LAARS Pennant PNCV User Manual

Page 1
Installation and Operation Instructions Document 1204D
Heating Systems Company
A subsidiary of CorporationBRADFORD WHITE
®
®
Installation and Operation Instructions for
Low Temperature
PENNANT
Hydronic Boiler Model PNCH
Water Heater Model PNCV
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty. For indoor installations, as an additional measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
AVERTISSEMENT
H2319100D
Page 2
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction ...................................................... 3
1.2 Model Identication .......................................... 4
1.3 Warranty .......................................................... 4
1.4 Dimensions ...................................................... 4
1.5 Locating the Appliance..................................... 4
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s) ...................... 6
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header ................... 6
1.8 Locating Appliance for Correct Horizontal Vent/Ducted Air Distance
From Outside Wall ........................................... 6
SECTION 2. Venting and Combustion Air
2.1 Combustion Air ................................................ 7
2.1.1 Combustion Air From Room ............................ 7
2.1.2 Intake Combustion Air...................................... 7
2.2 Venting ............................................................. 8
2.2.1 Vent Categories ............................................... 8
2.2.2 Category I Vent ................................................ 8
2.2.3 Common Venting Systems .............................. 8
2.2.4 Category III Vent .............................................. 9
2.3 Locating Vent & Combustion Air Terminals ...... 9
2.3.1 Side Wall Vent Terminal ................................... 9
2.3.2 Side Wall Combustion Air Terminal ................ 12
2.3.3 Vertical Vent Terminal .................................... 12
2.3.4 Vertical Combustion Air Terminal ................... 12
2.4 Common Vent Test – Boilers ......................... 12
2.5 Vent Terminals for Outdoor Units ................... 13
SECTION 3. Gas Supply and Piping
3.1 Gas Supply and Piping .................................. 14
SECTION 4A. Water Connections – Pennant Boiler
4A.1 Heating System Piping:
Hot Supply Connections – Boiler ................... 16
4A.2 Cold Water Make-Up – Boiler ........................ 16
4A.3 Water Flow Requirements – Boiler ................ 16
4A.4 Freeze Protection – Boiler ............................. 16
SECTION 4B. Water Connections – Pennant Water Heater
4B.1 Water System Piping – Water Heater ............ 17
4B.2 Hot Water Supply Piping – Water Heater ...... 17
4B.3 Water Flow Requirements – Water Heater .... 17
4B.4 Combined Water (potable)
Heating and Space Heating ........................... 17
4B.5 Freeze Protection – Water Heater ................. 17
SECTION 5. Electrical Connections
5.1 Main Power .................................................... 20
5.1.1 Sizes 500-1500 .............................................. 21
5.1.2 Sizes 1750-2000 ............................................ 21
5.1.3 Separate Pump Circuit................................... 21
5.1.4 All Sizes ......................................................... 21
5.2 Field Wiring ................................................... 21
SECTION 6. Operating Instructions
6.1 Filling the Boiler System ................................ 28
6.2 Sequence of Operation .................................. 28
6.3 Temperature (Operating) Control ................... 29
6.3.1 Temperature Control Overview ...................... 29
6.3.2 Programming Parameters-Boilers ................. 29
6.3.3 Programming Parameters-Water Heaters ..... 30
6.4 Limit Controls ................................................. 30
6.5 Operating the Burner and Set Up .................. 30
6.5.1 Set Up for 0 to 2500 Feet Altitude.................. 30
6.5.2 High Altitude Adjustment and Set Up ............. 31
6.6 Shutting Down the Pennant ........................... 31
6.7 To Restart the Pennant .................................. 31
SECTION 7. Maintenance
7.1 System Maintenance ..................................... 32
7.2 Appliance Maintenance and
Component Description ................................. 32
7.2.1 Burners .......................................................... 32
7.2.2 Filter ............................................................... 33
7.2.3 Gas Valves ..................................................... 33
7.2.4 Manual Reset High Limit Control ................... 33
7.2.5 Automatic Reset High Limit Control ............... 33
7.2.6 Temperature Control ...................................... 33
7.2.7 Ignition Control............................................... 33
7.2.8 Ignitor ............................................................. 34
7.2.9 Transformer ................................................... 34
7.2.10 Blowers .......................................................... 34
7.2.11 Flow Switch ....................................................34
7.2.12 Heat Exchanger Coil ...................................... 34
SECTION 8. Trouble Shooting
8.1 Resolving Lockouts........................................ 35
8.2 Delayed Ignition – Possible Causes .............. 35
8.3 Short Cycling – Boiler .................................... 35
8.4 Short Cycling – Water Heater ........................ 36
8.5 High Gas Consumption.................................. 36
8.6 Troubleshooting Pennant Controls ................ 36
SECTION 9. Replacement Parts
9.1 General Information ....................................... 36
9.2 Parts List ........................................................ 36
Page 3
Low Temperature Pennant
SECTION 1. General Information
USING THIS MANUAL – Because the Pennant Boilers and Pennant Water Heaters are identical appliances, with the exception of materials of manufacture, labels and ultimate use application, this manual provides information for the proper installation, operation and maintenance of both products. Where differences exist between the application of the appliances and their operation, the sections pertinent to only one appliance or the
other will be so identied.
In the Commonwealth of Massachusetts, this appliance must be installed by a licensed plumber or
gas tter.
WARNING
To minimize the risk of electric shock, fire or other hazards which could result in property damage, injury, or death. The Pennant hydronic, boiler or water heater must be installed in accordance with the procedures detailed in this manual, or the Laars Heating Systems warranty may be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of the Natural Gas and Propane Installation Code, CSA B149.1 and/or applicable local codes. Where
Afin de réduire au minimum les risques de commotion électrique, de feu ou d’autre nature, qui pourraient causer des dommages matériels, des blessures ou des accidents mortels, les chaudières à eau chaude ou les chauffe-eau Pennant doivent être installés conformément aux directives détaillées contenues dans ce manuel, à défaut de quoi la garantie fournie par Laars Heating Systems serait annulée. L’installation doit être conforme aux exigences de la réglementation locale en vigueur et, aux États-Unis, à l’édition la plus récente du Natural Fuel Gas Code (Code pour le gaz combustible naturel) ANSI Z223.1/NFPA54. Au Canada, l’installation doit respecter les exigences de la plus récente édition du Code d’installation du gaz naturel et du propane CSA B149.1, et/ou des codes locaux de construction en vigueur. Lorsque la réglementation locale l’exige, l’installation des appareils électroménagers Pennant doit respecter les exigences du Standard for Controls and Safety Devices for Automatically Fired Boilers (Code pour les équipements de commande et de sécurité des chaudières à combustion automatique), ANSI/ ASME CSD-1. Toute modification apportée à la chaudière, aux régulateurs de gaz ou au câblage, peut compromettre la garantie. Si certaines conditions particulières rendent des adaptations nécessaires, consulter un représentant du fabricant avant d’entreprendre ces modifications.
required by the authority having jurisdiction, the installation of Pennant appliances must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modifications to the boiler, its gas controls, or wiring may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
All application and installation procedures
should be reviewed completely before proceeding with
the installation. Consult the Laars Heating Systems
factory, or local factory representative, with any issues
or questions regarding this equipment. Experience
has shown that most operating issues are caused by
improper installation.
The Pennant appliance is protected against over
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of Laars Heating Systems’ Low temperature Pennant copper tube appliances, sizes 500-2000 (standard appliances
pressurization. A pressure relief valve is tted to all appliances. It is installed on the outlet header, at the water outlet of the appliance.
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13 in. w.c. (3.2 kPa).
are covered in a separate manual). Read it carefully before installation.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P N C A C C 2
AVERTISSEMENT
Page 3
SERIES
P N C
USAGE
H
V
SIZE
0 5 0 0
0 7 5 0
1 0 0 0
1 2 5 0
1 5 0 0
1 7 5 0
2 0 0 0
FUEL
N
P
ALTITUDE
A
LOCATION
C
FIRING
MODE
C ON-OFF
REVISION
2
HEAT
EXCHANGER
B
C
N
P
OPTIONS
CODE
X
J
PUMP
OPTIONS
H
N
S C
B
D
Page 4
Page 4
LAARS Heating Systems
All installations must be made in accordance
with:
1) In the U.S., the " National Fuel Gas Code "ANSI Z223.1/NFPA54, Latest Edition and all applicable
local codes as required by the Authorities Having Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane Installation Code", CSA B149.1, latest edition and all applicable local codes as required by the AHJ.
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC), ANSI/NFPA 70, latest Edition and all applicable local
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part 1”, CSA STD. C22.1 and all applicable local codes as required by the AHJ.
This appliance must be electrically grounded in accordance with the applicable codes and standards
referenced above.
1.2 ModelIdentication
Consult the rating plate on the unit. The
following information describes the model number
structure.
Model Character Designation
1-3 Model Series Designation
P N C = Pennant
4 Usage
H = Hydronic V = Volume Water
5-8 Size
0 5 0 0 = 500,000 BTU/h input 0 7 5 0 = 750,000 BTU/h input 1 0 0 0 = 999,000 BTU/h input 1 2 5 0 = 1,250,000 BTU/h input 1 5 0 0 = 1,500,000 BTU/h input 1 7 5 0 = 1,750,000 BTU/h input 2 0 0 0 = 1,999,000 BTU/h input
9 Fuel
N = Natural Gas P = Propane
10 Altitude
A = 0-10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-Off
13 Revision
2 = Revision Level 2
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. PNCV) C = Glass-lined cast iron / copper (std. PNCH) N = Glass-lined cast iron / cu-nickel P = Glass-lined cast iron / cu-nickel / brz trim
15 Option Code
X = Standard Low Temp Control J = CSD-1, FM, IRI, IL
16 Pump Options
H = TACO, Hard water pump (PNCV only) N = TACO, Normal water pump S = TACO, Soft water pump (PNCV only) C = B&G, Hard water pump (PNCV only) B = B&G, Normal water pump D = B&G, Soft water pump (PNCV only)
1.3 Warranty
Laars Heating Systems’ appliances are covered
by a limited warranty. Owners should submit online
warranty registration at www.Laars.com.
All warranty claims must be made to an authorized Laars Heating Systems representative, directly to Customer Service, or online at www.Laars.com.
Claims must include the serial number and model (this information can be found on the rating plate),
installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.4 Dimensions
See Figure 1.
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of any connections will result in damage to the area
adjacent to the appliance or to lower oors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certied by CSA­International for installation on combustible ooring; in basements; in closets, utility rooms or alcoves.
Pennant Boilers or Water Heaters must never be installed on carpeting. The location for the appliance
should be chosen with regard to the vent pipe lengths
and external plumbing. The unit shall be installed such
that the gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement, control
replacement, etc.). When vented vertically, the Pennant
must be located as close as practical to a chimney or
outside wall. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level
Page 5
Low Temperature Pennant
13.7
35
B
C
W*
V*
A
12.4
31
H
20.24
514
FRONT VIEW
REAR VIEW
W*
V*
TOP VIEW
FLOW SWITCH
INLET
OUTLET
3WAY ACTUATOR
TEMPERATURE
SWITCH
PRV
F
(W)
2
5
LEFT SIDE VIEW
PUMP
PUMP
G
(V)
19.7
50
41.5
105
35.3
89
29.3
74
7.75
20
13.8
35
13.7
35
RIGHT SIDE VIEW
D
C
W*
B
V*
E
Dimensions shown in
inches cm
Page 5
Size A B C D E F G H
500 33½ 85 15¾ 40 15 29¾ 76 32¾ 83 20 22 46 117 6 15 8 20 6 15 750 45½ 11 6 21¾ 55 15 29¾ 76 32¾ 83 20 22 58 147 6 15 10 25 8 20
Air
Conn.
W*
Vent
Conn.
V*
Horiz.
Vent Pipe
1000 57½ 146 28¾ 73 15 29¾ 76 32¾ 83 20 7 18 70 178 8 20 10 25 8 20 1250 68 172 34 86 101∕826 30¾ 78 29½ 75 22 22 80 203 8 20 12 30 8 20 1500 78½ 199 39¾ 101 101∕826 30¾ 78 29½ 75 22 22 91 231 8 20 12 30 8 20 1750 89 226 44½ 113 101∕826 30¾ 78 29½ 75 22 22 101 256 8 20 14 36 8 20 2000 99½ 253 49¾ 126 101∕826 30¾ 78 29½ 75 22 22 112 284 12 30 14 36 12 30
*Air and vent connections may be on top or back of the Pennant, and are eld convertible. Dimensions in inches cm
Figure 1. Dimensional Data.
Page 6
Page 6
LAARS Heating Systems
above grade such that blockage of the terminal from
accumulated debris or precipitation is prevented.
