LAARS Mini-Therm II JVT User Manual

Installation and Operation Instructions Document 1025Y
Installation and Operation Instructions for
TM
Mini-Therm II
Residential Gas-Fired
THERM
INI-
LAARS
M
Hydronic Boilers
Models JVS, JVT Sizes 50-225
U.S. Patent No. 1,609,692 Canada Patent No. 383,318
Vent damper is optional in some provinces of Canada.
These instructions are to be stored in the packet
provided on the boiler.
FOR YOUR SAFETY : This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
If the information in this manual is not
WARNING
followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
AVERTISSEMENT
H0071400Y
A subsidiary of BRADFORD WHITE
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction...................................................3
1.2 Warranty....................................................... 3
1.3 Codes and Standards...................................3
1.4 Technical Assistance.................................... 3
1.5 Materials Installer Must Provide ...................3
1.5.1 Materials for All Installations......................... 3
1.5.2 Materials for Most Installations ..................... 3
1.5.3 Diagnostic Tools...........................................4
1.6 Specifications ...............................................4
1.6.1 General Specifications ................................. 4
1.6.2 Dimensions...................................................4
SECTION 2. Installation Instructions
2.1 Introduction...................................................4
2.2 Field Assembly ............................................. 5
2.3.1 Clearances ...................................................6
2.3.2 Flooring ........................................................ 6
SECTION 3. Venting
3.1 Combustion Air Supply.................................7
3.2 Exhaust Venting ........................................... 7
3.3 Vent Pipe Sizing and General
Installation .................................................... 8
3.4 Common Venting Systems ........................... 8
3.4.1 Venting Multiple Appliances ......................... 8
3.4.2 Inspection of Commonly Vented
Appliances.................................................... 9
SECTION 4. Gas Connections
4.1 Gas Supply and Piping...............................10
4.2 Special Precautions for LP Gas..................11
SECTION 6. Electrical
6.1 General Information.................................... 16
6.2 Main Power ................................................16
6.3 Grounding...................................................21
6.4 Auxiliary Devices ........................................ 21
6.4.1 Flow Switch ................................................ 21
6.4.2 Heat Anticipator..........................................21
SECTION 7. Operating Instructions
7.1 Normal Operation ....................................... 21
7.2 Start-up.......................................................22
7.2.1 Filling the System ....................................... 22
7.2.2 Boiler Start-up ............................................ 22
7.3 Lighting and Shutdown Procedures ........... 23
7.3.1 Lighting the Boiler....................................... 23
7.3.2 Shutdown ................................................... 24
7.3.2.1 Main Burner Shutdown (JVT Only)............. 24
7.3.2.2 Complete Shutdown ................................... 24
7.4 High Altitude Burner
Air Shutter Adjustment................................24
SECTION 8. Maintenance
8.1 General Maintenance ................................. 25
8.2 Boiler Components and Their
Operation....................................................26
SECTION 9. Troubleshooting
9.1 General Boiler Troubleshooting.................. 27
9.2 Troubleshooting Guide ............................... 28
9.3 Troubleshooting Honeywell S8600
Intermittent Pilot System.............................29
9.4 Electrical Troubleshooting .......................... 30
SECTION 5. Water Connections
5.1 Water Piping...............................................12
5.1.1 By-pass Piping ........................................... 12
5.2 Alternate Auto-Bypass Operation ............... 12
5.3 Flow Requirements .................................... 15
5.4 Chilled Water Systems ............................... 16
5.5 Oxygen Permeable Systems ...................... 16
5.6 Anti-Freeze................................................. 16
SECTION 10. Glossary
10.1 Glossary of Terms ...................................... 30
SECTION 11. Replacement Parts
11.1 Ordering Information ..................................31
11.2 Parts List ....................................................31
11.3 Exploded View............................................ 34
Mini-Therm II Hydronic Boiler
Page 3
SECTION 1. General Information
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of Laars Model JV copper tube hydronic boilers.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the Laars factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
These boilers are available in two configurations; the JVT has a thermocouple/continuous burning pilot, and the JVS has an electronic intermittent ignition device (I.I.D.). Look for the model designation on the rating plate, which can be found on top of the boiler in the right rear corner. If the unit is part of a Mini­Combo II (model MC) Residential Gas-Fired Space/ Water Heater, refer also to Document 8001, Mini­Combo II Installation and Operation Instructions.
