LAARS Mini-Therm JVi User Manual

Mini-Therm JVi Venting Material 10-27 December 14, 2010
To: Manufacturer’s Representatives, Distributors, Contract Service Centers, Regional Sales Managers
and Internal Departments
From: Tom Gervais, International Sales Director
There has been an instance of confusion regarding suitable venting material for use on the Mini-Therm JVi
product with
Mini-Them manual has been updated to more clearly indicate what is an allowable vent material.
In Canada: Use "BH-Type" vent materials certified to ULC-S636 Class I (more than 135°C, but not more
than 245°C flue gas temperature), made of AL29-4C stainless steel or equal.
'RQRWXVHSODVWLFYHQWLQJRIDQ\NLQG
Addendum to Mini-Therm JVi Manual
This Addendum applies to the following Documents:
Models Affected Sizes Part No. Doc. No.
Mini-Therm JVi, JVH 50-225 H2020900D Doc. 1080D
Page 8 Change to Column 2 Table:
Materials Vent Length
1H-2. Horizontal Venting - Category III (a) Vent Connections
In U.S.A.: UL type 304, 316 or 294-C Up to a maximum
stainless steel, 26 gauge minimum. of 55' (17m) of In Canada: Use "BH-Type" vent equivalent pipe materials certified to ULC-S636 run (including Class I (more than 135°C, but not required elbows). more than 245°C flue gas temperature), made of AL29-4C stainless steel or equal.
Do not use plastic venting of any kind.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Ad viso rs)
20 INDUSTRIAL WAY, ROCHESTER, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Technical Support)
1869 SISMET ROAD, MISSISSAUGA, ONTARIO, CANADA L4W 1W8 • 905.238.0100 • Fax 905.366.0130
Installation and Operation Instructions Document 1080D
Installation and Operation Instructions for
Mini-Therm JVi
Induced Draft Residential Gas-Fired Hydronic Boilers
Model JVH
These instructions are to be stored next to the boiler for reference purposes.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hydronic boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H2020900D
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction................................................... 3
1B. Warranty.......................................................3
1C. Heater Identification......................................3
1D. Flow Requirements.......................................3
1E. Boiler Placement ..........................................4
1F. Gas Supply and Piping .................................4
1G. Combustion Air Supply .................................5
1H. Venting .........................................................6
1H-1. Vertical Venting - Category I .........................7
1H-2. Horizontal Venting - Category III ...................8
1H-3. Common Venting System ............................. 9
1I. Water Piping of Boiler System ....................10
1I-1. By-Pass Piping ........................................... 10
1J. Chilled Water Systems ............................... 10
1K. Electrical Wiring .......................................... 12
1L. Filling the System ....................................... 12
SECTION 2. Operating Procedures
2A. System Start-up ..........................................13
2B. Sequence of Operation ............................... 15
SECTION 3.
3A. Maintenance ...............................................17
3B. Electrical Troubleshooting .......................... 18
Mini-Therm JVi
Page 3
SECTION 1. General Information
WARNING
The JVi induced draft hydronic boiler must be installed in accordance with the procedures detailed in this manual, or the Laars warranty will be voided. The installation must conform to the requirements of the local jurisdiction having authority, and, in the United States, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the installation must conform with the latest edition of CAN/CGA B149.1 OR .2 installation codes for gas burning appliances, and/or local codes. Any modifications to the boiler, its gas controls, gas orifices, wiring or draft inducer assembly may void the warranty. If field conditions require modifications, consult the factory representative before initiating such modifications.
1A. Introduction
This manual provides information necessary for the installation, operation, and maintenance of the Laars Model JVi induced draft, low pressure, copper tube hydronic boilers. These boilers are available in two configurations; the JVH has a hot surface pilot ignition system and the JVP has an electronic intermittent ignition device (I.I.D.). Look for the model designation on the rating plate, which can be found on top of the boiler.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Laars factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
1B. Warranty
The Laars Model JVi induced draft boilers are covered by a limited warranty. A copy of the warranty
is printed on the back cover of this manual. The owner should fill out the warranty registration card and return it to Laars.
