoor Reset
IMPORTANT
The dip switches must be set correctly. Carefully, check the details of the installation and
WIRING THE POWER INPUTS
voltage wiring.
LINE.
NEUT.
WIRING THE INPUT TERMINALS
and
NOT
be installed in between boiler connections to header. If the sensor does not
register the output of all the stages, it will not be able to Sequence properly.
2 COM
Mounting Holes
LINE
NEUT
Surge
Suppressor
Power Switch
Ground
Line
Neut
INPUTS
1 2 3
4
5 6
Sensor Com Shield + Sensor Com
TEMPPRES 4-20 ma
Shield
To Temperature Sensor
in Common Header
Page 6
6
and dip switch 7 must be
monitor the 4-20mA input to change the set point. (See wiring sensor on pg. 3) Also, see pg. 23 for
EMS programming parameters.
and
SETBACK
setting to 0 the
SHUTDOWN
feature is enabled by
were on will remain on until the System Delay is over, then they will also turn off.
SHUTDOWN
feature can be used whenever it is desirable to turn off the SC from a remote
SETBACK
is enabled by adjusting control
SETBACK
setting to a value higher
than 0 and closing a dry contact wired to terminals 7 and 8, the SC will immediately reduce the
temperature of the circulating hot water by the
SETBACK
setting amount (see pg. 20 to
SETBACK)
SHUTDOWN/SETBACK
signal must be a dry contact only to terminals 7 and 8. No voltage can be
placed across the
SHUTDOWN/SETBACK
terminals.
and
) and Domestic Hot Water (
).
PROVE
feature is used to check system components’ operation before activating any stages. See
pg. 24 for typical applications.
PROVE
input terminals are open, the SC will enable only the System Output relay. All Stage
PROVE
input is open.
DHW
) input is enabled by closing a dry contact, the Calculated water
temperature or the Set Point will change to 200°F and the decimal point on the left-most digit on the
DHW
input will take priority over the outdoor reset function or the Outdoor Cutoff temperature.
Regardless of outdoor temperature, when the
DHW
input is closed, the SC will Sequence stages to
hold 200°F.
NO
external conditions must be met before Stage Output is activated and terminals
and
are not used for Domestic Hot
Water (see pg. 25),
DO NOT
remove the factory installed jumper across the
PROVE/DHW
terminals.
PROVE/DHW
signal must be a dry contact only to terminals 9 and 10. No voltage can be placed across the
PROVE/DHW
terminals.
IMPORTANT
input terminals must be
and
).
). If it is installed, it will act as an Outdoor
windows, exhaust fans, vents, or other possible heat sources.
and 12.
Note that both sensor shields will be connected
to terminal 3.
Dry Contact
Prove or Domestic
Hot Water Signal
INPUTS
5 6 7
8910
11
Sensor Com
DryContact
Only
DryContact
Only
SHUTDOWN
/SETBACK
PROVE
/DHW
OUTD
4-20 ma
INPUTS
5 6 7
89101112
Sensor Com
DryContact
Only
DryContact
Only
SHUTDOWN
/SETBACK
PROVE
/DHW
4-20 ma
OUTDOOR
To Outdoor Sensor
In Shade
Shield
2 3
4
Com Shield +
TEMP
4
5 6
+ Sensor Com
4-20 ma
SC Source Current
24VDC Excitation Voltage
(-) Input
(+) Signal
INPUTS
5 6 7
8
9
Sensor Com
DryContact
Only
DryContact
SHUTDOWN
/SETBACK
PROVE
4
+
4-20 ma
Dry Contact
Shutdown and
Setback Signal
4
5 6
+ Sensor Com
4-20 ma
EMS Sourcing Current
(-) Input
(+) Signal
Page 7
WIRING THE STAGE OUTPUTS
WIRING THE SYSTEM OUTPUT
- If there is no call for stage output, the System relay is off
- On a call for stage output, the System relay is energized
- When the
PROVE
input is made, the lead stage is energized
- The System relay remains energized as long as any stage is active
- When the last stage turns off, the System relay remains energized for the period of
time set by the System Delay (see pg. 22)
- Then the System relay is turned off.
