LAARS Pennant PNCP User Manual

Page 1
Installation and Operation Instructions Document 3164E
Installation and Operation Instructions for
PENNANT
Pool Heater Model PNCP
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency, or gas supplier.
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualié ou par le fournisseur de gaz.
AVERTISSEMENT
H2311900E
Page 2
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction ...................................................... 3
1.2 Model Identication .......................................... 3
1.3 Warranty .......................................................... 4
1.4 Dimensions ...................................................... 4
1.5 Locating the Appliance..................................... 4
1.6 Locating Heater with Respect to Pool
System Loop .................................................... 6
1.7 Locating Appliance for Correct Horizontal Vent/
Ducted Air Distance From Outside Wall .......... 6
SECTION 2.
Venting and Combustion Air
2.1 Combustion Air ................................................ 6
2.1.1 Combustion Air From Room ............................ 6
2.1.2 Intake Combustion Air...................................... 7
2.2 Venting ............................................................. 7
2.2.1 Vent Categories ............................................... 7
2.2.2 Category I Vent ................................................ 8
2.2.3 Common Venting Systems .............................. 8
2.2.4 Category III Vent .............................................. 8
2.3 Locating Vent & Combustion Air Terminals ...... 8
2.3.1 Side Wall Vent Terminal ................................... 8
2.3.2 Side Wall Combustion Air Terminal .................. 9
2.3.3 Vertical Vent Terminal .................................... 10
2.3.4 Vertical Combustion Air Terminal ................... 10
2.4 Vent Terminals for Outdoor Units ................... 10
SECTION 3.
Gas Supply and Piping
3.1 Gas Supply and Piping ...................................11
SECTION 4A. Water Connections
4.1 Piping ............................................................. 12
4.2 Automatic Chlorinators .................................. 13
4.3 Sensor Locations ........................................... 13
SECTION 5. Electrical Connections
5.1 Main Power .................................................... 13
5.1.1 Sizes 500-1500 .............................................. 13
5.1.2 Sizes 1750-2000 ............................................ 13
5.1.3 Separate Pump Circuit................................... 13
5.1.4 Auxiliary Time Clock Wiring ........................... 14
5.1.5 All Sizes ......................................................... 14
5.2 Temperature (Operating) Control .................. 14
5.3 Programming the Temperature Control ......... 14
5.3.1 Temperature Control Overview ...................... 14
5.3.2 Programming Control Parameters ................. 14
5.3.3 Setpoint - LSP ................................................ 15
5.3.4 Differential - dLS ............................................ 16
5.3.5 Pump Operation............................................. 16
5.3.6 Heater Purge (Pump Delay) - PD .................. 16
5.4 Limit Controls ................................................. 16
SECTION 6.
Operating Instructions
6.1 Sequence of Operation .................................. 16
6.2 Filling the Heater System............................... 17
6.3 Operating the Burner and Set Up .................. 17
6.3.1 Set Up for 0 to 2500 Feet Altitude.................. 17
6.3.2 High Altitude Adjustment and Set Up ............. 18
6.4 Shutting Down the Pennant ........................... 18
6.5 Backwash Switch Operation .......................... 18
6.6 Spring and Fall Operation
Stand-by Service ........................................... 19
6.7 Winter Operation............................................ 19
6.8 To Restart the Pennant .................................. 19
6.9 Therapeutic Pools (Spas) .............................. 19
SECTION 7. Maintenance
7.1 System Maintenance ..................................... 20
7.2 Appliance Maintenance and
Component Description ................................. 20
7.2.1 Burners .......................................................... 20
7.2.2 Filter ............................................................... 20
7.2.3 Gas Valves ..................................................... 20
7.2.4 Pool Loop High Limit Control ......................... 20
7.2.5 Automatic Reset High Limit Control ............... 20
7.2.6 Temperature Control ...................................... 21
7.2.7 Ignition Controls ............................................. 21
7.2.8 Ignitors ........................................................... 21
7.2.9 Ignition Sensors ............................................. 21
7.2.10 Transformer ................................................... 21
7.2.11 Blowers .......................................................... 21
7.2.12 Flow Switch ................................................... 21
7.2.13 Heat Exchanger Coil...................................... 21
SECTION 8.
Trouble Shooting
8.1 Resolving Lockouts........................................ 22
8.2 Delayed Ignition – Possible Causes .............. 22
8.3 Short Cycling ................................................. 22
8.4 High Gas Consumption.................................. 23
8.5 Troubleshooting the Pool Heater
Temperature Control ...................................... 23
8.6 Troubleshooting Pennant Controls ................ 23
SECTION 9.
Replacement Parts
9.1 General Information ....................................... 23
9.2 Parts List ........................................................ 23
Page 3
Pennant Pool Heater
Page 3
SECTION 1. General Information
In the Commonwealth of Massachusetts, this
appliance must be installed by a licensed plumber or
gas tter.
WARNING
The Pennant pool heater must be installed in
accordance with the procedures detailed in this manual, or the Laars Heating Systems warranty
may be voided. The installation must conform to
the requirements of the local jurisdiction having
authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA54. In Canada, the installation must conform to the latest edition of CAN/CGA-B149.1, Natural Gas Installation Code or CAN/CGA-B149.2, Propane Gas Installation Code, and/or local codes. Where required by the authority having jurisdiction,
the installation of Pennant appliances must conform to the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ ASME CSD-1. Any modications to the boiler, its gas controls, or wiring may void the warranty. If eld conditions require modications, consult the factory representative before initiating such modications.
1.1 Introduction
This manual provides information necessary for
the installation, operation, and maintenance of Laars
Heating Systems Pennant copper tube pool heaters. Read it carefully before installation.
All application and installation procedures
should be reviewed completely before proceeding with
the installation. Consult the Laars Heating Systems
factory, or local factory representative, with any issues
or questions regarding this equipment. Experience
has shown that most operating issues are caused by
improper installation.
The Pennant appliance is protected against over
pressurization. A pressure relief valve is tted to all appliances. It is installed on the outlet header, at the water outlet of the appliance.
IMPORTANT: The inlet gas pressure to the appliance must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance
with the 1). American National Standard Z223.1/ NFPA54-Latest Edition “National Fuel Gas Code” or 2). CAN/CGA 1-B149 “Installation Codes for Gas Burning Appliances and Equipment” and with the
requirement of the local utility or other authorities
having jurisdiction. Such applicable requirements take
precedence over the general instructions contained
herein.
All electrical wiring is to be done in accordance
with the local codes, or in the absence of local
codes, with: 1). The National Electrical Code ANSI/ NFPA No. 70-latest Edition, or 2). CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance
must be electrically grounded in accordance with these
codes.
1.2 Model Identication
Consult the rating plate on the unit. The
following information describes the model number
structure.
Model Character Designation
1-3 Model Series Designation
P N C = Pennant
4 Usage
P = Pool Heater
5-8 Size
0 5 0 0 = 500,000 BTU/h input 0 7 5 0 = 750,000 BTU/h input 1 0 0 0 = 999,000 BTU/h input 1 2 5 0 = 1,250,000 BTU/h input 1 5 0 0 = 1,500,000 BTU/h input 1 7 5 0 = 1,750,000 BTU/h input 2 0 0 0 = 1,999,000 BTU/h input
9 Fuel
N = Natural Gas P = Liquid Propane
10 Altitude
A = 0-10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-off
13 Revision
2 = Second version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P N C P A C C 2
SERIES
P N C
USAGE
P
SIZE
0 5 0 0
0 7 5 0
1 0 0 0
1 2 5 0
1 5 0 0
1 7 5 0
2 0 0 0
FUEL
N
P
ALTITUDE
A
LOCATION
C
FIRING
MODE
C (ON/OFF)
REVISION
2
HEAT
EXCHANGER
B
P
OPTIONS
CODE
X
J
PUMP
OPTIONS
N
B
Page 4
Page 4
LAARS Heating Systems
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. PNCP) P = Glass-lined cast iron / cu-nickel / brz trim
15 Option Code
X = Standard unit J = CSD-1, FM, IRI, IL
16 Pump Options
N = Pump mounted, TACO, normal water pump B = Pump mounted, B&G, optional normal water pump
1.3 Warranty
Laars Heating Systems appliances are covered by a limited warranty. Owners should submit online warranty registration at www.Laars.com.
All warranty claims must be made to an authorized Laars Heating Systems representative, directly to Customer Service, or online at www.Laars.com.
Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment whether visible or concealed.
1.4 Dimensions
(See Figure 1.)
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area
adjacent to the appliance or to lower oors of the
structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certied by CSA­International for installation on combustible ooring; in basements; in closets, utility rooms or alcoves. The location for the appliance should be chosen
with regard to the vent pipe lengths and external
plumbing. The unit shall be installed such that the gas
ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Pennant must be located as close as practical to a chimney or outside wall. If the vent terminal and/or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade.
The dimensions and requirements that are shown
in Table 2 should be met when choosing the locations for the appliance.
HORIZONTAL AIR COLLAR HEATER VENT COLLAR VENT PIPE & PIPE MAX. PIPE MAX. NO. SIDE WALL SIDE WALL SIZE SIZE DIAMETER* DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL AIR TERMINAL
IN. CM IN. CM IN CM FT. M PART NUMBER PART NUMBER
500 8 20 6 15 6 15 50 15 3 CA001401 20260701 750 10 25 8 20 6 15 50 15 3 CA001402 20260701 1000 10 25 8 20 8 20 50 15 3 CA001402 20260703 1250 12 30 8 20 8 20 50 15 3 CA001403 20260703 1500 12 30 8 20 8 20 50 15 3 CA001403 20260703 1750 14 36 8 20 8 20 50 15 3 CA001405 20260703
2000 14 36 12 30 12 30 50 15 3 CA001404 20260706
*Horizontal venting requires stainless vent pipe. See Table 5.
Table 1. Horizontal Vent / Combustion Air Parameters.