All warranty claims must be made to an authorized Laars representative or directly to the factory. Claims must include the boiler serial number and model (this information can be found on the rating plate), installation date and name of the installer. Shipping costs are not included in the warranty coverage. Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect each item for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed .
1C. Heater Identification
Consult the rating plate on the boiler. The following example simplifies the heater identification:
123456
JV H 125 N C S
Table 1. Heater Identification.
1. Basic boiler series model
2. Ignition system: (H) Hot surface pilot ignition
3. Input rate X 1000 BTU/Hr
4. Gas Type: (N) Natural (P) Propane
5. Firing rate: (C) On/off, induced draft
6. Options: (S) Standard, (P) with Pump,
(A) Extra Aquastat
1D. Flow Requirements
All high recovery, low volume water boilers must have adequate flow for proper operation. Pump selection is critical to this goal, and pumps should be selected to provide for correct system design water temperature rise. Table 2 details temperature rise and water flow for the Mini-Therm boilers.
8°C
15°F
Size
50 5.3 0.3 0.3 0.1 4.0 0.3 0.2 0.1 3.2 0.2 0.1 0.0
75 8.0 0.5 0.6 0.2 6.0 0.4 0.3 0.1 4.8 0.3 0.2 0.1 100 10.7 0.7 1.3 0.4 8.0 0.5 0.7 0.2 6.4 0.4 0.5 0.2 125 13.3 0.8 2.2 0.7 10.0 0.6 1.3 0.4 8.0 0.5 0.8 0.2 160 17.0 1.1 2.5 0.8 12.8 0.8 1.8 0.5 10.2 0.6 1.2 0.4 225 24.0 1.5 5.0 1.5 18.0 1.1 3.1 0.9 14.4 0.9 1.9 0.6
ft = Pressure drop (headloss) through the boiler in feet of water. m = Pressure drop (headloss) through the boiler in meters of water.
Flow Rate Headloss Flow Rate Headloss Flow Rate Headloss
gpm l/s ft m gpm l/s ft m gpm l/s ft m
gpm = Water Flow in gallons per minute. l/s = Water flow in liters per second.
Note: Shaded area is the recommended flow and temperature rise.
Table 2. Temperature Rise (degrees °F, degrees °C).
20°F
11°C
25°F
14°C
Page 4
LAARS Heating Systems
Damage from improper flow is not warranted.
Failure to insure proper water flow through the heat exchanger of the boiler will void the Laars warranty. Flow can be verified by measuring the difference in water temperatures between the boiler inlet (system return) and outlet (system supply). For example: For a JV-100 installation, the inlet water temperature is 160°F (71ºC), and the outlet temp­erature is 180°F (82ºC). That means there is a 20ºF (11ºC) temperature rise through the boiler. According to Table 2, that would indicate a flow rate of 8 gpm (0.5 l/s). Temperature rise must be measured with the longest (highest head) zone calling for heat alone.
Other factors to be considered before selecting a pump are pipe size, the number and type of fittings throughout the system, smoothness of the interior surface of the pipe, the quantity of water flowing through the pipe, whether a glycol solution (for freeze protection) is being used, and the total length of piping in the system. Table 3 can help in proper pump selection.
1/2" Pipe 3/4" Pipe 1" Pipe 1-1/4" Pipe
Size
Pump
H.P.
1/25 1/12 1/25 1/12 1/6 1/25 1/12 1/6 1/25 1/12 1/6 50 50 99 390 680 * * * * * * * 75 * 35 160 300 460 640 * * * * *
100 * * 77 150 260 330 620 * * * * 125 * * 27 80 140 170 360 600 * * * 160 * * * 25 72 57 160 330 190 480 * 225 * * * * * * * 110 * 69 330
*A circular and/or primary/secondary piping are required. Consult factory.