The dimensions and requirements that are shown
in Table 1 should be met when choosing the locations
for the appliance.
1.6 Locating Pump-Mounted Water Heater with Respect to Storage Tank(s)
For best results, the Pennant water heater should
be located within 15 feet (4.6m) of the storage tank(s). The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter pipe or tubing may be
acceptable. Consult the factory for assistance.
Appliance
Surface
Left Side 1 2.5 24 61 Right Side 1 2.5 24 61 Top 1 2.5 12 30 Back 1 2.5 12** 30** Front 1 2.5 36 91 Vertical
(Category 1)
Vent Horizontal
(Category 3) Vent
*1" (2.5 cm) when b-vent is used. **When vent and/or combustion air connects to the back, recommended clearance is 36" (91cm).
Required
Clearance From
Combustible Material
inches cm inches cm
6* 15.2*
per UL 1738 venting system supplier's instructions
Table 1. Clearances.
Recommended Service Access
Clearance
1.7 Locating Pump-Mounted Boiler with Respect to Return/Supply Header
For the best results, Pennant should be located
within 15 feet (4.6m) of the supply and return headers. The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter tubing may be
acceptable. Consult the factory for assistance.
1.8 Locating Appliance for Correct Horizontal Vent/Ducted Air Distance From Outside Wall
The forced draft combustion air blower(s) in the
appliance has/have sufcient power to pull air and vent
properly when the guidelines for horizontal air and vent are followed (see Table 2).
NOTE: On some models, the vent collar size is larger than the size of the vent pipe that can be used. Vent collar size and horizontal pipe diameters can be found in Table 1. The larger vent collar size is to accommodate Category I (vertical) vent systems.
NOTE: When located on the same wall, the Pennant combustion air intake terminal must be installed a minimum of 12" (30cm) below the exhaust vent terminal and separated by a minimum of 36 inches (91cm) horizontally.
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other
debris.
Size
500 8 20 6 15 6 15 50 15 3 CA001401 20260701
750 10 25 8 20 6 15 50 15 3 CA001401 20260701 1000 10 25 8 20 8 20 50 15 3 CA001402 20260703 1250 12 30 8 20 8 20 50 15 3 CA001403 20260703 1500 12 30 8 20 8 20 50 15 3 CA001403 20260703 1750 14 36 8 20 8 20 50 15 3 CA001403 20260703 2000 14 36 12 30 12 30 50 15 3 CA001404 20260706
Vent Collar
Size
in cm in cm in cm ft m
Horizontal
Vent Pipe
Diameter
Table 2. Horizontal Vent / Combustion Air Parameters.
Intake
Air Collar
& Pipe
Diameter
Max. Pipe
Length
Max. No.
of Elbows
Side Vent
Terminal
Part Number
Side Wall Combustion Air Terminal
Part Number
Page 7
Low Temperature Pennant
Page 7
SECTION 2. Venting and Combustion Air
WARNING
For indoor installations, as an additional measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.
AVERTISSEMENT
Pour des installations intérieures, Laars recommande fortement, comme mesure de sécurité supplémentaire, l’installation de détecteurs de monoxyde de carbone adaptés dans le voisinage de l’appareil et dans chacune des pièces habitées adjacentes.
2.1 Combustion Air
Pennant boilers and water heaters must have provisions for combustion and ventilation air in accordance with the applicable sections addressing requirements for air for combustion and ventilation of
the National Fuel Gas Code, ANSI Z223.1. In Canada, the applicable sections of the Natural Gas and Propane Installation Code (CSA B149.1) must be followed. In
all cases any and all applicable local installation codes
must also be followed.
A Pennant appliance may receive combustion air from the space in which it is installed, or it can be
ducted directly to the unit from the outside. Proper ventilation air must be provided in either case.
2.1.1 Combustion Air From Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Method 1: Two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of
the bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per 4000 Btu/hr (5.5 square cm/kW) of total input rating of all equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than
1 square inch per 2000 Btu/hr (11 square cm/kW) of total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method, for each
Pennant model.
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (7 square cm/kW) of the total input rating of all equipment located in the enclosure. This
opening must not be less than the sum of the areas of
all vent connectors in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety
codes or, in absence of such requirements, follow
CSA B149.1, the Natural Gas and Propane Installation Code.
2.1.2 Intake Combustion Air
The combustion air can be taken through the
wall, or through the roof. When taken from the wall, it
must be taken from out-of-doors by means of the Laars horizontal wall terminal (see Table 2). When taken
from the roof, a eld-supplied rain cap or an elbow
arrangement must be used to prevent entry of rain water (see Figure 2).
Use single-wall galvanized pipe, per Table
4, for the combustion air intake (see Table 2 for
appropriate size). Route the intake to the heater as directly as possible. Seal all joints with tape. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is 50 feet (15.2m). Three elbows have been calculated into the 50-foot (15.2m)
Size 500 125 807
750 188 1213 1000 250 1613 1250 313 2020 1500 375 2420 1750 438 2826 2000 500 3226
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at oor level
and one at the ceiling, so the total net free area could be
double the gures indicated.
This chart is for use when communicating directly with the outdoors. For special conditions and alternate methods, refer to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of louvers. Correct for screen resistance to the net free area if a screen is installed. Check all local codes applicable to combustion air.
Table 3. Combustion Air Openings.
Square inches Square cm
Each Opening*
Page 8
Page 8
LAARS Heating Systems
linear run. Subtract 10 allowable linear feet (3.0m) for
every additional elbow used (see Table 2). When fewer
than 3 elbows are used, the maximum linear pipe length allowed is still 50 feet (15.2m).
The connection for the intake air pipe is on the
lter box. Pennant appliances may have venting and combustion air ducting attached to the top or the back. They are shipped with the connections at the top. For
attaching either or both pipes to the back, the mounting
anges are reversible by removing the mounting screws and orienting the anges in the desired position. Replace the screws after positioning anges. Run a bead of silicone around the collar and slide the pipe over the collar. Secure with sheet metal screws.
In addition to air needed for combustion, air shall also be supplied for ventilation, including all air required for comfort and proper working conditions
for personnel. The Pennant loses less than 1 percent of
its input rating to the room, but other heat sources may
be present.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired Pennant venting, it may
be considered a Category I or a Category III appliance.
In general, a vertical vent system will be a Category
I system. However, in rare instances, a Pennant’s
vertical vent system may be considered Category
III. In the U.S., the National Fuel Gas Code (ANSI Z223.1), or in Canada the Natural Gas and Propane Installation Code (CSA B149.1), denes a Category I
vent system, and includes rules and tables to size these
vent systems. If the Pennant’s vertical vent system
does not satisfy the criteria for Category I venting, it
must be vented as a Category III system.
All Pennant vent systems which discharge horizontally (without the use of a power venter) are
considered Category III vent systems.
(negative) 0.1 in. w.c.
If using a power venter for any type of Category
I venting, the draft should be set between (negative)
0.01 and 0.05 in. w.c.
2.2.3 Common Venting Systems
Pennant units are Category I fan-assisted when
vented vertically and adhering to all applicable codes.
Pennant units are not allowed to be vented into a common horizontal vent system, unless a properly sized vent fan is used, and the common vent system is properly designed by the vent fan manufacturer or
a qualied engineer. When common venting Pennant
fan-assisted unit with other appliances through
one shared vertical duct called a “common vent”,
special care must be taken by the installer to ensure
safe operation. In the event that the common vent
is blocked, it is possible, especially for fan-assisted devices, to vent backwards through non-operating appliances sharing the vent, allowing combustion
products to inltrate occupied spaces. If the appliances are allowed to operate in this condition, serious injury or death may occur.
WARNING
Operation of appliances with a blocked common vent may lead to serious injury or death. Safety devices must be implemented to prevent blocked common vent operation. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
2.2.2 Category I Vent
When vented as a Category I appliance, the
vent system must conform to the National Fuel Gas Code (ANSI Z223.1-Latest Edition) in the U.S., or in Canada, to the Natural Gas and Propane Installation Code (CSA B149.1 latest edition). The vent system must be sized and installed for a Category I Fan­Assisted Appliance.
If chimney height is greater than 25 feet, or if multiple units are vented into the same vertical vent, a barometric damper must be installed on each
appliance, such that the ue draft does not exceed
Term Description Pipe Single-wall galvanized steel pipe, 24 gauge
minimum (either insulated or non-insulated)
Joint Sealing Permanent duct tape or aluminum tape
Table 4. Required Combustion Air Piping Material.
Figure 2. Combustion Air and Vent Through Roof.
Page 9
Low Temperature Pennant
Page 9
AVERTISSEMENT
Le fonctionnement d’appareils connectés à un évent commun bouché peut provoquer de sérieuses blessures corporelles ou la mort. Des dispositifs de sécurité doivent être mis en place pour empêcher que les appareils soient utilisés avec un évent commun bouché. Si un fonctionnement sécuritaire de tous les appareils reliés à un évent commun et si la prévention des dégagements accidentels de gaz de combustion dans des zones habitées ne peuvent pas être assurés, un évent commun ne doit pas être mis en place et les appareils doivent être munis d’évents individuels séparés.
It is for this reason that, in addition to
following proper vent sizing, construction and safety
requirements from the National Fuel Gas Code, ANSI Z223.1 or in Canada, from the Natural Gas and Propane Installation Code (CSA B149.1) as well as
all applicable local codes, it is required that installers provide some means to prevent operation with a
blocked common vent. It is suggested that a blocked
vent safety system be employed such that if the switch
from one appliance trips due to excessive stack spill
or back pressure indicating a blocked vent condition, that all appliances attached to the vent be locked out
and prevented from operating. Note that the Pennant
is equipped with a blocked vent safety (pressure)
switch, as shipped. However, this safety switch has
only been designed and tested to be effective in installations where the Pennant is vented separately
and NOT common vented with other appliances. As an
additional precaution, it is recommended that a Carbon
Monoxide (CO) alarm be installed in all enclosed spaces containing combustion appliances. If assistance
is required in determining how a blocked vent safety
system should be connected to a LAARS product, please call Applications Engineering at the Rochester phone number on the back cover of this manual.
Refer to the installation and operating
instructions on all appliances to be common vented for instructions, warnings, restrictions and safety
requirements. If safe operation of all appliances
connected to a common vent cannot be assured,
including prevention of spillage of ue gases into
living spaces, common venting should not be applied,
and appliances should each be vented separately.
2.2.4 Category III Vent
When the Pennant is vented with horizontal discharge, it must be installed per this installation manual and the venting system manufacturer’s
installation instructions. The vent system must be
sealed stainless steel, per Table 5.
Route the vent pipe to the heater as directly as possible. Seal all joints and provide adequate hangers
as required in the venting system manufacturer’s
installation instructions. Horizontal portions of the
venting system must be supported to prevent sagging and may not have any low sections that could trap
condensate.
The unit must not support the weight of the vent
pipe. Horizontal runs must slope downwards not less than ¼ inch per foot (2 cm/m) from the unit to the vent terminal.
L’appareil ne doit pas supporter le poids de la gaine d’évent. Les parties horizontales doivent être installées avec une pente de 2 cm/m (1/4 inch par pied) descendant de l’appareil vers la sortie de l’évent.
Reference Table 2 for the size of the Category III vent system. Up to three elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable linear feet (3.0m) for every additional elbow used.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Side Wall Vent Terminal
The appropriate Laars side wall vent terminal must be used, and is listed in the installation and
operation manual. The terminal provides a means of
installing the vent piping through the building wall,
and must be located in accordance with ANSI Z223.1/ NFPA 54 and applicable local codes. In Canada, the installation must be in accordance with CSA B149.1 and local applicable codes. Consider the following
when installing the terminal:
1. Figure 3 shows the requirements for mechanical
vent terminal clearances for the U.S. and Canada.
2. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
3. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows,
gravity inlets or other openings. Whenever
possible, locations under windows or near doors
should be avoided.
4. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine
that a vent terminal must be higher than the
minimum shown in codes, depending upon local
conditions.
5. Locate the terminal so the vent exhaust does
not settle on building surfaces or other nearby
objects. Vent products may damage such surfaces
or objects.
6. If the boiler or water heater uses ducted
combustion air from an intake terminal located
on the same wall, locate the vent terminal at least
Term Description
Pipe Must comply with UL Standard 1738 such
as Type AL29-4C Stainless Steel (either insulated or non-insulated).
Joint
Sealing
Table 5. Required Horizontal Venting Material.
Follow vent manufacturer's instructions.