Page 5
Pennant Pool Heater
Page 5
Shipping Weight Size lbs. kg 500 480 218 750 560 254 1000 670 304 1250 730 331 1500 815 370 1750 880 400
Dimensions shown in
inches cm
AIR VENT HORIZ. CONN. CONN. VENT SIZE A B C D E F G H W* V* PIPE
500 33½ 85 15¾ 40 15 29¾ 76 32¾ 83 20 22 46 117 6 15 8 20 6 15
750 45½ 116 21¾ 55 15 29¾ 76 32¾ 832022 58 147 6 15 10 25 8 20
1000 57½ 146 28¾ 73 15 29¾ 76 32¾ 8320 7 18 70 178 8 20 10 25 8 20
1250 68 172 34 86 101/8 26 30¾ 78 29½ 75 22 22 80 203 8 20 12 30 8 20
1500 78½ 199 39¾ 101 101/8 26 30¾ 78 29½ 75 22 22 91 231 8 20 12 30 8 20
1750 89 226 44½ 113 101/8 26 30¾ 78 29½ 75 22 22 101 256 8 20 14 36 8 20
2000 99½ 253 49¾ 126 101/8 26 30¾ 78 29½ 75 22 22 112 284 12 30 14 36 12 30
*Air and vent connections may be on top or back of the Pennant, and are eld convertible. Dimensions in inches cm.
Figure 1. Dimensional Data.
Page 6
Page 6
LAARS Heating Systems
1.6 Locating Heater with Respect to Pool System Loop
For the best results, the Pennant should be
located within 15 feet (4.6m) of the pool system loop. The pump is sized for 30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter piping shall be used. Consult the factory for assistance.
1.7 Locating Appliance for Correct Horizontal Vent/Ducted Air Distance
From Outside Wall
The forced draft combustion air blower/blowers
in the appliance has/have sufcient power to pull air
and vent properly when the following guidelines for horizontal air and vent are followed (see Table 1).
NOTE: On all model sizes, the vent collar size is larger than the size of the vent pipe that can be used. Vent collar size and horizontal pipe diameters can be found in Table 1. The larger vent collar size is to accommodate Category I (vertical) vent systems.
NOTE: When located on the same wall, the Pennant
combustion air intake terminal must be installed
a minimum of 12" (30cm) below the exhaust vent
terminal and separated by a minimum of 36 inches (91cm) horizontally.
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other debris. Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result.
SECTION 2.
Venting and Combustion Air
2.1 Combustion Air
Pennant pool heaters must have provisions for
combustion and ventilation air in accordance with
section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections
7.2, 7.3 or 7.4 of CAN/CGA B149, Installation Codes, or applicable provisions of the local building codes.
A Pennant appliance may receive combustion
air from the space in which it is installed, or it can be
ducted directly to the unit from the outside. Ventilation air must be provided in either case. Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result.
2.1.1 Combustion Air From Room
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
Method 1: Two permanent openings, one
commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per 4000
REQUIRED RECOMMENDED APPLIANCE CLEARANCE FROM SERVICE ACCESS
SURFACE COMBUSTIBLE MATERIAL CLEARANCE
inches cm inches cm Left Side 1 2.5 24 61 Right Side 1 2.5 24 61 Top 1 2.5 12 30 Back 1 2.5 **12** 30** Front 1 2.5 36 91 Vertical (Category 1) 6* 15.2* Vent
Horizontal per UL1738 venting (Category 3) system supplier’s Vent instructions
*1" (2.5cm) when b-vent is used. **When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).
Table 2. Clearances.
BOILER EACH OPENING*
SIZE SQUARE INCHES SQUARE CM
500 125 807 750 188 1213 1000 250 1613 1250 313 2020 1500 375 2420 1750 438 2826 2000 500 3226
*Net Free Area in Square Inches / Square cm Area indicated is for one of two openings; one at oor level and
one at the ceiling, so the total net free area could be double the
gures indicated. This chart is for use when communicating directly with the
outdoors. For special conditions and alternate methods, refer to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of
louvers. Correct for screen resistance to the net free area if a screen is installed. Check all local codes applicable to
combustion air.
Table 3. Combustion Air Openings.
Page 7
Pennant Pool Heater
Page 7
Btu/hr (5.5 square cm/kW) of total input rating of all equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than
1 square inch per 2000 Btu/hr (11 square cm/kW) of total input rating of all equipment in the enclosure. Table 3 shows data for this sizing method, for each Pennant model.
Method 2: One permanent opening, commencing within 12 inches (30 cm) of the top of the enclosure, shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (7 square cm/kW) of the total input rating of all equipment located in the enclosure. This
opening must not be less than the sum of the areas of
all vent connectors in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow
CAN/CGA B149.
2.1.2 Intake Combustion Air
Never obtain combustion air from the pool area. Corrosion of and/or damage to the pool heater may result. The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the Laars horizontal wall terminal (see Table 1). When taken from the roof, a eld-supplied rain cap or an elbow
arrangement must be used to prevent entry of rain water (see Figure 2).
Use single-wall galvanized pipe, per table 4, for the combustion air intake (see Table 1 for appropriate size). Route the intake to the heater as directly as possible. Seal all joints with tape. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is 50 feet (15.2m). Three elbows have been calculated into the 50-foot (15.2m) linear run. Subtract 10 allowable linear feet (3.0m) for every additional elbow used (see Table 1). When fewer than 3 elbows are used, the maximum linear pipe length allowed is still 50 feet (15.2m).
TERM DESCRIPTION
Pipe Single-wall galvanized steel pipe, 24 gauge minimum (either insulated or non-insulated)
Joint Permanent duct tape or aluminum tape Sealing
The connection for the intake air pipe is on the
lter box. The Pennant appliances may have venting
and combustion air ducting attached to the top or the
back. They are shipped with the connections at the top. For attaching either or both pipes to the back, the mounting anges are reversible by removing the mounting screws and orienting the anges in the desired position. Replace the screws after positioning anges. Run a bead of silicone around the collar and slide the pipe over the collar. Secure with sheet metal screws.
In addition to air needed for combustion, air
shall also be supplied for ventilation, including all air
required for comfort and proper working conditions for personnel. The Pennant loses less than 1 percent of
its input rating to the room, but other heat sources may
be present.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired Pennant venting, it
may be considered a Category I or a Category III
appliance. In general, a vertical vent system will be a Category I system. However, in rare instances, a
Pennant’s vertical vent system may be considered
Category III. In the U.S., the National Fuel Gas Code (American National Standard Z223.1-Latest Edition), or in Canada the CSA B149.1 (latest edition), denes
a Category I vent system, and includes rules and tables
to size these vent systems. If the Pennant’s vertical
vent system does not satisfy the criteria for Category I
venting, it must be vented as a Category III system.
All Pennant vent systems which discharge
horizontally (without the use of a power venter) are
considered Category III vent systems.
Table 4. Required Combustion Air Piping Material.
Figure 2. Combustion Air and Vent Through Roof.
Page 8
Page 8
LAARS Heating Systems
2.2.2 Category I Vent
When vented as a category I appliance, the vent
system must conform to the National Fuel Gas Code (American National Standard Z223.1-Latest Edition) in the U.S., or in Canada, to CSA B149.1 (latest edition). The vent system must be sized and installed for a Category I Fan-Assisted Appliance.
If chimney height is greater than 25 feet, or
if multiple units are vented into the same vertical vent, a barometric damper must be installed on each
appliance, such that the ue draft does not exceed (negative) 0.1" w.c.
If using a power venter for any type of Category
I venting, the draft should be set between (negative)
0.01 and 0.10" w.c.
2.2.3 Common Venting Systems
Pennant units are Category I fan-assisted when
vented vertically and adhering to all applicable codes.
Pennant units are not allowed to be vented into a
common horizontal vent system, unless a properly-
sized vent fan is used, and the common vent system is properly designed by the vent fan manufacturer or
a qualied engineer.When common venting Pennant fan-assisted heaters with other appliances through one shared vertical duct called a “common vent”, special care must be taken by the installer to ensure safe operation. In the event that the common vent is blocked, it is possible, especially for fan-assisted devices, to vent backwards through non-operating
appliances sharing the vent, allowing combustion
products to inltrate occupied spaces. If the appliances are allowed to operate in this condition, serious injury or death may occur.
WARNING
Operation of appliances with a blocked common vent may lead to serious injury or death. Safety
devices must be implemented to prevent blocked common vent operation. If safe operation of all appliances connected to a common vent cannot
be assured, including prevention of spillage of ue
gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
It is for this reason that, in addition to
following proper vent sizing, construction and safety
requirements from the National Fuel Gas Code, ANSI Z223.1 or in Canada, from CSA B149.1 as
well as all applicable local codes, it is required that installers provide some means to prevent operation
with a blocked common vent. It is suggested that a blocked vent safety system be employed such that if the switch from one appliance trips due to excessive stack spill or backpressure indicating a blocked vent
condition, that all appliances attached to the vent be
locked out and prevented from operating. (Note that
the Pennant Pool Heater is equipped with a blocked vent safety (pressure) switch, as shipped.) As an
additional precaution, it is recommended that a Carbon
Monoxide (CO) alarm be installed in all enclosed spaces containing combustion appliances. If assistance is required in determining how a blocked vent safety
system should be connected to a LAARS product,
please call Applications Engineering at the telephone number on back cover of this manual.
Refer to the installation and operating instructions on all appliances to be common vented for instructions, warnings, restrictions and safety
requirements. If safe operation of all appliances
connected to a common vent cannot be assured,
including prevention of spillage of ue gasses into
living spaces, common venting should not be applied,
and appliances should each be vented separately.
2.2.4 Category III Vent
When the Pennant is vented with horizontal discharge, it must be installed per this installation manual and the venting system manufacturer’s
installation instructions. The vent system must be
sealed stainless steel, per Table 5.
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers
as required in the venting system manufacturer’s
Installation Instructions. Horizontal portions of the
venting system must be supported to prevent sagging and may not have any low sections that could trap
condensate. The unit must not support the weight of the vent pipe. Horizontal runs must slope downwards not less than ¼ inch per foot (2 cm/m) from the unit to the vent terminal. Reference Table 1 for the size of the Category III vent system. Up to three elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable linear feet (3.0m) for every additional elbow used.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Side Wall Vent Terminal
The Laars side wall vent hood (listed in Table
1) must be used when the heater is vented through
a side wall. It provides a means of installing vent
piping through the building wall, and must be located
in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada the installation must be in accordance with CAN/CGA B149.1 or .2 and
TERM DESCRIPTION Pipe Must comply with UL Standard 1738 such as Type 29-4C Stainless Steel
(either insulated or non-insulated).
Joint Follow vent manufacturer’s instructions
Sealing
Table 5. Required Horizontal Venting Material.
Page 9
Pennant Pool Heater
Page 9
Figure 3. Combustion Air and Vent Through Side Wall.
local applicable codes (see Figure 3). Consider the following when installing the terminal:
1. Through-the-wall vent terminals must terminate at least 7-feet above a public walkway.
2. Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets. The National Fuel Gas Code requires that it be at least 3 feet (0.9m) above any such inlet
that is within a horizontal distance of 10 feet (3m).
3. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows,
gravity inlets or other openings. The National Fuel Gas Code requires that it be located at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (0.3m) above such openings.
Whenever possible, locations under windows or
near doors should be avoided.
4. Locate the vent terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30 cm)
above grade, but the installer may determine it should be higher, depending upon local
conditions.
5. Locate the terminal so the vent exhaust does
not settle on building surfaces and other nearby
objects. Vent products may damage such surfaces or objects.
6. Locate the terminal at least 6 feet (1.8m)
horizontally from any gas or electric metering,
regulating, or relief equipment.
7. If the Pennant uses ducted combustion air from an intake terminal located on the same wall, locate the vent terminal at least 3 feet (0.9m)
horizontally from the combustion air terminal,
and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.
8. Note that side wall vent terminals for models 750-2000 are shipped with reducers for the vent
collars, to accommodate horizontal vent sizes, shown in Table 1.
WARNING
The outdoor vent terminal gets hot. Unit must be
installed in such a way as to reduce the risk of burns from contact with the vent terminal.
2.3.2 Side Wall Combustion Air Terminal
Never obtain combustion air from the pool area.
Corrosion of and/or damage to the pool heater may result. The Laars side wall combustion air terminal (listed in Table 1) must be used when the unit takes its combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning uid, chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject to damage by accident or vandalism.
3. Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel
Page 10
Page 10
LAARS Heating Systems
Gas Code requires that it be at least 12 inches (30
cm) above grade, but the installer may determine it should be higher, depending upon local
conditions.
4. If the Pennant is side-wall vented to the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal (see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 2).
2.4 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from
falling into the Pennant.
Part numbers for the terminals to cover the vent
and combustion air openings are shown in Table
6. Vent opening must be on top of the unit, and the combustion air opening must be on the back of the unit. The terminals are connected directly to the unit. No vent piping is used.
Alternately, the installer may use a short piece
of galvanized single wall or B-vent and an approved rain cap for the vent termination. A minimum 12" of vent height is acceptable. In addition, a properly sized single wall galvanized 90° ell can be used for the intake air terminal, with the open end of the ell facing down to prevent rain inltration. The combustion air
inlet opening must still be high enough to prevent
blockage by snow (see Section 2.3.2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
eld-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2). The opening on the end of the terminal must be at least
12" (30cm) above the point at which it penetrates the
roof, and high enough above the roof line to prevent
blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.
OUTDOOR VENT OUTDOOR SIZE TERMINAL COMBUSTION
AIR TERMINAL
500 20254703 D2007900 750 20254705 D2007900 1000 20254705 D2008000 1250 D2007700 D2008000 1500 D2007700 D2008000 1750 D2007800 D2008000 2000 D2007800 D2008200
Table 6. Vent Terminals for Outdoor Units
Page 11
Pennant Pool Heater
Page 11
SECTION 3.
Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or oor stands, not by the appliance.
The Pennant’s gas train allows the user to pipe
the gas from either the right side or the left side of
the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side.
If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on
the right side may be moved to the left.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is tted for the proper type of gas by checking the rating plate. Laars
Heating Systems appliances are normally
equipped to operate at elevations up to 2000 feet (610m). Pennant appliances may be adjusted to operate properly at higher elevations; however,
input will be reduced if the heating value of the
gas supply is below sea level values.
2. The maximum inlet gas pressure must not exceed 13" W.C (3.2kPa). The minimum inlet gas pressure is 5" W.C. (1.2kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to action of liqueed petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping during any pressure testing of that system at test
pressures in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or
less than 1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
Caution
Do not use open ame to check for leaks.
NOTE: The Pennant appliance and all other gas
appliances sharing the gas supply line must be ring
at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at
the supply pressure port on the gas valve. Low gas
pressure could be an indication of an undersized
gas meter, undersized gas supply lines and/or an obstructed gas supply line. The Pennant may not re if the gas pressure lower than 5" w.c.
DISTANCE FROM GAS METER
SIZE AND
GAS TYPE 0-100' 0-31m 100-200' 31-61m 200-300' 61-91m 500 natural 1-1/2" 3.8cm 2" 5.1cm 2" 5.1cm
500 propane 1" 2.5cm 1-1/2" 3.8cm 1-1/2" 3.8cm
750 natural 2" 5.1cm 2" 5.1cm 2-1/2" 6.4cm
750 propane 1-1/2" 3.8cm 1-1/2" 3.8cm 2" 5.1cm
1000 natural 2" 5.1cm 2-1/2" 6.4cm 3" 7.6cm
1000 propane 1-1/2" 3.8cm 2" 5.1cm 2-1/2" 6.4cm
1250 natural 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm
1250 propane 2" 5.1cm 2" 5.1cm 2-1/2" 6.4cm
1500 natural 2-1/2" 6.4cm 3" 7.6cm 3" 7.6cm
1500 propane 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm
1750 natural 2-1/2" 6.4cm 3" 7.6cm 3" 7.6cm
1750 propane 2" 5.1cm 2-1/2" 6.4cm 2-1/2" 6.4cm
2000 natural 3" 7.6cm 3" 7.6cm 3-1/2" 8.9cm
2000 propane 2-1/2" 6.4cm 2-1/2" 6.4cm 3" 7.6cm
Notes:
1. These gures are based on 1/2" (0.12kPa) water column
pressure drop.
2. Check supply pressure and local code requirements before
proceeding with work.
3. Pipe ttings must be considered when determining gas pipe
sizing.
OR LAST STAGE REGULATOR
Table 7. Gas Piping Size.
Figure 4. Typical Gas Train Conguration.
Page 12
Page 12
LAARS Heating Systems
SECTION 4. Water Connections
4.1 Piping
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used when rigid hangers are installed. Maintain 1" clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to
a drain or in a manner to prevent injury in the event of
pressure relief. Install shutoff valves where required by code.
Pennant Pool Heaters are equipped with mounted
pumps, which serve the heater plus 30 feet of full­sized piping with a normal number of ttings. If the pool’s loop is more than 15 feet away from the heater, please contact the factory.
A mixing system is mounted on the heater. The system consists of a three-way valve, temperature control and piping. The temperature sensor for the control is in the heater inlet. When the control detects water temperature that is below 120°F (49°C), it will direct the three-way valve to actuate, which sends water from the outlet of the heater back to the inlet. The outlet water that is diverted to the inlet mixes with the return water from the pool, and keeps the inlet temperature at or above 120°F (49°C) (see Figure 5).
This keeps cold return water from causing condensing on the outside of the Pennant heat exchanger.
IMPORTANT NOTE: Since heater outlet temperatures can reach 150°F (66°C) in some cases, copper or CPVC are recommended materials for heater connection piping. PVC material may be used for the inlet valve and the piping upstream of it.
When pipe, ttings, grids or any other element of the lter system are made of plastic materials, they may be damaged by the momentary “back siphoning” of hot water from the heater when the lter pump stops running.
See Figure 6 for proper connection of the Pennant heater to the pool loop.
4.2 Automatic Chlorinators
Figure 5. Mixing System.
The Pennant Pool Heater is shipped with a eld-installed mixing system, and must be piped in primary­secondary style, as shown. A remote pool temperature sensor and remote pool temperature high limit are wired to the Pennant, to be mounted in the pool water loop, as shown.
Figure 6. Pool Heater Piping.
Page 13
Pennant Pool Heater
Page 13
A concentration of chlorine in the heater can be
very destructive; therefore the following rules about
the installation and operation of such devices must be followed:
1. The chlorinator should be installed so it
introduces the gas or solution downstream of the
heater.
2. The chlorinator should be wired so it cannot operate unless the lter pump is operating.
3. The chlorinator should be provided with an anti-
siphon device so that the draining of the piping after the pump shuts off will not siphon chlorine
solution into the heater.
4. When the operation of a chlorinator is such
that it must be installed in the pump suction, or some other place where the chlorine solution
ows through the heater, corrosion of the heater can occur. Excessive concentrations of
chlorine resulting from improper adjustment or chlorinator equipment failure are responsible
for this corrosion. The heater warranty does not cover the resulting damage to the heat exchanger.
4.3 Sensor Locations
Two sensors must be installed in the pool loop, as
shown in Figure 6. The inlet sensor for the temperature
control must be installed in the pool loop within 12” (30 cm) of the inlet to the heater. This sensor is not installed in a well. For sensitivity, it must be installed in direct contact with the pool water ow. The second
sensor, the high limit sensor, must be installed in the
pool loop within 12” (30 cm) downstream of the heater outlet. This sensor is a capillary and bulb. It shall be used with the immersion well that is provided.
SECTION 5. Electrical Connections
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electrical
Code, Part 1, in Canada. Do not rely on the gas
or water piping to ground the metal parts of the
boiler. Plastic pipe or dielectric unions may isolate the boiler electrically. Service and maintenance
personnel, who work on or around the boiler, may be standing on wet oors and could be electrocuted
by an ungrounded boiler.
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made in the eld
wiring terminal strip, which is located at the right side
of the appliance.
NOTE: All internal electrical components have been
prewired. No attempt should be made to connect electrical wires to any other location except the eld wiring strip.
5.1 Main Power
5.1.1 Sizes 500-1500
Pennant pool heater sizes 500-1500 use a single
120-volt fused supply. The installer can change the
single service heaters to use a separate circuit for the
pump, if desired. Instructions to make this change are found in Section 5.1.3.
Pennant 500-1500 main power (L1, N1 & Ground) shall be connected to the three wires (10 AWG) supplied. Over-current protection ratings can be found in Table 8.
5.1.2 Sizes 1750-2000
Pennant Sizes 1750-2000 require two 120-volt fused supplies.
Heater circuit can be identied with 10AWG wires to include black, white and green (all solid colors). Pump circuit can be identied with three 12AWG wires to include a black wire with a white tracer (stripe), a white and green wire.
5.1.3 Separate Pump Circuit
Conversion to separate pump circuit will necessitate removing the three jumpers within
the internal wiring of the 120-volt portion of the
heater (see Figure 7). Only do this with the power disconnected to the unit!
To rewire the pump circuit, bring in another
120-volt fused supply (L2, N2 & Ground). Connect incoming power (L2) to the main power switch using
Page 14
Page 14
LAARS Heating Systems
spade (fork) terminal. From the other side of the main power switch connect to the main terminal block using a ¼" female insulated quick connect. This will be
the same position where the jumper had terminated (see Figure 7). Connect N2 and Ground to the main
terminal block using ¼" female insulated quick connect (refer to Figure 7).