1. Chart is based on 30°F (17°C) maximum temperature rise.
2. Calculations are based on Type L copper tubing with one zone valve and eight elbows.
3. Typical circulating pumps: 1/25 HP=Taco 007, B&G LR-20 or SLC-25, Grundfos UP15-42F, or equivalent. 1/2 HP=B&G LR-12, Grudnfos U26-42F, or equivalent. 1/6 HP=B&G series HV, Grundfo UP43-75, or equivalent.
Table 3. Maximum Suggested Circuit Length in Feet.
Pump H.P. Pump H.P. Pump H.P.
1E. Boiler Placement
WARNING
This boiler is intended for indoor installation only.
1. The boiler must be placed to provide clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces. Avoid locations which can be damaged by water or moisture.
2. A minimum of 15" (381mm) access must be available in front of the boiler for burner tray removal. Consult local codes for clearances to hot water pipes and accessories.
4
(102)
6
(152)
Air
Openings
Figure 1. Closet Installation.
MIN
2
(51)
6
(152)
2
(51)
5
(127)
23
(584)
TOP
VIEW
SIDE VIEW
Dimensions in inches (mm).
3. If the boiler is to be installed in a garage, all burners and burner ignition devices must have a minimum 18" (457mm) clearance above the floor.
4. The Model JVi-50 through JVi-225 boilers can be installed in a closet as long as the minimum clearances shown in Table 4 are observed. Special attention should be paid to clearances between the front of the boiler and the closet door when it is closed (see Figure 1).
Caution
Do not install this boiler in a location subject to negative pressure, or improper operation will occur.
Boiler Sizes:
50 to
225
*1" (25mm) clearance using Type B double wall vent pipe.
Left Right
Side Side
2" 5" 2" 4" 6" 23"
51mm 127mm 51mm 102mm 152mm 584mm
Table 4. Minimum Boiler Clearances
From Combustible Surfaces.
Rear Front Flue* Top
5. All boilers are designed and certified for
installation on a combustible floor. Ensure that the boiler is level from all sides. NEVER store objects on or around the boiler. Boilers must NEVER be installed on carpeting.
1F. Gas Supply and Piping
Review the following instructions before
proceeding with the installation.
1. Verify that the boiler is fitted for the proper type of gas by checking the rating plate. Laars boilers
Mini-Therm JVi
Page 5
are normally equipped to operate below a 2000' (610m) altitude. Boilers equipped to operate at higher altitudes have appropriate stickers or tags attached next to the rating plate.
2. Use the figures in Table 5 to provide adequate gas piping from the gas meter to the boiler.
3. A trap (drip leg) must be provided ahead of the gas controls (see Figure 3). A manual gas shutoff valve approximately 5' (1.5m) above the floor must also be provided for service, convenience and safety. Check the local codes.
4. Disconnect the boiler from the gas supply pipe before pressure testing the pipe for gas leaks.
5. Provide gas supply pressure to the boiler per Table 6. The regulator is pre-set at the factory, and normally requires no further adjustment.
NOTE : The boiler and all other gas appliances
sharing the boiler gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersized gas meter and/or obstructed gas supply line.
Distance From Gas Meter in Feet (m)
0-50' (0-15)
50-100' (15-30)
100-200' (30-60)
NOTE: These figures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but maintain a 1/2" minimum diameter. A 'normal' number of Tees and elbows have been taken into allowance.
50 75 100 125 160 225
1/2 3/4 3/4 3/4 1 1 3/4 3/4 3/4 1 1 1-1/4 3/4 1 1 1 1-1/4 1-1/4
Boiler Size
Inches
Table 5. Gas Piping Sizes.
