Installation and Operation Instructions Document 1204D
Heating Systems Company
A subsidiary ofCorporationBRADFORD WHITE
®
®
Installation and Operation
Instructions for
Low Temperature
™
PENNANT
Hydronic Boiler
Model PNCH
Water Heater
Model PNCV
FOR YOUR SAFETY:This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or
death. Improper installation and/or operation will void the warranty. For indoor installations, as an
additional measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide
detectors in the vicinity of this appliance and in any adjacent occupied spaces.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from
a nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed
by a qualified installer, service agency, or gas
supplier.
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute blessure
ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage
de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
trouvez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
9.1 General Information ....................................... 36
9.2 Parts List ........................................................ 36
Page 3
Low Temperature Pennant
SECTION 1.
General Information
USING THIS MANUAL – Because the
Pennant Boilers and Pennant Water Heaters are
identical appliances, with the exception of materials
of manufacture, labels and ultimate use application,
this manual provides information for the proper
installation, operation and maintenance of both
products. Where differences exist between the
application of the appliances and their operation,
the sections pertinent to only one appliance or the
other will be so identied.
In the Commonwealth of Massachusetts, this
appliance must be installed by a licensed plumber or
gas tter.
WARNING
To minimize the risk of electric shock, fire or other
hazards which could result in property damage,
injury, or death. The Pennant hydronic, boiler or
water heater must be installed in accordance with
the procedures detailed in this manual, or the Laars
Heating Systems warranty may be voided. The
installation must conform to the requirements of
the local jurisdiction having authority, and, in the
United States, to the latest edition of the National
Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada,
the installation must conform to the latest edition
of the Natural Gas and Propane Installation Code,
CSA B149.1 and/or applicable local codes. Where
Afin de réduire au minimum les risques de
commotion électrique, de feu ou d’autre nature,
qui pourraient causer des dommages matériels,
des blessures ou des accidents mortels, les
chaudières à eau chaude ou les chauffe-eau
Pennant doivent être installés conformément aux
directives détaillées contenues dans ce manuel, à
défaut de quoi la garantie fournie par Laars Heating
Systems serait annulée. L’installation doit être
conforme aux exigences de la réglementation locale
en vigueur et, aux États-Unis, à l’édition la plus
récente du Natural Fuel Gas Code (Code pour le
gaz combustible naturel) ANSI Z223.1/NFPA54. Au
Canada, l’installation doit respecter les exigences
de la plus récente édition du Code d’installation du
gaz naturel et du propane CSA B149.1, et/ou des
codes locaux de construction en vigueur. Lorsque
la réglementation locale l’exige, l’installation des
appareils électroménagers Pennant doit respecter
les exigences du Standard for Controls and Safety
Devices for Automatically Fired Boilers (Code pour
les équipements de commande et de sécurité des
chaudières à combustion automatique), ANSI/
ASME CSD-1. Toute modification apportée à la
chaudière, aux régulateurs de gaz ou au câblage,
peut compromettre la garantie. Si certaines
conditions particulières rendent des adaptations
nécessaires, consulter un représentant du fabricant
avant d’entreprendre ces modifications.
required by the authority having jurisdiction, the
installation of Pennant appliances must conform
to the Standard for Controls and Safety Devices
for Automatically Fired Boilers, ANSI/ASME
CSD-1. Any modifications to the boiler, its gas
controls, or wiring may void the warranty. If field
conditions require modifications, consult the factory
representative before initiating such modifications.
All application and installation procedures
should be reviewed completely before proceeding with
the installation. Consult the Laars Heating Systems
factory, or local factory representative, with any issues
or questions regarding this equipment. Experience
has shown that most operating issues are caused by
improper installation.
The Pennant appliance is protected against over
1.1 Introduction
This manual provides information necessary for
the installation, operation, and maintenance of Laars
Heating Systems’ Low temperature Pennant copper
tube appliances, sizes 500-2000 (standard appliances
pressurization. A pressure relief valve is tted to all
appliances. It is installed on the outlet header, at the
water outlet of the appliance.
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13 in. w.c. (3.2 kPa).
are covered in a separate manual). Read it carefully
before installation.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P N C A C C 2
AVERTISSEMENT
Page 3
SERIES
P N C
USAGE
H
V
SIZE
0 5 0 0
0 7 5 0
1 0 0 0
1 2 5 0
1 5 0 0
1 7 5 0
2 0 0 0
FUEL
N
P
ALTITUDE
A
LOCATION
C
FIRING
MODE
CON-OFF
REVISION
2
HEAT
EXCHANGER
B
C
N
P
OPTIONS
CODE
X
J
PUMP
OPTIONS
H
N
S
C
B
D
Page 4
Page 4
LAARS Heating Systems
All installations must be made in accordance
with:
1) In the U.S., the " National Fuel Gas Code "ANSI
Z223.1/NFPA54, Latest Edition and all applicable
local codes as required by the Authorities Having
Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and all
applicable local codes as required by the AHJ.
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC),
ANSI/NFPA 70, latest Edition and all applicable local
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part
1”, CSA STD. C22.1 and all applicable local codes as
required by the AHJ.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
B = Glass-lined CI / copper / brz trim (std. PNCV)
C = Glass-lined cast iron / copper (std. PNCH)
N = Glass-lined cast iron / cu-nickel
P = Glass-lined cast iron / cu-nickel / brz trim
15 Option Code
X = Standard Low Temp Control
J = CSD-1, FM, IRI, IL
16 Pump Options
H = TACO, Hard water pump (PNCV only)
N = TACO, Normal water pump
S = TACO, Soft water pump (PNCV only)
C = B&G, Hard water pump (PNCV only)
B = B&G, Normal water pump
D = B&G, Soft water pump (PNCV only)
1.3 Warranty
Laars Heating Systems’ appliances are covered
by a limited warranty. Owners should submit online
warranty registration at www.Laars.com.
All warranty claims must be made to an authorized
Laars Heating Systems representative, directly to
Customer Service, or online at www.Laars.com.
Claims must include the serial number and model
(this information can be found on the rating plate),
installation date, and name of the installer. Shipping
costs are not included in the warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.4 Dimensions
See Figure 1.
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower oors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certied by CSAInternational for installation on combustible ooring;
in basements; in closets, utility rooms or alcoves.
Pennant Boilers or Water Heaters must never be
installed on carpeting. The location for the appliance
should be chosen with regard to the vent pipe lengths
and external plumbing. The unit shall be installed such
that the gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement, control
replacement, etc.). When vented vertically, the Pennant
must be located as close as practical to a chimney or
outside wall. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area, both
terminals should be installed at an appropriate level
*Air and vent connections may be on top or back of the Pennant, and are eld convertible. Dimensions in inches cm
Figure 1. Dimensional Data.
Page 6
Page 6
LAARS Heating Systems
above grade such that blockage of the terminal from
accumulated debris or precipitation is prevented.
The dimensions and requirements that are shown
in Table 1 should be met when choosing the locations
for the appliance.
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results, the Pennant water heater should
be located within 15 feet (4.6m) of the storage tank(s).
The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter pipe or tubing may be
acceptable. Consult the factory for assistance.
Appliance
Surface
Left Side12.52461
Right Side12.52461
Top12.51230
Back12.5 12** 30**
Front12.53691
Vertical
(Category 1)
Vent
Horizontal
(Category 3)
Vent
*1" (2.5 cm) when b-vent is used.
**When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).
Required
Clearance From
Combustible Material
inchescminchescm
6*15.2*
per UL 1738 venting
system supplier's
instructions
Table 1. Clearances.
Recommended
Service Access
Clearance
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
For the best results, Pennant should be located
within 15 feet (4.6m) of the supply and return headers.
The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter tubing may be
acceptable. Consult the factory for assistance.
1.8 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
From Outside Wall
The forced draft combustion air blower(s) in the
appliance has/have sufcient power to pull air and vent
properly when the guidelines for horizontal air and
vent are followed (see Table 2).
NOTE: On some models, the vent collar size is
larger than the size of the vent pipe that can be
used. Vent collar size and horizontal pipe diameters
can be found in Table 1. The larger vent collar
size is to accommodate Category I (vertical) vent
systems.
NOTE: When located on the same wall, the
Pennant combustion air intake terminal must
be installed a minimum of 12" (30cm) below the
exhaust vent terminal and separated by a minimum
of 36 inches (91cm) horizontally.
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other
Table 2. Horizontal Vent / Combustion Air Parameters.
Intake
Air Collar
& Pipe
Diameter
Max. Pipe
Length
Max. No.
of Elbows
Side Vent
Terminal
Part Number
Side Wall
Combustion
Air Terminal
Part Number
Page 7
Low Temperature Pennant
Page 7
SECTION 2.
Venting and Combustion Air
WARNING
For indoor installations, as an additional measure
of safety, Laars strongly recommends installation of
suitable Carbon Monoxide detectors in the vicinity of
this appliance and in any adjacent occupied spaces.
AVERTISSEMENT
Pour des installations intérieures, Laars
recommande fortement, comme mesure de sécurité
supplémentaire, l’installation de détecteurs de
monoxyde de carbone adaptés dans le voisinage
de l’appareil et dans chacune des pièces habitées
adjacentes.
2.1 Combustion Air
Pennant boilers and water heaters must have
provisions for combustion and ventilation air in
accordance with the applicable sections addressing
requirements for air for combustion and ventilation of
the National Fuel Gas Code, ANSI Z223.1. In Canada,
the applicable sections of the Natural Gas and Propane
Installation Code (CSA B149.1) must be followed. In
all cases any and all applicable local installation codes
must also be followed.
