U.S. Patent No. 1,609,692
Canada Patent No. 383,318
JVH
These instructions are to be stored next to the boiler for reference purposes.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed
exactly, a re or explosion may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the
re department.
Installation and service must be performed by
a qualied installer, service agency, or gas
supplier.
Vent damper is optional in some provinces of Canada..
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas
vous servir des téléphones dansle bâtiment
où vous êtes.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur
de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés
par un installateur ou un service d’entretien
This manual provides information necessary for the
installation, operation, and maintenance of the Laars
Model JV low pressure, copper tube hydronic boilers.
These boilers are available in two congurations; the
JVH has a hot surface pilot ignition system and the
JVS has an electronic intermittent ignition device
(I.I.D.). Look for the model designation on the rating
plate, which can be found on top of the boiler.
All application and installation procedures should
be reviewed completely before proceeding with
the installation. Consult the Laars factory, or local
factory representative, with any problems or questions
regarding this equipment. Experience has shown that
most operating problems are caused by improper
installation.
WARNING
This hydronic boiler must be installed in
accordance with the procedures detailed in this
manual, or the Laars warranty will be voided. The
installation must conform to the requirements of
the local jurisdiction having authority, and, in the
United States, to the latest edition of the National
Fuel Gas Code, ANSI Z223.1. In Canada, the
installation must conform with the latest edition of
CAN/CGA B149.1 OR .2 installation codes for gas
burning appliances, and/or local codes.
Any modications to the boiler, its gas controls,
gas orices, wiring or draft inducer assembly
may void the warranty. If eld conditions require
modications, consult the factory representative
before initiating such modications.
Page 3
1B. Warranty
The Laars Model JV boilers are covered by a limited
warranty. The owner should ll out the warranty
registration card and return it to Laars.
All warranty claims must be made to an authorized
Laars representative or directly to the factory. Claims
must include the boiler serial number and model (this
information can be found on the
rating plate), installation date, and name of the
installer. Shipping costs are not included in the
warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
The warranty does not cover damage caused by
improper assembly installation, operation or eld
modication.
ATTENTION
L' eau chaude chaudière doit être installé en
conformité avec les procédures détaillées dans
ce manuel, ou le Laars garantie sera annulée.
L'installation doit être conforme aux exigences
de la juridiction locale ayant l'autorité, et, aux
ÉTATS-UNIS , à la dernière édition du National
gaz carburant Code, ANSI Z223.1. Au Canada,
l'installation doit être conforme à la plus récente
édition de la norme CAN/CGA B149.1 ou .2 codes
d'installation gaz pour appareils de combustion et/
ou codes locaux.
Page 4
1C. Heater Identication
Consult the rating plate on the boiler. The following
example simplies the heater identication:
123456789101112
VJU2
LAARS Heating Systems
MODEL
J V
IGNIT
SYST
S
H
Table 1. Boiler Model Identication.
SIZE
0 5 0
0 7 5
1 0 0
1 2 5
1 6 0
2 2 5
FUEL
N
P
FIRING
SYST
JVH
1stand 2nd CharaCters (series name)
JV = mini-therm
3rd CharaCter (ignition system)
h = hot surfaCe pilot
4ththru 6th CharaCters (size)
input mBtu / h
7th CharaCter (fuel)
n = natural gasp = propane gas
8th CharaCter (firing system)
C = on / off
9th CharaCter (ConstruCtion option)
s = standard
10th CharaCter (altitudein feet)
s = (0 - 2,000) naturalor (0 - 5,000) propanei = (5,001 - 8,000) naturaland propaneJ = (8,001 - 10,000 naturaland propane
11th CharaCter (Country)
u = usa & Canada
12th CharaCter (reVision)
2 = seCond reVision
CONST
OPTION
C
D
S
P
I
J
ALTITUDE
S
I
J
COUNTRY
U
REVISION
2
JVS
1stand 2nd CharaCters (series name)
JV = mini-therm
3rd CharaCter (ignition system)
s = spark ignition
4ththru 6th CharaCters (size)
input mBtu / h
7th CharaCter (fuel)
n = natural gasp = propane gas
8th CharaCter (firing system)
D = on / off
9th CharaCter (ConstruCtion option)
i = (standard)
J = pump (050-125 only)
10th CharaCter (altitudein feet)
s = (0 - 2,000) naturalor (0 - 5,000) propanei = (5,001 - 8,000) naturaland propaneJ = (8,001 - 10,000 naturaland propane
11th CharaCter (Country)
u = usa & Canada
12th CharaCter (reVision)
2 = seCond reVision
SECTION 2.