Page 10
Page 10
LAARS Heating Systems
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm) deck, or balcony
B= Clearance to window or door that may Direct Vent Only: 12 inches (30 cm)
be opened Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm) to side of opening; 1 foot (30 cm) above opening
C= Clearance to permanently closed window See note 4 See note 5 D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal See note 4 See note 5 distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soffit See note 4 See note 5 F= Clearance to outside corner See note 4 See note 5 G= Clearance to inside corner See note 4 See note 5 H= Clearance to each side of center line See note 4 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm) J= Clearance to non mechanical air supply Direct Vent Only: 12 inches (30 cm)
inlet to building or the combustion air inlet Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm) to any other appliance to side of opening; 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m) horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in this driveway located on public property location
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3) or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.
5. For clearances not specified in CSA B149.1, clearance is in accordance with local installation codes and the requirements of the gas supplier.
Figure 3. Vent Terminal Clearances.
Page 11
Low Temperature Pennant
Page 11
3 feet (0.9m) horizontally from the combustion
air terminal, and locate the vent terminal at least
1 foot (0.3m) above the combustion air terminal.
WARNING
The outdoor vent terminal gets hot. Unit must be installed in such a way as to reduce the risk of burns from contact with the vent terminal.
AVERTISSEMENT
La sortie d’évent à l’extérieur devient très chaude. Elle doit être installée de façon à réduire le risque de brûlures au contact de l’extrémité de l’évent.
Important Note: Massachusetts Code Requirement.
From Massachusetts Rules and Regulations 248 CMR 5.08:
(a) For all side wall horizontally vented gas
fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination
is less than seven (7) feet above nished grade
in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall
horizontal vented gas fueled equipment, the
installing plumber or gastter shall observe that a hard-wired carbon monoxide detector with
an alarm and battery back-up is installed on
the oor level where the gas equipment is to be installed. In addition, the installing plumber or gastter shall observe that a battery operated or hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property
owner to secure the services of qualied licensed
professionals for the installation of hard-wired
carbon monoxide detectors. a. In the event that the side wall
horizontally vented gas fueled equipment is installed in a crawl space or an attic, the
hard-wired carbon monoxide detector with
alarm and battery back-up may be installed
on the next adjacent oor level.
b. In the event that the requirements of
this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply
with the above requirements; provided,
however, that during said thirty (30) day
period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
3. SIGNAGE.
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print size no less than one-half (½) inch
in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION.
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon
monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontal vented gas
fueled equipment installed in a room or structure separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall
include:
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2. A complete parts list for the venting system
Page 12
Page 12
LAARS Heating Systems
design or venting system.
(d) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fuel gases,
but identies “special venting systems”, the following requirements shall be satised by the manufacturer:
1. The referenced “special venting system”
instructions shall be included with the appliance
or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
(e) A copy of all installation instructions for all
Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
2.3.2 Side Wall Combustion Air Terminal
The Laars side wall combustion air terminal
(listed in Table 2) must be used when the unit takes
its combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning uid, chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject to damage by accident or vandalism.
3. Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30
cm) above grade, but the installer may determine it should be higher, depending upon local
conditions.
4. If the Pennant is side-wall vented to the same
wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high
enough above the roof line to prevent blockage from
snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm)
below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
eld-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2). The opening on the end of the terminal must be at least
12" (30cm) above the point at which it penetrates the
roof, and high enough above the roof line to prevent
blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
2.4 Common Vent Test — Boilers
When an existing boiler is removed from a
common venting system, the common venting system is likely to be too large for proper venting of the
appliances remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system
are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is non blockage or restriction, leakage, corrosion
and other deciencies which could cause an unsafe condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the ame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, replace dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
Page 13
Low Temperature Pennant
Page 13
conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in
Appendix F in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
2.4 Véricationdeséventscommuns— Chaudières
Lorsqu’une chaudière existante est déconnectée
du réseau d’évents commun, ce réseau d’évents commun devient probablement trop grand pour les appareils qui lui restent connectés. Lorsqu’une chaudière existante est retirée, les étapes suivantes doivent être accomplies pour chaque appareil qui reste connecté au réseau d’évents commun utilisé, alors que les autres appareils qui sont encore connectés au réseau commun d’évents ne sont pas en fonctionnement.:
1. Sceller toutes les ouvertures non utilisées du système d'évacuation.
2. Inspecter de façon visuelle le système d'évacuation pour déterminer la grosseur et l'inclinaison horizontale qui conviennent et s'assurer que le système est exempt d'obstruction, d'étranglement, de fuite, de corrosion et autres défaillances qui pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre l'espace où les appareils toujours raccordés au système d'évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d'évacuation common et tous les ventilateurs d'extraction comme les hottes de cuisinière et les ventilateurs des salles de bain. S'assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d'été. Fermer les registres des cheminées.
4. Mettre l'appareil inspecté en marche. Suivre les instructions d'allumage. Réegler le thermostat de façon continue.
5. Faire fonctionner le brûleur principal pendant 5 min ensuite, déterminer si le coupe-tirage déborde à l'ouverture de décharge. Utiliser la
amme d'une allumette ou d'une chandelle ou la
fumée d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode indiquée ci-dessus, que chaque appareil raccordé au système d'évacuation est mis à l'air libre de façon adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
7. Tout mauvais fonctionnement du système d'évacuation commun devrait être corrigé de façon que l'installation soit conforme au National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'installation CSA-B149.1. Si la grosseur d'une section du système devrait
être modié, le système devrait être modié pour
respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) les codes d'installation CSA-B149.1
2.5 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from
falling into the Pennant.
If local codes allow, outdoor installations may
use 1' (one foot) of appropriately sized galvanized
single wall or type "B" vent and a rain cap for exhaust vent termination in the default conguration (venting out of the top). An appropriately sized 90° elbow,
positioned with the opening facing down, may be used
on the combustion air inlet in the default conguration on the back of the unit. Note that some local codes may require a higher vertical vent height, extending above any perimeter fencing, etc. In installations
where the appearance of the vent is objectionable, the
low prole vent terminals listed in Table 6 may be used.
Part numbers for the low prole terminals to
cover the vent and combustions air openings are shown in Table 6.
Size Outdoor
Vent
Terminal 500 20254703 D2007900 750 20254705 D2007900
1000 20254705 D2008000 1250 D2007700 D2008000 1500 D2007700 D2008000 1750 D2007800 D2008000 2000 D2007800 D2008200
Table 6. Vent Terminals for Outdoor Units.
Outdoor Combustion Air Terminal
Page 14
Page 14
LAARS Heating Systems
SECTION 3. Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or oor stands, not by the appliance.
The Pennant’s gas train allows the user to pipe
the gas from either the right side or the left side of
the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side.
If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on
the right side may be moved to the left.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is tted for the proper type of gas by checking the rating plate. Pennant
appliances are equipped to operate at elevations
up to 10,000 feet (3050m). Pennant appliances
may be adjusted to operate properly at altitudes above 2500 feet (see Section 6.5.2) and the input will be reduced if the heating value of the gas
supply is below sea level values.
2. The maximum inlet gas pressure must not exceed 13" w.c. (3.2kPa). The minimum inlet gas pressure is 5 in. w.c. (1.2 kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to action of liqueed petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping during any pressure testing of that system at test
pressures in excess of 0.5 psig (3.45 kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or
less than 0.5 psig (3.45 kpa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Do not use open flame to check for leaks. An open flame could lead to explosion, which could result in property damage, serious injury or death.
AVERTISSEMENT
Ne recherchez pas les fuites avec une flamme nue. Une flamme nue peut provoquer une explosion qui peut causer des dommages matériels, de sérieuses blessures corporelles ou la mort.
NOTE: The Pennant appliance and all other gas appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line.
Distance from Gas Meter or Last Stage Regulator
Size and
Gas Type 0-100'
500 natural 1½" 3.8 cm 2" 5.1 cm 2" 5.1 cm 500 propane 1" 2.5 cm 1½" 3.8 cm 1½" 3.8 cm 750 natural 2" 5.1 cm 2" 5.1 cm 2½" 6.4 cm 750 propane 1½" 3.8 cm 1½" 3.8 cm 2" 5.1 cm 1000 natural 2" 5.1 cm 2½" 6.4 cm 3" 7.6 cm 1000 propane 1½" 3.8 cm 2" 5.1 cm 2½" 6.4 cm 1250 natural 2½" 6.4 cm 2½" 6.4 cm 3" 7.6 cm 1250 propane 2" 5.1 cm 2" 5.1 cm 2½" 6.4 cm 1500 natural 2½" 6.4 cm 3" 7.6 cm 3" 7.6 cm 1500 propane 2" 5.1 cm 2½" 6.4 cm 2½" 6.4 cm 1750 natural 2½" 6.4 cm 3" 7.6 cm 3" 7.6 cm 1750 propane 2" 5.1 cm 2½" 6.4 cm 2½" 6.4 cm 2000 natural 3" 7.6 cm 3" 7.6 cm 3½" 8.9 cm 2000 propane 2½" 6.4 cm 2½" 6.4 cm 3" 7.6 cm
Notes:
1. These gures are based on 1/2" (0.12 kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe ttings must be considered when determining gas pipe sizing.
0-31 m 100-200' 31-61m 200-300' 61-91m
Table 7. Gas Piping Size.
Page 15
Low Temperature Pennant
SENSOR
VALV E
THERMOMETER
SENSOR
TEMPERATURE
GLOBE VALV E
CHECK VALV E
W/ FAST FILL BYPASS
PRESSURE REDUCING VALV E
WITH AIR SCOOP AND AUTO AIR VENT
EXPANSION TANK
3-WAY VALVE
VALV E
VALV E
PURGE
PUMP
ADDITIONAL REQUIREMENTS.
WITH LOCAL CODES AND ORDINANCES FOR
PIPING CONFIGURATION AND VA LVING, CHECK
WARNING: THIS DRAWING SHOWS SUGGESTED
INSTALLAIR VENTS AT HIGH POINTS IN SYSTEM.
PIPING&SIZING OF EXPANSION TANK PER TANK MANUFACTURER'S INSTRUCTIONS.
PRIMARY/SECONDARY MANDATORY FOR ALL VARIABLE FLOW SYSTEMS.
BOILER WATER CONNECTIONS (INLET/OUTLET) MAYVARY. VERIFY CONNECTION ORIENTATION.
BOILER CIRCUIT PIPING MUST BE EQUAL BOILER WATER CONNECTION SIZE.
DIMENSION "C" TO BE4PIPE DIAMETERS.
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS.
TEMPERATURE SENSORS REQUIRE FIELD INTERLOCK TO BOILER CONTROLS.
COMBINED FLOW OF ALL BOILERS.
COMMON PIPING MUST BE SIZED FOR
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER AND 30 FEET OF FULL-SIZED PIPING.
MINIMUM INLET WATER TEMP = 70°F
LEGEND
Cold Water
Make-Up
Pump
System
Supply
System
System
Return
C
3-Way Valve
Mounted on Pennant
Pump Mounted
on Pennant
System Return
PRIMARY/SECONDARY MANDATORY FOR ALL VARIABLE FLOW SYSTEMS.
INSTALLAIR VENTS AT HIGH POINTS IN SYSTEM.
PIPING&SIZING OF EXPANSION TANK PER TANK MANUFACTURER'S INSTRUCTIONS.
COMMON PIPING MUST BE SIZED FOR COMBINED FLOW OF ALL BOILERS.
BOILER WATER CONNECTIONS (INLET/OUTLET) MAYVARY. VERIFY CONNECTION ORIENTATION.
BOILER CIRCUIT PIPING MUST BE EQUAL BOILER WATER CONNECTION SIZE.
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER FULL-SIZED PIPING.
DIMENSION "C" TO BE4PIPE DIAMETERS. MINIMUM INLET WATER TEMP = 70°F
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS.
TEMPERATURE SENSORS REQUIRE FIELD INTERLOCK TO BOILER CONTROLS.
AND 30 FEET OF
WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING, CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
C
C
System
Pump
Cold Water
Make-Up
3-Way Valve
Mounted on Pennant
System
Supply
Page 15
THERMOMETER
TEMPERATURE
Figure 4. Suggested Piping - Hydronic Boiler.
GLOBE VA LV E
CHECK VA LV E
LEGEND
PRESSURE REDUCING VA LVE W/ FAST FILL BYPASS
PURGE
Pump Mounted
3-WAY VALV E
VALV E
on Pennant
EXPANSION TANK WITH AIR SCOOP AND AUTO AIR VENT
PUMP
Figure 5. Hydronic Piping — One Boiler, Multi-Temperature System.