A Pennant appliance may receive combustion
air from the space in which it is installed, or it can be
ducted directly to the unit from the outside. Proper
ventilation air must be provided in either case.
2.1.1 Combustion Air From Room
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Method 1: Two permanent openings, one
commencing within 12 inches (30 cm) of the top
and one commencing within 12 inches (30 cm) of
the bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts,
with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the
outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per 4000
Btu/hr (5.5 square cm/kW) of total input rating of all
equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening
shall have a minimum free area of not less than
1 square inch per 2000 Btu/hr (11 square cm/kW) of
total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method, for each
Pennant model.
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors
or spaces that directly communicate with the outdoors
and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (7 square cm/kW) of the total input
rating of all equipment located in the enclosure. This
opening must not be less than the sum of the areas of
all vent connectors in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform
to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety
codes or, in absence of such requirements, follow
CSA B149.1, the Natural Gas and Propane Installation
Code.
2.1.2 Intake Combustion Air
The combustion air can be taken through the
wall, or through the roof. When taken from the wall, it
must be taken from out-of-doors by means of the Laars
horizontal wall terminal (see Table 2). When taken
from the roof, a eld-supplied rain cap or an elbow
arrangement must be used to prevent entry of rain
water (see Figure 2).
Use single-wall galvanized pipe, per Table
4, for the combustion air intake (see Table 2 for
appropriate size). Route the intake to the heater as
directly as possible. Seal all joints with tape. Provide
adequate hangers. The unit must not support the
weight of the combustion air intake pipe. Maximum
linear pipe length allowed is 50 feet (15.2m). Three
elbows have been calculated into the 50-foot (15.2m)
Area indicated is for one of two openings; one at oor level
and one at the ceiling, so the total net free area could be
double the gures indicated.
This chart is for use when communicating directly with the
outdoors. For special conditions and alternate methods, refer
to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of
louvers. Correct for screen resistance to the net free area
if a screen is installed. Check all local codes applicable to
combustion air.
Table 3. Combustion Air Openings.
Square inchesSquare cm
Each Opening*
Page 8
Page 8
LAARS Heating Systems
linear run. Subtract 10 allowable linear feet (3.0m) for
every additional elbow used (see Table 2). When fewer
than 3 elbows are used, the maximum linear pipe
length allowed is still 50 feet (15.2m).
The connection for the intake air pipe is on the
lter box. Pennant appliances may have venting and
combustion air ducting attached to the top or the back.
They are shipped with the connections at the top. For
attaching either or both pipes to the back, the mounting
anges are reversible by removing the mounting
screws and orienting the anges in the desired
position. Replace the screws after positioning anges.
Run a bead of silicone around the collar and slide the
pipe over the collar. Secure with sheet metal screws.
In addition to air needed for combustion, air
shall also be supplied for ventilation, including all air
required for comfort and proper working conditions
for personnel. The Pennant loses less than 1 percent of
its input rating to the room, but other heat sources may
be present.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired Pennant venting, it may
be considered a Category I or a Category III appliance.
In general, a vertical vent system will be a Category
I system. However, in rare instances, a Pennant’s
vertical vent system may be considered Category
III. In the U.S., the National Fuel Gas Code (ANSI
Z223.1), or in Canada the Natural Gas and Propane
Installation Code (CSA B149.1), denes a Category I
vent system, and includes rules and tables to size these
vent systems. If the Pennant’s vertical vent system
does not satisfy the criteria for Category I venting, it
must be vented as a Category III system.
All Pennant vent systems which discharge
horizontally (without the use of a power venter) are
considered Category III vent systems.
(negative) 0.1 in. w.c.
If using a power venter for any type of Category
I venting, the draft should be set between (negative)
0.01 and 0.05 in. w.c.
2.2.3 Common Venting Systems
Pennant units are Category I fan-assisted when
vented vertically and adhering to all applicable codes.
Pennant units are not allowed to be vented into a
common horizontal vent system, unless a properly
sized vent fan is used, and the common vent system
is properly designed by the vent fan manufacturer or
a qualied engineer. When common venting Pennant
fan-assisted unit with other appliances through
one shared vertical duct called a “common vent”,
special care must be taken by the installer to ensure
safe operation. In the event that the common vent
is blocked, it is possible, especially for fan-assisted
devices, to vent backwards through non-operating
appliances sharing the vent, allowing combustion
products to inltrate occupied spaces. If the
appliances are allowed to operate in this condition,
serious injury or death may occur.
WARNING
Operation of appliances with a blocked common
vent may lead to serious injury or death. Safety
devices must be implemented to prevent blocked
common vent operation. If safe operation of all
appliances connected to a common vent cannot
be assured, including prevention of spillage of flue
gasses into living spaces, common venting should
not be applied, and appliances should each be
vented separately.
2.2.2 Category I Vent
When vented as a Category I appliance, the
vent system must conform to the National Fuel Gas
Code (ANSI Z223.1-Latest Edition) in the U.S., or in
Canada, to the Natural Gas and Propane Installation
Code (CSA B149.1 latest edition). The vent system
must be sized and installed for a Category I FanAssisted Appliance.
If chimney height is greater than 25 feet, or
if multiple units are vented into the same vertical
vent, a barometric damper must be installed on each
appliance, such that the ue draft does not exceed
Joint Sealing Permanent duct tape or aluminum tape
Table 4. Required Combustion Air Piping Material.
Figure 2. Combustion Air and Vent Through Roof.
Page 9
Low Temperature Pennant
Page 9
AVERTISSEMENT
Le fonctionnement d’appareils connectés à un
évent commun bouché peut provoquer de sérieuses
blessures corporelles ou la mort. Des dispositifs de
sécurité doivent être mis en place pour empêcher
que les appareils soient utilisés avec un évent
commun bouché. Si un fonctionnement sécuritaire
de tous les appareils reliés à un évent commun et si
la prévention des dégagements accidentels de gaz
de combustion dans des zones habitées ne peuvent
pas être assurés, un évent commun ne doit pas
être mis en place et les appareils doivent être munis
d’évents individuels séparés.
It is for this reason that, in addition to
following proper vent sizing, construction and safety
requirements from the National Fuel Gas Code,
ANSI Z223.1 or in Canada, from the Natural Gas and
Propane Installation Code (CSA B149.1) as well as
all applicable local codes, it is required that installers
provide some means to prevent operation with a
blocked common vent. It is suggested that a blocked
vent safety system be employed such that if the switch
from one appliance trips due to excessive stack spill
or back pressure indicating a blocked vent condition,
that all appliances attached to the vent be locked out
and prevented from operating. Note that the Pennant
is equipped with a blocked vent safety (pressure)
switch, as shipped. However, this safety switch has
only been designed and tested to be effective in
installations where the Pennant is vented separately
and NOT common vented with other appliances. As an
additional precaution, it is recommended that a Carbon
Monoxide (CO) alarm be installed in all enclosed
spaces containing combustion appliances. If assistance
is required in determining how a blocked vent safety
system should be connected to a LAARS product,
please call Applications Engineering at the Rochester
phone number on the back cover of this manual.
Refer to the installation and operating
instructions on all appliances to be common vented
for instructions, warnings, restrictions and safety
requirements. If safe operation of all appliances
connected to a common vent cannot be assured,
including prevention of spillage of ue gases into
living spaces, common venting should not be applied,
and appliances should each be vented separately.
2.2.4 Category III Vent
When the Pennant is vented with horizontal
discharge, it must be installed per this installation
manual and the venting system manufacturer’s
installation instructions. The vent system must be
sealed stainless steel, per Table 5.
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers
as required in the venting system manufacturer’s
installation instructions. Horizontal portions of the
venting system must be supported to prevent sagging
and may not have any low sections that could trap
condensate.
The unit must not support the weight of the vent
pipe. Horizontal runs must slope downwards not less
than ¼ inch per foot (2 cm/m) from the unit to the vent
terminal.
L’appareil ne doit pas supporter le poids de la
gaine d’évent. Les parties horizontales doivent être
installées avec une pente de 2 cm/m (1/4 inch par pied)
descendant de l’appareil vers la sortie de l’évent.
Reference Table 2 for the size of the Category
III vent system. Up to three elbows can be used with
50 linear feet (15.2m) of pipe. Subtract 10 allowable
linear feet (3.0m) for every additional elbow used.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Side Wall Vent Terminal
The appropriate Laars side wall vent terminal
must be used, and is listed in the installation and
operation manual. The terminal provides a means of
installing the vent piping through the building wall,
and must be located in accordance with ANSI Z223.1/
NFPA 54 and applicable local codes. In Canada, the
installation must be in accordance with CSA B149.1
and local applicable codes. Consider the following
when installing the terminal:
1. Figure 3 shows the requirements for mechanical
vent terminal clearances for the U.S. and Canada.
2. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
3. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows,
gravity inlets or other openings. Whenever
possible, locations under windows or near doors
should be avoided.
4. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine
that a vent terminal must be higher than the
minimum shown in codes, depending upon local
conditions.
5. Locate the terminal so the vent exhaust does
not settle on building surfaces or other nearby
objects. Vent products may damage such surfaces
or objects.
6. If the boiler or water heater uses ducted
combustion air from an intake terminal located
on the same wall, locate the vent terminal at least
TermDescription
PipeMust comply with UL Standard 1738 such
as Type AL29-4C Stainless Steel
(either insulated or non-insulated).
Joint
Sealing
Table 5. Required Horizontal Venting Material.
Follow vent manufacturer's instructions.