Boiler Assembly and Placement
2A. Field Assembly
These boilers are available in two congurations; the
JVH has a hot surface ignition pilot and integral draft
fan, and the JVS has an electronic intermittent ignition
device (I.I.D.). Look for the model designation on the
rating plate, which can be found on top of the boiler in
the right rear corner.
The Laars automatic vent dampers are standard on
all JVS models. The Laars side wall power venters
can be used on JVS models. Special instructions for
their installation are included in the vent damper and
power venter package. Read them carefully before
installation.
Mini-Therm JV
Vent Damper (JVS only):
1. Mini-Therm JVS boilers have built-in draft
diverter for natural draft operation.
2. Find the vent damper box which is located in the
boiler package.
3. Install the vent damper directly to the top of the
draft diverter outlet with the damper operator
facing to the front of the boiler, and with the ow
direction arrow pointing upward. Use the vent
damper wire harness provided with the boiler
to connect the vent damper to the boiler. The
bracket end of the harness should be connected to
the vent damper actuator.
4. For Model JVS only: Install the metal plug
provided with the vent damper onto the damper
plate hole.
5. Do not modify the automatic vent damper device.
It is very important that no other vents are closed.
Provide at least six inches clearance between
the automatic vent damper and combustible
construction, and be sure to allow access for
servicing the damper.
Temperature/Pressure Gauge: Install the temp/
pressure gauge provided in the parts box.
Page 5
2C. Flooring
JVS model boilers can only be installed on
noncombustible ooring.
JVH model boilers are designed and certied for
installation on a combustible oor.
All boilers must be installed on a level oor and
must NEVER be installed on carpeting.
NEVER store objects on or around the boiler.
Noncombustible ooring is dened as ooring
material and surface nish not capable of being
ignited and burning and with no combustible materials
against the underside. Acceptable materials are those
consisting entirely of a combination of steel, iron,
brick, tile, concrete, slate, glass or plaster.
The JVS model boilers can be installed on a
combustible oor if a noncombustible base
assembly, available from Laars, is used. See the JVS
Parts List at the back of this manual for the appropriate
Noncombustible Base Kit part number.
2B. Boiler Placement
1. The boiler must be placed to provide clearances
on all sides for maintenance and inspection. There
must also be minimum distances maintained from
combustible surfaces. Avoid locations which can
be damaged by water or moisture.
2. A minimum of 15" (381mm) access must be
available in front of the boiler for burner tray
removal. Consult local codes for clearances to hot
water pipes and accessories.
3. If the boiler is to be installed in a garage, all
burners and burner ignition devices must have
a minimum 18" (457mm) clearance
above the oor.
4. Boilers can be installed in a closet as long as
the minimum clearances shown in Table 2 are
observed. Special attention should be paid to
clearances between the front of the boiler and the
closet door when it is closed (see Figure 2).
WARNING
This boiler is intended for indoor installation only.
Do not install this boiler in a location subject to
negative pressure, or improper operation will occur.
Avertissement
Cette chaudière est destiné pour une installation
intérieure uniquement. Ne pas installer cette
chaudière dans un endroit soumis à pression
négative, ou fonctionnement incorrect se produira
Figure 1. Typical Combustible Floor Installation.