PROVE
inputs. The
PROVE
input can be used in a
and the Shutdown is not
- The System relay will be energized when any stage is active
- After the last stage is turned off, the System relay will remain energized for the period of time set by the System Delay (see pg.
22) and then turn off.
- When the outdoor temperature below the Outdoor Cutoff + 2°F (
+ 2°F), the
- Otherwise, the System relay will be off above
+ 2°F (after the System Delay
has expired).• When the control is set
- The System relay will be off for an adjustable period of time set by the DHW Priority Time
- After the Priority Time has elapsed, when the outdoor temperature is below the Outdoor Cutoff + 2°F (
+ 2°F) setting, the
- When the outdoor temperature is 2°F above the Outdoor Cutoff (
+
2°F), the System relay will be off at all times.
switch in the
AUTO
position.
switch in the
position.
LEAD STAGE
switch in the
AUTO
position for automatic rotation.
SYSTEM
C.
N.C.
N.O.
Combustion
Air Damper
Line
Neut
SYSTEM
C.
N.C.
N.O.
System Pump
Line
Neut
WARNING
Page 8
the parameters are correct, there is no need to make any adjustments.
reapply power.
the SC will operate in Fahrenheit. If the display shows
then the SC will operate in Celsius.
button to increase the value,
DOWN
button to decrease the value.
and
(see pg. 25).
the Input terminals
and
will function in the Prove mode. If the display shows
then the same
terminals will function in the DHW mode.
button to increase the value, or
the
DOWN
button to decrease the value.
will fl ash.
Normal
or PID type Sequencing mode provides the most stable operation. Stages are turned on or off
based on the rate of change of the system temperature and the impact a stage has on that rate.
) Sequencing
mode that brings on stages proportionally, based on how high above or far below the Set Point the current system temperature is.
For more details, see pg. 21.
(Normal) then the SC will Sequence in the PID type mode. If the display shows
then SC will
around the Set Point
button to increase the value, or the
DOWN
button to decrease the value.
will fl ash. This completes the startup Sequence and the SC will display the sensor temperature.
the SC will operate in Fahrenheit. If the display shows
then the SC will operate in Celsius.
button to increase the value,
DOWN
button to decrease the value.
Minimum Water Temperature
INCREMENT
AUTO
OFF
LEAD STAGE
ROTATION
For Automatic Lead
Stage Rotation
Output
OFF
AUTO
ON
For Non-Active
Stages
For Stages Which are
to be Part of the
Automatic Sequence
Page 9
button to increase the
value, or the
DOWN
button to decrease the value.
will fl ash.
and
(see pg. 25).
the Input terminals
and
will function in the Prove mode. If the display shows
then the same
terminals will function in the DHW mode.
button to increase the value, or
the
DOWN
button to decrease the value.
will fl ash.
based on the rate of change of the system temperature and the impact a stage has on that rate.
Sequencing mode
that brings on stages proportionally, based on how high above or far below the Set Point the current system temperature is. For
more details, (see pg. 21).
then the SC will Sequence in the PID type mode. If the display shows
then SC will
button to increase the value, or the
DOWN
button to decrease the value.
will fl ash. This completes the startup Sequence and the SC will display the sensor temperature.
Page 10
ADJUSTING THE CONTROL SETTING
SELECT SETTING
button.