The Laars automatic vent dampers are standard on all U.S. and Canadian models. The Laars side wall power venters can be used on both JVS and JVT models. Special instructions for their installation are included in the vent damper and power venter package. Read them carefully before installation.
1.2 Warranty
The Laars Model JV boilers are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Laars.
All warranty claims must be made to an authorized Laars representative or directly to the factory. Claims must include the boiler serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
The warranty does not cover damage caused by improper assembly installation, operation or field modification.
1.3 Codes and Standards
The JV Hydronic Boiler (or Mini-Therm II) is design certified by CSA (Canadian Standards Association) as complying with the latest edition of
the “Standard for Gas Fired Low Pressure Steam and Hot Water Boilers”, ANSI Z21.13 in the USA and CAN1-4.9 in Canada.
All Laars boilers must be installed in accordance with the local building and installation codes as per the utility or authorities having jurisdiction. All local codes take precedence over national codes.
In the absence of local codes, refer to the following national codes for installation:
1. In the United States, the latest edition of "The
National Fuel and Gas Code", ANSI Z223.1.
Specifically, refer to Chapter 10, "Venting of
Equipment".
2. In Canada, the latest edition of "The Installation
Codes for Gas Burning appliances and
Equipment", CSA B149.1.
Any changes to the boiler, gas controls, gas orifices, wiring, draft diverter, or improper installation may void the warranty. If change is required to any of the above, consult the factory.
1.4 Technical Assistance
Consult Laars Heating Systems or your local Laars factory representative with any questions or problems involving the specifications, installation, and operation of your Laars equipment. An experienced technical support staff is ready to assist you in assuring the proper performance and application of Laars products. For technical support call the Laars Heating Systems Technical Service Department.
1.5 Materials Installer Must Provide
1.5.1 Materials for All Installations
The following items are needed and are to be supplied by the installer for all Mini-Therm II boiler installations:
1. The correct size gas pipe to supply the gas to the
boiler (see Section 4.1 for correct gas pipe size).
2. A CSA listed manually operated gas valve to be
installed in the gas line outside of the boiler
jacket.
3. A suitable gas union joint or other removable
connector to connect the boiler to the gas line
outside of the boiler.
4. Plumbing items needed to provide a sediment
trap (drip leg) in the gas line between the manual
gas valve and the union to the boiler.
5. A 115 VAC power supply. A junction box is not
needed at the boiler, connections are made inside
of the boiler’s control panel (see Figure 8).
6. Vent pipe of the same or larger diameter as the
vent damper or draft diverter outlet (see Section
3.3 for venting instructions).
1.5.2 Materials for Most Installations
In addition to the items listed above, the following items may be needed:
Page 4
LAARS Heating Systems
1. Plumbing materials for the bypass piping, which
is required for: a. Any system where the return water
temperature may be less than 120°F, such as in-floor radiant systems, snow melt systems or other systems where a “cold start” is expected frequently due to thermostat setbacks, etc. See Figure 11.
b. Any system where the temperature rise
across the heat exchanger is above 30°F (see Section 5 and Figure 7).
2. Combustion air grates for openings sized in accordance with Section 3.1.
3. Field interlock wiring for any motorized combustion air louvers to ensure the boiler does not fire if motorized louvers do not open.