Page 10
Page 10
LAARS Heating Systems
U.S. Installations (see note 1) Canadian Installations (see note 2)
B= Clearance to window or door that may Direct Vent Only: 12 inches (30 cm)
be opened Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to side of opening; 1 foot (30 cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal See note 4 See note 5
distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soffit See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner See note 4 See note 5
H= Clearance to each side of center line See note 4 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to non mechanical air supply Direct Vent Only: 12 inches (30 cm)
inlet to building or the combustion air inlet Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to any other appliance to side of opening; 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in thisdriveway located on public property location
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specified in CSA B149.1, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
Figure 3. Vent Terminal Clearances.
Page 11
Low Temperature Pennant
Page 11
3 feet (0.9m) horizontally from the combustion
air terminal, and locate the vent terminal at least
1 foot (0.3m) above the combustion air terminal.
WARNING
The outdoor vent terminal gets hot. Unit must be
installed in such a way as to reduce the risk of
burns from contact with the vent terminal.
AVERTISSEMENT
La sortie d’évent à l’extérieur devient très chaude.
Elle doit être installée de façon à réduire le risque
de brûlures au contact de l’extrémité de l’évent.
Important Note: Massachusetts Code Requirement.
From Massachusetts Rules and Regulations 248
CMR 5.08:
(a) For all side wall horizontally vented gas
fueled equipment installed in every dwelling,
building or structure used in whole or in
part for residential purposes, including those
owned or operated by the Commonwealth and
where the side wall exhaust vent termination
is less than seven (7) feet above nished grade
in the area of the venting, including but not
limited to decks and porches, the following
requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS.
At the time of installation of the side wall
horizontal vented gas fueled equipment, the
installing plumber or gastter shall observe that
a hard-wired carbon monoxide detector with
an alarm and battery back-up is installed on
the oor level where the gas equipment is to be
installed. In addition, the installing plumber or
gastter shall observe that a battery operated or
hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the
dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property
owner to secure the services of qualied licensed
professionals for the installation of hard-wired
carbon monoxide detectors.
a. In the event that the side wall
horizontally vented gas fueled equipment
is installed in a crawl space or an attic, the
hard-wired carbon monoxide detector with
alarm and battery back-up may be installed
on the next adjacent oor level.
b. In the event that the requirements of
this subdivision cannot be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply
with the above requirements; provided,
however, that during said thirty (30) day
period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE
DETECTORS.
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
3. SIGNAGE.
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print size no less than one-half (½) inch
in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION.
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontal vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM
PROVIDED. When the manufacturer of
Product Approved side wall horizontally
vented gas equipment provides a venting
system design or venting system components
with the equipment, the instructions provided
by the manufacturer for installation of the
equipment and the venting system shall
include:
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2. A complete parts list for the venting system
Page 12
Page 12
LAARS Heating Systems
design or venting system.
(d) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the manufacturer
of a Product Approved side wall horizontally
vented gas fueled equipment does not
provide the parts for venting the fuel gases,
but identies “special venting systems”, the
following requirements shall be satised by
the manufacturer:
1. The referenced “special venting system”
instructions shall be included with the appliance
or equipment installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
(e) A copy of all installation instructions for all
Product Approved side wall horizontally
vented gas fueled equipment, all venting
instructions, all parts lists for venting
instructions, and/or all venting design
instructions shall remain with the appliance
or equipment at the completion of the
installation.
2.3.2 Side Wall Combustion Air Terminal
The Laars side wall combustion air terminal
(listed in Table 2) must be used when the unit takes
its combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning uid,
chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject
to damage by accident or vandalism.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches (30
cm) above grade, but the installer may determine
it should be higher, depending upon local
conditions.
4. If the Pennant is side-wall vented to the same
wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point
at which it penetrates the roof. It must extend at least
2 feet (0.6m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0m), and high
enough above the roof line to prevent blockage from
snow. When the combustion air is taken from the roof,
the combustion air must terminate at least 12" (30cm)
below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
eld-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2).
The opening on the end of the terminal must be at least
12" (30cm) above the point at which it penetrates the
roof, and high enough above the roof line to prevent
blockage from snow. When the vent terminates on the
roof, the combustion air must terminate at least 12"
(30cm) below the vent terminal.
2.4 Common Vent Test — Boilers
When an existing boiler is removed from a
common venting system, the common venting system
is likely to be too large for proper venting of the
appliances remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system
are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
non blockage or restriction, leakage, corrosion
and other deciencies which could cause an
unsafe condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
replace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
Page 13
Low Temperature Pennant
Page 13
conforms with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and/or CSA B149.1,
Natural Gas and Propane Installation Codes.
When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum size
as determined using the appropriate tables in
Appendix F in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Natural
Gas and Propane Installation Codes.
2.4 Véricationdeséventscommuns—
Chaudières
Lorsqu’une chaudière existante est déconnectée
du réseau d’évents commun, ce réseau d’évents
commun devient probablement trop grand pour
les appareils qui lui restent connectés. Lorsqu’une
chaudière existante est retirée, les étapes suivantes
doivent être accomplies pour chaque appareil qui
reste connecté au réseau d’évents commun utilisé,
alors que les autres appareils qui sont encore
connectés au réseau commun d’évents ne sont pas en
fonctionnement.:
1. Sceller toutes les ouvertures non utilisées du
système d'évacuation.
2. Inspecter de façon visuelle le système
d'évacuation pour déterminer la grosseur et
l'inclinaison horizontale qui conviennent et
s'assurer que le système est exempt d'obstruction,
d'étranglement, de fuite, de corrosion et autres
défaillances qui pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l'espace où les appareils toujours
raccordés au système d'évacuation sont installés
et les autres espaces du bâtiment. Mettre en
marche les sécheuses, tous les appareils non
raccordés au système d'évacuation common
et tous les ventilateurs d'extraction comme
les hottes de cuisinière et les ventilateurs des
salles de bain. S'assurer que ces ventilateurs
fonctionnent à la vitesse maximale. Ne pas faire
fonctionner les ventilateurs d'été. Fermer les
registres des cheminées.
4. Mettre l'appareil inspecté en marche. Suivre les
instructions d'allumage. Réegler le thermostat de
façon continue.
5. Faire fonctionner le brûleur principal pendant
5 min ensuite, déterminer si le coupe-tirage
déborde à l'ouverture de décharge. Utiliser la
amme d'une allumette ou d'une chandelle ou la
fumée d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode
indiquée ci-dessus, que chaque appareil
raccordé au système d'évacuation est mis à l'air
libre de façon adéquate. Remettre les portes
et les fenêtres, les ventilateurs, les registres de
cheminées et les appareils au gaz à leur position
originale.
7. Tout mauvais fonctionnement du système
d'évacuation commun devrait être corrigé
de façon que l'installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA
54 et (ou) aux codes d'installation CSA-B149.1.
Si la grosseur d'une section du système devrait
être modié, le système devrait être modié pour
respecter les valeurs minimales des tableaux
pertinents de l'appendice F du National Fuel Gas
Code, ANSI Z223.1/NFPA 54 et (ou) les codes
d'installation CSA-B149.1
2.5 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper
terminals to prevent rain, snow and other objects from
falling into the Pennant.
If local codes allow, outdoor installations may
use 1' (one foot) of appropriately sized galvanized
single wall or type "B" vent and a rain cap for exhaust
vent termination in the default conguration (venting
out of the top). An appropriately sized 90° elbow,
positioned with the opening facing down, may be used
on the combustion air inlet in the default conguration
on the back of the unit. Note that some local codes
may require a higher vertical vent height, extending
above any perimeter fencing, etc. In installations
where the appearance of the vent is objectionable, the
low prole vent terminals listed in Table 6 may be
used.
Part numbers for the low prole terminals to
cover the vent and combustions air openings are
shown in Table 6.
the gas from either the right side or the left side of
the unit. As shipped, the right side of the gas train is
capped off, and there is a manual valve on the left side.
If desired, the manual valve on the left side of the gas
train may be moved to the right side, and the cap on
the right side may be moved to the left.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is tted for the proper
type of gas by checking the rating plate. Pennant
appliances are equipped to operate at elevations
up to 10,000 feet (3050m). Pennant appliances
may be adjusted to operate properly at altitudes
above 2500 feet (see Section 6.5.2) and the input
will be reduced if the heating value of the gas
supply is below sea level values.
2. The maximum inlet gas pressure must not
exceed 13" w.c. (3.2kPa). The minimum inlet gas
pressure is 5 in. w.c. (1.2 kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
7. All threaded joints should be coated with
piping compound resistant to action of liqueed
petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 0.5 psig (3.45 kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 0.5 psig (3.45 kpa).
10. The appliance and its gas connection must be
leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Do not use open flame to check for leaks. An open
flame could lead to explosion, which could result in
property damage, serious injury or death.
AVERTISSEMENT
Ne recherchez pas les fuites avec une flamme nue.
Une flamme nue peut provoquer une explosion qui
peut causer des dommages matériels, de sérieuses
blessures corporelles ou la mort.
NOTE: The Pennant appliance and all other gas
appliances sharing the gas supply line must be firing
at maximum capacity to properly measure the inlet
supply pressure. The pressure can be measured at
the supply pressure port on the gas valve. Low gas
pressure could be an indication of an undersized
gas meter, undersized gas supply lines and/or an
obstructed gas supply line.
