Laars Pennant PNCP 500, Pennant PNCP 750, Pennant PNCP 1250, Pennant PNCP 1500, Pennant PNCP 1750 Installation And Operation Instructions Manual

...
Installation and Operation Instructions Document 3164D
Installation and Operation Instructions for
Pennant
Pool Heater Model PNCP
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
If the information in this manual is not
WARNING
followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
AVERTISSEMENT
H2311900D
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction..................................................... 3
1.2 Model Identification......................................... 3
1.3 Warranty......................................................... 4
1.4 Dimensions..................................................... 4
1.5 Locating the Appliance ................................... 4
1.6 Locating Heater with Respect to Pool
System Loop................................................... 6
1.7 Locating Appliance for Correct Horizontal Vent/
Ducted Air Distance From Outside Wall ......... 6
SECTION 2. Venting and Combustion Air
2.1 Combustion Air ............................................... 6
2.1.1 Combustion Air From Room........................... 6
2.1.2 Intake Combustion Air .................................... 7
2.2 Venting ........................................................... 7
2.2.1 Vent Categories.............................................. 7
2.2.2 Category I Vent............................................... 7
2.2.3 Common Venting Systems ............................. 8
2.2.4 Category III Vent............................................. 8
2.3 Locating Vent & Combustion Air Terminals .... 8
2.3.1 Side Wall Vent Terminal ................................. 8
2.3.2 Side Wall Combustion Air Terminal ................ 9
2.3.3 Vertical Vent Terminal .................................. 10
2.3.4 Vertical Combustion Air Terminal ................. 10
2.4 Vent Terminals for Outdoor Units ................. 10
SECTION 3. Gas Supply and Piping
3.1 Gas Supply and Piping ................................. 10
SECTION 6. Operating Instructions
6.1 Sequence of Operation................................. 14
6.2 Filling the Heater System ............................. 15
6.3 Operating the Burner and Set Up ................. 15
6.3.1 Set Up for 0 to 2500 Feet Altitude ................ 15
6.3.2 High Altitude Adjustment and Set Up ........... 16
6.4 Shutting Down the Pennant.......................... 16
6.5 Backwash Switch Operation......................... 17
6.6 Spring and Fall Operation
Stand-by Service .......................................... 17
6.7 Winter Operation .......................................... 17
6.8 To Restart the Pennant ................................ 17
6.9 Therapeutic Pools (Spas) ............................. 17
SECTION 7. Maintenance
7.1 System Maintenance .................................... 18
7.2 Appliance Maintenance and
Component Description ................................ 18
7.2.1 Burners......................................................... 18
7.2.2 Filter ............................................................. 18
7.2.3 Gas Valves ................................................... 19
7.2.4 Pool Loop High Limit Control........................ 19
7.2.5 Automatic Reset High Limit Control.............. 19
7.2.6 Temperature Control .................................... 19
7.2.7 Ignition Controls............................................ 19
7.2.8 Ignitors.......................................................... 1 9
7.2.9 Ignition Sensors............................................ 19
7.2.10 Transformer.................................................. 19
7.2.11 Blowers ........................................................ 19
7.2.12 Flow Switch .................................................. 19
7.2.13 Heat Exchanger Coil .................................... 20
SECTION 4A. Water Connections
4.1 Piping ........................................................... 11
4.2 Automatic Chlorinators ................................. 12
4.3 Sensor Locations.......................................... 12
SECTION 5. Electrical Connections
5.1 Main Power................................................... 13
5.2 Temperature (Operating) Control ................. 13
5.3 Programming the Temperature Control........ 1 3
5.3.1 Temperature Control Overview .................... 13
5.3.2 Programming Control Parameters................ 14
5.3.3 Setpoint - LSP .............................................. 14
5.3.4 Differential - dLS........................................... 14
5.3.5 Pump Operation ........................................... 14
5.3.6 Heater Purge (Pump Delay) - PD ................. 14
5.4 Limit Controls................................................ 14
SECTION 8. Trouble Shooting
8.1 Resolving Lockouts ...................................... 20
8.2 Delayed Ignition – Possible Causes ............. 21
8.3 Short Cycling ................................................ 21
8.4 High Gas Consumption ................................ 21
8.5 Troubleshooting the Pool Heater
Temperature Control .................................... 21
8.6 Troubleshooting Pennant Controls ............... 21
SECTION 9. Replacement Parts
9.1 General Information...................................... 22
9.2 Parts List....................................................... 22
Pennant Pool Heater
Page 3
SECTION 1. General Information
In the Commonwealth of Massachusetts, this appliance must be installed by a licensed plumber or gas fitter.