5.1.4 Auxiliary Time Clock Wiring
If a time clock is used to control the pool lter
pump operation, a separate switch or relay must be
used to shut off the heater at least 15 minutes before the lter pump is shut off. A remote switch or relay, if installed, should be connected across the “Other Ints” terminals on the eld-wiring terminal strip (see Figure 9) after removing the factory-installed jumper from those terminals. For manual shut off, a switch is provided and identied with a label on the right side of the heater.
All eld-installed electrical safety devices and
controllers may also be connected across the Pennant’s
“Other Ints” terminals after the factory-installed jumper is removed. If a remote switch or relay (mentioned above) is installed, the other eld-installed
electrical safety devices and controllers should be
wired in series with that switch or relay.
5.1.5 All Sizes
Wiring diagrams are shown in Section 10 in Figures 13 through 17. Field wiring is shown in Section 10 in Figure 18.
IMPORTANT NOTE: If the backwash operation is
manual the heater must be shut off manually during
backwashing.
5.2 Temperature (Operating) Control
The Pennant temperature control operates by
measuring the pool loop return temperature, before
the heater inlet piping. It is adjustable to a maximum of 104° F and will prevent heater operation at return temperatures above 104° F. It also controls the pool
heater pump and the temperature of the water entering
the heat exchanger. It also controls the Pennant pump operation and the mixing system, which tempers the water entering the heat exchanger to prevent damage from condensation. The sensors for the control are installed as shown in Figure 6 and Section 4.3, Sensor Locations. The automatic mixing system sensor, already installed, is shown in Figure 5. During operation, the automatic mixing system diverts water from the outlet to the inlet to “pre warm” the water to a minimum inlet temperature of 120°F. This prevents
condensation from forming, which can damage the
heater.
5.3 Programming the Temperature
Control
5.3.1 Temperature Control Overview
The digital display on the control has the
following uses:
To display the actual pool loop temperature
during normal operating mode.
To allow the user to view and adjust the
control settings.
Figure 8 identies the control buttons.
The Pool Heater Temperature Control face
contains an LCD screen and four (4) buttons (see Figure 8). The LCD screen will display the pool loop return temperature during normal operation. When the control is rst powered up, it displays . It then displays the temperature at the pool loop sensor.
After the temperature is displayed, the current settings
(parameters) may be viewed. To scroll through the
parameters, press the down arrow button to advance to
the next parameter.
Figure 7. Removing Jumpers.
5.3.2 Programming Control Parameters
There are four (4) control parameters that may be set. They are the Pool Loop Temperature (LSP), the Pool Loop Temperature Differential (dLS), the Boiler Temperature (bsp) and the Pump Off Delay (Pd).
The pool loop temperature (desired pool
temp-erature) is set by changing the LSP parameter.
After scrolling through the parameters until LSP is
displayed, press the enter button. The setpoint will be displayed. Press the up arrow or down arrow buttons until the desired setpoint is displayed. Press the enter button and the setpoint will be activated. The
display will return to indicating the present pool loop
temperature.
In addition to the ability to set the pool loop temperature, the differential associated with that
setting may also be adjusted. The differential is set by
Page 15
Pennant Pool Heater
Page 15
changing the dLS parameter. After scrolling through
the parameters until dLS is displayed, press the enter
button. The setpoint will be displayed. Press the up
arrow or down arrow buttons until the desired setpoint
is displayed. Press the enter button and the setpoint will be activated. The display will return to indicating the present pool loop temperature.
The boiler operating temperature is set by
changing the bsp parameter. After scrolling through
the parameters until bsp is displayed, press the enter
button. The setpoint will be displayed. Press the up
arrow or down arrow buttons until the desired setpoint
is displayed. Press the enter button and the setpoint will be activated. The display will then return to indicating the pool loop temperature.
The last parameter that may be adjusted is Pd,
the pump off delay. After again scrolling through the parameters until Pd is displayed, press the enter button. The pump delay time will be displayed. The pump off delay may be set between 0.1 and 10 minutes. Press
the up arrow or down arrow buttons until the desired
setpoint is displayed. Press the enter button and the setpoint will be activated. The display will again return to indicating the present pool loop temperature.
By depressing the upper left hand button at
any time during the programming, the menu may be
returned to the beginning.
5.3.3 Setpoint - LSP
The setpoint is the desired temperature around
which the heater will control (desired pool temp­erature). It is adjustable between 60° F and 104° F.
SINGLE TWO CIRCUIT SIZE CIRCUIT HEATER PUMP
500 20 15 15
750 20 15 15
1000 (TACO) 20 / (B&G) 30 20 15
1250 30 25 15
1500 30 25 15
1750 25 20
2000 25 20
Figure 8. Pool Heater Controller.
Table 8. Electrical Data (Amps).
Figure 9. Typical Control Panel.
Page 16
Page 16
LAARS Heating Systems
5.3.4 Differential - dLS
The differential (dLS) is the number of degrees
between the temperature at which the heater turns off
and the temperature at which the heater restarts. It is adjustable from 1° F to 10° F.
5.3.5 Pump Operation
The pump energizes when there is a heat demand.
5.3.6 Heater Purge (Pump Delay) - Pd
After a demand is satised, the pump will continue to run for a preset length of time. That length of time is adjustable from 0.1 to 10 minutes and is programmed by the parameter Pd.
Caution
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
5.4 Limit Controls
In addition to the pool heater temperature control,
Pennant appliances are tted with a Pool Loop high limit set at 135° F and an automatic reset heater high limit with a maximum setting of 190° F.
The Pool Loop high-limit sensing bulb is to be
installed in the sensor well (supplied), downstream of the heater (see Figure 6). If sufcient capillary length
exists to reach the sensor location, the control may
remain in its location near the rear of the cabinet on the right side, behind the slide out drawer (see Figure
9). If the sensor location is farther from the heater than
the capillary will reach to, then the control should be
moved to the remote location and the wires extended to the new location of the control. If the controller
needs to be moved, and it is being moved to an outdoor location, the control will need to be put in a
weather-tight enclosure to protect it from rain, snow, etc.
The other limit control limits the temperature of
the discharge from the heat exchanger to a maximum of 190° F. This limit should be set to a minimum of 175° F. To set the limit controls, remove the control
panel cover and pull the control panel out to gain
access. Appliances with reversed heat exchangers
have the limit controls relocated to the left side of the
appliance. The left access door must be removed to gain access to the limit controls on these appliances.
SECTION 6.
Operating Instructions
6.1 Sequence of Operation
The amber “Ready” light on the front panel
indicates that the control system is energized. Upon
a call for heat from the pool temperature control, the
green “Heat” indicator on the front panel will light.
The green “Pump” indicator on the front panel
will light.
Once the water ow switch makes, and if all of the safety interlocks are closed, the ignition module(s) will energize the blower(s) for a 15-second pre-purge, followed by a 20-second period to allow the ignitor(s) to heat.
Energizing the blower pressurizes the air box
(which supplies air to the burners) and closes the
normally-open contact(s) of the airow pressure switch(es). This allows the ignition module to proceed with the ignition sequence.
The blocked ue pressure switch senses the pressure difference between the exhaust plenum and the blower inlet plenum. It will interrupt the airow sensing circuit if this pressure exceeds a maximum value. If airow is not proven, the ignition module
will either attempt ignition again (up to three times) or
will lockout (if the optional lockout ignition module is used).
The ignition module checks that the ignitor
current has reached a minimum value and energizes
the gas valves at the end of the ignitor-heating period.
The green indicators on the front panel will light,
indicating that the gas valves are open.
After a 4-second trial for ignition, the ignitor switches off, and unless the ame sensor detects a ame, the gas valves will close and the ignition
module will either attempt ignition again (up to three
times) or will lockout (if the optional lockout ignition module is used). Note: at this point, if gas pressure is
below the required 5" w.c. minimum, the pool heater will lock out.
If ame is sensed, the burner will continue to re as long as there is a call for heat. Pennant 1250, 1500, 1750 and 2000 models start at part load. When the gas valves controlled by the rst ignition module
are energized, the second ignition module is energized
and enters the same ignition sequence just described. If there is a subsequent loss of ame signal, the burner will attempt re-ignition up to three times (only once if optional lockout ignition module is used.) Loss of ame signal from the rst ignition module will cause shutdown of the heater.
When the call for heat is satised, the gas valves close and the blower(s) continues to run for 30 seconds. The pump will continue to run for the length
of time selected at startup by the adjustment of the
pump time delay (Pd).
Page 17
Pennant Pool Heater
Page 17
If a call for heat is prevented from being satised either by a safety interlock or due to an ignition lockout, the red “Service” indicator on the front panel will light. To reset the standard ignition module, toggle the Pennant power switch off, and then on again. (To reset the optional single try lockout ignition module, the reset button on the module must be pressed.
Interrupting power to this module will not reset the
lockout.)
The Pennant 1250, 1500, 1750 and 2000 models
have two ignition modules that control different
burners.
6.2 Filling the Heater System
1. Ensure the system is fully connected, lled with
water and all valves are open.
2. Start up heater according to the procedure in this
manual. Operate the entire system for one (1)
hour.
3. After placing the unit in operation, the ignition
system safety shutoff device must be tested. First,
shut off the manual gas valve, and call the unit
for heat. After the pre-purge and ignitor heat-up
time, the main gas terminals will be energized,
attempting to light, for four (4) seconds, and
then will de-energize. The unit will go into
lockout mode. Second, turn the power off and
then on again, push the reset button (optional
Ignition Module only), open the manual gas
valve and allow the unit to light. While the unit is
operating, close the manual gas valve and ensure
that power to the main gas valve no longer exists.
4. Check the entire system for leaks.
Caution
Protect the heater from low pH water if an “acid
start up” or similar technique is used. Corrosion of
the heater and heat exchanger due to low pH water is not covered under the limited warranty. The water
must be neutralized to normal pH levels before
lling the heater and starting up the system.
Important: The installer is responsible for identifying
to the owner/operator the location of all emergency
shutoff devices.
WARNING
Do not use this appliance if any part has been
under water. Immediately call a qualied service
technician to inspect the appliance and to replace any part of the control system and any gas control
that may have been under water.