4. A suitable non-combustible base if installed on a combustible floor (see Section 2.3.2)
1.5.3 Diagnostic Tools
The following materials are needed to verify
correct installation:
1. Gas manometer to verify gas pressure
2. Strap-on, digital or infrared thermometer to check temperature rise across the heat exchanger.
3. Suggested: Draft gauge and combustion test equipment.
1.6 Specifications
1.6.1 General Specifications
1. Installation Location: Certified for use in Indoor Applications only
2. Minimum Clearance From Combustible Material: See Table 1 in Section 2.3.1.
3. Supply Gas Type: Certified for use with Natural Gas and LP Gas
4. Gas Pipe/Boiler Gas Valve Connection:
Nat LP
50-225 ½" NPT ½" NPT
5. Inlet Gas Supply Pressure:
Minimum Maximum Natural Gas: 5.5" WC 10.5" WC LP Gas: 10.0" WC 13.0" WC
6. Water Pipe/Boiler Connection: 1 ¼" NPT
7. Water Flow Rate: See Table in Section 5.2
8. Pressure Relief Valve: 30 PSI
9. Recommended system pressure: 12 PSI
10. Exhaust Vent Connection Size: 50 4" Diameter 75-100 5" Diameter 125-160 6" Diameter 225 7" Diameter
11. Electrical Supply: 115 Volts AC
12. Modification of Boiler for High Altitude: Mini-Therm II Boilers are normally shipped from the factory in the low altitude (sea level) operational configuration. When requested, the boilers can be configured and shipped for higher altitudes. For field conversions to change altitude configurations, conversion parts are available from Laars. For more information or call the Customer Service Department.
1.6.2 Dimensions
See Figure 1 for a diagram showing the boiler’s
exterior dimensions and dimensions to critical connections on the boiler.
SECTION 2. Installation Instructions
2.1 Introduction
WARNING
Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury, or death.
AVERTISSEMENT
Une installation ou un entretien in adéquat peut causer la nausée ou l’asphyxie en raison du monoxyde de carbone présent dans les gaz de combustion et même entrainer des blessures graves ou la mort.
Install the Mini-Therm II boilers and vent
dampers in accordance with the procedures in this manual, local codes and ordinances, and in accordance with the latest edition of the appropriate national code (see Section 1.3 “Codes and Standards”).
All gas-fired products require correct installation
to assure safe operation. The requirements for boilers include the following:
1. Field assembly
2. Appropriate site location (clearances) and flooring
3. Sufficient combustion and ventilation air
4. Properly sized gas meter and piping
5. Proper electrical wiring (if required)
6. Adequate water flow This manual provides the information needed to
meet these requirements. Review all application and installation procedures completely before continuing the installation.
NOTE: The Mini-Therm II boiler is approved for indoor installation only.
Mini-Therm II Hydronic Boiler
Vent Damper optional in Canada
Front
View
Top
View
Left Side View
BD
V
E
9-1/4
24
7
18
17-3/4 451
Vent Damper Harness
1-1/4 NPT
Draft
Diverter
A/2
C
A
In Return
T&P Gauge
Out Supply
PRV
Vent Damper Harness
Vent Damper
Draft Diverter
(built-in)
Temp Press Gauge
Dimensions in inches cm
Dimensions
inches cm
Size* A B C D E V
50 13-3/8 34 27-3/4 71 23-5/8 60 21-3/4 55 26-1/2 67 4 10 1-1/4 1/2
75 13-3/8 34 27-3/4 71 24-1/8 61 21-3/4 55 27-1/2 70 5 13 1-1/4 1/2 100 16-7/8 43 28-3/4 73 24-1/8 61 22-3/4 58 27-1/2 70 5 13 1-1/4 1/2 125 16-7/8 43 28-3/4 73 23-5/8 60 22-3/4 58 27-1/2 70 6 15 1-1/4 1/2 160 20-3/8 52 28-3/4 73 23-5/8 60 22-3/4 58 27-1/2 70 6 15 1-1/4 1/2 225 25-5/8 65 31-1/2 80 23-1/4 59 23-3/4 63 27-1/2 70 7 18 1-1/4
* Values shown are for both JVS and JVT Models **1/2 for propane
Figure 1. Dimensional Information.
Page 5
Water Gas Conn. Conn.
in. in.
*3/4**
2.2 Field Assembly
1. Mini-Therm II boilers have built-in draft diverter for natural draft operation.
2. Find the vent damper box which is located in the boiler package.
3. Install the vent damper directly to the top of the draft diverter outlet with the damper operator facing to the front of the boiler, and with the flow direction arrow pointing upward. Use the vent damper wire harness provided with the boiler to connect the vent damper to the boiler. The bracket end of the harness should be connected to the vent damper actuator.