Page 16
Page 16
LAARS Heating Systems
SECTION 4A. Water Connections — Pennant Boiler
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psig (82.7 kPa) static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size)
to a drain or in a manner to prevent injury in the event
of pressure relief. Install an air purger, an air vent, a diaphragm-type expansion tank, and a hydronic ow check in the system supply loop. Minimum ll pressure must be 12 psig (82.7 kPa). Install shutoff valves where required by code.
See suggested piping diagrams (Figures 4-5).
These diagrams are meant only as a guide. Com pon­ents required by local codes must be properly installed.
Note the recommended location of the
temperature sensor on the diagrams; you must provide
a location for the additional sensor shipped with the
Pennant. This sensor may be strapped onto pipe from 1" to 4" diameter, or inserted into an immersion well.
4A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet connection of an automatic ll valve.
2. Install a suitable back ow preventer between the automatic ll valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air
handling appliances where they may be exposed to refrigerated air circulation must be equipped with ow
control valves or other automatic means to prevent gravity circulation of the boiler water during the
cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be provided with a low water cutoff device either as a part
of the boiler or at the time of boiler installation.
4A.3 Water Flow Requirements — Boiler
Low Temperature Pennant Boilers are equipped
with a mounted pump. The pumps are sized for the
boiler’s head loss and 30 feet of full-size piping (same
size as boiler outlet), with a normal number of ttings.
The boilers must be piped in a primary-secondary sys-
tem, such that the boiler’s pump only serves the boiler.
Figures 4 and 5 show examples of this type of piping.
The minimum inlet water temperature to the
Pennant is 70°F (20°C). The mixing system on the Pennant will ensure that the heat exchanger in the Pennant does not see water that is less than 120°F (49°C), so that excessive condensation does not form on the heat exchanger.
Table 8 shows a relationship between water ow
through the boiler and the temperature difference (rise)
between the inlet and outlet of the boiler. This table
will enable the user to test the boiler for proper water
ow. Since the boiler has a mixing system that sends
a portion of the hot water from the boiler outlet to the
boiler inlet, the water ow coming out of the mixing
system will vary, depending on the return water
temperature.
4A.4 Freeze Protection — Boiler
Boiler installations are not recommended in areas where the danger of freezing exists unless proper precautions are made for freeze protection. A non toxic, heating system, anti-freeze may be added to the
hydronic system provided that the concentration does
not exceed 50% and the anti freeze contains an anti foamant. Power outage, interruption of gas supply,
failure of system components, activation of safety
devices, etc., may prevent a boiler from ring. Any time a boiler is subjected to freezing conditions,
and the boiler is not able to re, and/or the water
is not able to circulate, there is a risk of freezing in the boiler or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the boiler, which could
result in leaking or ooding conditions.
IMPORTANT NOTES: Different glycol products may provide varying degrees of protection. Glycol products must be maintained properly in a heating system, or they may become ineffective. Consult the glycol speci­fications, or the glycol manufacturer, for information about specific products, maintenance of solutions, and set up according to your particular conditions. Never use ethylene glycol (automotive antifreeze).
Size 20°F (11°C) 25°F (14°C) 30°F (17°C) 35°F (19°C)
gpm lpm gpm lpm gpm lpm gpm lpm
500 43 161 34 129 26 107 24 92
750 64 241 51 193 43 161 36 138 1000 85 321 68 257 57 214 49 184 1250 106 401 85 322 71 269 61 231 1500 128 483 102 386 85 322 73 276 1750 N/R N/R 11 9 451 99 375 85 322 2000 N/R N/R 103 515 113 429 97 368
Notes: gpm = gallons per minute, lpm = liters per minute, Maximum temperature rise is 35°F (19°C), as shown. N/R = not recommended.
Table 8. Temperature Rise - Boiler.
Page 17
Low Temperature Pennant
Page 17
SECTION 4B. Water Connections — Pennant Water Heater
4B.1 Water System Piping — Water Heater
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used when rigid hangers are installed.
The Pennant can be used with several different
types of readily available storage tanks. Pennant units have a circulating pump built into the water heater.
The pumps used are sized for the head loss through the
heater, plus 30 feet (9.1 m) of full-sized piping (same size as boiler outlet) and a normal number of ttings.
Pumps used are sized for soft, normal or hard water, so make sure the unit matches the water quality of the
installation.
Pipe the outlet from the heater’s relief valve such that any discharge from the relief valve will be conducted to a suitable place for disposal when relief
occurs. Do not reduce line size or install any valves in this line. The line must be installed to allow complete drainage of both the valve and the line.
Suggested piping diagrams are shown in Figures
6,7,8 and 9. These diagrams are meant only as a guide.
Components required by local codes must be properly
installed.
Note the recommended location of the temperature sensor on the diagrams. The Pennant is
shipped with an additional sensor that can be used in
the storage tank, in lieu of a separate tank thermostat.
The minimum inlet water temperature for the
Low-Temp Pennant is 70°F (20°C). The mixing
system on the Pennant will ensure that the heat
exchanger in the Pennant does not see water that is less than 120°F (49°C), so that excessive condensation does not form on the heat exchanger.
4B.2 Hot Water Supply Piping — Water Heater
Follow the tank manufacturer’s guidelines for completion of the hot water system connections.
NOTE: A listed temperature and pressure relief valve listed as complying with the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems (ANSI Z21.22/ CSA 4.4), of suitable discharge capacity must be installed in the separate storage tank system.
If the Pennant water heater is installed in a closed
water supply system, such as one having a backow
preventer in the cold water supply line, the relief valve
may discharge periodically, due to thermal expansion. Means (such as a properly-sized expansion tank) shall be provided to control thermal expansion. Contact the
water supplier or local plumbing inspector on how to
control this situation.
4B.3 Water Flow Requirements — Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
be deposited on the unit’s heat exchanger. This is commonly known as scaling. The amount of minerals will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water ow requirements for the Pennant water heater are based upon the hardness of the water. The water ow
is kept high enough to prevent scaling, but low enough
to prevent tube erosion. For extremely soft or hard water, cupro-nickel tubes are available. Contact a
Laars representative if you have questions or concerns
about water quality.
Pennant water heaters are built with a mounted
pump that is sized for soft, normal or hard water. The
pumps used are sized for the head loss through the
heater, plus 30 feet (9.1m) of full-sized piping (same size as heater outlet) and a normal number of ttings.
Table 9 species water ow rates for water
heaters, which will enable the user to ensure that the
Pennant is getting the correct water ow when it is in operation.
4B.4 Combined Water Heating (potable)
and Space Heating — Water Heater
NOTE: Combined systems must be allowed by and
installed per local codes.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
water used for space heating.
This water heater when used to supply potable water shall not be connected to any heating system or component(s) previously used with a non-potable
water heating appliance.
When the system requires water for heating at temperatures higher than required for other uses, an anti-scald mixing or tempering valve shall be installed to temper the water for those uses in order to reduce scald hazard potential.
4B.5 Freeze Protection — Water Heater
Although Pennant water heaters are design-
Page 18
Page 18
LAARS Heating Systems
certied for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from ring. Any time a heater is subjected to freezing conditions, and the
heater is not able to re, and/or the water is not
able to circulate, there is a risk of freezing in the heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or ooding conditions.
Contact the local factory representative or Laars
for additional information.
Size
500 45 68 90 19 13 9 170 257 341 10 7 5
750 45 68 90 28 19 14 170 257 341 16 10 8 1000 45 68 90 38 25 19 170 257 341 21 14 10 1250 68 68 90 31 31 24 257 257 341 17 17 13 1500 68 68 90 38 38 28 257 257 341 21 21 16 1750 68 68 90 44 44 33 257 257 341 24 24 18 2000 112 112 112 30 30 30 424 424 424 17 17 17
Notes:
Soft Water = 1 to 7.5 grains hardness Normal Water = 7.6 to 17 grains hardness
GPM Water Flow Temperature Rise °F LPM Water Flow Temperature Rise °C
Soft Normal Hard Soft Normal Hard Soft Normal Hard Soft Normal Hard
Hard Water = more than 17 grains hardness GPM = gallons per minute LPM = liters per minute
Table 9. Temperature Rise — Water Heater.
Figure 6. Suggested Piping — One Water Heater, One Tank.
Page 19
Low Temperature Pennant
Page 19
Figure 7. Suggested Piping — Multiple Water Heaters, One Tank.
Figure 8. Suggested Piping — One Water Heater, Multiple Tanks.
Page 20
Page 20
LAARS Heating Systems
Figure 9. Suggested Piping — Multiple Water Heaters, Multiple Tanks.
SECTION 5. Electrical Connections
WARNING
The appliance must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electrical Code, Part 1, in Canada. Do not rely on the gas or water piping to ground the metal parts of the boiler. Plastic pipe or dielectric unions may isolate the boiler electrically. Service and maintenance personnel, who work on or around the boiler, may be standing on wet floors and could be electrocuted by an ungrounded boiler.
L’appareil doit être relié à la terre conformément aux exigences de la réglementation locale ou, en l’absence d’une telle réglementation, à la plus récente édition du National Electrical Code (Code national de l’électricité) ANSI/NFPA 70 aux États­Unis, et à la plus récente édition du Code Canadien de l’électricité 1 Code Part 1) CSA C22.1, au Canada. N’utilisez pas les tuyauteries d’eau ou de gaz pour mettre à la terre les pièces métalliques de la chaudière; des tuyauteries en plastique ou des raccords union diélectriques peuvent isoler électriquement la chaudière. Les employés qui sont appelés à travailler sur la chaudière ou autour peuvent être électrocutés par une chaudière qui n’est pas mise à la terre.
AVERTISSEMENT
ère
partie (Canadian Electrical
Page 21
Low Temperature Pennant
Page 21
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made in the eld
wiring terminal strip, which is located to the left of the
blower.
NOTE: All internal electrical components have been pre-wired. No attempt should be made to connect elec­trical wires to any other location except the wiring box.
5.1 Main Power
5.1.1 Sizes 500-1500
Pennant sizes 500-1500 use a single 120-volt
fused supply. The installer can change the single
service heaters to use a separate circuit for the pump, if
desired. Instructions to make this change are found in
Section 5.1.3.
Pennant 500-1500 main power (L1, N1 & Ground) shall be connected to the three wires (10 AWG) supplied. Over-current protection ratings can be
found in Table 10.
5.1.2 Sizes 1750-2000
Pennant sizes 1750-2000 require two 120-volt fused supplies.
Heater circuit can be identied with 10AWG
wires to include black, white and green (all solid
colors). Pump circuit can be identied with three 12AWG wires to include a black wire with a white tracer (stripe), a white and green wire.
5.1.3 Separate Pump Circuit
Conversion to separate pump circuit will neces­sitate removing the three jumpers within the internal wiring of the 120-volt portion of the heater (see Figure
10). Only do this with the power disconnected to the
unit!
To rewire the pump circuit, bring in another
120-volt fused supply (L2, N2 & Ground). Connect
incoming power (L2) to the main power switch using
spade (fork) terminal. From the other side of the main
power switch connect to the main terminal block using
a ¼" female insulated quick connect. This will be
the same position where the jumper had terminated (see Figure 10). Connect N2 and Ground to the main
terminal block using ¼" female insulated quick connect
(refer to Figure 10).
5.1.4 All Sizes
Ladder diagrams are shown in Figures 12 and 13. Wiring diagrams are shown in Figures 14 through 16.
Field wiring is shown in Figure 11.
on the Pennant temperature control at the factory.
External Alarm: The eld terminal strip has
terminals for a dry contact that is closed when the
ignition control locks out. These terminals are labeled “ALRM” and “ALRM”.
Additional Call For Heat: Terminals labeled
“COMD” and “HTD” can be used to call the Pennant for heat. These terminals are shipped with a jumper between them. Remove the jumper to use these terminals. The Pennant is controlled by the temperature
sensor, and the temperature must be calling for heat
for the Pennant to re, regardless of any connections between “COMD” and “HTD”, but the Pennant will not re if this connection is broken.
Other Field Interlocks: Other safety switches
that are intended to prevent the Pennant from ring
(such as fan proving switches, powered louver end
switches, etc.) The terminals are marked “OTHER INTS <COM> <NO>”. These terminals are shipped with a jumper between them. Remove jumper to use these terminals. The Pennant will not re if this connection is broken.
Size Circuit Heater Pump
500 20 15 15 750 20 15 15 1000 (TACO) 20 / (B&G) 30 20 15 1250 30 25 15 1500 30 25 15 1750 25 20 2000 25 20
Table 10. Electrical Data (Amps).
Single Two Circuit
5.2 Field Wiring
Temperature Sensor: The Low Temperature Pennant is controlled by a sensor that requires place-
ment in the system loop or storage tank. A sensor well is shipped with the unit, as well. This sensor placement
allows the Pennant to be called for heat, based on the
system temperature. The sensor is wired to terminals
Figure 10. Removing Jumpers.