6.3 Operating the Burner and Set Up
6.3.1 Set Up for 0 to 2500 Feet Altitude
The setup must be checked before the unit is put in operation. Problems such as failure to start, rough ignition, strong exhaust odors, etc. can be due to
improper setup. Damage to the heater resulting from improper setup is not covered by the limited warranty.
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are lled with water and all air has been bled from both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. Switch on the appliance power switch located on the right side of the unit.
5. The Pennant will enter the start sequence, as long as the unit is being called for heat. The blower and pump come on for pre-purge, then the ignitor warm-up sequence starts and after the ignitor warm-up is complete and all safety devices are veried, the gas valves open. If ignition doesn’t occur, check that there is proper gas supply. Wait 5 minutes and start the unit again. During
initial start up, air in the gas line may cause the
Pennant to "lock out" during the rst few trials for ignition. Depending on the ignition modules
installed, the manual reset button on the ignition module(s) may need to be depressed to restart the
heater.
6. When the unit is running, the supply gas pressure must be checked. Inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet gas pressure is 5" W.C. (1.2kPa).
7. Once the inlet gas pressure is veried, the
outlet gas pressure from each valve (manifold
gas pressure) must be checked, and adjusted, if necessary. The manifold gas pressure must be
2.5" W.C. (0.62kPa).
8. Complete the setup by checking the CO2 at the outlet of the unit. The CO2 should be 8% for natural gas, or 9.2% for propane.
9. After placing the appliance in operation, the Burner Safety Shutoff Device must be tested.
To test:
(a) Close gas shutoff valve with burner
operating.
(b) The ame will go out and blower will
continue to run for the post purge cycle. Three (3) additional attempts to light will
follow (only one (1) attempt for optional
module). Ignition will not occur as the gas is off. The ignition control will lockout, and
will have to be reset before the unit will
operate. The ignition control reset button
is located on each ignition control, in the lower right corner, and can be reset by
depressing. It is not marked on the ignition control label.
(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will start again and the burner will start. The
Page 18
Page 18
LAARS Heating Systems
appliance will return to its previous mode
of operation.
NOTE: Models 1250, 1500, 1750 and 2000 have two ignition controls and two ignitors.
6.3.2 High Altitude Adjustment and Set Up
Pennant appliances may be operated at high
altitude (7700 ft., 2347 m) with a reduction in output of approximately 10%. At elevations higher than 7700 ft. (2347 m) the reduction in output will exceed 10% and at elevations below 7700 ft. (2347 m) it will be less than 10%. When adjusted properly, the appliance will perform properly at any altitude. High altitude
adjustment must not be made on appliances operating
at elevations below 2500 ft. (762 m).
No orice changes are required to adjust the
Pennant appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the gas
valve manifold pressure and the air shutter(s). The
required instruments used to assist in these adjustments
are a CO2 or O2 Analyzer and a U-Tube Manometer or other device capable of reading a pressure of 2.5-3.0 inches W.C. (0.62-0.75 kPa).
Start the adjustment process by checking the CO2 in the “as installed” condition. Adjust the air shutter(s) so that the CO2 is about 8% or the O2 is about 6.8% for appliances operating on Natural Gas. For appliances operating on LP Gas adjust the air shutter(s) so that the CO2 is about 9.2% or the O2 is about 6.8%. Appliances
with two blowers should be adjusted so that the air
shutters below each blower are open the same amount.
Once the CO2 or O2 has been set, the manifold pressure may be adjusted. Remove the 1/8 NPT plug
from the lower side of the gas valve that is to be set
and install a tting, hose and manometer. Start the appliance and observe the manifold pressure. Manifold pressure must be adjusted to 3.0 in. W.C. (0.75 kPa)
(for high altitude only, standard operating pressure is
2.5 in. W.C. (0.62 kPa)). It is adjusted by removing the
slotted cap on the gas valve and turning the adjustment
screw (beneath the cap) clockwise to increase pressure . After the adjustments have been completed, the t-
ting, hose and manometer have been removed and the
1/8" plug has been replaced, replace the cap. Repeat this process until all gas valves have been set. Note:
The pressure can be set only when the appliance is operating and only when the particular gas valve being
adjusted is energized by a call for heat.
After all of the gas valve manifold pressures
have been set, the CO2 or O2 must be reset. CO2 or O2
will have changed when the manifold pressure was
HEATER MINIMUM FILTER MODEL PUMP FLOW RATE
PNCP 500 240 GPM PNCP 750 360 GPM
Table 9. Minimum Filter Pump Flow Rates For Spas.
adjusted. Open the air shutter(s) to reduce the CO2 or O2 to the values achieved previously.
The procedure is complete when all gas valves
are adjusted to a manifold pressure of 3.0 in. W.C. (0.75 kPa) and the CO2 is adjusted to 8.0% for Natural Gas appliances or 9.2% for LP appliances. When using an O2 analyzer, the correct O2 is 6.8% for both Natural Gas and LP appliances.
Caution
Should any odor of gas be detected, or if the gas burner does not appear to be functioning in a normal manner, close main shutoff valve, do not
shut off switch, and contact your heating contractor,
gas company, or factory representative.
6.4 Shutting Down the Pennant
1. Switch off the shutdown switch (located above the Main Power Switch).
2. Wait until the “pump” light (located on the front panel) goes out.
3. Switch off the main electrical disconnect switch.
4. Close all manual gas valves.
5. If freezing is anticipated, drain the Pennant and
be sure to also protect piping connected to the
Pennant from freezing.
This step to be performed by a qualied service person.
6.5 Backwash Switch Operation
Pennant Pool Heaters are equipped with a lter
backwash switch, which is located above the main power switch. The switch is intended to provide a
means by which the heater can be safely shut down for
pool lter service, without causing nuisance tripping of the heater high limit.
This switch is internally wired in series with the
Other Interlocks terminals, and will interrupt the call for heat signal when open. Please note that when the backwash switch is active the heater “Service” light will be illuminated.
To place the heater into backwash mode proceed
as follows:
1. Turn the backwash switch down to the “Filter Backwash Mode” position.
2. Wait for the heater outlet temperature to drop
down to a temperature equal to the pool water
return temperature.
3. Turn the main power switch off. Pool lter servicing may now proceed normally.
After completion of the lter servicing, place the heater back into service as follows:
1. Turn the main power switch on.
2. Allow time for the pump to turn on, and purge air from the heater.
3. Turn the backwash switch up to the “Normal” position.
Page 19
Pennant Pool Heater
Page 19
The service light will turn out, and the heater will
resume normal operation. Please note that if the heater
is equipped with a low water cut off there will be a
brief delay while the LWCO completes a self-check.
6.6 Spring and Fall Operation Stand-by Service
Turn the thermostat down to approximately 70°F
(21°C). This will prevent the pool and surrounding
ground from becoming chilled and permit the pool to be raised to swimming temperature in a shorter length
of time. Do Not Operate below 60°F (16°C).
6.7 Winter Operation Complete Shutdown
1. See Section 6.4
2. If the heater is not protected from freezing
temperatures, it should be completely drained
before the rst frost. Drain the heater by removing the plug at the end of the inlet/outlet header casting. Also, remove the small plug at the bottom of the pump housing. Do not replace either plug until the time that relling is desired. The heater must be level for complete draining.
When compressed air is used to blow out lines,
it is still necessary to follow these directions. Because of the potential for electrical power
failure or pump failure, freeze protection should never be accomplished by operating the pool
heater and the lter pump. Either of those failures
will potentially allow a freeze up and cause
damage to the heater and the attached system.
3. Improper use of the heater: The Laars PNCP
pool heater is not designed for continuous use as
a “anti-freezing” device for pools. Operating the
heater at low water temperatures will damage the
heat exchanger.
6.8 To Restart the Pennant
If drained, follow Section 6.2 in this manual for
proper lling and purging.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the pool aquastat to its lowest setting.
5. Open all manual gas valves.
6. Reset all safety switches.
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a prepurge period and ignitor warm-up period, followed by ignition.
6.9 Therapeutic Pools (Spas)
Therapeutic pools or “spa” pools are usually
piped and controlled so that very warm or hot water, often with air injection, is forced at high velocity
into a conned area of a swimming pool or into a small separate pool. For the purposes of this manual,
any application in which the water temperature is
maintained above 85°F (30°C) is considered a spa.
SPECIAL SET-UP AND OPERATING
PROCEDURES APPLY TO SPAS.
1. Models PNCP1000 and larger should not be used for spas due to their higher temperature rises.
2. To ensure that the spa inlet does not exceed 104°F (40°C), the spa lter pump must circulate water at the minimum ow rates shown in Table 9.
NOTE: Maximum Spa Temperature Is Assumed To Be 100°F (38°C).
3. Spas are excellent for relaxation, body-
conditioning and for arthritic and rheumatic
problems, but can be hazardous.
WARNING
The U. S. Consumer Product Safety Commission
has warned that elevated temperatures in spas and hot tubs can be hazardous. Follow these “Safety
Rules for Hot Tubs:”
Spa or hot tub water temperatures should never
exceed 104°F (40°C). A temperature of 100°F (38°C) is considered safe for a healthy adult. Special caution is suggested for young children.
Drinking of alcoholic beverages before or during
hot tub use can cause drowsiness, which could
lead to unconsciousness and subsequently lead
to drowning.
Pregnant women beware! Soaking in water
above 102°F (39°C) can cause fetal damage
during the rst three months of pregnancy
(resulting in the birth of a brain-damaged or
deformed child). Pregnant women should stick
to the 100°F (38°C) maximum rule.
Before entering the spa or hot tub, users should
check the water temperature with an accurate thermometer; spa or hot tub thermostats may err in regulating water temperatures by as much
as 4°F (2°C).
Persons with a medical history of heart disease,
circulatory problems, diabetes or blood pressure problems should obtain their physician’s advice before using spas or hot tubs.
Persons taking medications which induce drowsiness, such as tranquilizers,
antihistamines or anticoagulants, should not use spas or hot tubs.
Page 20
Page 20
LAARS Heating Systems
SECTION 7. Maintenance
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if required, per the instructions on the pump.
2. Inspect the venting system for obstruction or leakage at least once a year. Periodically clean the inlet air lter and the screens in the vent ter­minal and combustion air terminal (when used).
3. Keep the appliance area clear and free from
combustible materials, gasoline, and other
ammable vapors and liquids.
4. If the appliance is not going to be used for extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
protected from freezing.
5. Low water cutoffs, if installed, should be checked every 6 months. Float type low water cutoff should be ushed periodically.
6. Inspect ue passages, and clean with brushes/ vacuums, if necessary. Sooting in ue passages indicates improper combustion. Determine the cause and correct.