As an alternative to the Laars Noncombustible Base
Kit, in the United States the National Fuel Gas
Code allows a heater to be placed on a combustible
surface when there is a platform under the heater
made of hollow masonry no less than 4 inches (102
millimeters [mm]) thick, covered with sheet metal at
least 24 gauge thick and extending beyond the full
Caution
Do not force motor operation when operator is
fastened to the damper by moving the damper
blade, turning the shaft or by turning the position
indicator.
Attention
Ne pas tourner le registre manuellement avec
ou sans courant électrique ou le moteur sera
endommagé.
Page 6
SizeABC
Wate r
Connection
Gas
Connection
in.
mm
in.
mm
in.
mm
50
75
100
125
160
225
13-3/8
13-3/8
16-7/8
16-7/8
20-3/8
25-5/8
340
340
429
429
518
651
3-1/8
2-1/4
5-3/4
5-1/2
7-1/4
10
79
57
146
140
184
254
2-7/8
2
2-7/8
2
2
2
73
51
73
51
51
51
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1/2
1/2
1/2
1/2
1/2
3/4
JVH
2D. JVH Dimensional Information
LAARS Heating Systems
Dimensions in
inches
mm
C B
7
180
6
152
2.4
61
25
635
JVH Dimensions
24
610
6
152
7
180
C B
25
635
2.4
61
24
610
Mini-Therm JV
JVS
Page 7
2D. JVS Dimensional Information
Dimensions in
inches
mm
7
180
9 -1/4
240
Water
SizeABCDEV
in. mmin. mmin. mmin. mmin. mm in. mm 1-1/41/2
5013-3/8 34027-3/4 71023-5/8 600 21-3/4 550 26-1/2 6704 101-1/41/2
7513-3/8 34027-3/4 71024-1/8 610 21-3/4 550 27-1/2 7005 131-1/41/2
width and depth of the heater by at least 12 inches
(305mm) in all directions. The masonry must be laid
with ends unsealed, and joints matched to provide
free circulation of air from side to side through the
masonry (see Figure 1). If the boiler is installed in a
carpeted alcove, the entire oor of the alcove must be
covered by a noncombustible platform.
2E. Clearance / Closet Installations
All Mini-Therm JV's can be installed in a closet as
long as the minimum clearances are observed.
See Table 2JVH and Figure 2JVH for
clearances required for the Mini-Therm JVH.
See Table 2JVS and Figure 2JVS for
clearances required for the Mini-Therm JVS
LAARS Heating Systems
Special attention should be paid to clearances
between the front of the boiler and the closet door
when it is closed.
Consult the American National Standard Z21.13 for
more information concerning closet installations. In
Canada, refer to the latest edition of CSA-B149.1.
Note: Clearances listed are manufacturer’s tested values. These are given as minimum values. Where local and national
codes apply, and values are different than those listed use the greater value to ensure safe operation.
Minimum Boiler Clearances from Combustible Surfaces.
Dégagements Minimaux à Assurer Entre Ics Parois de L’appareil et leo Constructions Combustibles
A
2
(51)
2
(51)
TOP
VIEW
4*
10
5
(127)
6
(152)
6 15
6 15
6 15
6
(152)
MIN
Air
Openings
Figure 2JVH. Closet Installation.
B
SIDE
VIEW
Dimensions in
inches (mm).
Dimensions in inches cm.
*6" for models JV160 to JV225.
Figure 2JVS. Closet Installation
Mini-Therm JV
Boiler SizeOutside Air AreaInside Air Area
sq. in
sq. cm
sq. in.
sq. cm
50
15
97
100
645
75
20
129
100
645
100
25
161
100
645
125
32
206
125
807
160
40
258
160
1032
225
60
387
225
1452
*Area indicated is for one of two openings: one at floor level
and one at the ceiling, so the total net free area would be
double the figures shown. For special conditions, refer to
NFPA54 ANSI Z223.1. In Canada, refer to the National
Standard CAN1-B149.1 or .2, which differs from this table.
NOTE: Check with louver manufacturers for Net Free Area of
Louvers. Correct for screen resistance to the Net Free Area if a
screen is used.