WARNING
The Pennant pool heater must be installed in accordance with the procedures detailed in this manual, or the Laars Heating Systems warranty may be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of CAN/CGA-B149.1, Natural Gas Installation Code or CAN/CGA-B149.2, Propane Gas Installation Code, and/or local codes. Where required by the authority having jurisdiction, the installation of Pennant appliances must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modifications to the boiler, its gas controls, or wiring may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of Laars Heating Systems Pennant copper tube pool heaters. Read it carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Laars Heating Systems factory, or local factory representative, with any issues or questions regarding this equipment. Experience has shown that most operating issues are caused by improper installation.
The Pennant appliance is protected against over pressurization. A pressure relief valve is fitted to all appliances. It is installed on the outlet header, at the water outlet of the appliance.
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance with the 1). American National Standard Z223.1/ NFPA54-Latest Edition “National Fuel Gas Code” or
2). CAN/CGA 1-B149 “Installation Codes for Gas Burning Appliances and Equipment” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with the local codes, or in the absence of local codes, with: 1). The National Electrical Code ANSI/NFPA No. 70-latest Edition, or 2). CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance must be electrically grounded in accordance with these codes.
1.2 Model Identification
Consult the rating plate on the unit. The following information describes the model number structure.
Model Character Designation
1-3 Model Series Designation
P N C = Pennant
4 Usage
P = Pool Heater
5-8 Size
0 5 0 0 = 500,000 BTU/h input 0 7 5 0 = 750,000 BTU/h input 1 0 0 0 = 999,000 BTU/h input 1 2 5 0 = 1,250,000 BTU/h input 1 5 0 0 = 1,500,000 BTU/h input 1 7 5 0 = 1,750,000 BTU/h input 2 0 0 0 = 1,999,000 BTU/h input
9 Fuel
N = Natural Gas P = Liquid Propane
10 Altitude
A = 0-10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-off
1234567891011 12 13 14 1516 PNC P A C C 2 N
SERIES
PN C
USAGE
P
SIZE
0500 0750 1000 1250 1500 1750 2000
FUEL
N P
ALTITUDE
A
LOCATION
C
FIRING
MODE
C (ON/OFF)
REVISION
2
HEAT
EXCHANGER
B C K N P S
OPTIONS
CODE
X J L
PUMP
OPTIONS
N
Page 4
LAARS Heating Systems
13 Revision
2 = Second version
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. PNCP) K = Bronze / copper P = Glass-lined cast iron / cu-nickel / brz trim S = Bronze / cu-nickel
15 Option Code
X = Standard unit J = CSD-1, FM, IRI, IL L = MN and LDS (Indoor units only)
16 Pump Options
N = Pump mounted, normal pump
1.3 Warranty
Laars Heating Systems’ Pennant appliances are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Laars Heating Systems.
All warranty claims must be made to an authorized Laars Heating Systems representative or directly to the factory. Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
1.4 Dimensions
(See Figure 1.)
1.5 Locating the Appliance
The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certified by CSA­International for installation on combustible flooring; in basements; in closets, utility rooms or alcoves. The location for the appliance should be chosen with regard to the vent pipe lengths and external plumbing. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Pennant must be located as close as practical to a chimney or outside wall. If the vent terminal and/or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade.
The dimensions and requirements that are shown in Table 2 should be met when choosing the locations for the appliance.
HEATER VENT COLLAR VENT PIPE & PIPE MAX. PIPE MAX. NO. SIDE WALL SIDE WALL
HORIZONTAL AIR COLLAR
SIZE SIZE DIAMETER* DIAMETER LENGTH OF ELBOWS VENT COMBUSTION
IN. CM IN. CM IN CM FT. M PART NUMBER PART NUMBER
500 8 20 6 15 6 15 50 15 3 CA001401 20260701
750 10 25 8 20 6 15 50 15 3 CA001402 20260701 1000 10 25 8 20 8 20 50 15 3 CA001402 20260703 1250 12 30 8 20 8 20 50 15 3 CA001403 20260703 1500 12 30 8 20 8 20 50 15 3 CA001403 20260703 1750 14 36 8 20 8 20 50 15 3 CA001405 20260703 2000 14 36 12 30 12 30 50 15 3 CA001404 20260706
*Horizontal venting requires stainless vent pipe. See Table 5.