7. Inspect the vent system and air intake system, and ensure that all joints are sealed properly. If
joints need to be resealed, completely remove
existing sealing material, and clean with alcohol. Apply new sealing material, and re-assemble.
7.2 Appliance Maintenance and Component Description
Only genuine Laars replacement parts should be used.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
7.2.1 Burners
Close main manual gas valve before proceeding.
Checking the burners for debris - Remove the ignitor
inspection panels(s) and ignitor(s) and inspect the
burners through the ignitor hole(s) using a ashlight to illuminate. If there is any indication of debris on
the burners that are visible, all the burners will need
to be inspected more thoroughly. Remove the screws from around the front of the air box (large panel from
which the ignitor inspection panel(s) were removed),
and remove the large panel. Remove the gas manifold assemblies and the burner panels. Inspect the burners.
Clean burners, if necessary, by blowing compressed air from the outside of the burners into the center
of the burner. A dirty burner may be an indication of improper combustion or dirty combustion air. Determine the cause, and correct. Replace the burners in the reverse order.
7.2.2 Filter
The lter used in the Pennant is washable with an 83% arrestance. Since the lter is washable, it will only need replacement in very rare cases. If lter
replacement is needed, it should only be replaced with
a factory part. Inspect the air lter. If there is debris on the air lter, remove it from the lter box, and wash it with mild soap and water. Ensure that the lter is completely dry before re-installing, in reverse order.
7.2.3 Gas Valves
The gas valves are designed to operate with
supply pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).
To remove a valve, shut off 120-volt power and the manual gas shutoff valve. Remove the top front panel from the unit. Disconnect the wires to the valve. Disengage the anged tting before and after the valve, and remove the valve. Re-install in reverse order. Ensure o-rings are properly installed for both inlet and outlet. Turn on manual gas shutoff valve and 120 volt power and check appliance operation and tightness of gas valve connections.
For location of gas train and control components,
see Figures 4, 11 and 9, 12 respectively.
The gas and electric controls on the appliance are engineered for long life and dependable operation, but the safety of the equipment depends on their
proper functioning. It is strongly recommended that a qualied service technician inspect the basic items listed below every year. a. Ignition controls b. Ignitors c. Water temperature control d. Automatic gas valve e. Pressure switches f. Blowers
7.2.4 Pool Loop High Limit Control
The high limit switch is an automatic reset switch
with an adjustable set point, up to 135°F (57°C). To replace the switch, shut off the 120-volt power to the appliance. Remove the cover from the switch to access the mounting screws. Remove the screws, and pull the switch off the control panel. Remove the capillary and
bulb from the thermal well located in the pool loop
adjacent to the heater outlet. Replace in reverse order.
7.2.5 Automatic Reset High Limit Control
An automatic reset high limit is used to limit
heater water from exceeding 200°F. The high limit switch has an adjustable set point, up to 190°F (88°C). To replace the switch, shut off the 120-volt power to the appliance. Remove the cover from the switch
Page 21
Pennant Pool Heater
Page 21
to access the mounting screws. Remove the screws, and pull the switch off the control panel. Remove the
capillary and bulb from the thermal well located in the
header. Replace in reverse order.
7.2.6 Temperature Control
The temperature control is a single stage control. To replace the control, shut off the 120-volt power to the appliance. Unplug all of the electrical connectors, remove the retainer clip and the control. Replace in reverse order.
7.2.7 Ignition Controls
The ignition controls ensure the proved
interrupted-type ignition system. They control the hot surface ignitor(s) and prove that the ame signal is appropriate for powering the gas valves. It also controls the blower’s pre-purge and post-purge. Pennant sizess 500, 750 and 1000 have one ignition control. Sizes 1250, 1500, 1750 and 2000 have two ignition controls. On these models, one ignition control provides for part-load start-up and the second control brings the heater to full rate, after the rst control has started the part-load burners.
To replace a control, shut off the 120-volt power to the appliance. Remove the cover from the control panel. Remove the electrical connectors from the ignition control. Take out the controller’s mounting screws, and pull the controller out. Replace in reverse order.
7.2.8 Ignitors
The ignitors used are 120v “Hot Surface” type.
They are energized whenever there is a call for heat and switched off when ignition is established and the
ame has been sensed. Pennant sizess 500, 750 and 1000 have one ignitor. Sizes 1250, 1500, 1750 and 2000 have two ignitors. To replace the ignitor, shut off the 120- volt power to the appliance, remove the ignitor access panel, disconnect the Molex connector, remove the two mounting screws on the ignitor ange, and pull the ignitor out. Install in reverse order, always using a new ignitor gasket with the replacement ignitor.
power. Unplug the transformer wires, remove the mounting screws and remove the transformer. Replace transformer in the reverse order.
7.2.11 Blowers
The combustion air blowers bring the combustion
air for the Pennant from the upper chamber to the
lower chamber. Mixing of the gas and air occurs in the burners. If a blower change is required, turn off the 120-volt power and gas supply to the unit. Remove the front panel. Disconnect the blower’s wire harness. Remove the screws at the blower ange, and pull the blower out. Replace blower in reverse order, ensuring that all joints are made correctly. After replacement,
ensure that the unit operates properly, by following
the set-up procedure in this manual. Use caution in
handling the blower, ensuring you do not put pressure
on the blower wheel.
7.2.12 Flow Switch
The unit uses a paddle-type ow switch to en-
sure the unit has water ow before ignition is allowed.
7.2.13 Heat Exchanger Coil
Caution
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or ame. To
prevent this from happening, dampen the soot
deposits with a wet brush or ne water spray before
servicing the heat exchanger.
The Pennant has a pre-mixed burner system. These systems provide the burners with sufcient air for complete combustion, and black carbon sooting is seldom experienced. If sooting is suspected, view ports for inspection of the heat exchanger are provided on both sides of the heater. They are located below the
headers, and are accessed by opening the small round
cover that is attached by one screw. In the unlikely event that there is a buildup of black carbon soot or other debris on the heat exchanger, clean per the
following:
Caution
Ignitor gets hot.
7.2.9 Ignition Sensors
The ignition sensors ensure that the main ame is ignited, so that raw gas is not allowed to ll the combustion chamber. The ignitors are the ignition sensors on Pennant appliances. There are no separate ignition sensors.
7.2.10 Transformer
The Pennant’s transformer is not capable of
supplying control voltage for external devices. Should a transformer need replacing, shut off the 120-volt
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas valve on the heater.
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header anges from the inlet and outlet.
6. Allow the heat exchanger to drain. Remove the front cover(s). Remove the venting and
remove the top, by removing the screws that
attach the top to the side panels. Remove the
Page 22
Page 22
LAARS Heating Systems
side panels. Remove the front lower panels sealing the combustion area. To remove the
gas train, disconnect the unions located above
the intermediate pan and the eld installed
union located outside the cabinet, and pull up, bringing the union end connectors through the
grommets in the intermediate pan. To remove
the intermediate pan, remove the slide out control
assembly and blower(s) to reveal the screws.
Remove the screws holding the intermediate pan,
and lift up to remove it. The heat exchanger has
integral metal sections attached, which connect
to the frame of the boiler. Locate and remove
the screws along the front, rear and bottom of the integral metal sections, and remove the heat
exchanger and metal sections by lifting up. On the larger appliances, a center heat exchanger
support must be unbolted before it can be
removed.
7. Remove the heat exchanger from the unit.
NOTE: The heat exchangers are heavy and will require two people to remove to avoid personal injury.
8. Clean the heat exchanger: A light accumulation
of soot or corrosion on the outside of the heat
exchanger can be easily removed. Use a wire
brush to remove loose soot and scale from the
heat exchanger. Do not use water or compressed air for cleaning.
9. NOTE: While the heat exchanger is out of the unit, inspect the rewall refractory insulation. Replace if necessary.
10. Inspect the inside of the copper tubes for scale buildup. Scale can build up on the inner surface of the heat exchanger tubes, which can restrict water ow. If the tubes show signs of scaling, clean the internal surface. Laars offers a tube cleaning kit part number R0010000.
11. Reassemble in the reverse order, and check appliance operation after start-up.
NOTE: The Warranty does not cover damage caused by lack of required maintenance, lack of water ow, or improper operating practices.
SECTION 8.
Trouble Shooting
8.1 Resolving Lockouts
There are many causes of lockouts. The three
most common causes are: (1) inadequate gas supply,
(2) poor combustion, (3) ignitor failure.
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP
tank (LP boilers) is not empty. Then, restart the boiler and observe the operational cycle. After a 15-second fan pre-purge, the ignitor will heat up for 20 seconds, and then the unit will light. If it does not, check the gas supply pressure to
the appliance, after resetting the appliance and
attempting another start-up. The gas pressure to the appliance must be above 5" W.C. (1.2kPa) throughout the entire start-up cycle. If it is not, correct the supply problem (check gas valves or supply piping). If the supply pressure is adequate, consult the factory for assistance.
2. Poor Combustion: Poor combustion should be suspected if there is a strong ue gas odor. The odor may result from an improper gas/air ratio (high or low O2 or CO2). Pennant appliances operate best with 45% excess air (8% CO2 on natural gas, 9.2% CO2 on LP). Check the CO2 of the appliance and adjust if necessary.
3. Ignitor failure: If the boiler goes through a
normal start cycle but combustion does not
occur, and the gas pressure is at least 5" w.c., ignitor failure may be the cause. Check the
ignitor by unplugging it, allowing it to cool to room temperature, and measuring the ignitor
resistance. It should be 50-80 ohms. If the resistance is not 50-80 ohms, replace the ignitor.
If the resistance is correct, reset the boiler and
check for 120 VAC at the ignitor plug during the start cycle. If there is no voltage, replace the faulty ignitor wire harness or the ignition control.
8.2 Delayed Ignition - Possible Causes
A defective burner can cause a delayed ignition.
If the gas supply pressure is proper and the gas valves are functioning properly, then burners should
be inspected. There should be no distortion or
perforations in the burners outside of the active burner
port area. Replace if indicated.
8.3 Short Cycling
Because of the large mass of pool systems, short
cycling should not exist. If it does, it will be caused by insufcient ow in the pool loop. Check that there is no blockage in the pool loop such as a plugged or partially plugged pool lter.