Gas Pressure
Minimum Supply
Pressure
Maximum Supply
Pressure
Manifold Gas
Pressure
Natural Gas Propane (LP)
in. W.C. kPa in. W.C. kPa
5.5 1.4 10 2.5
9 2.2 14 3.4
4 1 9 2.2
Table 6. Gas Pressure Measurement.
6. Before operating the boiler, the complete gas supply system and all connections must be tested for leaks using a soap solution.
1G. Combustion Air Supply
The boiler location must provide sufficient air
supply for proper combustion, and ventilation of the surrounding area as outlined in the latest edition of
TEMPERATURE GAUGE
2.4
(6.1)
25
(635)
REF
INDUCED DRAFT BLOWER/ MOTOR
PULL-OUT GAS MANIFOLD BURNER TRAY
C
4
(102)
DIA.
B
Size A B C
mm
50
75 100 125 160 225
in.
13-3/8 13-3/8 16-7/8 16-7/8 20-3/8 25-5/8
340 340 429 429 518 651
in.
3-1/8 2-1/4 5-3/4 5-1/2 7-1/4
10
Table 7. JVi Dimensions.
TEMP./PRESSURE GAUGE
mm 79
57 146 140 184 254
(178)
Water
Connection
mm
in.
73
2-7/8
2
2-7/8
2 2 2
7
11.8
(298)
51 73 51 51 51
6
(152)
1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4
1-1/4" NPT TEE 2X
DRAIN
Gas
Connection
1/2 1/2 1/2 1/2 1/2 3/4
4.9
(124)
8.9
(226)
A
Figure 2. Dimension Information.
Dimensions in inches (mm).
18 (457) REF.
24 (610)
REF.
Page 6
LAARS Heating Systems
U.S. ANSI standard Z223.1 or in Canada, CAN/CGA­B149.1 or .2, and any local codes that may be applicable.
In general, these requirements specify that the boiler rooms which represent confined spaces should be provided with two permanent air supply openings; one within 12 inches (305mm) of the ceiling, the other within 12 inches (305mm) of the floor.
Outside Air Supply: When combustion air is supplied directly through an outside wall, each opening should have a minimum free area of one square inch per 4,000 BTU/h (6 sq. cm per 1.2 kW) input of the total input rating of all appliances in the enclosed area.
Inside Air Supply: When combustion is supplied from inside the building, each opening should have a minimum free area of one square inch per 1,000 BTU/h (6 sq. cm per 0.3 kW) input of the total input rating of all appliances in the enclosed area. These openings should never be less than 100 square inches (645 sq. cm).
NOTE: In Canada, follow Canadian Standard, CAN/CGA-B149 or local codes.
Boiler Size Outside Air Area Inside Air Area
sq. in
50
75 100 125 160 225
*Area indicated is for one of two openings: one at floor level and one at the ceiling, so the total net free area would be double the figures shown. For special conditions, refer to NFPA54 ANSI Z223.1. In Canada, refer to the National Standard CAN1-B149.1 or .2, which differs from this table. NOTE: Check with louver manufacturers for Net Free Area of Louvers. Correct for screen resistance to the Net Free Area if a screen is used.
15 20 25 32 40 60
Table 8. Minimum Recommended
Air Supply to Boiler Room.
sq. cm
97 129 161 206 258 387
sq. in.
100 100 100 125 160 225
sq. cm
645 645 645
807 1032 1452
Exhaust Fans or Vents: Any equipment which
exhausts air from the boiler room can deplete the combustion air supply or reverse the natural draft action of venting system. This could cause flue products to accumulate in the boiler room. Additional air must be supplied to compensate for such exhaust.
The information in Table 8 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
If a blower or fan is used to supply air to the boiler room, the installer should make sure it does not create drafts which could cause nuisance shutdowns. If a blower is necessary to provide adequate combustion air to the boiler, a suitable switch or equivalent must be wired into the boiler control circuit to prevent the boiler from firing unless the blower is operating.