4. For Model JVS only: Install the metal plug provided with the vent damper onto the damper plate hole. Disregard the metal plug in case of standing (continuous) pilot boilers. For all JVT
models, the damper plate hole should never be blocked.
5. Do not modify the automatic vent damper device. It is very important that no other vents are closed. Provide at least six inches clearance between the automatic vent damper and combustible construction, and be sure to allow access for servicing the damper.
6. Install the temperature/pressure gauge provided in the parts box.
Figure 2. Field Assembly Items.
Page 6
Caution
Do not force motor operation when operator is fastened to the damper by moving the damper blade, turning the shaft or by turning the position indicator.
LAARS Heating Systems
6 15
4*
10
6 15
Attention
Ne pas tourner le registre manuellement avec ou sans courant électrique ou le moteur sera endommagé.
2.3.1 Clearances
The boiler must be placed to provide clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces (see Table 1).
Boiler Sizes 50-125 160-225 Clearances in cm in cm Left side 6 15 6 15 Right side 6 15 6 15 Rear 6 15 6 15 Front 4 10 6 15 Flue 6 15 6 15 Top 23 48 36 91
Note: Clearances listed in Table 1 are manufacturer’s tested values. These are given as minimum values. Where local and national codes apply, and values are different than those listed in Table 1, use the greater value to ensure safe operation.
Table 1. Minimum Boiler Clearances
From Combustible Surfaces.
Dégagements Minimaux à Assurer Entre Ics Parois de
L’appareil et leo Constructions Combustibles
At least 15" (381mm) access must be available in front of the boiler for burner removal. Consult local codes for clearances to hot water pipes and accessories.
If the boiler is to be installed in a garage, all burners and burner ignition devices must have a minimum 18" (457mm) clearance above the floor.
The Model JV-50 through JV-100 boilers can be installed in a closet, as long as the minimum clearances shown in Table 1 and Figure 3 are observed. Special attention should be paid to clearances between the front of the boiler and the closet door when it is closed.
Consult the American National Standard Z21.13 for more information concerning closet installations. In Canada, refer to the latest edition of CSA-B149.1.
6 15
Dimensions in inches cm.
*6" for models JV160 to JV225.
Figure 3. Closet and Alcove Installation (see Table 3).
2.3.2 Flooring
The boiler shall be installed on a level floor of
noncombustible construction or on fire-resistant slabs or arches. Noncombustible flooring is defined as flooring material and surface finish not capable of being ignited and burning and with no combustible materials against the underside. Acceptable materials are those consisting entirely of a combination of steel, iron, brick, tile, concrete, slate, glass or plaster. Do not install the heater directly on a combustible wood or carpet floor without placing a noncombustible platform between the floor and the heater.
The boiler can be installed on a combustible floor if a noncombustible base assembly, available from Laars, is used. See the boiler rating plate or the Parts List (Section 11) of this manual for the appropriate base part number. Boilers must never be
installed directly on carpeting.
As an alternative to the Laars noncombustible base plate, in the United States, the National Fuel Gas Code allows a heater to be placed on a combustible surface when there is a platform under the heater made of hollow masonry no less than 4 inches (102 millimeters [mm]) thick, covered with sheet metal at least 24 gauge thick and extending beyond the full width and depth of the heater by at least 12 inches (305mm) in all directions. The masonry must be laid with ends unsealed, and joints matched to provide free circulation of air from side to side through the masonry (see Figure 4). If the boiler is installed in a carpeted alcove, the entire floor of the alcove must be covered by a noncombustible platform.
12"
12" Min.
Min.
(305mm)
Hollow
Sheet Metal Cover
Sheet Metal Cover
Min. Thickness 24 Gauge
Min. Thickness 24
Galvanized
Gauge Galvanized
Hollow
Concrete
Concrete Block
Block
Figure 4. Typical Combustible Floor Installation.
Mini-Therm II Hydronic Boiler
Page 7
SECTION 3. Venting
3.1 Combustion Air Supply
The boiler location must provide sufficient air supply for proper combustion, and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223.1 or in Canada, CSA-B149.1, and any local codes that may be applicable.