Table 1. Horizontal Vent / Combustion Air Parameters.
TERMINAL AIR TERMINAL
Pennant Pool Heater
Page 5
Shipping Weight Size lbs. kg 500 480 218 750 560 254 1000 670 304 1250 730 331 1500 815 370
Dimensions shown in
inches cm
SIZE A B C D E F G H W* V* PIPE
1750 880 400
AIR VENT HORIZ.
CONN. CONN. VENT
500 33½ 85 15¾ 40 15 29¾ 76 32¾ 83 20 22 46 117 6 15 8 20 6 15
750 45½ 116 21¾ 55 15 29¾ 76 32¾ 83 20 22 58 147 6 15 10 25 8 20 1000 57½ 146 28¾ 73 15 29¾ 76 32¾ 83 20 7 18 70 178 8 20 10 25 8 20 1250 68 172 34 86 101/8 26 30¾ 78 29½ 75 22 22 80 203 8 20 12 30 8 20 1500 78½ 199 39¾ 101 101/8 26 30¾ 78 29½ 75 22 22 91 231 8 20 12 30 8 20 1750 89 226 44½ 113 101/8 26 30¾ 78 29½ 75 22 22 101 256 8 20 14 36 8 20 2000 99½ 253 49¾ 126 101/8 26 30¾ 78 29½ 75 22 22 112 284 12 30 14 36 12 30
*Air and vent connections may be on top or back of the Pennant, and are field convertible. Dimensions in inches cm.
Figure 1. Dimensional Data.
Page 6
LAARS Heating Systems
1.6 Locating Heater with Respect to Pool System Loop
For the best results, the Pennant should be
located within 15 feet (4.6m) of the pool system loop. The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter piping shall be used. Consult the factory for assistance.
1.7 Locating Appliance for Correct Horizontal Vent/Ducted Air Distance From Outside Wall
The forced draft combustion air blower/blowers
in the appliance has/have sufficient power to pull air and vent properly when the following guidelines for horizontal air and vent are followed (see Table 1).
NOTE: On all model sizes, the vent collar size is larger than the size of the vent pipe that can be used. Vent collar size and horizontal pipe diameters can be found in Table 1. The larger vent collar size is to accommodate Category I (vertical) vent systems.
NOTE: When located on the same wall, the Pennant combustion air intake terminal must be installed a minimum of 12" (30cm) below the exhaust vent terminal and separated by a minimum of 36 inches (91cm) horizontally.
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other debris. Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result.
SECTION 2. Venting and Combustion Air
2.1 Combustion Air
Pennant pool heaters must have provisions for combustion and ventilation air in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections
7.2, 7.3 or 7.4 of CAN/CGA B149, Installation Codes, or applicable provisions of the local building codes.
A Pennant appliance may receive combustion air from the space in which it is installed, or it can be ducted directly to the unit from the outside. Ventilation air must be provided in either case. Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result.
2.1.1 Combustion Air From Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Method 1: Two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr
APPLIANCE CLEARANCE FROM SERVICE ACCESS
REQUIRED RECOMMENDED
SURFACE COMBUSTIBLE MATERIAL CLEARANCE
inches cm inches cm
Left Side 1 2.5 24 61
Right Side 1 2.5 24 61
Top 1 2.5 12 30 Back 1 2.5 **12** 30** Front 1 2.5 36 91
Vertical
(Category 1) 6* 15.2*
Vent
Horizontal per UL1738 venting
(Category 3) system supplier’s
Vent instructions
*1" (2.5cm) when b-vent is used. **When vent and/or combustion air connects to the back, recommended clearance is 36" (91cm).
Table 2. Clearances.
BOILER
SIZE SQUARE INCHES SQUARE CM
500 125 807
750 188 1213 1000 250 1613 1250 313 2020 1500 375 2420 1750 438 2826
2000 500 3226
*Net Free Area in Square Inches / Square cm Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area could be double the figures indicated.