Page 22
Page 22
LAARS Heating Systems
Figure 11. Field Wiring.
Page 23
Low Temperature Pennant
Page 23
Figure 12. Ladder Diagram, Sizes 500-1000.
Page 24
Page 24
LAARS Heating Systems
Figure 13. Ladder Diagram, Sizes 1250-2000.
Page 25
Low Temperature Pennant
Page 25
Figure 14. Wiring Diagram, Sizes 500-1000.
Page 26
Page 26
LAARS Heating Systems
Figure 15. Wiring Diagram, Sizes 1250-1500.
Page 27
Low Temperature Pennant
Page 27
Figure 16. Wiring Diagram, Sizes 1750-2000.
Page 28
Page 28
LAARS Heating Systems
SECTION 6. Operating Instructions
6.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all bleeding devices and open make-up water valve. Allow system to fill slowly.
2. If make-up water pump is employed, adjust
pressure switch on pumping system to provide
a minimum of 12 psi (81.8 kPa) at the highest point in the heating loop.
3. If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator
to provide at least 12 psi (81.8 kPa) at the highest point in the heating loop.
4. Open bleeding devices on all radiation units
at the high points in the piping throughout the system, unless automatic air bleeders are
provided at such points.
5. Run system circulating pump for a minimum of 30 minutes with the boiler shut off.
6. Open all strainers in the circulating system,
check flow switch operation, and check for
debris. If debris is present, clean out to ensure proper circulation.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank should not exceed ¼ of the total, with the balance lled with air.
9. Start up boiler according to the procedure in this manual. Operate the entire system, including the pump, boiler, and radiation units for one (1) hour.
10. Recheck the water level in the expansion tank. If the water level exceeds ¼ of the volume of the expansion tank, open the tank drain, and drain to that level.
11. Shut down the entire system and vent all
radiation units and high points in the system
piping, as described in Step 4.
12. Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up water valve.
13. Check gauge for correct water pressure and also check water level in the system. If the height
indicated above the boiler insures that water is at the highest point in the circulating loop, then the
system is ready for operation.
14. Refer to local codes and the make-up water
valve manufacturer’s instructions as to whether the make-up water valve should be left open or
closed.
15. After placing the unit in operation, the ignition system safety shutoff device must be tested. First,
shut off the manual gas valve, and call the unit
for heat. After the pre-purge and ignitor heat-up
time, the main gas terminals will be energized,
attempting to light, for four (4) seconds, and then will de-energize. The unit will go into lockout mode. Second, turn the power off and then on
again, open the manual gas valve and allow the
unit to light. While the unit is operating, close the
manual gas valve and ensure that power to the
main gas valve has been cut.
16. Within three (3) days of start-up, recheck all air bleeders and the expansion tank as described in Steps 4 and 8 above.
Important: The installer is responsible for identifying to the owner/operator the location of all emergency shutoff devices.
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that may have been under water.
AVERTISSEMENT
N’utilisez pas cet appareil si l’une de ses pièces est passée sous l’eau. Appelez tout de suite un techni­cien en entretien et en réparation pour inspection de l’appareil et remplacement des pièces du sys­tème de commande, et des pièces de commande du circuit gaz, qui sont passées sous l’eau.
6.2 Sequence of Operation
The amber “Ready” light on the front panel
indicates that the control system is energized. Upon a
call for heat from the system temperature sensor, the
green “Heat” indicator on the front panel will light. The green “Pump” indicator on the front panel will light.
Once the water ow switch makes, and if all of
the safety interlocks are closed, the ignition module(s) will energize the blower(s) for a 15-second pre-purge, followed by a 20-second period to allow the ignitor(s)
to heat.
Energizing the blower pressurizes the air box
(which supplies air to the burners) and closes the
normally-open contact(s) of the airow pressure switch(es). This allows the ignition module to proceed with the ignition sequence.
The blocked ue pressure switch senses the
pressure difference between the exhaust plenum and the blower inlet plenum. It will interrupt the airow sensing circuit if this pressure exceeds a maximum value. If airow is not proven, the ignition module
will either attempt ignition again (up to three times) or will lockout (if the optional lockout ignition module is
used).
The ignition module checks that the ignitor
current has reached a minimum value and energizes
the gas valves at the end of the ignitor-heating period.
The green indicators on the front panel will
light, indicating that the gas valves are open. After a 4-second trial for ignition, the ignitor switches off, and
Page 29
Low Temperature Pennant
Page 29
unless the ame sensor detects a ame, the gas valves
will close and the ignition module will either attempt ignition again (up to three times) or will lockout (if the
optional lockout ignition module is used).
Note: At this point, if gas pressure is below the required 5” w.c. minimum, the Pennant may lock out.
If ame is sensed, the burner will continue to re as long as there is a call for heat. If there is a subsequent loss of ame signal, the burner will attempt
re-ignition up to three times (only once if optional
lockout ignition module is used.) Loss of ame signal from the rst ignition module will cause shutdown of the heater.
When the call for heat is satised, the gas
valves close and the blower(s) continues to run for 30
seconds. The pump will continue to run for the length
of time selected at startup by the adjustment of the
pump time delay (Pd).
If a call for heat is prevented from being satised
either by a safety interlock or due to an ignition lock-
out, the red “Service” indicator on the front panel will light. To reset the standard ignition module, toggle the Pennant power switch off, and then on again. (To
reset the optional single try lockout ignition module,
the reset button on the module must be pressed. Inter ­rupting power to this module will not reset the lockout.)
The Pennant 1250 through 2000 models have two
ignition modules that control different burners.
6.3 Temperature (Operating) Control
The Pennant temperature control operates by
measuring the system temperature. It also controls the Pennant pump operation and the mixing system, which tempers the water entering the heat exchanger to prevent damage from excessive condensation.
6.3.1 Temperature Control Overview
The digital display on the control has the following uses:
• To display the system temperature during
normal operating mode.
• To allow the user to view and adjust the control
settings. There are four buttons on the controller. Top left returns to the beginning. Bottom left is the enter button. Top right is the up arrow. Bottom right is the down arrow.
The temperature control face contains an LCD
screen. The LCD screen will display the system temperature during normal operation. When the control is rst powered up, it displays “ZZZ”. It then ashes the control software number. It then displays the temperature at the system sensor. After
the temperature is displayed, the current settings
(parameters) may be viewed. To scroll through the
parameters, press the down arrow button to advance
to the next parameter. Press the enter button to choose that parameter. Press the up or down arrow to raise, lower or toggle to value of that parameter. Press enter to save a changed value.
By depressing the upper left hand button at
any time during the programming, the menu may be
returned to the beginning.
After about 30 seconds of button inactivity, the
display will revert back to the system temperature.
6.3.2 Programming Parameters - Boilers
When the control is rst turned on, it ashes “ZZZ” and then “022” to indicate that the boiler software is in the control. When the down arrow is pressed, the boiler menu is brought up.
rT – Boiler Return Temperature
This is a display only. This is the temperature at
the boiler’s inlet sensor. This is not system return
temperature, as the water has been mixed with
hot outlet water, for boiler protection.
oAt – Outdoor Air Temperature
This is a display only. This is the outdoor air
temperature, if outdoor reset is used. Must use
optional outdoor reset sensor (p/n 2400-021).
CSP – Calculated Setpoint
This is a display only. When outdoor reset is
used, this is the temperature that is calculated by
the control, based on the settings and conditions,
which becomes the setpoint of the boiler.
bSP – Boiler Setpoint
This is the setpoint for rT (the boiler inlet
temperature sensor). Default is 190°F. Range is
from 140°F to 210°F.
LSP – System Setpoint
This is the setpoint for system, read at the system
sensor that is placed in the system loop. Default
is 180°F. Range is from 60°F to 210°F.
LdF – System Setpoint Differential
This is the differential for LSP. Default is 2.0°F.
Range is 1°F to 30°F.
bdf – Boiler Setpoint Differential
This is the differential for bSP. Default is 10°F.
Range is 1°F to 30°F.
oAr – Outdoor Reset
This enables or disables the outdoor reset
function. Default is “oFF”. Toggle to “on”
if outdoor reset is going to be used. Must use
optional outdoor reset sensor (p/n 2400-021).
oTo - Warm Outdoor Temperature
Upper point of reset curve, where system shutoff
is desired. Default 65°F. Range is 55°F to 70°F.
oAC – Design Temperature
Lower point of reset curve, at which the
maximum water setpoint is needed. Default is
0°F. Range is from –50°F to 60°F.
oAL – Minimum Setpoint
This is the minimum allowable calculated
setpoint, regardless of outdoor temperature.
Default is 160°F. Range is 70°F to 180°F.
Page 30
Page 30
LAARS Heating Systems
oAH – Maximum Setpoint
This is the maximum allowable calculated setpoint, regardless of outdoor temperature. Default is 190°F. Range is 90°F to 210°F.
rc – Reset Ratio
The ratio of air temperature movement to water
temperature movement. Sets the slope of the reset curve. Default is 1.0. Range is from 0.5 to 5.0.
SP – Minimum Mixed Temperature
This setting is fixed at 125°F, and cannot be change by the user.
Pd – Pump Delay
This is the time delay for the boiler’s mounted
pump. The pump will run for this delay time after the call for heat has ended. Default is 2 minutes. Range is from 0.1 minutes to 10 minutes.
Uni - Units
This allows the user to choose between °F (default) and °C.
6.3.3 Programming Parameters – Water Heaters
When the control is rst turned on, it ashes “ZZZ” and then “018” to indicate that the boiler software is in the control. When the down arrow is pressed, the boiler menu is brought up.
rT – Heater Return Temperature
This is a display only. This is the temperature
at the heater’s inlet sensor. This is not system
return temperature, as the water has been mixed
with hot outlet water, for heater protection.
bSP – Heater Setpoint
This is the setpoint for rT (the heater inlet
temperature sensor). Default is 140°F. Range is
from 140°F to 190°F.
LSP – System Setpoint
This is the setpoint for system, read at the system
sensor that is placed in the system loop. Default
is 140°F. Range is from 60°F to 190°F.
LdF – System Setpoint Differential
This is the differential for LSP. Default is 2.0°F.
Range is 1°F to 30°F.
Pd – Pump Delay
This is the time delay for the heater’s mounted
pump. The pump will run for this delay time after
the call for heat has ended. Default is 2 minutes.
Range is from 0.1 minutes to 10 minutes.
SP – Minimum Mixed Temperature
This setting is fixed at 125°F, and cannot be
change by the user.
bdf – Heater Setpoint Differential
This is the differential for bSP. Default is 10°F.
Range is 1°F to 30°F.
Uni - Units
This allows the user to choose between °F
(default) and °C.
CAUTION Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
6.4 Limit Controls
Pennant appliances are tted with an automatic
reset high limit and a manual reset high limit, both
sensing the outlet temperature of the Pennant.
Water heater high limits are adjustable up to
200°F (93°C) and boiler high limits are adjustable up to 240°F (116°C).
To set the limit controls, remove the control
panel cover and pull the control panel out to gain
access.
6.5 Operating the Burner and Set Up
6.5.1 Set Up for 0 to 2500 Feet Altitude
The Pennant appliance utilizes a modular design
to achieve its stage-ring. The setup must be checked before the unit is put in operation. Problems such as failure to start, rough ignition, strong exhaust odors, etc. can be due to improper setup. Damage to the
Pennant resulting from improper setup is not covered
by the limited warranty.
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are lled with water and all air has been bled from both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. Switch on the appliance power switch located on the right side of the unit.
5. The Pennant will enter the start sequence, as long as the unit is being called for heat. The blower
and pump come on for pre-purge, then the ignitor warm-up sequence starts and after the ignitor warm-up is complete and all safety devices are
veried, the gas valves open. If ignition doesn’t occur, check that there is proper gas supply. Wait 5 minutes and start the unit again. During
initial start up, air in the gas line may cause the
Pennant to “lock out” during the rst few trials for ignition. Depending on the ignition modules
installed, the manual reset button on the ignition modules may need to be depressed to restart the
Pennant.
6. When the unit is running, the supply gas pressure must be checked. Inlet gas pressure must not exceed 13” W.C. (3.2kPa). The minimum inlet gas pressure is 5” W.C. (1.2kPa).
7. Once the inlet gas pressure is veried, the
outlet gas pressure from each valve (manifold gas pressure) must be checked, and adjusted, if
Page 31
Low Temperature Pennant
Page 31
necessary. The manifold gas pressure must be
2.5” W.C. (0.62kPa).