In general, these requirements specify that boiler rooms which represent confined spaces should be provided with two permanent air supply openings; one within 12 inches (305mm) of the ceiling, the other within 12 inches (305mm) of the floor (see Table 2).
Outside Air Area*
Boiler Size
50 15
75 20 100 25 125 32 160 40 225 60
*Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area would be double the figures indicated. For special conditions, refer to NFPA54 ANSI Z223.1. In Canada refer to the National Standard CSA B149.1
which differs from this table.
NOTE: Check with louver manufacturers for Net Free Area of louvers. Correct for screen resistance to the Net Free Area if a screen is installed. Check all local codes applicable to combustion air.
Table 2. Minimum Recommended
Important: See gas piping selection chart, Table 3 for
gas line sizing. In all cases, pipe size is larger than inlet connection on heater. Run pipe size shown in chart and reduce at heater inlet.
Outside Air
Sq. In. sq cm
Area in Sq. In.*
97 129 161 206 258 387
Air Supply to Boiler Room.
Outside Air Supply: When combustion air is
supplied directly through an outside wall, each opening should have a minimum free area of one square inch per 4,000 BTU/h (1.2kW) input of the total input rating of all appliances in the enclosed area.
If air is provided through horizontal ducts, each opening and duct must provide one square inch of flow area for each 2000 BTU/h (0.6 kW). These requirements are summarized in Table 2. Note that the required size of openings shall be based on the net free area of each opening. Where the free area of louver or grille is known it shall be used in calculating the effective free area. Where the free area are not known, it shall be assumed that wood louvers will have 25 percent free area, and metal louvers and grilles will have 75 percent free area.
Inside Air Area*
Inside Air
Sq. In. sq cm
Area in Sq. In.* (sq cm)
100 645 100 645 100 645 125 807 160 1032 225 1452
Inside Air Supply: When combustion is
supplied from inside the building, each opening should have a minimum free area of one square inch per 1,000 BTU/h (0.3kW) input of the total input rating of all appliances in the enclosed area. These openings should never be less than 100 square inches (645 sq. cm).
Note: In Canada, follow Canadian Standard, CSA­B149.1 or local codes.
Exhaust Fans or Vents: Any equipment which
exhausts air from the boiler room can deplete the combustion air supply or reverse the natural draft action of the venting system. This could cause flue products to accumulate in the boiler room. Additional air must be supplied to compensate for such exhaust.
The information in Table 2 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
If a blower or fan is used to supply air to the boiler room, the installer should make sure it does not create drafts which could cause nuisance shutdowns of the pilot. If a blower is necessary to provide adequate combustion air to the boiler, a suitable switch or equivalent must be wired into the boiler control circuit to prevent the boiler from firing unless the blower is operating.
The boiler must be completely isolated and protected from any source of corrosive chemical fumes such as those emitted by trichlorethylene, perchlorethylene, chlorine, etc.
WARNING
Do not store any chemical, cleaners, or other corrosive material near combustion air openings or in the room. Avoid locating dryer vents in the vicinity of combustion air openings. Failure to prevent corrosive materials from mixing with combustion air can result in reduced boiler life and unsafe boiler operation.
AVERTISSEMENT
N’entrepposer aucun produit chimique, produit nettoyant ou produit corrosif à proximité des bouches d’air de combustion ou dans la pièce. Éviter de placer des tuyaux de ventilation pour sécheuse à proximité des bouches d’air de combustion. Le fait de laisser des maitières corrosives se mélanger à l’air de combustion risque de réduire le cycle de vie de l’appareil de chauffage et de compromettre son fonctionnement.
3.2 Exhaust Venting
Vent piping must be of the same or larger diameter as the vent damper or draft diverter outlet. The only correct procedure for vent pipe sizing is to do so in accordance with Table 3 and the applicable installation code as stated in the following warning.
Page 8
LAARS Heating Systems
WARNING
Vent pipe diameter must be as required by the National fuel Gas Code Z223.1 or the Canadian Installation Codes for Gas Appliances CSA-B149.1. Undersize pipe can result in inadequate venting and oversize pipe can result in vent condensation. In either case the result can be release of combustion products to the indoors. This can cause serious injury or death by carbon monoxide poisoning or asphyxiation.