This chart is for use when communicating directly with the outdoors. For special conditions and alternate methods, refer to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of louvers. Correct for screen resistance to the net free area if a screen is installed. Check all local codes applicable to
combustion air.
Table 3. Combustion Air Openings.
EACH OPENING*
Pennant Pool Heater
Page 7
(5.5 square cm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (11 square cm/kW) of total input rating of all equipment in the enclosure. Table 3 shows data for this sizing method, for each Pennant model.
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (7 square cm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
2.1.2 Intake Combustion Air
Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result. The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the Laars horizontal wall terminal (see Table 2). When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2).
Use single-wall galvanized pipe, per table 4, for the combustion air intake (see Table 1 for appropriate size). Route the intake to the heater as directly as possible. Seal all joints with tape. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is 50 feet (15.2m). Three elbows have been calculated into the 50-foot (15.2m) linear run. Subtract 10 allowable linear feet (3.0m) for every additional elbow used (see Table 1). When fewer than 3 elbows are used, the maximum linear pipe length allowed is still 50 feet (15.2m).
The connection for the intake air pipe is on the filter box. The Pennant appliances may have venting and combustion air ducting attached to the top or the back. They are shipped with the connections at the top. For attaching either or both pipes to the back, the mounting flanges are reversible by removing the mounting screws and orienting the flanges in the desired position. Replace the screws after positioning flanges. Run a bead of silicone around the collar and slide the pipe over the collar. Secure with sheet metal screws.
In addition to air needed for combustion, air shall also be supplied for ventilation, including all air required for comfort and proper working conditions for personnel. The Pennant loses less than 1 percent of its input rating to the room, but other heat sources may be present.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired Pennant venting, it may be considered a Category I or a Category III appliance. In general, a vertical vent system will be a Category I system. However, in rare instances, a Pennant’s vertical vent system may be considered Category III. In the U.S., the National Fuel Gas Code (American National Standard Z223.1-Latest Edition), or in Canada the CSA B149.1 (latest edition), defines a Category I vent system, and includes rules and tables to size these vent systems. If the Pennant’s vertical vent system does not satisfy the criteria for Category I venting, it must be vented as a Category III system.
All Pennant vent systems which discharge horizontally (without the use of a power venter) are considered Category III vent systems.
TERM DESCRIPTION
Pipe
Joint
Sealing
Table 4. Required Combustion Air Piping Material.
Single-wall galvanized steel pipe, 24 gauge
minimum (either insulated or non-insulated)
Permanent duct tape or aluminum tape
Figure 2. Combustion Air and Vent Through Roof.
Page 8
LAARS Heating Systems
2.2.2 Category I Vent
When vented as a category I appliance, the vent system must conform to the National Fuel Gas Code (American National Standard Z223.1-Latest Edition) in the U.S., or in Canada, to CSA B149.1 (latest edition). The vent system must be sized and installed for a Category I Fan-Assisted Appliance.
If chimney height is greater than 25 feet, or if multiple units are vented into the same vertical vent, a barometric damper must be installed on each appliance, such that the flue draft does not exceed (negative) 0.1" w.c.
If using a power venter for any type of Category I venting, the draft should be set between (negative)
0.01 and 0.10" w.c.
2.2.3 Common Venting Systems
Pennant units are Category I fan-assisted when vented vertically and adhering to all applicable codes. Pennant units are not allowed to be vented into a common horizontal vent system, unless a properly­sized vent fan is used, and the common vent system is properly designed by the vent fan manufacturer or a qualified engineer.When common venting Pennant fan-assisted heaters with other appliances through one shared vertical duct called a “common vent”, special care must be taken by the installer to ensure safe operation. In the event that the common vent is blocked, it is possible, especially for fan-assisted devices, to vent backwards through non-operating appliances sharing the vent, allowing combustion products to infiltrate occupied spaces. If the
appliances are allowed to operate in this condition, serious injury or death may occur.