Distance from Gas Meter or Last Stage Regulator
Size and
Gas Type0-100'
500 natural1½"3.8 cm2"5.1 cm2"5.1 cm
500 propane1"2.5 cm1½"3.8 cm1½"3.8 cm
750 natural2"5.1 cm2"5.1 cm2½"6.4 cm
750 propane1½"3.8 cm1½"3.8 cm2"5.1 cm
1000 natural2"5.1 cm2½"6.4 cm3"7.6 cm
1000 propane1½"3.8 cm2"5.1 cm2½"6.4 cm
1250 natural2½"6.4 cm2½"6.4 cm3"7.6 cm
1250 propane2"5.1 cm2"5.1 cm2½"6.4 cm
1500 natural2½"6.4 cm3"7.6 cm3"7.6 cm
1500 propane2"5.1 cm2½"6.4 cm2½"6.4 cm
1750 natural2½"6.4 cm3"7.6 cm3"7.6 cm
1750 propane2"5.1 cm2½"6.4 cm2½"6.4 cm
2000 natural3"7.6 cm3"7.6 cm3½"8.9 cm
2000 propane2½"6.4 cm2½"6.4 cm3"7.6 cm
Notes:
1. These gures are based on 1/2" (0.12 kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe ttings must be considered when determining gas pipe sizing.
0-31 m100-200'31-61m200-300'61-91m
Table 7. Gas Piping Size.
Page 15
Low Temperature Pennant
SENSOR
VALV E
THERMOMETER
SENSOR
TEMPERATURE
GLOBE VALV E
CHECK VALV E
W/ FAST FILL BYPASS
PRESSURE REDUCING VALV E
WITH AIR SCOOP AND
AUTO AIR VENT
EXPANSION TANK
3-WAY VALVE
VALV E
VALV E
PURGE
PUMP
ADDITIONAL REQUIREMENTS.
WITH LOCAL CODES AND ORDINANCES FOR
PIPING CONFIGURATION AND VA LVING, CHECK
WARNING: THIS DRAWING SHOWS SUGGESTED
INSTALLAIR VENTS AT HIGH POINTS IN SYSTEM.
PIPING&SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS.
PRIMARY/SECONDARY MANDATORY FOR ALL
VARIABLE FLOW SYSTEMS.
BOILER WATER CONNECTIONS (INLET/OUTLET)
MAYVARY. VERIFY CONNECTION ORIENTATION.
BOILER CIRCUIT PIPING MUST BE EQUAL
BOILER WATER CONNECTION SIZE.
DIMENSION "C" TO BE4PIPE DIAMETERS.
DOTTED DEVICES INDICATE ALTERNATE
LOCATIONS.
TEMPERATURE SENSORS REQUIRE FIELD
INTERLOCK TO BOILER CONTROLS.
COMBINED FLOW OF ALL BOILERS.
COMMON PIPING MUST BE SIZED FOR
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH
BOILER AND 30 FEET OF FULL-SIZED PIPING.
MINIMUM INLET WATER TEMP = 70°F
LEGEND
Cold Water
Make-Up
Pump
System
Supply
System
System
Return
C
3-Way Valve
Mounted on Pennant
Pump Mounted
on Pennant
System
Return
PRIMARY/SECONDARY MANDATORY FOR ALL
VARIABLE FLOW SYSTEMS.
INSTALLAIR VENTS AT HIGH POINTS IN SYSTEM.
PIPING&SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS.
COMMON PIPING MUST BE SIZED FOR
COMBINED FLOW OF ALL BOILERS.
BOILER WATER CONNECTIONS (INLET/OUTLET)
MAYVARY. VERIFY CONNECTION ORIENTATION.
BOILER CIRCUIT PIPING MUST BE EQUAL
BOILER WATER CONNECTION SIZE.
BOILER CIRC. PUMP SIZED FOR FLOW
THROUGH BOILER
FULL-SIZED PIPING.
DIMENSION "C" TO BE4PIPE DIAMETERS.
MINIMUM INLET WATER TEMP = 70°F
DOTTED DEVICES INDICATE ALTERNATE
LOCATIONS.
TEMPERATURE SENSORS REQUIRE FIELD
INTERLOCK TO BOILER CONTROLS.
AND 30 FEET OF
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
C
C
System
Pump
Cold Water
Make-Up
3-Way Valve
Mounted on Pennant
System
Supply
Page 15
THERMOMETER
TEMPERATURE
Figure 4. Suggested Piping - Hydronic Boiler.
GLOBE VA LV E
CHECK VA LV E
LEGEND
PRESSURE REDUCING VA LVE
W/ FAST FILL BYPASS
PURGE
Pump Mounted
3-WAY VALV E
VALV E
on Pennant
EXPANSION TANK
WITH AIR SCOOP AND
AUTO AIR VENT
PUMP
Figure 5. Hydronic Piping — One Boiler, Multi-Temperature System.
Page 16
Page 16
LAARS Heating Systems
SECTION 4A.
Water Connections —
Pennant Boiler
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psig (82.7
kPa) static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed. Maintain 1" clearance
to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size)
to a drain or in a manner to prevent injury in the event
of pressure relief. Install an air purger, an air vent,
a diaphragm-type expansion tank, and a hydronic
ow check in the system supply loop. Minimum ll
pressure must be 12 psig (82.7 kPa). Install shutoff
valves where required by code.
See suggested piping diagrams (Figures 4-5).
These diagrams are meant only as a guide. Com ponents required by local codes must be properly installed.
Note the recommended location of the
temperature sensor on the diagrams; you must provide
a location for the additional sensor shipped with the
Pennant. This sensor may be strapped onto pipe from
1" to 4" diameter, or inserted into an immersion well.
4A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet
connection of an automatic ll valve.
2. Install a suitable back ow preventer between the
automatic ll valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a
refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium from
entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air
handling appliances where they may be exposed to
refrigerated air circulation must be equipped with ow
control valves or other automatic means to prevent
gravity circulation of the boiler water during the
cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be
provided with a low water cutoff device either as a part
of the boiler or at the time of boiler installation.
4A.3 Water Flow Requirements — Boiler
Low Temperature Pennant Boilers are equipped
with a mounted pump. The pumps are sized for the
boiler’s head loss and 30 feet of full-size piping (same
size as boiler outlet), with a normal number of ttings.
The boilers must be piped in a primary-secondary sys-
tem, such that the boiler’s pump only serves the boiler.
Figures 4 and 5 show examples of this type of piping.
The minimum inlet water temperature to the
Pennant is 70°F (20°C). The mixing system on the
Pennant will ensure that the heat exchanger in the
Pennant does not see water that is less than 120°F
(49°C), so that excessive condensation does not form
on the heat exchanger.
Table 8 shows a relationship between water ow
through the boiler and the temperature difference (rise)
between the inlet and outlet of the boiler. This table
will enable the user to test the boiler for proper water
ow. Since the boiler has a mixing system that sends
a portion of the hot water from the boiler outlet to the
boiler inlet, the water ow coming out of the mixing
system will vary, depending on the return water
temperature.
4A.4 Freeze Protection — Boiler
Boiler installations are not recommended in
areas where the danger of freezing exists unless proper
precautions are made for freeze protection. A non
toxic, heating system, anti-freeze may be added to the
hydronic system provided that the concentration does
not exceed 50% and the anti freeze contains an anti
foamant. Power outage, interruption of gas supply,
failure of system components, activation of safety
devices, etc., may prevent a boiler from ring. Any
time a boiler is subjected to freezing conditions,
and the boiler is not able to re, and/or the water
is not able to circulate, there is a risk of freezing in
the boiler or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the boiler, which could
result in leaking or ooding conditions.
IMPORTANT NOTES: Different glycol products may
provide varying degrees of protection. Glycol products
must be maintained properly in a heating system, or
they may become ineffective. Consult the glycol specifications, or the glycol manufacturer, for information
about specific products, maintenance of solutions, and
set up according to your particular conditions. Never
use ethylene glycol (automotive antifreeze).
Notes: gpm = gallons per minute, lpm = liters per minute,
Maximum temperature rise is 35°F (19°C), as shown.
N/R = not recommended.
Table 8. Temperature Rise - Boiler.
Page 17
Low Temperature Pennant
Page 17
SECTION 4B.
Water Connections —
Pennant Water Heater
4B.1 Water System Piping —
Water Heater
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed.
The Pennant can be used with several different
types of readily available storage tanks. Pennant units
have a circulating pump built into the water heater.
The pumps used are sized for the head loss through the
heater, plus 30 feet (9.1 m) of full-sized piping (same
size as boiler outlet) and a normal number of ttings.
Pumps used are sized for soft, normal or hard water,
so make sure the unit matches the water quality of the
installation.
Pipe the outlet from the heater’s relief valve
such that any discharge from the relief valve will be
conducted to a suitable place for disposal when relief
occurs. Do not reduce line size or install any valves in
this line. The line must be installed to allow complete
drainage of both the valve and the line.
Suggested piping diagrams are shown in Figures
6,7,8 and 9. These diagrams are meant only as a guide.
Components required by local codes must be properly
installed.
Note the recommended location of the
temperature sensor on the diagrams. The Pennant is
shipped with an additional sensor that can be used in
the storage tank, in lieu of a separate tank thermostat.
The minimum inlet water temperature for the
Low-Temp Pennant is 70°F (20°C). The mixing
system on the Pennant will ensure that the heat
exchanger in the Pennant does not see water that is
less than 120°F (49°C), so that excessive condensation
does not form on the heat exchanger.
4B.2 Hot Water Supply Piping —
Water Heater
Follow the tank manufacturer’s guidelines for
completion of the hot water system connections.
NOTE: A listed temperature and pressure relief
valve listed as complying with the Standard for
Relief Valves and Automatic Gas Shutoff Devices
for Hot Water Supply Systems (ANSI Z21.22/
CSA 4.4), of suitable discharge capacity must be
installed in the separate storage tank system.
If the Pennant water heater is installed in a closed
water supply system, such as one having a backow
preventer in the cold water supply line, the relief valve
may discharge periodically, due to thermal expansion.