AVERTISSEMENT
Le diamètre des tuyaux de ventilation doit répondre aux exigences du National Fuel Gas Code Z223.1 ou du code canadien des installations des appareils à gaz CSA B149.1. Des tuyaux trop petits rispquent d’entraîner une ventilation inadéquate et des tuyaux trop gros risquent de provoquer une condensation dans les tuyaux. Dans un cas comme dans l’autre, des produits de combustion risquent de s’échapper dans le bâtiment et causer des blessures graves ou l’asphyxie par le monoxyde de carbone.
JVS/JVT Vent Pipe Diameter
Size inch cm
50 4 10
75 5 13 100 5 13 125 6 15 160 6 15 225 7 18
Table 3. Exhaust Vent Connection Size.
3.3 Vent Pipe Sizing and General Installation
All vent installations and boiler stacking must be
designed and installed in accordance with all local, state or provincial codes and with:
1. Chapter 7, “Venting of Equipment” of the national Fuel Gas Code, ANSI 223.1 latest edition, or the applicable provisions of the local building codes.
2. In Canada, CSA-B149.1. The draft diverter outlet is to be connected to an
unobstructed vent pipe of the same or larger diameter, terminating outside the building. The vent pipe must have a listed vent cap and extend at least two feet above any object with a ten foot radius. All connections should be made with rustproof sheet metal screws.
Do not weld or fasten the vent pipe to the boiler draft diverter. The weight of the stack must not rest on the boiler.
The draft diverter and boiler top must be easily removable for normal boiler service and inspection.
Avoid horizontal runs of the vent pipe, and 90° elbows, reductions and restrictions. Horizontal runs should have at least a 1/4" rise per foot (20mm per meter) in the direction of flow. A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints.
Avoid terminating boiler vents near air conditioning or air supply fans. The fans can pick up exhaust flue products from the boiler and return them inside the building, creating a possible health hazard. Do not located the vent terminal where flue products could strike against building materials and cause degradation.
Always use double-wall or insulated vent pipe when used as a chimney (Type B or equivalent). In cold weather, uninsulated outside vents can chill the rising flue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling flue products into the boiler room. Use engineered venting tables acceptable to the authority having jurisdiction to size the venting pipe or liner.
Avoid oversize vent piping or extremely long runs of the pipe which may cause excessive cooling and condensation.
Before connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions. When inspection reveals that an existing chimney is not safe for the intended application, it shall be rebuilt to conform to nationally recognized standards (see National Building Code or ANSI/NFPA 211), lined or relined with a suitable liner, or replaced with a vent or chimney suitable for the equipment to be attached.
3.4 Common Venting Systems
3.4.1 Venting Multiple Appliances
When common venting JVS or JVT natural draft boilers with other appliances through one shared duct called a “common vent”, special care must be taken by the installer to ensure safe operation. In the event that the common vent is blocked, it is possible, especially for fan-assisted devices, to vent backwards through non-operating appliances sharing the vent, allowing combustion products to infiltrate occupied spaces. If
the appliances are allowed to operate in this condition, serious injury or death may occur.
IMPORTANT NOTE: Do not use sheet metal screws at the snap lock joints of Type B gas vents.
Mini-Therm II Hydronic Boiler
Page 9
WARNING
Operation of appliances with a blocked common vent may lead to serious injury or death. Safety devices must be implemented to prevent blocked common vent operation. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
AVERTISSEMENT
Le fonctionnement des appareils avec un système d’évacuation bloqué peut provoquer des blessures graves, voire la mort. Des dispositifs de sécurité doivent être installés pour éviter le blocage des systèmes d’évacuation. Si le fonctionnement de tous les appareils connectés à un système d’évacuation commun ne peut pas être assuré, y compris la prévention de la dispersion des gaz toxiques dans les espaces habités, on ne devrait pas installer un système d’évacuation commun et chaque appareil devrait être ventilé séparément.