SECTION 3.
Air and Venting
3A. Combustion Air Supply
The boiler location must provide sufcient air
supply for proper combustion, and ventilation of
the surrounding area as outlined in the latest edition
of U.S. ANSI standard Z223.1 or in Canada, CAN/
CGA-B149.1 or .2, and any local codes that may be
applicable.
In general, these requirements specify that the
boiler rooms which represent conned spaces should
be provided with two permanent air supply openings;
one within 12 inches (305mm) of the ceiling, the other
within 12 inches (305mm) of the oor.
Page 9
NOTE: In Canada, follow Canadian Standard,
CAN/CGA-B149 or local codes.
Outside Air Supply: When combustion air is
supplied directly through an outside wall, each
opening should have a minimum free area of one
square inch per 4,000 BTU/h (6 sq. cm per 1.2 kW)
input of the total input rating of all appliances in the
enclosed area.
Inside Air Supply: When combustion is supplied
from inside the building, each opening should have
a minimum free area of one square inch per 1,000
BTU/h (6 sq. cm per 0.3 kW) input of the total input
rating of all appliances in the enclosed area. These
openings should never be less than 100 square inches
(645 sq. cm).
CHIMNEY
Table 3. Minimum Recommended
Air Supply to Boiler Room
Exhaust Fans or Vents: Any equipment which
exhausts air from the boiler room can deplete the
combustion air supply or reverse the natural draft
action of venting system. This could cause ue
products to accumulate in the boiler room. Additional
air must be supplied to compensate for such exhaust.
The information in Table 3 is not applicable in
installations where exhaust fans or blowers of any
type are used. Such installations must be designed by
qualied engineers.
If a blower or fan is used to supply air to the boiler
room, the installer should make sure it does not create
drafts which could cause nuisance shutdowns. If a
blower is necessary to provide adequate combustion
air to the boiler, a suitable switch or equivalent must
be wired into the boiler control circuit to prevent the
boiler from ring unless the blower is operating.
The boiler must be completely isolated and
protected from any source of corrosive chemical
fumes such as those emitted by trichloroethylene,
perchloroethylene, chlorine, etc.
3B. Venting
3 (0.9)
MIN.
WALL OR
PARAPET
NOTE: NO HEIGHT
ABOVE PARAPET
REQUIRED WHEN
FROM WALLS OR
PARAPET IS MORE
THAN 10 FT. (3.0m)
CHIMNEY
RIDGE
MORE THAN 10
(3.0)
2 (0.6)
MIN.
CHIMNEY
10 (3.0)
3 (0.9)
MIN.
The boiler vent collar must be fastened directly to
an unobstructed vent pipe with rustproof sheet metal
screws no longer than 1/2” (13mm) and located to
prevent interference with the inducer damper.
Do not weld the vent pipe to the boiler collar. The
weight of the stack must not rest on the boiler. The
boiler top must be easily removable for normal boiler
service and inspection.
Vent Categories: Mini-Therm JVS is a natural draft
appliance for Category I venting only. JVH is a
fan-assisted product that can be vented vertically in a
properly-designed Category I system, or can be vented
horizontally as a Category III appliance, per this
installation manual.
WARNING
This boiler must be vented in accordance with
Part 7, Venting of Equipment, of the latest edition
of the National Fuel Gas code, ANSI Z223.1 and
all applicable local building codes. In Canada,
follow CAN/CGA B149 Installation codes.
Improper venting of this appliance can result in
excessive levels of carbon monoxide which can
result in severe personal injury or death!
AVERTISSEMENT
Cette chaudière doit être ventilé, conformément
aux dispositions de la partie 7, de la ventilation de
l'équipement, de la dernière édition du National
gaz carburant code, ANSI Z223.1 et tous les
codes du bâtiment locaux. Au Canada, CAN/
CGA B149 codes d'installation. Une mauvaise
ventilation de cet appareil peut entraîner des
niveaux excessifs de monoxyde de carbone qui
peut entraîner de graves blessures ou la mort!