Means (such as a properly-sized expansion tank) shall
be provided to control thermal expansion. Contact the
water supplier or local plumbing inspector on how to
control this situation.
4B.3 Water Flow Requirements —
Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
be deposited on the unit’s heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water
ow requirements for the Pennant water heater are
based upon the hardness of the water. The water ow
is kept high enough to prevent scaling, but low enough
to prevent tube erosion. For extremely soft or hard
water, cupro-nickel tubes are available. Contact a
Laars representative if you have questions or concerns
about water quality.
Pennant water heaters are built with a mounted
pump that is sized for soft, normal or hard water. The
pumps used are sized for the head loss through the
heater, plus 30 feet (9.1m) of full-sized piping (same
size as heater outlet) and a normal number of ttings.
Table 9 species water ow rates for water
heaters, which will enable the user to ensure that the
Pennant is getting the correct water ow when it is in
operation.
4B.4 Combined Water Heating (potable)
and Space Heating — Water Heater
NOTE: Combined systems must be allowed by and
installed per local codes.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
water used for space heating.
This water heater when used to supply potable
water shall not be connected to any heating system
or component(s) previously used with a non-potable
water heating appliance.
When the system requires water for heating at
temperatures higher than required for other uses,
an anti-scald mixing or tempering valve shall be
installed to temper the water for those uses in order
to reduce scald hazard potential.
4B.5 Freeze Protection — Water Heater
Although Pennant water heaters are design-
Page 18
Page 18
LAARS Heating Systems
certied for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from ring. Any time a
heater is subjected to freezing conditions, and the
heater is not able to re, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
Hard Water = more than 17 grains hardness
GPM = gallons per minute
LPM = liters per minute
Table 9. Temperature Rise — Water Heater.
Figure 6. Suggested Piping — One Water Heater, One Tank.
Page 19
Low Temperature Pennant
Page 19
Figure 7. Suggested Piping — Multiple Water Heaters, One Tank.
Figure 8. Suggested Piping — One Water Heater, Multiple Tanks.
Page 20
Page 20
LAARS Heating Systems
Figure 9. Suggested Piping — Multiple Water Heaters, Multiple Tanks.
SECTION 5.
Electrical Connections
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and
with latest edition of CSA C22.1 Canadian Electrical
Code, Part 1, in Canada. Do not rely on the gas
or water piping to ground the metal parts of the
boiler. Plastic pipe or dielectric unions may isolate
the boiler electrically. Service and maintenance
personnel, who work on or around the boiler, may be
standing on wet floors and could be electrocuted by
an ungrounded boiler.
L’appareil doit être relié à la terre conformément
aux exigences de la réglementation locale ou,
en l’absence d’une telle réglementation, à la plus
récente édition du National Electrical Code (Code
national de l’électricité) ANSI/NFPA 70 aux ÉtatsUnis, et à la plus récente édition du Code Canadien
de l’électricité 1
Code Part 1) CSA C22.1, au Canada. N’utilisez
pas les tuyauteries d’eau ou de gaz pour mettre
à la terre les pièces métalliques de la chaudière;
des tuyauteries en plastique ou des raccords
union diélectriques peuvent isoler électriquement
la chaudière. Les employés qui sont appelés à
travailler sur la chaudière ou autour peuvent être
électrocutés par une chaudière qui n’est pas mise à
la terre.
AVERTISSEMENT
ère
partie (Canadian Electrical
Page 21
Low Temperature Pennant
Page 21
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made in the eld
wiring terminal strip, which is located to the left of the
blower.
NOTE: All internal electrical components have been
pre-wired. No attempt should be made to connect electrical wires to any other location except the wiring box.
5.1 Main Power
5.1.1 Sizes 500-1500
Pennant sizes 500-1500 use a single 120-volt
fused supply. The installer can change the single
service heaters to use a separate circuit for the pump, if
desired. Instructions to make this change are found in
Section 5.1.3.
Pennant 500-1500 main power (L1, N1 &
Ground) shall be connected to the three wires (10
AWG) supplied. Over-current protection ratings can be
found in Table 10.
5.1.2 Sizes 1750-2000
Pennant sizes 1750-2000 require two 120-volt
fused supplies.
Heater circuit can be identied with 10AWG
wires to include black, white and green (all solid
colors). Pump circuit can be identied with three
12AWG wires to include a black wire with a white
tracer (stripe), a white and green wire.
5.1.3 Separate Pump Circuit
Conversion to separate pump circuit will necessitate removing the three jumpers within the internal
wiring of the 120-volt portion of the heater (see Figure
10). Only do this with the power disconnected to the
unit!
To rewire the pump circuit, bring in another
120-volt fused supply (L2, N2 & Ground). Connect
incoming power (L2) to the main power switch using
spade (fork) terminal. From the other side of the main
power switch connect to the main terminal block using
a ¼" female insulated quick connect. This will be
the same position where the jumper had terminated
(see Figure 10). Connect N2 and Ground to the main
terminal block using ¼" female insulated quick connect
(refer to Figure 10).
5.1.4 All Sizes
Ladder diagrams are shown in Figures 12 and 13.
Wiring diagrams are shown in Figures 14 through 16.
Field wiring is shown in Figure 11.
on the Pennant temperature control at the factory.
External Alarm: The eld terminal strip has
terminals for a dry contact that is closed when the
ignition control locks out. These terminals are labeled
“ALRM” and “ALRM”.
Additional Call For Heat: Terminals labeled
“COMD” and “HTD” can be used to call the Pennant
for heat. These terminals are shipped with a jumper
between them. Remove the jumper to use these
terminals. The Pennant is controlled by the temperature
sensor, and the temperature must be calling for heat
for the Pennant to re, regardless of any connections
between “COMD” and “HTD”, but the Pennant will
not re if this connection is broken.
Other Field Interlocks: Other safety switches
that are intended to prevent the Pennant from ring
(such as fan proving switches, powered louver end
switches, etc.) The terminals are marked “OTHER
INTS <COM> <NO>”. These terminals are shipped
with a jumper between them. Remove jumper to
use these terminals. The Pennant will not re if this
connection is broken.
Temperature Sensor: The Low Temperature
Pennant is controlled by a sensor that requires place-
ment in the system loop or storage tank. A sensor well
is shipped with the unit, as well. This sensor placement
allows the Pennant to be called for heat, based on the
system temperature. The sensor is wired to terminals
Figure 10. Removing Jumpers.
Page 22
Page 22
LAARS Heating Systems
Figure 11. Field Wiring.
Page 23
Low Temperature Pennant
Page 23
Figure 12. Ladder Diagram, Sizes 500-1000.
Page 24
Page 24
LAARS Heating Systems
Figure 13. Ladder Diagram, Sizes 1250-2000.
Page 25
Low Temperature Pennant
Page 25
Figure 14. Wiring Diagram, Sizes 500-1000.
Page 26
Page 26
LAARS Heating Systems
Figure 15. Wiring Diagram, Sizes 1250-1500.
Page 27
Low Temperature Pennant
Page 27
Figure 16. Wiring Diagram, Sizes 1750-2000.
Page 28
Page 28
LAARS Heating Systems
SECTION 6.
Operating Instructions
6.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to fill slowly.
2. If make-up water pump is employed, adjust
pressure switch on pumping system to provide
a minimum of 12 psi (81.8 kPa) at the highest
point in the heating loop.
3. If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator
to provide at least 12 psi (81.8 kPa) at the highest
point in the heating loop.
4. Open bleeding devices on all radiation units
at the high points in the piping throughout
the system, unless automatic air bleeders are
provided at such points.
5. Run system circulating pump for a minimum of
30 minutes with the boiler shut off.
6. Open all strainers in the circulating system,
check flow switch operation, and check for
debris. If debris is present, clean out to ensure
proper circulation.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank
should not exceed ¼ of the total, with the balance
lled with air.
9. Start up boiler according to the procedure in this
manual. Operate the entire system, including the
pump, boiler, and radiation units for one (1) hour.
10. Recheck the water level in the expansion tank. If
the water level exceeds ¼ of the volume of the
expansion tank, open the tank drain, and drain to
that level.
11. Shut down the entire system and vent all
radiation units and high points in the system
piping, as described in Step 4.
12. Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.
13. Check gauge for correct water pressure and also
check water level in the system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.
14. Refer to local codes and the make-up water
valve manufacturer’s instructions as to whether
the make-up water valve should be left open or
closed.
15. After placing the unit in operation, the ignition
system safety shutoff device must be tested. First,
shut off the manual gas valve, and call the unit
for heat. After the pre-purge and ignitor heat-up
time, the main gas terminals will be energized,
attempting to light, for four (4) seconds, and then
will de-energize. The unit will go into lockout
mode. Second, turn the power off and then on
again, open the manual gas valve and allow the
unit to light. While the unit is operating, close the
manual gas valve and ensure that power to the
main gas valve has been cut.
16. Within three (3) days of start-up, recheck all air
bleeders and the expansion tank as described in
Steps 4 and 8 above.
Important: The installer is responsible for identifying
to the owner/operator the location of all emergency
shutoff devices.
WARNING
Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
that may have been under water.
AVERTISSEMENT
N’utilisez pas cet appareil si l’une de ses pièces est
passée sous l’eau. Appelez tout de suite un technicien en entretien et en réparation pour inspection
de l’appareil et remplacement des pièces du système de commande, et des pièces de commande
du circuit gaz, qui sont passées sous l’eau.
6.2 Sequence of Operation
The amber “Ready” light on the front panel
indicates that the control system is energized. Upon a
call for heat from the system temperature sensor, the
green “Heat” indicator on the front panel will light.