WARNING
Operation of appliances with a blocked common vent may lead to serious injury or death. Safety devices must be implemented to prevent blocked common vent operation. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
It is for this reason that, in addition to following proper vent sizing, construction and safety requirements from the National Fuel Gas Code, ANSI Z223.1 or in Canada, from CSA B149.1 as well as all applicable local codes, it is required that installers provide some means to prevent operation with a blocked common vent. It is suggested that a blocked vent safety system be employed such that if the switch from one appliance trips due to excessive stack spill or backpressure indicating a blocked vent condition, that all appliances attached to the vent be locked out and prevented from operating. (Note that the Pennant Pool
Heater is equipped with a blocked vent safety (pressure) switch, as shipped.) As an additional precaution, it is recommended that a Carbon Monoxide (CO) alarm be installed in all enclosed spaces containing combustion appliances. If assistance is required in determining how a blocked vent safety system should be connected to a LAARS product, please call Applications Engineering at (603) 335-
6300. Refer to the installation and operating
instructions on all appliances to be common vented for instructions, warnings, restrictions and safety requirements. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
2.2.4 Category III Vent
When the Pennant is vented with horizontal
discharge, it must be installed per this installation manual and the venting system manufacturer’s installation instructions. The vent system must be sealed stainless steel, per Table 5.
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe. Horizontal runs must slope downwards not less than ¼ inch per foot (2 cm/m) from the unit to the vent terminal. Reference Table 2 for the size of the Category III vent system. Up to three elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable linear feet (3.0m) for every additional elbow used.
TERM DESCRIPTION
Pipe Must comply with UL Standard 1738
such as Type 29-4C Stainless Steel
(either insulated or non-insulated).
Joint Follow vent manufacturer’s instructions
Sealing
Table 5. Required Horizontal Venting Material.
2.3 Locating Vent & Combustion Air Terminals
2.3.1 Side Wall Vent Terminal
The Laars side wall vent hood (listed in Table 1)
must be used when the heater is vented through a side wall. It provides a means of installing vent piping through the building wall, and must be located in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada the installation must be in accordance with CAN/CGA B149.1 or .2 and
Pennant Pool Heater
Page 9
*When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet.
Figure 3. Combustion Air and Vent Through Side Wall.
local applicable codes (see Figure 3). Consider the following when installing the terminal:
1. Through-the-wall vent terminals must terminate at least 7-feet above a public walkway.
2. Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets. The National Fuel Gas Code requires that it be at least 3 feet (0.9m) above any such inlet that is within a horizontal distance of 10 feet (3m).
3. Locate the vent terminal so that vent gases cannot enter the building through doors, windows, gravity inlets or other openings. The National Fuel Gas Code requires that it be located at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (0.3m) above such openings. Whenever possible, locations under windows or near doors should be avoided.
4. Locate the vent terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30 cm) above grade, but the installer may determine it should be higher, depending upon local conditions.
5. Locate the terminal so the vent exhaust does not settle on building surfaces and other nearby objects. Vent products may damage such surfaces or objects.
6. Locate the terminal at least 6 feet (1.8m) horizontally from any gas or electric metering, regulating, or relief equipment.
7. If the Pennant uses ducted combustion air from an intake terminal located on the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.
8. Note that side wall vent terminals for models 750-2000 are shipped with reducers for the vent collars, to accommodate horizontal vent sizes, shown in Table 1.
WARNING
The outdoor vent terminal gets hot. Unit must be installed in such a way as to reduce the risk of burns from contact with the vent terminal.
2.3.2 Side Wall Combustion Air Terminal
Never obtain combustion air from the pool area.
Corrosion of and/or damage to the pool heater may result. The Laars side wall combustion air terminal (listed in Table 1) must be used when the unit takes its combustion air through a duct from a side wall. Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning fluid, chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject to damage by accident or vandalism.
3. Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel
Page 10
LAARS Heating Systems
Gas Code requires that it be at least 12 inches (30 cm) above grade, but the installer may determine it should be higher, depending upon local conditions.
4. If the Pennant is side-wall vented to the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal (see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2). The opening on the end of the terminal must be at least 12" (30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
2.4 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from falling into the Pennant.
Part numbers for the terminals to cover the vent
and combustion air openings are shown in Table 6. Vent opening must be on top of the unit, and the combustion air opening must be on the back of the unit. The terminals are connected directly to the unit. No vent piping is used.