Set Point Control with Normal Sequencing Temperature or External Set Point pg. 10
Set Point Control with Oversize System Sequencing Temperature or External Set Point pg. 11
Outdoor Reset Control with Normal Sequencing pg. 12
Outdoor Reset Control with Oversize System Sequencing pg. 13
Press SELECT
SELECT
SETTING
UP
DOWN
Press and
Hold to
Adjust
Press to Scroll
Through Control
Settings
Control Settings
Display
Button
Once
Twice
♦
♦♦
3 Times
3 or 4 Times
4 or 5 Times
5 or 6 Times
6 or 7 Times
7 or 8 Times
7 or more Times
8 or more Times
8 or more Times
♦♦
♦♦
♦♦
SET POINT CONTROL WITH NORMAL SEQUENCING
Dip Switch 8 - OFF
DISPLAYPress and hold either the UP or DOWN button to adjust
The Set Point is the temperature which the SC will sequence stages to hold. Note that if you are
using the External Set Point, you will not be able to change the Set Point unless you adjust the 4-
Set Point
Outdoor Temp
Outdoor Cutoff
Reaction Time
System Delay
Purge Time
Boiler runtime
Program Offset
Last Stage Hold
Setback
DHW Priority Time
20mA input. The Set Point is adjustable between -30
This is the outdoor sensor temperature value.
Available only when the outdoor sensor is installed. When the outdoor temperature falls below the
Outdoor Cutoff value, the SC will activate stages for heat. The Outdoor Cutoff can be set ON or OFF
and from 40 to 100°F. Default is 60°F.
The Reaction Time controls the minimum run time for a stage (1/2 the Reaction Time). Also, it controls how long should a stage run before it activates/subtracts another stage. It is adjustable from half
a minute (0.5) to 8.0 minutes. Default is 2 minutes.
The System Delay controls how long the System relay will remain energized after the last Output has
been turned off or the outdoor temperature rises above the Starter. The System Delay is adjustable
from 0 to 30 minutes. Default is 0.
The Purge Time should be set to the length of the unit’s purge cycle. The Purge Time will apply
when any ON/OFF unit is activated. On multiple stage units, the Purge Time will only apply to the Lo
stages. The Purge Time is adjustable from 0.0 to 10.0 minutes.
This is the minimum amount of time any boiler will run after the Purge cycle has been completed. This
timer does not apply when only one stage is running, the Last Stage Hold LSH applies in that case.
The Boiler Runtime is adjustable between 0 to 60 minutes. Default is 0.
The Programmed Offset fi ne tunes the External Set Point. With a known 4mA input, the offset can be
set to make the External Set Point 110°F. The Program Offset is adjustable between -10
Default is 0°F.
To prevent short cycling of the last stage in low load conditions, the system temperature can exceed
the Set Point by the amount selected by the Last Stage Hold before the last stage is turned off. The
Last Stage Hold is adjustable between 0°F to 20°F. Default is 10°F.
The Setback adjusts the number of degrees the Set Point water temperature will be reduced when
Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a
closure. The Setback is adjustable from 0°F to 40°F. Default is 0°F.
Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is
OFF ) This setting adjusts the amount of time the System relay output will remain off during a DHW
call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will
energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.
Default is 0.
°F to 250°F. Default is 70°F.
Default is 0.
°F to +10°F.
8 or more Times
♦ Actual temperature values are not adjustable
♦♦ May not be available, depending on status of the outdoor sensor and dip switches.
♦
Default
The SC returns to the default display of system water temperature.
Page 11
Press SELECT
Button
Once
SET POINT CONTROL WITH OSS SEQUENCING
Dip Switch 8 - OFF
DISPLAYPress and hold either the UP or DOWN button to adjust
The Set Point is the temperature which the SC will sequence stages to hold. Note that if you are
Set Point
using the External Set Point, you will not be able to change the Set Point unless you adjust the 420mA input. The Set Point is adjustable between -30
°F to 250°F. Default is 70°F.
♦
Twice
3 Times
♦♦
3 or 4 Time
4 or 5 Times
4 or more Times
5 or more Times
5 or more Times
5 or more Times
Outdoor Temp
Outdoor Cutoff
System Delay
♦♦
Program Offset
Throttling Range
♦♦
Setback
♦♦
DHW Priority Time
♦
Default
This is the outdoor sensor temperature value.