The green “Pump” indicator on the front panel will
light.
Once the water ow switch makes, and if all of
the safety interlocks are closed, the ignition module(s)
will energize the blower(s) for a 15-second pre-purge,
followed by a 20-second period to allow the ignitor(s)
to heat.
Energizing the blower pressurizes the air box
(which supplies air to the burners) and closes the
normally-open contact(s) of the airow pressure
switch(es). This allows the ignition module to proceed
with the ignition sequence.
The blocked ue pressure switch senses the
pressure difference between the exhaust plenum and
the blower inlet plenum. It will interrupt the airow
sensing circuit if this pressure exceeds a maximum
value. If airow is not proven, the ignition module
will either attempt ignition again (up to three times) or
will lockout (if the optional lockout ignition module is
used).
The ignition module checks that the ignitor
current has reached a minimum value and energizes
the gas valves at the end of the ignitor-heating period.
The green indicators on the front panel will
light, indicating that the gas valves are open. After a
4-second trial for ignition, the ignitor switches off, and
Page 29
Low Temperature Pennant
Page 29
unless the ame sensor detects a ame, the gas valves
will close and the ignition module will either attempt
ignition again (up to three times) or will lockout (if the
optional lockout ignition module is used).
Note: At this point, if gas pressure is below the
required 5” w.c. minimum, the Pennant may lock out.
If ame is sensed, the burner will continue to
re as long as there is a call for heat. If there is a
subsequent loss of ame signal, the burner will attempt
re-ignition up to three times (only once if optional
lockout ignition module is used.) Loss of ame signal
from the rst ignition module will cause shutdown of
the heater.
When the call for heat is satised, the gas
valves close and the blower(s) continues to run for 30
seconds. The pump will continue to run for the length
of time selected at startup by the adjustment of the
pump time delay (Pd).
If a call for heat is prevented from being satised
either by a safety interlock or due to an ignition lock-
out, the red “Service” indicator on the front panel will
light. To reset the standard ignition module, toggle
the Pennant power switch off, and then on again. (To
reset the optional single try lockout ignition module,
the reset button on the module must be pressed. Inter rupting power to this module will not reset the lockout.)
The Pennant 1250 through 2000 models have two
ignition modules that control different burners.
6.3 Temperature (Operating) Control
The Pennant temperature control operates by
measuring the system temperature. It also controls
the Pennant pump operation and the mixing system,
which tempers the water entering the heat exchanger to
prevent damage from excessive condensation.
6.3.1 Temperature Control Overview
The digital display on the control has the
following uses:
• To display the system temperature during
normal operating mode.
• To allow the user to view and adjust the control
settings. There are four buttons on the controller. Top
left returns to the beginning. Bottom left is the enter
button. Top right is the up arrow. Bottom right is the
down arrow.
The temperature control face contains an LCD
screen. The LCD screen will display the system
temperature during normal operation. When the
control is rst powered up, it displays “ZZZ”. It
then ashes the control software number. It then
displays the temperature at the system sensor. After
the temperature is displayed, the current settings
(parameters) may be viewed. To scroll through the
parameters, press the down arrow button to advance
to the next parameter. Press the enter button to choose
that parameter. Press the up or down arrow to raise,
lower or toggle to value of that parameter. Press enter
to save a changed value.
By depressing the upper left hand button at
any time during the programming, the menu may be
returned to the beginning.
After about 30 seconds of button inactivity, the
display will revert back to the system temperature.
6.3.2 Programming Parameters - Boilers
When the control is rst turned on, it ashes
“ZZZ” and then “022” to indicate that the boiler
software is in the control. When the down arrow is
pressed, the boiler menu is brought up.
rT – Boiler Return Temperature
This is a display only. This is the temperature at
the boiler’s inlet sensor. This is not system return
temperature, as the water has been mixed with
hot outlet water, for boiler protection.
oAt – Outdoor Air Temperature
This is a display only. This is the outdoor air
temperature, if outdoor reset is used. Must use
optional outdoor reset sensor (p/n 2400-021).
CSP – Calculated Setpoint
This is a display only. When outdoor reset is
used, this is the temperature that is calculated by
the control, based on the settings and conditions,
which becomes the setpoint of the boiler.
bSP – Boiler Setpoint
This is the setpoint for rT (the boiler inlet
temperature sensor). Default is 190°F. Range is
from 140°F to 210°F.
LSP – System Setpoint
This is the setpoint for system, read at the system
sensor that is placed in the system loop. Default
is 180°F. Range is from 60°F to 210°F.
LdF – System Setpoint Differential
This is the differential for LSP. Default is 2.0°F.
Range is 1°F to 30°F.
bdf – Boiler Setpoint Differential
This is the differential for bSP. Default is 10°F.
Range is 1°F to 30°F.
oAr – Outdoor Reset
This enables or disables the outdoor reset
function. Default is “oFF”. Toggle to “on”
if outdoor reset is going to be used. Must use
optional outdoor reset sensor (p/n 2400-021).
oTo - Warm Outdoor Temperature
Upper point of reset curve, where system shutoff
is desired. Default 65°F. Range is 55°F to 70°F.
oAC – Design Temperature
Lower point of reset curve, at which the
maximum water setpoint is needed. Default is
0°F. Range is from –50°F to 60°F.
oAL – Minimum Setpoint
This is the minimum allowable calculated
setpoint, regardless of outdoor temperature.
Default is 160°F. Range is 70°F to 180°F.
Page 30
Page 30
LAARS Heating Systems
oAH – Maximum Setpoint
This is the maximum allowable calculated
setpoint, regardless of outdoor temperature.
Default is 190°F. Range is 90°F to 210°F.
rc – Reset Ratio
The ratio of air temperature movement to water
temperature movement. Sets the slope of the reset
curve. Default is 1.0. Range is from 0.5 to 5.0.
SP – Minimum Mixed Temperature
This setting is fixed at 125°F, and cannot be
change by the user.
Pd – Pump Delay
This is the time delay for the boiler’s mounted
pump. The pump will run for this delay time after
the call for heat has ended. Default is 2 minutes.
Range is from 0.1 minutes to 10 minutes.
Uni - Units
This allows the user to choose between °F
(default) and °C.
6.3.3 Programming Parameters – Water
Heaters
When the control is rst turned on, it ashes
“ZZZ” and then “018” to indicate that the boiler
software is in the control. When the down arrow is
pressed, the boiler menu is brought up.
rT – Heater Return Temperature
This is a display only. This is the temperature
at the heater’s inlet sensor. This is not system
return temperature, as the water has been mixed
with hot outlet water, for heater protection.
bSP – Heater Setpoint
This is the setpoint for rT (the heater inlet
temperature sensor). Default is 140°F. Range is
from 140°F to 190°F.
LSP – System Setpoint
This is the setpoint for system, read at the system
sensor that is placed in the system loop. Default
is 140°F. Range is from 60°F to 190°F.
LdF – System Setpoint Differential
This is the differential for LSP. Default is 2.0°F.
Range is 1°F to 30°F.
Pd – Pump Delay
This is the time delay for the heater’s mounted
pump. The pump will run for this delay time after
the call for heat has ended. Default is 2 minutes.
Range is from 0.1 minutes to 10 minutes.
SP – Minimum Mixed Temperature
This setting is fixed at 125°F, and cannot be
change by the user.
bdf – Heater Setpoint Differential
This is the differential for bSP. Default is 10°F.
Range is 1°F to 30°F.
Uni - Units
This allows the user to choose between °F
(default) and °C.
CAUTION
Should overheating occur or the gas supply fail to
shut off, turn off the manual gas control valve to the
appliance.
6.4 Limit Controls
Pennant appliances are tted with an automatic
reset high limit and a manual reset high limit, both
sensing the outlet temperature of the Pennant.
Water heater high limits are adjustable up to
200°F (93°C) and boiler high limits are adjustable up
to 240°F (116°C).
To set the limit controls, remove the control
panel cover and pull the control panel out to gain
access.
6.5 Operating the Burner and Set Up
6.5.1 Set Up for 0 to 2500 Feet Altitude
The Pennant appliance utilizes a modular design
to achieve its stage-ring. The setup must be checked
before the unit is put in operation. Problems such as
failure to start, rough ignition, strong exhaust odors,
etc. can be due to improper setup. Damage to the
Pennant resulting from improper setup is not covered
by the limited warranty.
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are
lled with water and all air has been bled from
both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. Switch on the appliance power switch located on
the right side of the unit.
5. The Pennant will enter the start sequence, as long
as the unit is being called for heat. The blower
and pump come on for pre-purge, then the ignitor
warm-up sequence starts and after the ignitor
warm-up is complete and all safety devices are
veried, the gas valves open. If ignition doesn’t
occur, check that there is proper gas supply.
Wait 5 minutes and start the unit again. During
initial start up, air in the gas line may cause the
Pennant to “lock out” during the rst few trials
for ignition. Depending on the ignition modules
installed, the manual reset button on the ignition
modules may need to be depressed to restart the
Pennant.
6. When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not
exceed 13” W.C. (3.2kPa). The minimum inlet
gas pressure is 5” W.C. (1.2kPa).
7. Once the inlet gas pressure is veried, the
outlet gas pressure from each valve (manifold
gas pressure) must be checked, and adjusted, if
Page 31
Low Temperature Pennant
Page 31
necessary. The manifold gas pressure must be
2.5” W.C. (0.62kPa).
8. Complete the setup by checking the CO2 at the
outlet of the unit. The CO2 should be 8% for
natural gas, or 9.2% for propane.
9. After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested.
To test:
(a) Close gas shutoff valve with burner
operating.