It is for this reason that, in addition to following proper vent sizing, construction and safety requirements from the National Fuel Gas Code, ANSI Z223.1 or in Canada, from CSA B149.1 as well as all applicable local codes, it is required that installers provide some means to prevent operation with a blocked common vent. It is suggested that a blocked vent safety system be employed such that if the switch from one appliance trips due to excessive stack spill or backpressure indicating a blocked vent condition, that all appliances attached to the vent be locked out and prevented from operating. As an additional precaution, it is recommended that a Carbon Monoxide (CO) alarm be installed in all enclosed spaces containing combustion appliances. If assistance is required in determining how a blocked vent safety system should be connected to a LAARS product, please call Applications Engineering at (603) 335-6300.
Refer to the installation and operating instructions on all appliances to be common vented for instructions, warnings, restrictions and safety requirements. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living spaces, common venting should not be applied, and appliances should each be vented separately.
3.4.2 Inspection of Commonly Vented Appliances
If the instrumentation of this boiler replaces an older boiler in a common vent system with other appliances, or if you remove additional appliances from the common vent, all the appliances must be checked for proper venting.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common
venting system.
Sceller toutes les ouvertures non utilisées du
système d’évacuation.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
Inspecter de façon visuelle le système
d’évacuation pour déterminer la grosseur et
l’inclinaison horizontale qui conviennent et
s’assurer que le système est exampt
d’obstruction, d’étranglement, de fuite, de
corrosion et autres défaillances qui pourraient
présenter des risques.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours
raccordés au système d’évacuation sont installés
et les autres espaces du bùtiment. Mettre en
marche les sécheuses, tous les appareils non
raccordés au systéme d’évacuation commun et
tous les ventilateurs d’extraction comme les
hottes de cuisinière et les ventilateurs des salles
de bain. S’assurer que ces ventilateurs
fonctionnent à la vitesse maximale. Ne pas faire
fonctionner les ventilateurs d’été. Fermer les
registres des cheminées.
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust
thermostat so appliance will operate
continuously.
Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de
façon que l’appareil fonctionne de façon
continue.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
Page 10
LAARS Heating Systems
flame of a match or candle, or smoke from a cigarette, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min ensuite, déterminer si le coupe-tirage déborde à l’ouverture de décharge. Utiliser la flamme d’une allumette ou d’une chandelle ou la fumée d’une cigarette, d’une cigare ou d’une pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
Une fois qu’il a été déterminé, selon la méthode inidquée ci-dessus, que chaque appareil raccordé au système d’évacuation est mis à l’air libre de façon adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1.
Tout mauvais fonctionnement du système d’évacuation commun devrait être corrigé de façon que l’installation soit conforme au national
Fuel Gas Code, ANSI Z223.1 et (ou) aux codes d}installation CSA-B149.1. Si la grosseur d’une
section du système d’évacuation doit être modifiée, le système devrait être modifié pour respecter les valeurs minimales des tableaux pertinents de l’appendices F du National Fuel
Gas Code, ANSI Z2231.1 et (ou) des codes d}installation CSA-B149.1.
SECTION 4. Gas Connections
4.1 Gas Supply and Piping
Review the following general instructions before
continuing the installation.
WARNING
The Mini-Therm II JVS and JVT boilers are designed for use with either natural gas or LP gas. Check the rating plate to be sure that the boiler is designed to use the type of gas being supplied. DO
NOT ATTEMPT TO CONVERT THIS HEATER FOR USE WITH ANY OTHER TYPE OF FUEL.
AVERTISSEMENT
Les appareils de chauffage à faibles sont conçus pour être utillsés avec du gaz naturel ou du gaz de pétrole liquéfié (GPL). Vérifiez l’information inscrite sur la plaque signalétique du pour vous assurer que l’appareil est conçu pour le type de gaz fourni. NE
PAS ESSAYER DE CONVERTIR CET APPAREIL À UN AUTRE TYPE DE GAZ.\
1. Gas piping installation must be in accordance with the latest edition of ANSI Z223.1 and all local codes. In Canada, the installation must be in accordance with CSA-B149.1 and all local codes that apply.