Available only when the outdoor sensor is installed. When the outdoor temperature falls below the
Outdoor Cutoff value, the SC will activate stages for heat. The Outdoor Cutoff can be set ON or OFF
and from 40 to 100°F.
The System Delay controls how long the System relay will remain energized after the last Output has
been turned off or the outdoor temperature rises above the Starter. The System Delay is adjustable
from 0 to 30 minutes. Default is 0.
The Programmed Offset fi ne tunes the Pressure input or the External Set Point. With a known 4mA
input, the offset can be set to make the External Set Point 110°F. The Program Offset is adjustable
between -10°F to +10°F. Default is 0°F.
The throttling range sets the number of degrees or psi above and below the Set Point where stages
will be turned on or off. The Throttle Range is adjustable from 1
24 for details.
The Setback adjusts the number of degrees the Set Point water temperature will be reduced when
Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a
closure. The Setback is adjustable from 0°F to 40°F. Default is 0°F.
Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is
OFF ) This setting adjusts the amount of time the System relay output will remain off during a DHW
call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will
energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.
Default is 0.
The SC returns to the default display of system water temperature.
Default is 60°F.
♦ Actual temperature values are not adjustable
♦♦ May not be available, depending on status of the outdoor sensor and dip switches.
°F to 20°F. Default is 5°F. See page
Page 12
Press SELECT
Button
Once♦
OUTDOOR RESET WITH NORMAL SEQUENCING
Dip Switch 6 and 7 - OFF and 8 - ON
DISPLAYPress and hold either the UP or DOWN button to adjust
This is the water temperature the SC will stage outputs to hold. It is based on outdoor temperature,
Calculated
Reset Ratio, and the Offset value. If OFF is shown, there is no call for heat. If PrF is shown, the SC
is waiting for a Prove signal before activating stages.
Twice
3 Times
4 Times
5 Times
6 Times
7 Times
8 Times
9 Times
10 Times
11 Times
12 Times
♦
Outdoor Temp
Outdoor Cutoff
Reset Ratio
Offset
Reaction Time
System Delay
Purge Time
Boiler runtime
Last Stage Hold
Setback
♦♦
DHW Priority Time
This is the outdoor sensor temperature value.
When the outdoor temperature falls below the Outdoor Cutoff value, the SC will give heat. When the
outdoor temperature is above the Outdoor Cutoff, the Calculated value will be OFF and no stages will
be activated except on a DHW call. The Outdoor Cutoff can be set ON or OFF and from 40 to 100°F.
Default is 60°F.
The Reset Ratio controls the amount of heat which enters the heating system based on the outdoor
temperature. A higher numbered Reset Ratio will result in a higher Calculated water temperature.
See the chart on pg. 19 for the reset curves. The Reset Ratio is adjustable from 1 to 12. Default is 7.
The Offset moves the reset curves vertically up or down. For example, changing the offset from 0 to
-10 will decrease the water temperature 10°F regardless of outdoor temperature or the reset curve
selected. The Offset is adjustable from -40
The Reaction Time controls the minimum run time for a stage (1/2 the Reaction Time). Also, it controls how long should a stage run before it activates/subtracts another stage. It is adjustable from half
a minute (0.5) to 8.0 minutes. Default is 2 minutes.
The System Delay controls how long the System relay will remain energized after the last Output has
been turned off or the outdoor temperature rises above the Starter. The System Delay is adjustable
from 0 to 30 minutes.
The Purge Time should be set to the length of the unit’s purge cycle. The Purge Time will apply
when any ON/OFF unit is activated. On multiple stage units, the Purge Time will only apply to the Lo
stages. The Purge Time is adjustable from 0.0 to 10.0 minutes.
This is the minimum amount of time any boiler will run after the Purge cycle has been completed. This
timer does not apply when only one stage is running, the Last Stage Hold LSH applies in that case.