8. Complete the setup by checking the CO2 at the outlet of the unit. The CO2 should be 8% for natural gas, or 9.2% for propane.
9. After placing the appliance in operation, the Burner Safety Shutoff Device must be tested.
To test: (a) Close gas shutoff valve with burner
operating.
(b) The ame will go out and blower will
continue to run for the post purge cycle. One additional attempt to light will follow. Ignition will not occur as the gas is off. The
ignition control will lockout, and will have
to be reset before the unit will operate.
(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will start again and the burner will start. The
appliance will return to its previous mode
of operation.
NOTE: Models 1250-2000 have two ignition controls and two ignitors, which work together to ensure all of the burners light properly.
6.5.2 High Altitude Adjustment and Set Up
Pennant appliances may be operated at high
altitude (7700 ft., 2347 m) with a reduction in output of approximately 10%. At altitudes of less than  or more than 7700 ft. (2347 m) the appliance will per-
form equally as well, but with differing reductions in
output. At elevations higher than 7700 ft. (2347 m) the reduction in output will exceed 10% and at elevations below 7700 ft. (2347 m) it will be less than 10%. High
altitude adjustment must not be made on appliances
operating at elevations below 2500 ft. (762 m).
No orice changes are required to adjust the
Pennant appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the gas
valve manifold pressure and the air shutter(s). The
required instruments used to assist in these adjustments
are a CO2 or O2 Analyzer and a U-Tube Manometer or other device capable of reading a pressure of 2.5-3.0 inches W.C. (0.62-0.75 kPa).
Start the adjustment process by checking the CO2
in the “as installed” condition. Adjust the air shutter(s) so that the CO2 is about 8% or the O2 is about 6.8% for appliances operating on Natural Gas. For appliances operating on LP Gas adjust the air shutter(s) so that the CO2 is about 9.2% or the O2 is about 6.8%. Appliances
with two blowers should be adjusted so that the air
shutters below each blower are open the same amount.
Once the CO2 or O2 has been set, the manifold
pressure may be adjusted. Remove the 1/8 NPT plug
from the lower side of the gas valve that is to be set
and install a tting, hose and manometer. Start the appliance and observe the manifold pressure. Manifold pressure must be adjusted to 3.0 in. W.C. (0.75 kPa)
(for high altitude only, standard operating pressure is
2.5 in. W.C. (0.62 kPa)). It is adjusted by removing the
slotted cap on the gas valve and turning the adjustment screw (beneath the cap) clockwise to increase pressure and replaced after the adjustments have been
completed and the tting, hose and manometer have been removed and the 1/8” plug has been replaced. Repeat this process until all gas valves have been set. Note: The pressure can be set only when the appliance
is operating and only when the particular gas valve being adjusted is energized by a call for heat from the
staging control.
After all of the gas valve manifold pressures
have been set, the CO2 or O2 must be reset. CO2 or O2
will have changed when the manifold pressure was
adjusted. Open the air shutter(s) to reduce the CO2 or O2 to the values achieved previously.
The procedure is complete when all gas valves
are adjusted to a manifold pressure of 3.0 in. W.C. (0.75 kPa) and the CO2 is adjusted to 8.0% for Natural Gas appliances or 9.2% for LP appliances. When using an O2 analyzer, the correct O2 is 6.8% for both Natural Gas and LP appliances.
CAUTION Should any odor of gas be detected, or if the gas burner does not appear to be functioning in a normal manner, close main shutoff valve, do not shut off switch, and contact your heating contractor, gas company, or factory representative.
6.6 Shutting Down the Pennant
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Pennant and
be sure to also protect building piping from
freezing.
This step to be performed by a qualied
service person.
6.7 To Restart the Pennant
If drained, follow Section 6.1 in this manual for
proper lling and purging.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch, manual reset high limit, etc.).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a pre-purge period and ignitor warm-up period, followed by ignition.
Page 32
Page 32
LAARS Heating Systems
SECTION 7. Maintenance
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
ammable vapors and liquids.
5. If the appliance is not going to be used for extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
protected from freezing.
6. Low water cutoffs, if installed, should be checked every 6 months. Float type low water cutoff should be ushed periodically.
7. Inspect ue passages, and clean with brushes/ vacuums, if necessary. Sooting in ue passages indicates improper combustion. Determine the cause and correct.
8. Inspect the vent system and air intake system,
and if the vent system is Category III, ensure
that all joints are sealed properly. If joints need
to be resealed, follow venting manufacturer's
instructions to clean and reseal vent system.
proper functioning. It is strongly recommended that a qualied service technician inspect the basic items listed below every year. a. Ignition control g. High limit b. Ignitor h. Pump c. Water temp. control i. Low water cutoff d. Automatic gas valve j. Relays e. Pressure switches k. Flow switch and tubing l. Gas train f. Blower m. Control components
7.2.1 Burners
Close main manual gas valve before proceeding.
Checking the burners for debris - Remove the ignitor
inspection panels(s) and ignitor(s) and inspect the
burners through the ignitor hole(s) using a ashlight to illuminate. If there is any indication of debris on
the burners that are visible, all the burners will need
to be inspected more thoroughly. Remove the screws from around the front of the air box (large panel from
which the ignitor inspection panel(s) were removed),
and remove the large panel. Remove the gas manifold assemblies and the burner panels. Inspect the burners.
Clean burners, if necessary, by blowing compressed air from the outside of the burners into the center
of the burner. A dirty burner may be an indication of improper combustion or dirty combustion air. Determine the cause, and correct. Replace the burners
in the reverse order
7.2 Appliance Maintenance and Component Description
Only genuine Laars replacement parts should be used.
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Attention
Lors d’entretien ou de réparation des commandes, étiquetez tous les câbles avant de les déconnecter. Des erreurs de câblage peuvent provoquer des fonctionnements incorrects et dangereux. Après toute intervention d’entretien ou de réparation, vérifier que l’appareil fonctionne correctement.
See Figures 17 and 18 for locations of gas train
and control components.
The gas and electric controls on the appliance
are engineered for long life and dependable operation, but the safety of the equipment depends on their
Figure 17. Gas Train Components.
Page 33
Low Temperature Pennant
Page 33
7.2.2 Filter
The lter used in the Pennant is washable. Since the lter is washable, it will only need replacement occasionally. If lter replacement is needed, it should only be replaced with a factory part. Inspect the air lter monthly, or more often in dirty environments. If there is debris on the air lter, remove it from the lter box, and wash it with mild soap and water. Ensure that the lter is completely dry before reinstalling.
7.2.3 Gas Valves
The gas valves are designed to operate with
supply pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).
To remove a valve, shut off 120-volt power
and the manual gas shutoff valve. Remove the top front panel from the unit. Disconnect the wires to the valve. Disengage the anged tting before and after the valve, and remove the valve. Re-install in reverse order. Ensure o-rings are properly installed for both inlet and outlet. Turn on manual gas shutoff valve and
120 volt power and check appliance operation and
tightness of gas valve connections.
7.2.4 Manual Reset High Limit Control
The high limit switch is manual reset switch with
an adjustable set point, up to 240°F (116°C) on boiler models and 200°F (93°C) on water heater models and boilers ordered with low temperature controls. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull the switch off the control panel. Remove the capillary and bulb from the thermal well located in the header. Replace in reverse order.
7.2.5 Automatic Reset High Limit Control
An automatic reset high limit is used in addition
to the manual reset high limit. The high limit switch has an adjustable set point, up to 240°F (116°C) on boiler models and 200°F (93°C) water heater models and boilers ordered with low temperature controls. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access the mounting screws. Remove the screws, and pull the switch off the control panel. Remove the capillary and bulb from the thermal well located in the header. Replace in reverse order.
7.2.6 Temperature Control
The temperature control is an on/off control that
also manages the mixing system.
To replace the control, disable the 120v supply
power to the appliance. Unplug all of the electrical connectors, remove the retainer clip and the control. Replace the control in the reverse order.
7.2.7 Ignition Control
The ignition controls ensure the proved interrupt-
ed-type ignition system. They control the hot surface ignitors and prove that the ame signal is appropri-
Figure 18. Typical Control Panel.
Page 34
Page 34
LAARS Heating Systems
ate for powering the gas valves. It also controls the blower’s pre-purge and post-purge. Pennant models 500 through 1000 have one ignition control. Models 1250 through 2000 have two ignition controls.
To replace a control, shut off the 120-volt power
to the appliance. Remove the cover from the control panel. Remove the electrical connectors from the ignition control. Take out the controller’s mounting screws, and pull the controller out. Replace in reverse order.
7.2.8 Ignitor
The ignitors used are 120v “Hot Surface” type.
They are energized whenever there is a call for heat and switched off when ignition is established and the
ame has been sensed. Pennant models 500 through 1000 have one ignitor. Models 1250 through 2000 have two ignitors. To replace the ignitor, shut off the
120-volt power to the appliance, remove the ignitor
access panel, disconnect the Molex connector, remove the two mounting screws on the ignitor ange, and pull the ignitor out. Install in reverse order, always using a new ignitor gasket with the replacement ignitor.
Caution
Ignitor gets hot. To avoid injury, handle the ignitor with caution.
Attention
Le dispositif d’allumage devient très chaud. Manipulez le dispositif d’allumage avec précaution.
7.2.9 Transformer
The Pennant’s transformer is not capable of
supplying control voltage for external devices such
as zone valves, which must have their own separate
power supply.
Some Pennant units have more than one transformer, and all transformers are not the same size, so ensure that replacement transformers are the
appropriate ones.
Should a transformer need replacing, shut off the
120-volt power. Unplug the transformer wires, remove the mounting screws and remove the transformer. Replace transformer in the reverse order.
7.2.10 Blowers
The combustion air blowers bring the combustion air for the Pennant from the upper chamber to the
lower chamber. Mixing of the gas and air occurs in the burners. Models 500, to 1000 each have one blower, and models 1250 to 2000 each have two blowers.
If a blower change is required, turn off the 120-
volt power and gas supply to the unit. Remove the front panel. Disconnect the blower’s wire harness. Remove the screws at the blower ange, and pull the
blower out. Replace blower in reverse order, ensuring that all joints are made correctly. After replacement,
ensure that the unit operates properly, by following the
set-up procedure in this manual.
7.2.11 Flow Switch
The Pennant uses a paddle-type ow switch to ensure that the unit has water ow before ignition is allowed. To replace the ow switch, turn off the 120­volt power to the appliance. Isolate the boiler or water heater from the system by closing the isolation valves.
Caution
Water may be hot enough to scald. Allow water to cool before proceeding.
Attention
L’eau peut être chaude au point de vous brûler. Laissez refroidir l’eau avant d’intervenir.
Release pressure in the system by actuating the pressure relief valves or eld supplied boiler drain valve. Remove cover from the ow switch and disconnect the wires. Unthread the ow switch from piping. Ensure the new ow switch paddles are
trimmed to the same size as the original paddles, and
reinstall in the reverse order. For boiler and other static
pressure systems, restore the system pressure to the
original setting (or 10 psi minimum).
7.2.12 Heat Exchanger Coil
WARNING
Black carbon soot buildup on a dirty heat exchanger can be ignited by a random spark or flame thereby creating a risk of fire or explosion. To prevent this from happening, dampen the soot deposits with a wet brush or fine water spray before servicing the heat exchanger.
AVERTISSEMENT
L’accumulation de suie sur un échangeur thermique sale peut s’enflammer au contact d’une étincelle ou d’une flamme et présenter un risque d’incendie ou d’explosion. Afin d’empêcher que cela se produise, humidifier les dépôts de suie à l’aide d’une brosse mouillée ou par une pulvérisation fine d’eau avant d’effectuer l’entretien de l’échangeur thermique.
The Pennant has a premixed burner system. These systems provide the burners with sufcient air
for complete combustion, and black carbon sooting is
seldom experienced. If sooting is suspected, view ports for inspection of the heat exchanger are provided on the side of the boiler. In the unlikely event that there is
a buildup of black carbon soot or other debris on the
heat exchanger, clean per the following:
Page 35
Low Temperature Pennant
Page 35
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas valve on the heater.
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header anges from the inlet and outlet.
6. Allow the heat exchanger to drain. Remove the
front cover(s) by removing the rubber access
strip(s) and the retaining screws. Remove the
venting and remove the top, by removing the
screws that attach the top to the side panels. Remove the side panels. Remove the front lower panels sealing the combustion area. To remove
the gas train, disconnect the unions located
below the intermediate pan and the eld installed
union located outside the cabinet, and pull up, bringing the union end connectors through the
grommets in the intermediate pan. To remove the
intermediate pan, remove the slide out control
assembly and blower(s) to reveal the screws. Remove the screws holding the intermediate pan, and lift up to remove it. The heat exchanger has
integral metal sections attached, which connect
to the frame of the boiler. Locate and remove
the screws along the front, rear and bottom of the integral metal sections, and remove the heat
exchanger and metal sections by lifting up. On the larger appliances, a center heat exchanger
support must be unbolted before it can be
removed..