Alternately, the installer may use a short piece of
OUTDOOR VENT OUTDOOR
SIZE TERMINAL COMBUSTION
AIR TERMINAL
500 20254703 D2007900
750 20254705 D2007900 1000 20254705 D2008000 1250 D2007700 D2008000 1500 D2007700 D2008000 1750 D2007800 D2008000 2000 D2007800 D2008200
galvanized single wall or B-vent and an approved rain cap for the vent termination. A minimum 12" of vent height is acceptable. In addition, a properly sized single wall galvanized 90° ell can be used for the intake air terminal, with the open end of the ell facing down to prevent rain infiltration. The combustion air inlet opening must still be high enough to prevent blockage by snow (see Section 2.3.2).
SECTION 3. Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not by the appliance.
The Pennant’s gas train allows the user to pipe the gas from either the right side or the left side of the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side. If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on the right side may be moved to the left.
Review the following instructions before proceeding with the installation.
1. Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Laars
Heating Systems appliances are normally
equipped to operate at elevations up to 2000
feet (610m). Pennant appliances may be adjusted
to operate properly at higher elevations;
however, input will be reduced if the heating
value of the gas supply is below sea level values.
2. The maximum inlet gas pressure must not exceed
DISTANCE FROM GAS METER
SIZE AND
GAS TYPE 0-100' 0-31m 100-200' 31-61m 200-300' 61-91m
500 natural 1-1/2" 3.8cm 2" 5.1cm 2" 5.1cm 500 propane 1" 2.5cm 1-1/2" 3.8cm 1-1/2" 3.8cm
750 natural 2" 5.1cm 2" 5.1cm 2-1/2" 6.4cm 750 propane 1-1/2" 3.8cm 1-1/2" 3.8cm 2" 5.1cm
1000 natural 2" 5.1cm 2-1/2" 6.4cm 3" 7.6cm 1000 propane 1-1/2" 3.8cm 2" 5.1cm 2-1/2" 6.4cm
1250 natural 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm 1250 propane 2" 5.1cm 2" 5.1cm 2-1/2" 6.4cm
1500 natural 2-1/2" 6.4cm 3" 7.6cm 3" 7.6cm 1500 propane 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm
1750 natural 2-1/2" 6.4cm 3" 7.6cm 3" 7.6cm 1750 propane 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm
2000 natural 3" 7.6cm 3" 7.6cm 3-1/2" 8.9cm 2000 propane 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm
Notes:
1. These figures are based on 1/2" (0.12kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing.
OR LAST STAGE REGULATOR
Table 6. Vent Terminals for Outdoor Units
Table 7. Gas Piping Size.
Pennant Pool Heater
Page 11
13" W.C (3.2kPa). The minimum inlet gas pressure is 5" W.C. (1.2kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
Caution
Do not use open flame to check for leaks.
NOTE: The Pennant appliance and all other gas appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line. The Pennant may not fire if the gas pressure lower than 5" w.c.
SECTION 4. Water Connections
4.1 Piping
Hot water piping should be supported by suitable hangers or floor stands. Do not support piping with this appliance. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to a drain or in a manner to prevent injury in the event of pressure relief. Install shutoff valves where required by code.
Pennant Pool Heaters are equipped with mounted pumps, which serve the heater plus 30 feet of full­sized piping with a normal number of fittings. If the pool’s loop is more than 15 feet away from the heater, please contact the factory.
A mixing system is mounted on the heater. The system consists of a three-way valve, temperature control and piping. The temperature sensor for the control is in the heater inlet. When the control detects water temperature that is below 120°F (49°C), it will direct the three-way valve to actuate, which sends water from the outlet of the heater back to the inlet. The outlet water that is diverted to the inlet mixes with the return water from the pool, and keeps the inlet temperature at or above 120°F (49°C) (see Figure 5). This keeps cold return water from causing condensing on the outside of the Pennant heat exchanger.
IMPORTANT NOTE: Since heater outlet temperatures can reach 150°F (66°C) in some cases, copper or CPVC are recommended materials for heater connection piping. PVC material may be used for the inlet valve and the piping upstream of it.
When pipe, fittings, grids or any other element of the filter system are made of plastic materials, they may be damaged by the momentary “back siphoning”
Mixing Controller Sensor (120°F) Pool Loop / Inlet (2 used)
Figure 5. Mixing System.Figure 4. Typical Gas Train Configuration.
Loading...
+ 25 hidden pages