The Boiler Runtime is adjustable between 0 to 60 minutes. Default is 0.
To prevent short cycling of the last stage in low load conditions, the system temperature can exceed
the Calculated water Temperature by the amount selected by the Last Stage Hold before the last
stage is turned off. The Last Stage Hold is adjustable between 0
The Setback adjusts the number of degrees the Set Point water temperature will be reduced when
Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a
closure. The Setback is adjustable from 0°F to 40°F. Default is 0°F.
Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is
OFF ) This setting adjusts the amount of time the System relay output will remain off during a DHW
call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will
energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.
Default is 0.
°F to 40°F. Default is 0°F.
Default is 0.
°F to 20°F. Default is 10°F.
12 to 13 Times
♦
Default
The SC returns to the default display of system water temperature.
♦ Actual temperature values are not adjustable
♦♦ May not be available, depending on status of the outdoor sensor and dip switches.
Page 13
Press SELECT
Button
Once♦
OUTDOOR RESET WITH OSS SEQUENCING
Dip Switch 6 and 7 - OFF and 8 - ON
DISPLAYPress and hold either the UP or DOWN button to adjust
This is the water temperature the SC will stage outputs to hold. It is based on outdoor temperature,
Calculated
Reset Ratio, and the Offset value. If OFF is shown, there is no call for heat. If PrF is shown, the SC
is waiting for a Prove signal before activating stages.
Twice
3 Times
4 Times
5 Times
6 Times
7 Times
8 Times
9 Times
♦
Outdoor Temp
Outdoor Cutoff
Reset Ratio
Offset
System Delay
Throttling Range
Setback
♦♦
DHW Priority Time
This is the outdoor sensor temperature value.
When the outdoor temperature falls below the Outdoor Cutoff value, the SC will give heat. When the
outdoor temperature is above the Outdoor Cutoff, the Calculated value will be OFF and no stages will
be activated except on a DHW call. The Outdoor Cutoff can be set ON or OFF and from 40 to 100°F.
Default is 60°F.
The Reset Ratio controls the amount of heat which enters the heating system based on the outdoor
temperature. A higher numbered Reset Ratio will result in a higher Calculated water temperature.
See the chart on pg. 19 for the reset curves. The Reset Ratio is adjustable from 1 to 12.
The Offset moves the reset curves vertically up or down. For example, changing the offset from 0 to
-10 will decrease the water temperature 10°F regardless of outdoor temperature or the reset curve
selected. The Offset is adjustable from -40
The System Delay controls how long the System relay will remain energized after the last Output has
been turned off or the outdoor temperature rises above the Starter. The System Delay is adjustable
from 0 to 30 minutes.
The throttling range sets the number of degrees or psi above and below the Set Point where stages
will be turned on or off. The Throttle Range is adjustable from 1°F to 20°F. Default is 5°F. See page 21
for details.
The Setback adjusts the number of degrees the Set Point water temperature will be reduced when
Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a
closure. The Setback is adjustable from 0°F to 40°F. Default is 0°F.
Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is
OFF ) This setting adjusts the amount of time the System relay output will remain off during a DHW
call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will
energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.
Default is 0.
°F to 40°F. Default is 0°F.
Default is 7.
9 to 10 Times♦
Default
The SC returns to the default display of system water temperature.
♦ Actual temperature values are not adjustable
♦♦ May not be available, depending on status of the outdoor sensor and dip switches.
Page 14
Additional output relays can be
WARNING
This Laars Heating Systems control is strictly an operating control; it should
SC
Outputs
Output
NO
C
Limit
Circuit
ON/OFF Units
Lo
Output
2 Stage Units
Hi
Output
NO
C
Hi
Circuit
Lo
Output
3 Stage Units
NO
C
Mid
Output
Hi
Output
Lo
Output
4 Stage Units
LoMid
Output
HiMid
Output
Hi
Output
NO
C
Limit
Circuit
NO
C
Limit
Circuit
NO
C
Mid
Circuit
NO
C
Hi
Circuit
NO
C
Limit
Circuit
NO
C
LoMid
Circuit
NO
C
HiMid
Circuit
NO
C
Hi
Circuit
through
) which is to be used must have
position (see pg. 23).