(b) The ame will go out and blower will
continue to run for the post purge cycle.
One additional attempt to light will follow.
Ignition will not occur as the gas is off. The
ignition control will lockout, and will have
to be reset before the unit will operate.
(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will
start again and the burner will start. The
appliance will return to its previous mode
of operation.
NOTE: Models 1250-2000 have two ignition controls
and two ignitors, which work together to ensure all of
the burners light properly.
6.5.2 High Altitude Adjustment and Set Up
Pennant appliances may be operated at high
altitude (7700 ft., 2347 m) with a reduction in output
of approximately 10%. At altitudes of less than or
more than 7700 ft. (2347 m) the appliance will per-
form equally as well, but with differing reductions in
output. At elevations higher than 7700 ft. (2347 m) the
reduction in output will exceed 10% and at elevations
below 7700 ft. (2347 m) it will be less than 10%. High
altitude adjustment must not be made on appliances
operating at elevations below 2500 ft. (762 m).
No orice changes are required to adjust the
Pennant appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the gas
valve manifold pressure and the air shutter(s). The
required instruments used to assist in these adjustments
are a CO2 or O2 Analyzer and a U-Tube Manometer or
other device capable of reading a pressure of 2.5-3.0
inches W.C. (0.62-0.75 kPa).
Start the adjustment process by checking the CO2
in the “as installed” condition. Adjust the air shutter(s)
so that the CO2 is about 8% or the O2 is about 6.8% for
appliances operating on Natural Gas. For appliances
operating on LP Gas adjust the air shutter(s) so that the
CO2 is about 9.2% or the O2 is about 6.8%. Appliances
with two blowers should be adjusted so that the air
shutters below each blower are open the same amount.
Once the CO2 or O2 has been set, the manifold
pressure may be adjusted. Remove the 1/8 NPT plug
from the lower side of the gas valve that is to be set
and install a tting, hose and manometer. Start the
appliance and observe the manifold pressure. Manifold
pressure must be adjusted to 3.0 in. W.C. (0.75 kPa)
(for high altitude only, standard operating pressure is
2.5 in. W.C. (0.62 kPa)). It is adjusted by removing the
slotted cap on the gas valve and turning the adjustment
screw (beneath the cap) clockwise to increase
pressure and replaced after the adjustments have been
completed and the tting, hose and manometer have
been removed and the 1/8” plug has been replaced.
Repeat this process until all gas valves have been set.
Note: The pressure can be set only when the appliance
is operating and only when the particular gas valve
being adjusted is energized by a call for heat from the
staging control.
After all of the gas valve manifold pressures
have been set, the CO2 or O2 must be reset. CO2 or O2
will have changed when the manifold pressure was
adjusted. Open the air shutter(s) to reduce the CO2 or
O2 to the values achieved previously.
The procedure is complete when all gas valves
are adjusted to a manifold pressure of 3.0 in. W.C.
(0.75 kPa) and the CO2 is adjusted to 8.0% for Natural
Gas appliances or 9.2% for LP appliances. When using
an O2 analyzer, the correct O2 is 6.8% for both Natural
Gas and LP appliances.
CAUTION
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, close main shutoff valve, do not
shut off switch, and contact your heating contractor,
gas company, or factory representative.
6.6 Shutting Down the Pennant
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Pennant and
be sure to also protect building piping from
freezing.
This step to be performed by a qualied
service person.
6.7 To Restart the Pennant
If drained, follow Section 6.1 in this manual for
proper lling and purging.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest
setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch,
manual reset high limit, etc.).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a pre-purge period and
ignitor warm-up period, followed by ignition.
Page 32
Page 32
LAARS Heating Systems
SECTION 7.
Maintenance
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
ammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
protected from freezing.
6. Low water cutoffs, if installed, should be
checked every 6 months. Float type low water
cutoff should be ushed periodically.
7. Inspect ue passages, and clean with brushes/
vacuums, if necessary. Sooting in ue passages
indicates improper combustion. Determine the
cause and correct.
8. Inspect the vent system and air intake system,
and if the vent system is Category III, ensure
that all joints are sealed properly. If joints need
to be resealed, follow venting manufacturer's
instructions to clean and reseal vent system.
proper functioning. It is strongly recommended that
a qualied service technician inspect the basic items
listed below every year.
a. Ignition control g. High limit
b. Ignitor h. Pump
c. Water temp. control i. Low water cutoff
d. Automatic gas valve j. Relays
e. Pressure switches k. Flow switch
and tubing l. Gas train
f. Blower m. Control components
7.2.1 Burners
Close main manual gas valve before proceeding.
Checking the burners for debris - Remove the ignitor
inspection panels(s) and ignitor(s) and inspect the
burners through the ignitor hole(s) using a ashlight
to illuminate. If there is any indication of debris on
the burners that are visible, all the burners will need
to be inspected more thoroughly. Remove the screws
from around the front of the air box (large panel from
which the ignitor inspection panel(s) were removed),
and remove the large panel. Remove the gas manifold
assemblies and the burner panels. Inspect the burners.
Clean burners, if necessary, by blowing compressed
air from the outside of the burners into the center
of the burner. A dirty burner may be an indication
of improper combustion or dirty combustion air.
Determine the cause, and correct. Replace the burners
in the reverse order
7.2 Appliance Maintenance and
Component Description
Only genuine Laars replacement parts should be used.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
Attention
Lors d’entretien ou de réparation des commandes,
étiquetez tous les câbles avant de les déconnecter.
Des erreurs de câblage peuvent provoquer des
fonctionnements incorrects et dangereux. Après
toute intervention d’entretien ou de réparation,
vérifier que l’appareil fonctionne correctement.
See Figures 17 and 18 for locations of gas train
and control components.
The gas and electric controls on the appliance
are engineered for long life and dependable operation,
but the safety of the equipment depends on their
Figure 17. Gas Train Components.
Page 33
Low Temperature Pennant
Page 33
7.2.2 Filter
The lter used in the Pennant is washable. Since
the lter is washable, it will only need replacement
occasionally. If lter replacement is needed, it should
only be replaced with a factory part. Inspect the air
lter monthly, or more often in dirty environments. If
there is debris on the air lter, remove it from the lter
box, and wash it with mild soap and water. Ensure that
the lter is completely dry before reinstalling.
7.2.3 Gas Valves
The gas valves are designed to operate with
supply pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).
To remove a valve, shut off 120-volt power
and the manual gas shutoff valve. Remove the top
front panel from the unit. Disconnect the wires to the
valve. Disengage the anged tting before and after
the valve, and remove the valve. Re-install in reverse
order. Ensure o-rings are properly installed for both
inlet and outlet. Turn on manual gas shutoff valve and
120 volt power and check appliance operation and
tightness of gas valve connections.
7.2.4 Manual Reset High Limit Control
The high limit switch is manual reset switch with
an adjustable set point, up to 240°F (116°C) on boiler
models and 200°F (93°C) on water heater models
and boilers ordered with low temperature controls. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull
the switch off the control panel. Remove the capillary
and bulb from the thermal well located in the header.
Replace in reverse order.
7.2.5 Automatic Reset High Limit Control
An automatic reset high limit is used in addition
to the manual reset high limit. The high limit switch
has an adjustable set point, up to 240°F (116°C) on
boiler models and 200°F (93°C) water heater models
and boilers ordered with low temperature controls. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull
the switch off the control panel. Remove the capillary
and bulb from the thermal well located in the header.
Replace in reverse order.
7.2.6 Temperature Control
The temperature control is an on/off control that
also manages the mixing system.
To replace the control, disable the 120v supply
power to the appliance. Unplug all of the electrical
connectors, remove the retainer clip and the control.
Replace the control in the reverse order.
7.2.7 Ignition Control
The ignition controls ensure the proved interrupt-
ed-type ignition system. They control the hot surface
ignitors and prove that the ame signal is appropri-
Figure 18. Typical Control Panel.
Page 34
Page 34
LAARS Heating Systems
ate for powering the gas valves. It also controls the
blower’s pre-purge and post-purge. Pennant models
500 through 1000 have one ignition control. Models
1250 through 2000 have two ignition controls.
To replace a control, shut off the 120-volt power
to the appliance. Remove the cover from the control
panel. Remove the electrical connectors from the
ignition control. Take out the controller’s mounting
screws, and pull the controller out. Replace in reverse
order.
7.2.8 Ignitor
The ignitors used are 120v “Hot Surface” type.
They are energized whenever there is a call for heat
and switched off when ignition is established and the
ame has been sensed. Pennant models 500 through
1000 have one ignitor. Models 1250 through 2000
have two ignitors. To replace the ignitor, shut off the
120-volt power to the appliance, remove the ignitor
access panel, disconnect the Molex connector, remove
the two mounting screws on the ignitor ange, and pull
the ignitor out. Install in reverse order, always using a
new ignitor gasket with the replacement ignitor.
Caution
Ignitor gets hot. To avoid injury, handle the ignitor
with caution.
Attention
Le dispositif d’allumage devient très chaud.
Manipulez le dispositif d’allumage avec précaution.
7.2.9 Transformer
The Pennant’s transformer is not capable of
supplying control voltage for external devices such
as zone valves, which must have their own separate
power supply.
Some Pennant units have more than one
transformer, and all transformers are not the same
size, so ensure that replacement transformers are the
appropriate ones.
Should a transformer need replacing, shut off the
120-volt power. Unplug the transformer wires, remove
the mounting screws and remove the transformer.
Replace transformer in the reverse order.
7.2.10 Blowers
The combustion air blowers bring the combustion
air for the Pennant from the upper chamber to the
lower chamber. Mixing of the gas and air occurs in the
burners. Models 500, to 1000 each have one blower,
and models 1250 to 2000 each have two blowers.