IMPORTANT
Only JVH (induced draft) models may be side-wall
vented per Section 3D without the addition of a
properly sized and installed power venter.
JVS must be connected only using Category Type
I methods and materials per Section 3C. JVH may
be connected per Category I or III (See Section 3D)
methods and materials. See fuel gas code for more
information regarding your venting application.
IMPORTANT
Seulement JVH (induits projet) modèles peut être
paroi ventilé par chapitre 3D sans l'addition de la
bonne taille et de puissance installée venter. JVS
doivent être connectés uniquement en utilisant
Type de catégorie I méthodes et matériaux par
Section 3C. JVH peut être connecté par catégorie
I ou III (voir section 3D) Les méthodes et les
matériaux. Voir gaz combustible code pour plus
d'informations concernant votre application
d'aération.
Avoid terminating boiler vents near air conditioning
or air supply fans. The fans can pick up exhaust
ue products from the boiler and return them to the
building, creating a possible health hazard.
Avoid oversized vent pipe or extremely long runs
Mini-Therm JV
Page 11
of the pipe, which may cause excessive cooling and
condensation.
3C. Vertical Venting - Category I
(JVS and JVH)
All venting must comply with fuel gas code and
be installed by a licensed professional.
The Mini-Therm JVS or JVH series boiler can
be vented into a masonry chimney, (see Figure 2)
provided several conditions are met:
1. The chimney must have an appropriate tile lining
that is clean, properly constructed and properly
sized.
2. The chimney passage way shall be examined to
ascertain that it is clear and free of obstructions.
WARNING
Do not store any chemical, cleaners, or other
corrosive material near combustion air openings
or in the room. Avoid locating dryer vents in the
vicinity of combustion air openings. Failure to
prevent corrosive materials from mixing with
combustion air can result in reduced boiler life
and unsafe boiler operation.
AVERTISSEMENT
N’entrepposer aucun produit chimique, produit
nettoyant ou produit corrosif à proximité des
bouches d’air de combustion ou dans la pièce.
Éviter de placer des tuyaux de ventilation pour
sécheuse à proximité des bouches d’air de
combustion. Le fait de laisser des maitières
corrosives se mélanger à l’air de combustion
risque de réduire le cycle de vie de l’appareil
de chauffage et de compromettre son
fonctionnement.
3. If a chimney rebuild is required, it shall conform
to nationally recognized standards (see National
Building Code or ANSI/NFPA 211).
4. The boiler must not be connected to a replace,
wood stove or other solid fuel burning
equipment.
5. When the boiler and a hot water heater are to be
connected to the same chimney, they must have
their own vent connector and enter the chimney
at least 6” (152mm) apart.
IMPORTANT NOTE: Always provide a minimum
clearance of 6” (152mm) between Type C (single wall)
vent pipe and any combustible materials.
WARNING
Single wall vent pipe must NEVER pass through
interior walls or through oors or ceilings! Failure
to comply with this warning could result in a re
causing property damage, personal injury, or death!
AVERTISSEMENT
Paroi simple tuyau d'évent doit jamais passer par
l'intérieur les murs ou par planchers ou plafonds
! Le non-respect de cet avertissement peut
provoquer un incendie causant des dommages
matériels ou corporels, ou de mort!
When installing the vent system, all applicable
national and local codes must be followed! The use
of thimbles, restops and other protective devices,
when penetrating combustible or noncombustible
construction, must be in accordance with all applicable
national and local codes.
VENT TERMINAL
4 (1.2)
MIN.
VENT
TERMINAL
Dimensions in
feet (m).
Figure 6. Horizontal Vent Termination.
4 (1.2)
MIN.
12 (3.7)
MIN.
3 (0.9)
MIN.
VENT TERMINAL
LESS THAN
(3.0)
FORCED
AIR INLET
10
6 (1.8) MIN.