WIRING THE STAGE OUTPUTS
SYSTEM,
must not exceed 15A.
contacts associated with it.
2 Stage (Lo/Hi) Units
relays associated with it.
relays associated with it.
4 Stage (Lo/LoMid/HiMid/Hi) Units
relays associated with it.
Page 15
which is to be used must have a relay installed in the socket.
SYSTEM
relay which can be used for main or system pumps, or
particular type of installation.
which does not have a relay must have its stage switch to the OFF
position (see pg. 23).
WIRING THE STAGE OUTPUTS
SYSTEM
must not exceed 15A.
2 Stage (Lo/Hi) Units
positions.
positions.
4 Stage (Lo/Mid/Hi) Units
positions.
SC
Outputs
ON/OFF Units
2 Stage Units
3 Stage Units
4 Stage Units
NO
C
To Pump
Starter
NO
C
Limit
Circuit
Boiler Pump
Output
Boiler
Output
NO
C
To Pump
Starter
Boiler Pump
Output
NO
C
Limit
Circuit
Lo
Output
NO
C
Hi
Circuit
Hi
Output
NO
C
To Pump
Starter
Boiler Pump
Output
NO
C
Limit
Circuit
Lo
Output
NO
C
Mid
Circuit
Mid
Output
NO
C
Hi
Circuit
Hi
Output
NO
C
To Pump
Starter
Boiler Pump
Output
NO
C
Limit
Circuit
Lo
Output
NO
C
LoMid
Circuit
LoMid
Output
NO
C
HiMid
Circuit
HiMid
Output
NO
C
Hi
Circuit
Hi
Output
WARNING
This Laars Heating Systems control is strictly an operating control; it should
verify proper operation and correct any safety problems prior to the installation of
this Laars Heating Systems control.
Additional output relays can be
Page 16
Boiler 3Boiler 2Boiler 1
Output 1
Output 2
Output 3
Outdoor
Sensor
System
Temperature
Sensor
System
Pump
DHW
Dry Contact
(optional)
SC
Laars
Connecting the SC Control to
three Pump-Mounted Boilers (or Boilers with Built-in
Pump Time Delay) and Domestic Hot Water
using Outdoor reset Setting
System
Output
Power
Sensor Inputs
Boiler 3Boiler 2Boiler 1
Output 1
Output 2
Output 3
Connect to 120VAC
see page 5
Outdoor
Sensor
System
Temperature
Sensor
System
Pump
DHW
Dry Contact
(optional)
SC
Laars
Connecting the SC6P Control to
three Non-Pump-Mounted Boilers and Domestic
Hot Water using Outdoor reset Setting
System
Output
Power
Sensor Inputs
Pump 3
Pump 2
Pump 1
Pump 3Pump 2Pump 1
Connect to 120VAC
see page 5
Plumbing
Class 1 Wiring
Class 2 Sensor Wiring
The laars SC Sequencing control DOES NOT source power for boiler stages or pumps. It operates as dry contact switch.
A separate power source for the burners and pumps must be supplied.1.Laars is aware that each installation is unique. Thus, Laars is not responsibe for any installation related to any electrical
or plumbing diagram generated by Laars. The provided illustrations are to demonstrate Laars' control operating concept only.
2.
The drawings do not necessrily depict the locations of inlet and outlet water connections. Inlet and outlet connections vary
by product type.
3.
Pump 3*Pump 2*Pump 1*
External Pump is used when boiler does not have mounted pump.
Pump is interlocked with boiler's pump time delay.
*
Page 17
6 Stage Sequencer - SC 6
The
SYSTEM
relay will be energized when any Stage Output relay is energized.