2. Check the gas supply to be sure that it is the same as the gas indicated on the boiler’s plate. Mini-Therm II JVS and JVT boilers, as shipped from the factory, are certified to operate within the altitude range indicated on the rating plate. If a field conversion to a different altitude range should be necessary, conversion parts are available for changing the altitude range of the heater. Refer to Doc. 6079 “Residential Parts Pricing Book” to order the correct part number.
Caution
Permanent damage to the gas valve will occur if the following procedures are not followed.
Attention
Vous endommagerez la soupape de gaz si vous ne respectez pas les procédures suivantes.
3. Use the figures in Table 4 to size the gas inlet piping from the gas meter to the heater. Check all local codes for compliance before installing the heater.
Mini-Therm II Hydronic Boiler
Page 11
Distance
From Gas
Meter
0-50'
0-15m
50-100'
15-30m
100-200'
30-60m
*Note: These figures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but maintain a 1/2" minimum diameter. A 'normal' number of Tees and elbows have been taken into allowance.
Table 4. Natural Gas Pipe Size Requirements*
Gas Supply Inlet
Tee Fitting
3 in. (76mm) Min.
50 75 100 125 160 225
1/2 3/4 3/4 3/4 1 1
3/4 3/4 3/4 1 1 1-1/4
3/4 1 1 1 1-1/4 1-1/4
Boiler Size
Pipe Size
To Equipment Inlet
Nipple
Supply Pressure Minimum Maximum
Natural Gas 5.5 Inches WC 10.5 Inches WC
(1.3 kPa) (2.5 kPa)
LP Gas 10.0 Inches WC 13.0 Inches WC
(2.4 kPa) (3.1 kPa)
Table 5. Gas Supply Pressure Requirements.
NOTE: The boiler and all other gas appliances
sharing the boiler gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line.
8. The correct high fire burner manifold gas pressure is stamped on the rating plate. The regulator is pre-set at the factory, and normally requires no further adjustment. For two-stage units (JVS100-225) be sure unit is able to fire at both high and low fire.
9. Before operating the boiler, the complete gas supply system and all connections must be tested for leaks using a leak detector solution. Do not use an open flame.
Cap
Figure 5. Typical design for a sediment trap/drip leg.
4. A sediment trap (drip leg) must be installed ahead of the gas controls (see Figure 5). Fit the trap with a threaded cap which can be removed for cleaning.
5. Install a manual gas shutoff valve for service and safety. Do not use a restrictive gas cock. Flexible gas connectors, if used, must be CSA rated for the total input rating of the boiler.
6. Disconnect the boiler and its individual shutoff valve from the gas supply system during pressure testing of the system at pressures higher than 1/2 pounds per square inch (psi) (3.45 kilopascals [kPa]). If the test pressure is equal to or less than 1/2 psi (3.45 kPa), close the manual shutoff valve on the heater during the piping pressure test.
7. If the gas supply pressure is less than required, check for undersized pipe between the meter and the boiler, a restrictive fitting, or an undersized gas meter. Gas supply pressures to the heater are listed in Table 5.
Caution
Some leak test solutions (including soap and water) may cause corrosion or stress cracking. Rinse the piping with water after testing.
Attention
Certaines solultions d’essai d’étanchéité (y compris l’eau et le savon) peuvent causer de la corrosion ou de la fissuration. Rincez les tuyaux à l’eau apprès l’essai d’étanchéité.
4.2 Special Precautions for LP Gas
LP Gas is heavier than air and can therefore more readily collect or “pool” in enclosed areas if provision for proper ventilation is not made. Be sure to pay special attention to proper ventilation for LP gas. Locate boilers a safe distance from LP gas cylinders and filling equipment. In the United States, consult the “National Fuel Gas Code” (NFPA 54 / ANSI Z223.1, latest edition) or in Canada, the Propane Installation Code (CSA-B149.1), any local codes and fire protection authorities about specific installation restrictions in your area.
NOTE: The maximum inlet gas pressure must not exceed the specified value. The minimum value listed is for the purpose of input adjustment. Refer to Table 5.
Loading...
+ 25 hidden pages