The boiler must be completely isolated and protected from any source of corrosive chemical fumes such as those emitted by trichloroethylene, perchloroethylene, chlorine, etc.
1H. Venting
WARNING
This boiler must be vented in accordance with Part 7, Venting of Equipment, of the latest edition of the National Fuel Gas code, ANSI Z223.1 and all applicable local building codes. In Canada, follow CAN/CGA B149 Installation codes. Improper venting of this appliance can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
The boiler vent collar must be fastened directly to an unobstructed vent pipe of the same diameter with rustproof sheet metal screws no longer than 1/2" (13mm) and located to prevent interference with the inducer damper.
DROP
HORIZONTAL
3" (76mm)
MIN.
Figure 3. Gas Supply Piping.
TO BOILER
SEDIMENT TRAP OR DRIP LEG
SEDIMENT TRAP OR DRIP LEG
TO BOILER
RISER
3" (76mm)
MIN.
Mini-Therm JVi
Page 7
Do not weld the vent pipe to the boiler collar. The weight of the stack must not rest on the boiler. The boiler top must be easily removable for normal boiler service and inspection.
Avoid terminating boiler vents near air conditioning or air supply fans. The fans can pick up exhaust flue products from the boiler and return them to the building, creating a possible health hazard.
Avoid oversized vent pipe or extremely long runs of the pipe, which may cause excessive cooling and condensation.
1H-1. Vertical Venting - Category I
The Mini-Therm JVi series boiler can be vented into a masonry chimney, (see Figure 4) provided several conditions are met:
1. The chimney must have an appropriate tile lining
that is clean, properly constructed and properly
sized.
2. The chimney passage way shall be examined to
ascertain that it is clear and free of obstructions.
3. If a chimney rebuild is required, it shall conform
to nationally recognized standards (see National
Building Code or ANSI/NFPA 211).
4. The boiler must not be connected to a fireplace,
wood stove or other solid fuel burning
equipment.
5. When the boiler and a hot water heater are to be
connected to the same chimney, they must have
their own vent connector and enter the chimney
at least 6" (152mm) apart.
(a) Vent Connections
Use type B double wall or type C single wall (26 gauge, minimum thickness), gas vent pipe from the boiler to the chimney. Installation of a riser, with a
minimum 12" (305mm) height above the boiler, is recommended. The vent system should be sloped up toward the chimney 1/4" per foot (20mm per meter). The vent connector must be supported for the design and weight of the material employed, to maintain clearances and prevent physical damage and separation of joints.
IMPORTANT NOTE: Always provide a
minimum clearance of 6" (152mm) between Type C (single wall) vent pipe and any combustible materials.
WARNING
Single wall vent pipe must NEVER pass through interior walls or through floors or ceilings! Failure to comply with this warning could result in a fire causing property damage, personal injury, or death!
When installing the vent system all applicable national and local codes must be followed! The use of thimbles, firestops and other protective devices, when penetrating combustible or noncombustible construction, must be in accordance with all applicable national and local codes.
Vertical vents of the induced draft JVi boilers must be installed in accordance with the code requirement for Category 1, Fan Assisted Appliances. Follow the requirements as indicated in the latest edition of ANSI Z223.1/NFPA 54, sizing of Category I Venting System and Appendix G, or in Canada, follow the instruction of CAN/CGA-B149 installation code.
An unused lined chimney can be used as a raceway for single wall vent pipe, (see Figure 5). Never run vent pipe through a flue that has another appliance attached to it.
CHIMNEY
LINER
THIMBLE
CLEANOUT
Figure 4. Chimney Venting. Figure 5. Vertical Venting.
1/4"
PER FT.
(20mm PER M)
SLOPE
VENT
SYSTEM
BOILER
CHIMNEY
LINER
THIMBLE
CLEANOUT
1/4"
PER FT.
(20mm PER M)
SLOPE
VENT
SYSTEM
12" (305mm)
BOILER
Loading...
+ 17 hidden pages