If a blower change is required, turn off the 120-
volt power and gas supply to the unit. Remove the
front panel. Disconnect the blower’s wire harness.
Remove the screws at the blower ange, and pull the
blower out. Replace blower in reverse order, ensuring
that all joints are made correctly. After replacement,
ensure that the unit operates properly, by following the
set-up procedure in this manual.
7.2.11 Flow Switch
The Pennant uses a paddle-type ow switch to
ensure that the unit has water ow before ignition is
allowed. To replace the ow switch, turn off the 120volt power to the appliance. Isolate the boiler or water
heater from the system by closing the isolation valves.
Caution
Water may be hot enough to scald. Allow water to
cool before proceeding.
Attention
L’eau peut être chaude au point de vous brûler.
Laissez refroidir l’eau avant d’intervenir.
Release pressure in the system by actuating
the pressure relief valves or eld supplied boiler
drain valve. Remove cover from the ow switch
and disconnect the wires. Unthread the ow switch
from piping. Ensure the new ow switch paddles are
trimmed to the same size as the original paddles, and
reinstall in the reverse order. For boiler and other static
pressure systems, restore the system pressure to the
original setting (or 10 psi minimum).
7.2.12 Heat Exchanger Coil
WARNING
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame thereby
creating a risk of fire or explosion. To prevent this
from happening, dampen the soot deposits with a
wet brush or fine water spray before servicing the
heat exchanger.
AVERTISSEMENT
L’accumulation de suie sur un échangeur thermique
sale peut s’enflammer au contact d’une étincelle ou
d’une flamme et présenter un risque d’incendie ou
d’explosion. Afin d’empêcher que cela se produise,
humidifier les dépôts de suie à l’aide d’une brosse
mouillée ou par une pulvérisation fine d’eau avant
d’effectuer l’entretien de l’échangeur thermique.
The Pennant has a premixed burner system.
These systems provide the burners with sufcient air
for complete combustion, and black carbon sooting is
seldom experienced. If sooting is suspected, view ports
for inspection of the heat exchanger are provided on
the side of the boiler. In the unlikely event that there is
a buildup of black carbon soot or other debris on the
heat exchanger, clean per the following:
Page 35
Low Temperature Pennant
Page 35
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas
valve on the heater.
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header anges from the inlet and
outlet.
6. Allow the heat exchanger to drain. Remove the
front cover(s) by removing the rubber access
strip(s) and the retaining screws. Remove the
venting and remove the top, by removing the
screws that attach the top to the side panels.
Remove the side panels. Remove the front lower
panels sealing the combustion area. To remove
the gas train, disconnect the unions located
below the intermediate pan and the eld installed
union located outside the cabinet, and pull up,
bringing the union end connectors through the
grommets in the intermediate pan. To remove the
intermediate pan, remove the slide out control
assembly and blower(s) to reveal the screws.
Remove the screws holding the intermediate pan,
and lift up to remove it. The heat exchanger has
integral metal sections attached, which connect
to the frame of the boiler. Locate and remove
the screws along the front, rear and bottom of
the integral metal sections, and remove the heat
exchanger and metal sections by lifting up. On
the larger appliances, a center heat exchanger
support must be unbolted before it can be
removed..
7. Remove the heat exchanger from the unit.
NOTE: Heat exchangers are heavy and may
require two people to remove to avoid personal
injury.
8. Clean the heat exchanger: A light accumulation
of soot or corrosion on the outside of the heat
exchanger can be easily removed. Use a wire
brush to remove loose soot and scale from the
heat exchanger.
9. NOTE: While the heat exchanger is out of the
unit, inspect the rewall refractory insulation.
Replace if necessary.
10. Inspect the inside of the copper tubes for scale
buildup. Scale can build up on the inner surface
of the heat exchanger tubes, which can restrict
water ow. If the tubes show signs of scaling,
clean the internal surface.
11. Reassemble in the reverse order, and check
appliance operation after start-up.
NOTE: The warranty does not cover damage
caused by lack of required maintenance, lack of
water flow, or improper operating practices.
SECTION 8.
Trouble Shooting
8.1 Resolving Lockouts
There are many causes of lockouts. The three
most common causes are: (1) inadequate gas supply,
(2) poor combustion, (3) ignitor failure.
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP
tank (LP boilers) is not empty. Then, restart the
boiler and observe the operational cycle. After
a 15-second fan pre-purge, the ignitor will heat
up for 40 seconds, and then the unit will light.
If it does not, check the gas supply pressure to
the appliance, after resetting the appliance and
attempting another start-up. The gas pressure to
the appliance must be above 5 in. w.c. (1.2 kPa)
throughout the entire start-up cycle. If it is not,
correct the supply problem (check gas valves or
supply piping). If the supply pressure is adequate,
consult the factory for assistance.
2. Poor Combustion: Poor combustion should be
suspected if there is a strong ue gas odor. The
odor may result from an improper gas/air ratio
(high or low O2 or CO2). Pennant appliances
operate best with 45% excess air (8% CO2 on
natural gas, 9.2% CO2 on LP). Check the CO2 of
the appliance and adjust if necessary.
3. Ignitor failure: If the boiler goes through a
normal start cycle but combustion does not
occur, ignitor failure should be suspected. Check
the ignitor by unplugging the ignitor plug and
measuring the ignitor resistance. It should be
50-80 ohms. If the resistance is not 50-80 ohms,
replace the ignitor. If the resistance is correct,
reset the boiler and check for 120 VAC at the
ignitor plug during the start cycle. If there is no
voltage, replace the faulty ignitor wire harness or
the ignition control.
8.2 Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition.
If the gas supply pressure is proper and the gas
valves are functioning properly, then burners should
be inspected. There should be no distortion or
perforations in the burners outside of the active burner
port area. Replace if indicated.
8.3 Short Cycling — Boiler
Boiler short cycling is caused when the
load on the boiler system swings rapidly causing
frequent cycling between call for heat and satised
conditions. If short cycling is a problem, it may be
due to an oversized boiler, improper control strategy,
incorrect set points or a load distribution problem.
The boiler controls must be set such that the heating
loop temperature setpoint does not interfere with
Page 36
Page 36
LAARS Heating Systems
the setpoint of the boiler operating control. If the set
points are correct and the system design, controls
scheme, etc. are xed, the temperature differentials
may be increased to reduce short cycling. If desired
temperature response is not achievable without short
cycling it may be necessary to install a buffer tank
in the system. Contact your Laars representative to
discuss possible remedies.
8.4 Short Cycling — Water Heater
Short cycling will generally occur only in
combination space heating and water heating
applications when the water heater is operating in the
space-heating mode. If the heating load drops below
the minimum input of the water heater for an extended
period, the water heater will have a tendency to short
cycle. If short cycling is frequently experienced,
regardless of the control’s attempt to limit it, the
heating load should be redistributed to control it.
If short cycling occurs in a water heater
application, it is probably caused by undersized
piping between the water heater and the storage tank
or by some other factor that restricts proper water
ow through the water heater. The cause should be
determined and corrected.
8.5 High Gas Consumption
Appliances operating with an improper air/
fuel ratio are very inefcient and consequently, have
very high gas consumption. Because efciency is
high when the CO2 is high (or O2 is low), appliances
operating with low CO2 or high O2 (especially LP
appliances) consume more gas. Adjust the CO2 or O2
for optimum efciency. If no combustion analyzing
equipment (CO2 or O2) is available then a proper
adjustment of the air/fuel ratio (CO2 or O2) cannot be
accomplished. The CO2 should be 8% at high re for
natural gas and 9.2% at high re for LP. To check the
CO2, rst verify that the supply gas pressure is within
5 to 13 in. w.c. (1.2 to 3.2 kPa). With the Pennant
running, set the air box pressure to 1.5 in. w.c. (0.37
kPa) (as a starting point), by adjusting the air shutter(s)
at the intake of the fan(s). Check the CO2, and adjust
the air shutters if further adjustment to the CO2 is
needed.
directly through the “inducer” terminals F1 and F2 of
the (Fenwal) ignition module. The 24V power to the
T’STAT terminal of both ignition modules is routed
through the safety interlocks.
All 24V wiring is routed through the diagnostic
PC board. Wiring harnesses connect between the
diagnostic PC board and the control components,
indicator board, or eld wiring terminal strip. The
diagnostic board contains LEDs that indicate open
status of the safety interlocks, and quick-connect
terminals that provide tests points for checking
voltage/continuity at various points in the control
circuit.
Line-voltage connections are routed via the
line-voltage terminal buss. Certain control elements
that may need to be rewired in the eld are connected
via the eld wiring terminal strip rather than to the
diagnostic PC board. These include the low-water
cutoff (LWCO), water ow switch, and inlet/outlet
water temperature sensors.
SECTION 9.
Replacement Parts
Only genuine Laars replacement parts should be used.
9.1 General Information
To order or purchase parts for the Laars Pennant,
contact your nearest Laars dealer or distributor. If
they cannot supply you with what you need, contact
Customer Service (see back cover for address,
telephone and fax numbers).
9.2 Parts List
See next page for the list of available replace-
ment parts. See Figures 19-21 for exploded views
of the boiler's component systems to help identify
replacements parts.
8.6 Troubleshooting Pennant Controls
A diagnostic panel, that includes test points, as
well as diagnostic lights, is provided in the control
module. It is located on the right side of the module,
behind the display. To access, remove the retaining
screws from the display cover panel and remove
it. Grasp the control module at its base and pull it
outward.
Pennant ladder diagrams are shown in Figures
12 and 13. The wiring connection diagrams are shown