Page 23
Pennant Pool Heater
Page 23
8.4 High Gas Consumption
Appliances operating with an improper air/ fuel ratio are very inefcient and consequently, have very high gas consumption. Because efciency is high when the CO2 is high (or O2 is low), appliances operating with low CO2 or high O2 (especially LP appliances) consume more gas. Adjust the CO2 or O2 for optimum efciency. If no combustion analyzing equipment (CO2 or O2) is available then a proper adjustment of the air/fuel ratio (CO2 or O2) cannot be accomplished. However, by briey snifng the ue gases it is possible to determine if the CO2 or O2 is within the proper range. No signicant ue gas odor should be detected when combustion is proper.
A strong piercing smell indicates poor combustion
and generally a lean mixture - low CO2 or high O The CO2 should be 8% (natural gas, 9.2% LP) at high re. To check the CO2, rst verify that the supply gas pressure is within 5" to 13" w.c. (1.2 to 3.2 kPa) With the Pennant running with both stages ring, set the air box pressure to 1.5" w.c. (0.37 kPa) (as a starting
point), by adjusting the air shutter(s) at the bottom of
the fan(s). Check the CO2, and adjust the air shutters if further adjustment to the CO2 is needed. Sizess 1250, 1500, 1750 and 2000 have two blowers and two air chambers (boxes). The pressure of each air box must be equal when the nal adjustment is made.
.
2
The 24V power to the T’STAT terminal of the ignition module(s) are routed through the safety interlocks.
The ladder diagram for sizess 1250, 1500, 1750
and 2000 is shown in Figure 14. These models have
two ignition modules, each with its own blower, and each controlling part of the input so that startup at
reduced input is provided. The blowers are energized by the ignition modules indirectly via switching relays.
When either ignition module receives a call for heat, it switches its blower to high speed and the blower of the
idle ignition module to low speed.
The wiring schematic for the Pennant 500 – 1000 is shown in Figure 15, and the schematic for the 1250 – 2000 models is shown in Figures 16 and 17. All 24V wiring is routed through the diagnostic PC board.
Wiring harnesses connect between the diagnostic PC board and the control components, indicator board,
or eld wiring terminal strip. The diagnostic board contains LEDs that indicate open status of the safety interlocks, and quick-connect terminals that provide tests points for checking voltage/continuity at various points in the control circuit.
Certain control elements that may need to be
rewired in the eld are connected via the eld wiring terminal strip rather than to the diagnostic PC board. These include the low-water cutoff (LWCO), external alarm, and water ow switch.
8.5 Troubleshooting the Pool Heater Temperature Control
With a Voltmeter, test for 24 VAC between
terminals 1 & 2 on the 10 pin connector. Check that
the sensor temperature is lower than the setpoint
temperature by at least the differential setting. If this is true, check that there is 24 VAC at the yellow wire on the 4 pin connector. If there is not 24 VAC, check that the high limit is not open. If there is 24 VAC at the yellow wire on the 4 pin connector and not at the light blue wire on that connector, replace the control.
8.6 Troubleshooting Pennant Controls
The Pennant series consists of three sizes with
one ignition module (500, 750 & 1000) and four sizess with two ignition modules (1250, 1500, 1750 and
2000).
A diagnostic panel, that includes test points, as
well as diagnostic lights, is provided in the control
module. It is located on the right side of the module, behind the display. To access, remove the retaining
screws from the display cover panel and remove
it. Grasp the control module at its base and pull it outward. Ladder diagrams are shown in Figures 13 and
14. Figure 13 shows the diagram for the 500, 750 &
1000. These have one blower and one ignition module.
The blower is energized directly through the “inducer” terminals F1 and F2 of the (Fenwal) ignition module.
SECTION 9.
Replacement Parts
Only genuine Laars replacement parts should be used.
9.1 General Information
To order or purchase parts for the Laars Pennant,
contact your nearest Laars dealer or distributor. If
they cannot supply you with what you need, contact
Customer Service (see back cover for address, telephone and fax numbers).
9.2 Parts List
See next page.
Page 24
Page 24
LAARS Heating Systems
Item Description Size Size Size Size Size Size Size
500 750 1000 1250 1500 1750 2000
Sheet Metal Components
See Figure 10
1 Panel, Jacket, Side Left 5C3420 5C3420 5C3420 5C3420 5C3420 5C3420 5C3420
2 Panel, Jacket, Side Right 5C3526 5C3526 5C3526 5C3526 5C3526 5C3526 5C3526
3 Panel, Jacket, Front 5C3320 7C3320 10C3320 12C3320
3 Panel, Jacket, Front, Left 15C3320 17C3320 20C3320
4 Panel, Jacket, Front, Right 15C3320 17C3320 20C3320
5 Panel, Jacket, Rear 5C3220 7C3220 10C3220 12C3220 15C3220 17C3220 20C3220
5A Panel, Jacket, Rear, Filter Enclosure 15C3026 15C3026 15C3026
6 Panel, Jacket, Top 5C3021 7C3021 10C3021 12C3021
Panel, Jacket, Top, Left 15C3021 17C3021 20C3021
7 Panel, Jacket, Top Right 15C3025 17C3025 20C3025
8 Control Door, Access 5C3011 5C3011 5C3011 5C3011 5C3011 5C3011 5C3011
9 Plate, Gas Pipe Seal 5C3304 5C3304 10C3304 20C3304 20C3304 20C3304 20C3304
(2) (2) (2) (2) (2) (2) (2)
10 Plate, Cover, Wiring 5C3502 5C3502 5C3502 5C3502 5C3502 5C3502 5C3502
11 Plate, Vent 5C3004 10C3004 10C3004 20C3004 20C3004 20C3004 20C3004
12 Cover, Vent Plate 20C3006 20C3006 20C3006 20C3006
13 Plate, Cover, Filter 5C3002 5C3002 5C3002 15C3002 15C3002 15C3002 15C3002
14 Collar, Vent 5C3106 10C3100 10C3100 15C3100 15C3100 20C3100 20C3100
15 Air Filter Assembly 5C3700 5C3700 10C3700 15C3700 15C3700 15C3700 20C3700
16 Air Filter R2014700 R2014700 R2014700 R2014700 R2014700 R2014700 R2014700
(1) (1) (1) (2) (2) (2) (2)
16A Trim, Jacket, Front 5C3019 7C3019 10C3019 12C3019 15C3019 17C3019 20C3019
16B Housing, Rain Shield, Pump 5F3015 5F3015 5F3015 5F3015 5F3015 5F3015 5F3015
16C Cover, Housing, Pump 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016
16D Bracket, Support, Pump Cover 5F3017 5F3017 5F3017 5F3017 5F3017 5F3017 5F3017
Internal Components
See Figures 11 and 12
17 Base Assembly 5C1020 7C1020 10C1020 12C1020 15C1020 17C1020 20C1020
18 Chamber, Front 5C2003 7C2003 10C2003 12C2003 15C2003 17C2003 20C2003
18A Chamber, Left Side, Front 5C2015 5C2015 5C2015 5C2015 5C2015 5C2015 5C2015
18B Chamber, Right Side, Front 5C2016 5C2016 5C2016 5C2016 5C2016 5C2016 5C2016
Page 25
Pennant Pool Heater
Page 25
Size Size Size Size Size Size Size
19 Chamber, Rear 5C2006 7C2006 10C2006 12C2006 15C2006 17C2006 20C2006
Item Description 500 750 1000 1250 1500 1750 2000
20 Chamber Assembly, Left, Bottom 5C2601 5C2601 5C2601 5C2601 5C2601 5C2601 5C2601
21 Chamber Assembly, Right, Bottom 5C2201 5C2201 5C2201 5C2201 5C2201 5C2201 5C2201
22 Chamber, Top 5C2001 7C2001 10C2001 12C2001 15C2001 17C2001 20C2001
23 Chamber, Side, Top 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002
24 Exhaust Plenum 5C2007 10C2007 10C2007 20C2007 20C2007 20C2007 20C2007
25 Bracket, Chamber, Front 5C2009 7C2009 10C2009
Bracket, Chamber, Front Left 12C2011 15C2011 17C2011 20C2011
26 Bracket, Chamber, Front Right 12C2009 15C2009 17C2009 20C2009
27 Divider, Chamber, Front 15C2010 20C2002
27A Divider, Upper, Chamber, Front 15C2005 15C2005
27B Divider, Lower, Chamber, Front 15C2002 15C2002
28 Cover, Chamber 5C2004 7C2004
Cover, Chamber, Front Left 10C2004 12C2010 15C2004 17C2010 20C2010
29 Door, Chamber Access 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005
(1) (1) (1) (2) (2) (2) (2)
30 Cover, Chamber, Front Right 12C2008 15C2004 17C2008 20C2008
Gasket Tape, Rear, Base (43') R2014500 R2014500 R2014500 R2014500 R2014500 R2014500 R2014500
Gasket Tape, Front, Base (63') R2014600 R2014600 R2014600 R2014600 R2014600 R2014600 R2014600
32 Ignitor, Hot Surface, with Gasket 2400-286 2400-286 2400-286 2400-286 2400-286 2400-286 2400-286
(1) (1) (2) (2) (2) (2) (2)
33 Tile, Side (Right and Left) T2015601 T2015601 T2015601 T2015601 T2015601 T2015601 T2015601
(2) (2) (2) (2) (2) (2) (2)
34 Tile, Front T2017300
(1)
35 Tile, Front, Left Side T2016200 T2016800 T2016800 T2016800 T2016800 T2016800
(1) (1) (1) (1) (1) (1)
35A Tile, Front, Right Side T2016300 T2017100 T2017900 T2017100 T2017900 T2017100
(1) (1) (1) (1) (1) (1)
35B Tile, Front, Center T2016900 T2016900 T2016900 T2016900
(1) (1) (2) (2)
36 Tile, Rear T2015700
(1)