7. Remove the heat exchanger from the unit. NOTE: Heat exchangers are heavy and may
require two people to remove to avoid personal
injury.
8. Clean the heat exchanger: A light accumulation
of soot or corrosion on the outside of the heat
exchanger can be easily removed. Use a wire
brush to remove loose soot and scale from the
heat exchanger.
9. NOTE: While the heat exchanger is out of the unit, inspect the rewall refractory insulation. Replace if necessary.
10. Inspect the inside of the copper tubes for scale buildup. Scale can build up on the inner surface of the heat exchanger tubes, which can restrict water ow. If the tubes show signs of scaling, clean the internal surface.
11. Reassemble in the reverse order, and check appliance operation after start-up.
NOTE: The warranty does not cover damage caused by lack of required maintenance, lack of water flow, or improper operating practices.
SECTION 8. Trouble Shooting
8.1 Resolving Lockouts
There are many causes of lockouts. The three
most common causes are: (1) inadequate gas supply,
(2) poor combustion, (3) ignitor failure.
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP
tank (LP boilers) is not empty. Then, restart the boiler and observe the operational cycle. After
a 15-second fan pre-purge, the ignitor will heat
up for 40 seconds, and then the unit will light.
If it does not, check the gas supply pressure to the appliance, after resetting the appliance and
attempting another start-up. The gas pressure to the appliance must be above 5 in. w.c. (1.2 kPa) throughout the entire start-up cycle. If it is not,
correct the supply problem (check gas valves or
supply piping). If the supply pressure is adequate, consult the factory for assistance.
2. Poor Combustion: Poor combustion should be suspected if there is a strong ue gas odor. The odor may result from an improper gas/air ratio (high or low O2 or CO2). Pennant appliances operate best with 45% excess air (8% CO2 on natural gas, 9.2% CO2 on LP). Check the CO2 of the appliance and adjust if necessary.
3. Ignitor failure: If the boiler goes through a
normal start cycle but combustion does not
occur, ignitor failure should be suspected. Check
the ignitor by unplugging the ignitor plug and
measuring the ignitor resistance. It should be 50-80 ohms. If the resistance is not 50-80 ohms, replace the ignitor. If the resistance is correct, reset the boiler and check for 120 VAC at the ignitor plug during the start cycle. If there is no
voltage, replace the faulty ignitor wire harness or
the ignition control.
8.2 Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition.
If the gas supply pressure is proper and the gas valves are functioning properly, then burners should
be inspected. There should be no distortion or
perforations in the burners outside of the active burner
port area. Replace if indicated.
8.3 Short Cycling — Boiler
Boiler short cycling is caused when the
load on the boiler system swings rapidly causing
frequent cycling between call for heat and satised conditions. If short cycling is a problem, it may be
due to an oversized boiler, improper control strategy,
incorrect set points or a load distribution problem.
The boiler controls must be set such that the heating loop temperature setpoint does not interfere with
Page 36
Page 36
LAARS Heating Systems
the setpoint of the boiler operating control. If the set
points are correct and the system design, controls
scheme, etc. are xed, the temperature differentials may be increased to reduce short cycling. If desired
temperature response is not achievable without short cycling it may be necessary to install a buffer tank
in the system. Contact your Laars representative to discuss possible remedies.
8.4 Short Cycling — Water Heater
Short cycling will generally occur only in combination space heating and water heating applications when the water heater is operating in the
space-heating mode. If the heating load drops below the minimum input of the water heater for an extended
period, the water heater will have a tendency to short
cycle. If short cycling is frequently experienced,
regardless of the control’s attempt to limit it, the
heating load should be redistributed to control it.
If short cycling occurs in a water heater application, it is probably caused by undersized piping between the water heater and the storage tank or by some other factor that restricts proper water
ow through the water heater. The cause should be determined and corrected.
8.5 High Gas Consumption
Appliances operating with an improper air/ fuel ratio are very inefcient and consequently, have very high gas consumption. Because efciency is high when the CO2 is high (or O2 is low), appliances operating with low CO2 or high O2 (especially LP appliances) consume more gas. Adjust the CO2 or O2 for optimum efciency. If no combustion analyzing equipment (CO2 or O2) is available then a proper adjustment of the air/fuel ratio (CO2 or O2) cannot be accomplished. The CO2 should be 8% at high re for natural gas and 9.2% at high re for LP. To check the CO2, rst verify that the supply gas pressure is within 5 to 13 in. w.c. (1.2 to 3.2 kPa). With the Pennant running, set the air box pressure to 1.5 in. w.c. (0.37
kPa) (as a starting point), by adjusting the air shutter(s)
at the intake of the fan(s). Check the CO2, and adjust the air shutters if further adjustment to the CO2 is needed.
directly through the “inducer” terminals F1 and F2 of the (Fenwal) ignition module. The 24V power to the
T’STAT terminal of both ignition modules is routed
through the safety interlocks.
All 24V wiring is routed through the diagnostic
PC board. Wiring harnesses connect between the
diagnostic PC board and the control components,
indicator board, or eld wiring terminal strip. The diagnostic board contains LEDs that indicate open
status of the safety interlocks, and quick-connect terminals that provide tests points for checking
voltage/continuity at various points in the control circuit.
Line-voltage connections are routed via the
line-voltage terminal buss. Certain control elements that may need to be rewired in the eld are connected via the eld wiring terminal strip rather than to the diagnostic PC board. These include the low-water cutoff (LWCO), water ow switch, and inlet/outlet water temperature sensors.
SECTION 9. Replacement Parts
Only genuine Laars replacement parts should be used.
9.1 General Information
To order or purchase parts for the Laars Pennant,
contact your nearest Laars dealer or distributor. If
they cannot supply you with what you need, contact Customer Service (see back cover for address,
telephone and fax numbers).
9.2 Parts List
See next page for the list of available replace-
ment parts. See Figures 19-21 for exploded views
of the boiler's component systems to help identify
replacements parts.
8.6 Troubleshooting Pennant Controls
A diagnostic panel, that includes test points, as well as diagnostic lights, is provided in the control
module. It is located on the right side of the module, behind the display. To access, remove the retaining
screws from the display cover panel and remove
it. Grasp the control module at its base and pull it outward.
Pennant ladder diagrams are shown in Figures
12 and 13. The wiring connection diagrams are shown
in Figures 14 through 16. The blower is energized
Page 37
Low Temperature Pennant
Page 37
Item Description Size Size Size Size Size Size Size
500 750 1000 1250 1500 1750 2000
Sheet Metal Components - SeeFigure19
1 Panel, Jacket, Side Left 5C3420 5C3420 5C3420 5C3420 5C3420 5C3420 5C3420
2 Panel, Jacket, Side Right 5C3521 5C3521 5C3521 5C3521 5C3521 5C3521 5C3521
3 Panel, Jacket, Front 5C3320 7C3320 10C3320 12C3320
3 Panel, Jacket, Front, Left 15C3320 17C3320 20C3320
4 Panel, Jacket, Front, Right 15C3320 17C3320 20C3320
5 Panel, Jacket, Rear 5C3220 7C3220 10C3220 12C3220 15C3220 17C3220 20C3220
5A Panel, Jacket, Rear, Filter Enclosure 15C3026 15C3026 15C3026
6 Panel, Jacket, Top 5C3021 7C3021 10C3021 12C3021
Panel, Jacket, Top, Left 15C3021 17C3021 20C3021
7 Panel, Jacket, Top Right 15C3025 17C3025 20C3025
8 Control Door, Access 5C3011 5C3011 5C3011 5C3011 5C3011 5C3011 5C3011
9 Plate, Gas Pipe Seal 5C3304 5C3304 10C3304 20C3304 20C3304 20C3304 20C3304
(2) (2) (2) (2) (2) (2) (2)
10 Plate, Cover, Wiring 5C3502 5C3502 5C3502 5C3502 5C3502 5C3502 5C3502
11 Plate, Vent 5C3004 5C3004 10C3004 20C3004 20C3004 20C3004 20C3004
12 Cover, Vent Plate 20C3006 20C3006 20C3006 20C3006
13 Plate, Cover, Filter 5C3002 5C3002 5C3002 20C3002 20C3002 20C3002 20C3002
(1) (1) (1) (2) (2) (2) (2)
14 Collar, Vent 5C3106 10C3100 10C3100 15C3100 15C3100 20C3100 20C3100
16 Air Filter R2014700 R2014700 R2014700 R2014700 R2014700 R2014700 R2014700
16A Trim, Jacket, Front 5C3019 7C3019 10C3019 12C3019 15C3019 17C3019 20C3019
16B Housing, Rain Shield, Pump 5C3015 5C3015 5C3015 5C3015 5C3015 5C3015 5C3015
16C Cover, Housing, Pump 5C3016 5C3016 5C3016 5C3016 5C3016 5C3016 5C3016
16D Bracket, Support, Pump Cover 5C3017 5C3017 5C3017 5C3017 5C3017 5C3017 20C3017
Internal Components - SeeFigures20and21
17 Base Assembly 5C1020 7C1020 10C1020 12C1020 15C1020 17C1020 20C1020
18 Chamber, Front 5C2003 7C2003 10C2003 12C2003 15C2003 17C2003 20C2003
18A Chamber, Left Side, Front 5C2015 5C2015 5C2015 5C2015 5C2015 5C2015 5C2015
18B Chamber, Right Side, Front 5C2016 5C2016 5C2016 5C2016 5C2016 5C2016 5C2016
19 Chamber, Rear 5C2006 7C2006 10C2006 12C2006 15C2006 17C2006 20C2006
20 Chamber Assembly, Left, Bottom 5C2602 5C2602 5C2602 5C2602 5C2602 5C2602 5C2602
21 Chamber Assembly, Right, Bottom 5C2200 5C2200 5C2200 5C2200 5C2200 5C2200 5C2200
22 Chamber, Top 5C2001 7C2001 10C2001 12C2001 15C2001 17C2001 20C2001
23 Chamber, Side, Top 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002
24 Exhaust Plenum 5C2007 10C2007 10C2007 20C2007 20C2007 20C2007 20C2007
25 Bracket, Chamber, Front 5C2009 7C2009 10C2009
Page 38
Page 38
LAARS Heating Systems
(1) (1) (1) (2) (2) (2) (2)
(1) (1) (2) (2) (2) (2) (2)
(2) (2) (2) (2) (2) (2) (2)
(1)
(1) (1) (1) (1) (1) (1)
(1) (1) (1) (1) (1) (1)
(1) (1) (2) (2)
(1)
(1) (1) (1) (1) (1) (1)
(1) (1) (1) (1) (1) (1)
(1) (1) (2) (2)
(1)
(1) (1) (1) (1) (1) (1)
(1) (1) (2) (2)
(1) (1) (1) (1) (1) (1)
Bracket, Chamber, Front Left 12C2011 15C2011 17C2011 20C2011
500 750 1000 1250 1500 1750 2000
26 Bracket, Chamber, Front Right 12C2009 15C2009 17C2009 20C2009
Item Description Size Size Size Size Size Size Size
27 Divider, Chamber, Front 15C2010 20C2002