GRADE
CAULK JOINTS
ANCHORED
FASTENER
THIMBLE
SHEET METAL
SCREWS
SEAL ENTIRE
CIRCUMFERENCE
OF JOINT
CAULK JOINTS
ANCHORED
FASTENER
EXHAUST
HOOD
VENT TERMINAL DETAIL
Page 12
Si ze
Diameter
No. of
Elbows
Horizontal Run Length
in.
mm
ft.
m
50 - 160
4
102
4
35
10.7
225
4
102
2
10
3.0
225
6
152
4
35
10.7
LAARS Heating Systems
Vertical vents of the induced draft JVH boilers must
be installed in accordance with the code requirement
for Category 1, Fan Assisted Appliances. Follow the
requirements as indicated in the latest edition of ANSI
Z223.1/NFPA 54, sizing of Category I Venting System
and Appendix G, or in Canada, follow the instruction
of CAN/CGA-B149 installation code.
An unused lined chimney can be used as a raceway
for single wall vent pipe, (see Figure 3). Never run
vent pipe through a ue that has another appliance
attached to it.
3D-1. Horizontal Venting - Category III
(JVH only)
When venting is horizontal, or cannot meet the
requirements of Category I, it can develop positive
pressure and must be installed in accordance with
this section and the specic vent manufacturer’s
instructions. Common venting is not allowed in
Category III systems.
BOILER VENTING
DETAIL
OUTSIDE WALL
VENT
SYSTEM
THIMBLE
BOILER
VENT TERMINAL
HOOD
Figure 7. Horizontal Venting.
SHEET METAL
SCREWS
12" (305mm)
*
MIN.
CAULK ENTIRE
JOINT, INCLUDING
THE SCREWS
*WHEN HORIZONTAL RUN
EXCEEDS 5 FT. (1.5m)
For best results, horizontal vent systems should
be as short and straight as possible. Material of vent
connectors shall be as follows:
DescriptionManufacturerProduct
High Temperature
RTV
2" (51mm) wide
Aluminum foil tape
- adhesively backed
Dow CorningTrade Mate
Venture
Product
#3243
2" (51mm) wide
Aluminum foil tape
3MProduct #433
- adhesively backed
Vent Sealing Materials.
MaterialsVent Length
In U.S.A.: UL type 304, 316 or 294-C
stainless steel or equal 26 gauge minimum.
In Canada: Use "BH-Type" vent
material certied to ULD-S636 Class I
(more than 135°C, but not more than 245°C
ue gas temperature), made of AL29-4C
stainless steel or equal.
Do not use plastic venting of any kind.
Up to a maximum
of 55' (17m) of
equivalent pipe run
(including required
elbows).
The boiler vent collar must be fastened to the vent
pipe with rustproof metal screws no longer than 1/2”
(13mm) and sealed with high temperature (500ºF /
260ºC) silicone sealant. For larger diameter vent pipes,
use a sealed reducer fastened directly to the boiler
collar and seal all joints as indicated in Figure 7.
Allow the sealant to cure for 24 hours before operating
the boiler.
The entire vent system must not exceed the size
specied in Table 4.
The following criteria must be observed:
1. Attach a vertical pipe at least 12” (305mm) high
to the boiler outlet before the horizontal run if
run exceeds 5 feet (see Figure 5).
2. Support the vent run at 3’ (.9m) intervals with
overhead hangers.
3D-2. Vent Connections (JVH only)
The vent system must be gas tight. All seams and
joints must be sealed with silicone sealant or adhesive
tape having a minimum temperature rating of 400°F
(204ºC). Use at least three corrosion resistant screws at
each slip joint, when required.
For each elbow eliminated, add 5’ (1.5m) of allowable vent.
Table 4. Horizontal Venting Conguration.
3. Pitch down the vent run, toward the vent terminal
(hood), 1/4” per foot (20mm per meter).
4. Do not locate any joint screws at the bottom of
the vent run.
3D-3. Vent Termination (JVH only)
The side wall vent terminal (hood), Laars Part
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.