37 Tile, Rear, Left Side T2017500 T2016600 T2016600 T2016600 T2016600 T2016600
(1) (1) (1) (1) (1) (1)
Page 26
Page 26
LAARS Heating Systems
Size Size Size Size Size Size Size
Item Description 500 750 1000 1250 1500 1750 2000
37A Tile, Rear, Right Side T2016600 T2016600 T2018100 T2016600 T2018100 T2016600
(1) (1) (1) (1) (1) (1)
37B Tile, Rear, Center T2017200 T2017200 T2017200 T2017200
(1) (1) (2) (2)
38 Tile, Bottom T2015500
(1)
39 Tile, Bottom, Left Side T2017400 T2017400 T2017400 T2017400 T2017400 T2017400
(1) (1) (1) (1) (1) (1)
39A Tile, Bottom, Right Side T2016500 T2017400 T2018000 T2017400 T2018000 T2017400
(1) (1) (1) (1) (1) (1)
39B Tile, Bottom, Center T2015900 T2015900 T2015900 T2015900
(1) (1) (2) (2)
41 Heat Exchanger, Copper R2014901 R2014902 R2014903 R2026701 R2014904 R2026702 R2014905
Heat Exchanger, Cupro-Nickel R2027801 R2027802 R2027803 R2027804 R2027805 R2027806 R2027807
42 Water Barrier, Inlet/outlet 20230103 20230103 20230103 20230103 20230103 20230103 20230103
43 Water Barrier, Inlet 10338300 10338300 10338300 10338300 10338300 10338300 10338300
44 Gasket, Header S0095100 S0095100 S0095100 S0095100 S0095100 S0095100 S0095100
(2) (2) (2) (2) (2) (2) (2)
45 Cover, In/Out, Glass-Lined Cast Iron 10364504 10364504 10364504 10364504 10364504 10364504 10364504
Cover, In/Out, Bronze 10364501 10364501 10364501 10364501 10364501 10364501 10364501
46 Well, Temperature Control RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300
47 Gasket, Flange S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S0063700
(2) (2) (2) (2) (2) (2) (2)
48 Flange, Cast Iron 10391302 10391302 10391302 10391302 10391302 10391302 10391302
Flange, Bronze 20255401 20255401 20255401 20255401 20255401 20255401 20255401
49 Relief Valve, PNCH, 75 PSI A0063300 A0063600 A0063600 A0063600 A0063600 A0002700 A0002700
Relief Valve, PNCV, 125 PSI RA0001200 RA0001200 RA0001200 RA0001200 A0064400 A0064400 A0066400
50 Tee, Adapter, Outlet, Cast Iron 20150302 20150302 20150302 20150302 20150302 20150313 20150313
Tee, Adapter, Outlet, Bronze 20150301 20150301 20150301 20150301 20150301 20150301 20150303
51 Flow Switch RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 RE0013000
52 Gauge, Temperature/Pressure RA0079000 RA0079000 RA0079000 RA0079000 RA0079000 RA0079000 RA0079000
54 Low Water Cutoff E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500
55 Pump Housing, Glass-lined, Cast Iron R20607600 R20607600 R20607600 R20607600 R20607600 R20607600 R20607600
Pump Housing, Bronze 10483300 10483300 10483300 10483300 10483300 10483300 10483300
56 Gasket, Pump Adapter not used on current production (was S0024600)
Page 27
Pennant Pool Heater
Page 27
57 Pump Adapter, Glass-lined Cast Iron not used on current production (was 10364200)
Pump Adapter, Bronze 10364201 10364201 10364201 10364201 10364201 10364201 10364201
58 Bafe,Diffuser,PumpInlet 10338400 10338400 10338400 10338400 10338400 10338400 10338400
59 Pressure Switch RE0240900 RE0240900 RE0240900 RE0240900 RE0240900 RE0240900 RE0240900
(2) (2) (2) (3) (3) (3) (3)
60 Blower R2060900 R2060900 R2060900 R2060900 R2060900 R2060900 R2060900
(1) (1) (1) (2) (2) (2) (2)
61 Weldment, Blower Mount 5C5300 5C5300 5C5300 5C5300 5C5300 5C5300 5C5300
(1) (1) (1) (2) (2) (2) (2)
Size Size Size Size Size Size Size
Item Description 500 750 1000 1250 1500 1750 2000
62 Damper,DuctAssembly,Blower 15C5400 15C5400 15C5400 15C5400
(2) (2) (2) (2)
Electrical Components
See Figure 12A
64 Bracket, Control Panel Mounting 5C7103 5C7103 5C7103 5C7103 5C7103 5C7103 5C7103
65 Terminal Board, Field Wiring E2307400 E2307400 E2307400 E2307400 E2307400 E2307400 E2307400
66 IgnitionControl,SingleTry,CSD-1 E2107300 E2107300 E2107300 E2107300 E2107300 E2107300 E2107300
(1) (1) (2) (2) (2) (2) (2)
66A IgniltionControl,3-Try,non-CSD-1 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900
(1) (1) (2) (2) (2) (2) (2)
67 DiagnosticBoard E2105500 E2105500 E2105500 E2105500 E2105500 E2105500 E2105500
68 Indicator Light Panel Board E2105600 E2105600 E2105600 E2105600 E2105600 E2105600 E2105600
69 Temperature Control E2321700 E2321700 E2321700 E2321700 E2321700 E2321700 E2321700
70 High Limit, Auto Reset, 200°F E2217700 E2217700 E2217700 E2217700 E2217700 E2217700 E2217700
71 High Limit, Auto Reset, 135°F E2104800 E2104800 E2104800 E2104800 E2104800 E2104800 E2104800
72 Relay,Pump(SPST) E0098300 E0098300 E0098300 E0098300 E0098300 E0098300 E0098300
Relay,Fan(DPDT) E0076600 E0076600 E0076600 E0076600
(2) (2) (2) (2)
74 Transformer E2310400 E2310400 E2310400 E2312800 E2312800 E2312800 E2312800
(2) (2) (2) (2)
75A CircuitBreaker(non-CSD-1) E22106200 E22106200 E22106200 E2318800 E2318800 E2318900 E2318900
CircuitBreaker,CSD-1 E22106200 E2318800 E2318800 E2318900 E2318900 E2318900 E2318900
75B Switch, Rocker, 30A, 125VAC E2343300 E2343300 E2343300 E2343300 E2343300 E2343300 E2343300
Sensor, Temp Control E2314300 E2314300 E2314300 E2314300 E2314300 E2314300 E2314300
Page 28
Page 28
LAARS Heating Systems
Size Size Size Size Size Size Size
Item Description 500 750 1000 1250 1500 1750 2000
Gas Train Components
See Figure 10
76 Manifold, Gas Supply 5C6700 7C6700 10C6700 12C6700 15C6700 17C6700 20C6700
77 Valve, Ball V2003100 V2003100 R2003700 R2011600 R2011600 R2011600 R2011600
Burner Trays
Note: Burner Tray Assemblies contain item numbers 78 through 81.
Burner Manifold Assy, 3 Burners, Right, Nat 5C6600 5C6600 5C6600 5C6600 5C6600
(1) (1) (2) (1) (1)
Burner Manifold Assy, 3 Burners, Left, Nat 5C6500 5C6500 5C6500 5C6500 5C6500
(1) (2) (3) (1) (2)
Burner Manifold Assy, 4 Burners, Right, Nat 10C6600 10C6600 10C6600 10C6600
(1) (1) (1) (2)
Burner Manifold Assy, 4 Burners, Left, Nat 10C6500 10C6500 10C6500 10C6500
(2) (2) (2) (4)
Burner Manifold Assy, 3 Burners, Right, LP 5C6620 5C6620 5C6620 5C6620 5C6620
(1) (1) (2) (1) (1)
Burner Manifold Assy, 3 Burners, Left, LP 5C6520 5C6520 5C6520 5C6520 5C6500
(1) (1) (3) (1) (2)
Burner Manifold Assy, 4 Burners, Right, LP 10C6620 10C6620 10C6620 10C6620
(1) (1) (1) (2)
Burner Manifold Assy, 4 Burners, Left, LP 10C6520 10C6520 10C6520 10C6520
(2) (2) (2) (4)
78 Valve, Gas, Combination V2017600 V2017600 V2017600 V2017600 V2017600 V2017600 V2017600
(2) (3) (3) (5) (5) (6) (6)
79 Valve, Manual Shutoff V2000200 V2000200 V2000200 V2000200 V2000200 V2000200 V2000200
(2) (3) (3) (5) (5) (6) (6)
80 Orice, Gas, Natural L2013000 L2013000 L2013000 L2013000 L2013000 L2013000 L2013000
(6) (9) (12) (15) (18) (21) (24)
Orice, Gas, Propane L2012400 L2012400 L2012400 L2012400 L2012400 L2012400 L2012400
(6) (9) (12) (15) (18) (21) (24)
81 Burner Manifold, 3 Burners, Right L2012900 L2012900 L2012900 L2012900 L2012900
(1) (1) (2) (1) (1)
Burner Manifold, 3 Burners, Left L2012800 L2012800 L2012800 L2012800 L2012800
Page 29
Pennant Pool Heater
Page 29
Size Size Size Size Size Size Size
(1) (2) (3) (1) (2)
Item Description 500 750 1000 1250 1500 1750 2000
Burner Manifold, 4 Burners, Right L2012700 L2012700 L2012700 L2012700
(1) (1) (1) (2)
Burner Manifold, 4 Burners, Left L2012600 L2012600 L2012600 L2012600
(2) (2) (2) (4)
82 Burner Tray, 3 Burners L2012200 L2012200 L2012200 L2012200 L2012200
(2) (3) (5) (2) (3)
Burner Tray, 4 Burners L2012500 L2012500 L2012500 L2012500
(3) (3) (3) (6)
82A Gasket, Burner Tray, 3 Burner S2012700 S2012700 S2012700 S2012700 S2012700
(2) (3) (5) (2) (3)
Gasket, Burner Tray, 4 Burner S2012500 S2012500 S2012500 S2012500
(3) (3) (3) (6)
Page 30
Page 30
LAARS Heating Systems
Figure 10. Sheet Metal Components.
Page 31
Pennant Pool Heater
Page 31
Figure 11. Internal Components.
Page 32
Page 32
Enlargement
from previous page
LAARS Heating Systems
A
Figure 12. Heat Exchanger Components.
Page 33
Pennant Pool Heater
SECTION 10. Wiring Diagrams
Page 33
Figure 13. Pennant 500 - 1000 Ladder Diagram.
Page 34
Page 34
LAARS Heating Systems
Figure 14. Pennant 1250 - 2000 Ladder Diagram.
Page 35
Pennant Pool Heater
Page 35
Figure 15. Pennant 500 - 1000 Wiring Schematic.
Page 36
Page 36
LAARS Heating Systems
Figure 16. Pennant 1250 - 1500 Wiring Schematic.
Page 37
Pennant Pool Heater
Page 37
Figure 17. Pennant 1750 - 2000 Wiring Schematic.
Page 38
Page 38
LAARS Heating Systems
Figure 18. Field Wiring.
Page 39
Pennant Pool Heater
Page 39
Page 40
Dimensions and specications subject to change without notice in accordance with our policy of continuous product improvement.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors & Technical Support)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1306 Document 3164E
H2311900E
Loading...