27A Divider, Upper, Chamber, Front 15C2005 15C2005
27B Divider, Lower, Chamber, Front 15C2002 15C2002
28 Cover, Chamber 5C2004 7C2004
Cover, Chamber, Front Left 10C2004 12C2010 15C2004 17C2010 20C2010
29 Door, Chamber Access 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005
30 Cover, Chamber, Front Right 10C2010 12C2008 15C2004 17C2008 20C2008
32 Ignitor, Hot Surface, with Gasket 2400-286 2400-286 2400-286 2400-286 2400-286 2400-286 2400-286
33 Tile, Side (Right and Left) T2015600 T2015600 T2015600 T2015600 T2015600 T2015600 T2015600
34 Tile, Front T2017300
35 Tile, Front, Left Side T2016200 T2016800 T2016800 T2016800 T2016800 T2016800
35A Tile, Front, Right Side T2016300 T2017100 T2017900 T2017100 T2017900 T2017100
35B Tile, Front, Center T2016900 T2016900 T2016900 T2016900
36 Tile, Rear T2015700
37 Tile, Rear, Left Side T2017500 T2016600 T2016600 T2016600 T2016600 T2016600
37A Tile, Rear, Right Side T2016600 T2016600 T2018100 T2016600 T2018100 T2016600
37B Tile, Rear, Center T2017200 T2017200 T2017200 T2017200
38 Tile, Bottom T2015500
39 Tile, Bottom, Left Side T2017400 T2017400 T2017400 T2017400 T2017400 T2017400
39A Tile, Bottom, Right Side T2016500 T2017400 T2018000 T2017400 T2018000 T2017400
39B Tile, Bottom, Center T2015900 T2015900 T2015900 T2015900
Page 39
Low Temperature Pennant
Page 39
(2) (2) (2) (2)
41 Heat Exchanger, Copper R2014901 R2014902 R2014903 R2026701 R2014904 R2026702 R2014905
500 750 1000 1250 1500 1750 2000
Heat Exchanger, Cupro-Nickel R2027801 R2027802 R2027803 R2027804 R2027805 R2027806 R2027807
Item Description Size Size Size Size Size Size Size
42 Water Barrier, Inlet/outlet 20305101 20305101 20305101 20305101 20305101 20305101 20305101
43 Water Barrier, Inlet 10338300 10338300 10338300 10338300 10338300 10338300 10338300
44 Gasket, Header S0095100 S0095100 S0095100 S0095100 S0095100 S0095100 S0095100
(2) (2) (2) (2) (2) (2) (2)
45 Cover, In/Out, Glass-Lined Cast Iron 10364504 10364504 10364504 10364504 10364504 10364504 10364504
Cover, In/Out, Bronze 10364501 10364501 10364501 10364501 10364501 10364501 10364501
46 Well, Temperature Control RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300
47 Gasket, Flange S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S0063700
(2) (2) (2) (2) (2) (2) (2)
48 Flange, Cast Iron 10391302 10391302 10391302 10391302 10391302 10391302 10391302
Flange, Bronze 20255401 20255401 20255401 20255401 20255401 20255401 20255401
49 Relief Valve, PNCH, 75 PSI A0063300 A0063600 A0063600 A0063600 A0063600 A0063600 A0002700
Relief Valve, PNCV, 125 PSI RA0001200 RA0001200 RA0001200 RA0001200 A0064400 A0064400 A0066400
50 Tee, Adapter, Outlet, Cast Iron 20130001 20130001 20130001 20130002 20130002 20130002 20130002
Tee, Adapter, Outlet, Bronze 20150301 20150301 20150301 20150301 20150301 20150301 20150303
51 Flow Switch RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 RE0013000
52 Gauge, Temperature/Pressure RA0079000 RA0079000 RA0079000 RA0079000 RA0079000 RA0079000 RA0079000
54 Low Water Cutoff R0021901 R0021901 R0021901 R0021901 R0021901 R0021901 R0021901
55 Pump Housing, Glass-lined, Cast Iron R20607600 R20607600 R20607600 R20607600 R20607600 R20607600 R20607600
Pump Housing, Bronze 10483300 10483300 10483300 10483300 10483300 10483300 10483300
56 Gasket, Pump Adapter S0024600 S0024600 S0024600 S0024600 S0024600 S0024600 S0024600
57 Pump Adapter, Glass-lined Cast Iron 10364200 10364200 10364200 10364200 10364200 10364200 10364200
Pump Adapter, Bronze 10364201 10364201 10364201 10364201 10364201 10364201 10364201
58 Bafe, Diffuser, Pump Inlet 10338400 10338400 10338400 10338400 10338400 10338400 10338400
59 Pressure Switch RE0240900 RE0240900 RE0240900 RE0240900 RE0240900 RE0240900 RE0240900
(2) (2) (2) (3) (3) (3) (3)
(1) (1) (1) (2) (2) (2) (2)
(1) (1) (1) (2) (2) (2) (2)
60 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900 A2111900
61 Weldment, Blower Mount 5C5300 5C5300 5C5300 5C5300 5C5300 5C5300 5C5300
62 Damper, Duct Assembly, Blower 15C5400 15C5400 15C5400 15C5400
Electrical Components - SeeFigure21A
64 Bracket, Control Panel Mounting 5C7103 5C7103 5C7103 5C7103 5C7103 5C7103 5C7103
65 Terminal Board, Field Wiring E2307400 E2307401 E2307402 E2307403 E2307404 E2307405 E2307406
Page 40
Page 40
LAARS Heating Systems
(1) (1) (2) (2) (2) (2) (2)
(1) (1) (2) (2) (2) (2) (2)
(2) (2) (2) (2)
(2) (2) (2) (2)
(1) (1) (2) (1) (1)
(1) (2) (3) (1) (2)
(1) (1) (1) (2)
(2) (2) (2) (4)
(1) (1) (2) (1) (1)
(1) (1) (3) (1) (2)
66 Ignition Control, Single Trial E2107300 E2107300 E2107300 E2107300 E2107300 E2107300 E2107300
Item Description Size Size Size Size Size Size Size
500 750 1000 1250 1500 1750 2000
Igniltion Control, Three Trial E2313900 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900
67 Diagnostic Board E2105500 E2105500 E2105500 E2105500 E2105500 E2105500 E2105500
68 Indicator Light Panel Board E2105600 E2105600 E2105600 E2105600 E2105600 E2105600 E2105600
69 Temperature Control E2321700 E2321700 E2321700 E2321700 E2321700 E2321700 E2321700
70 High Limit, Auto Reset, PNCH RE0014400 RE0014400 RE0014400 RE0014400 RE0014400 RE0014400 RE0014400
High Limit, Auto Reset, PNCV, 210F Max. E2217700 E2217700 E2217700 E2217700 E2217700 E2217700 E2217700
71 High Limit, Manual Reset, PNCH RE0015900 RE0015900 RE0015900 RE0015900 RE0015900 RE0015900 RE0015900
High Limit, Manual Reset, PNCV, 210F Max. E2217800 E2217800 E2217800 E2217800 E2217800 E2217800 E2217800
72 Relay, Pump (SPST) E0098300 E0098300 E0098300 E0098300 E0098300 E0098300 E0098300
Relay, Fan (DPDT) E0076600 E0076600 E0076600 E0076600
73 Terminal Bus (12 Position) E2040500 E2040500 E2040500 E2040500 E2040500 E2040500 E2040500
74 Transformer E2310400 E2310400 E2310400 E2312800 E2312800 E2312800 E2312800
75 Circuit Breaker E2318800 E2318800 E2318800 E2318800 E2318800 E2318800 E2318800
Switch, Rocker E2322700 E2322700 E2322700 E2322700 E2322700 E2322700 E2322700
Sensor, Universal (shipped loose) R2014800 R2014800 R2014800 R2014800 R2014800 R2014800 R2014800
Switch, Rocker (main power) not shown E2343300 E2343300 E2343300 E2343300 E2343300 E2343300 E2343300
Gas Train Components - SeeFigure20
76 Manifold, Gas Supply 5C6700 7C6700 10C6700 12C6700 15C6700 17C6700 20C6700
77 Valve, Ball V2003100 V2003100 V2003200 V2003300 V2003300 V2003300 V2003300
Burner Trays - Note: Burner Tray Assemblies contain item numbers 78 through 80.
not Burner Tray Assembly, 3 Burners, Right, Nat 5C6600 5C6600 5C6600 5C6600 5C6600
shown
Burner Tray Assembly, 3 Burners, Left, Nat 5C6500 5C6500 5C6500 5C6500 5C6500
Burner Tray Assembly, 4 Burners, Right, Nat 10C6600 10C6600 10C6600 10C6600
Burner Tray Assembly, 4 Burners, Left, Nat 10C6500 10C6500 10C6500 10C6500
Burner Tray Assembly, 3 Burners, Right, LP 5C6620 5C6620 5C6620 5C6620 5C6600
Burner Tray Assembly, 3 Burners, Left, LP 5C6520 5C6520 5C6520 5C6520 5C6500
Page 41
Low Temperature Pennant
Page 41
(1) (1) (1) (2)
(2) (2) (2) (4)
(2) (3) (3) (5) (5) (6) (6)
(2) (3) (3) (5) (5) (6) (6)
(6) (9) (12) (15) (18) (21) (24)
(6) (9) (12) (15) (18) (21) (24)
(1) (1) (2) (1) (1)
(1) (1) (3) (1) (2)
(1) (1) (1) (2)
(2) (2) (2) (4)
(2) (3) (5) (2) (3)
(3) (3) (3) (6)
(3) (3) (3) (6)
(2) (3) (5) (2) (3)
Burner Tray Assembly, 4 Burners, Right, LP 10C6620 10C6620 10C6620 10C6620
500 750 1000 1250 1500 1750 2000
Item Description Size Size Size Size Size Size Size
Burner Tray Assembly, 4 Burners, Left, LP 10C6520 10C6500 10C6520 10C6520
78 Valve, Gas, Combination V2017600 V2017600 V2017600 V2017600 V2017600 V2017600 V2017600
79 Valve, Manual Shutoff V2000200 V2000200 V2000200 V2000200 V2000200 V2000200 V2000200
Orice, Gas, Natural L2013000 L2013000 L2013000 L2013000 L2013000 L2013000 L2013000
Orice, Gas, Propane L2012400 L2012400 L2012400 L2012400 L2012400 L2012400 L2012400
80 Burner Manifold, 3 Burners, Right L2012900 L2012900 L2012900 L2012900 L2012900
Burner Manifold, 3 Burners, Left L2012800 L2012800 L2012800 L2012800 L2012800
Burner Manifold, 4 Burners, Right L2012700 L2012700 L2012700 L2012700
Burner Manifold, 4 Burners, Left L2012600 L2012600 L2012600 L2012600
81 Burner Tray, 3 Burners L2012200 L2012200 L2012200 L2012200
Burner Tray, 4 Burners L2012500 L2012500 L2012500 L2012500
82 Gasket, Burner Tray, 3 Burner S2012700 S2012700 S2012700 S2012700 S2012700
Gasket, Burner Tray, 4 Burner S2012500 S2012500 S2012500 S2012500
Gasket Tape, Rr, Base (43') R2014500 R2014500 R2014500 R2014500 R2014500 R2014500 R2014500
Gasket Tape, Ft Air Chamber (63') R2014600 R2014600 R2014600 R2014600 R2014600 R2014600 R2014600
Page 42
Page 42
CONTROLLER COMPONENTS
LAARS Heating Systems
Figure 19. Sheet Metal Components.
DETAIL "A" TYPICAL CONTROLLER
DETAIL “A”
COMPONENTS
TYPICAL
Page 43
Low Temperature Pennant
28
60
NOTES: Model 2000 shown for reference.
41
25
61
62
Page 43
24
SEE ENLARGEMENT
(DETAIL “A”)
ON PREVIOUS PAGE
ON NEXT PAGE
59
22
77
78
79
80
SEE ENLARGEMENT
(DETAIL “B”)
ON NEXT PAGE
76
81
82
32
18
18A
20
36/37
34/35
38/39
33
35B
27/A/B
17
37B
26
39B
39A
35A
18B
23
37A
33
19
21
29
30
Figure 20. Internal Components.
Page 44
Page 44
55
56
57
44
42
Pennant Hydronic Boiler
SIZE TACO PUMP P/N B&G PUMP P/N
500 A2117201 A2121803 750 A2117201 A2121803 1000 A2117202 A2121802 1250 A2117202 A2121802 1500 A2117203 A2121801 1750 A2117203 A2121801 2000 A2117204 A2121800
LAARS Heating Systems
58
DETAIL “B” MOUNTED PUMP HEAT EXCHANGER COMPONENTS
42
43
44
45
46
47
54
49
50
52
51
Pennant Water Heater with TACO Pump
TACO PUMP P/N SIZE Soft Water Normal Water Hard Water
500 A2117201 A2117201 A2117203 750 A2117201 A2117201 A2117203 1000 A2117201 A2117202 A2117203 1250 A2117201 A2117202 A2117203 1500 A2117201 A2117203 A2117203 1750 A2117203 A2117203 A2117203 2000 A2117204 A2117204 A2117204
Pennant Water Heater with B&G Pump
B&G PUMP P/N SIZE Soft Water Normal Water Hard Water
500 A2121803 A2121803 A2121801 750 A2121803 A2121803 A2121801 1000 A2121803 A2121802 A2121801 1250 A2121803 A2121802 A2121801 1500 A2121803 A2121801 A2121801 1750 A2121801 A2121801 A2121801 2000 A2121800 A2121800 A2121800
Figure 21. Detail of Internal Components.
84
Laars Heating Systems Company reserves the right to change specifications, components, fea­tures, or to discontinue products without notice.
83
800.900.9276 • Fax 800.559.1583 (CustomerService,ServiceAdvisors&TechnicalSupport)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (ApplicationsEngineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1306 Document 1204D
H2319100D
Loading...