LAARS Mini-Combo id MCH User Manual

Page 1
Installation and Operation Instructions Document 2101B
and Operation
Instructions for
Mini-Combo id
Model MCH
Induced Draft
Residential Gas-Fired
Space/Water Heater
Note: This document is to be used in conjunction with Document 1080, Installation and Operating Instructions for Mini-Therm JVi boilers.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, gas supplier, or call the factory.
H2100200B
Page 2
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1A. Hazards and Your Safety —
Hot Water Can Scald!...................................3
SECTION 2.
Installation .................................................
2A. Location........................................................ 5
2B. Heater Placement.........................................5
2C. Piping ........................................................... 5
2D. Wiring ...........................................................6
3
Page 3
Mini-Combo id
Page 3
SECTION 1. General Information
WARNING
This manual supplies information on the application, installation and operation of the indirect water heater unit. operation of the hydronic boiler (Document 1080) is supplied along with this manual. Both manuals should be reviewed completely before proceeding with the installation.
Failure to follow the instructions provided may result in personal injury, death or substantial property damage.
Any modifications to the boiler, water tank, gas and water connections, or wiring may void warranty.
Consult the factory or local factory representative with any questions or problems regarding this equipment.
Hazards and Your Safety — Hot Water Can Scald!
Consumer Product Safety Commission and some
states/provinces recommend a temperature setting of 130°F (54°C) or less. The water heater thermostat is factory set to approximately 120°F (49°C). If thermostat will be set above factory setting, install an anti-scald valve at either the water heater or at each hot water faucet.
A complete instruction manual of the
• Studies have indicated that dangerous bacteria can form in potable water distribution system if certain minimum water temperatures are not maintained. Contact local health department for more information.
SECTION 2. Installation
This installation must conform with the
instructions in this manual and, where applicable:
• Local, state, provincial, and national codes, laws, regulations and ordinances.
• In Canada — CAN/CGA B149.1 or B149.2 installation Code.
Where the recommendations made in this manual
differ from local or national codes, the local or national codes take precedence.
2A. Location
This water heater/boiler unit is not intended for
outdoor installation. Select a convenient location where water leakage from the tank or connections will not result in damage to areas adjacent to the appliance or to lower floors of the structure. When a safe location cannot be found, install a suitable drain pan under the appliance, and pipe it to an adequate drain.
• Tempering valves are not anti-scald valves since they do not have a positive shutoff in case cold water supply fails. They are not recommended for shower/tub service. If needed, install an anti­scald valve at each shower/tub.
• Water heated to a temperature suitable for clothes washing, dish washing and other sanitizing needs can scald and cause permanent injury.
• Children and elderly, infirm, or physically handicapped persons are more likely to be injured by hot water. Never leave them unattended in a bathtub or shower. Never allow small children to use a hot water tap or draw their own bath. If anyone using hot water in the building fits this description, or if state/province laws or local codes require certain water temperature at hot water taps, take special precautions:
Install an anti-scald valve at water heater or at each hot water faucet, bath, and shower outlet.
Use lowest practical temperature setting.
2
(51)
63.5
(1613)
Figure 1. Closet Installation.
25.25 (641)
29
(737)
4 (102)
Top Clearance
23 (584)
57.75
(1467)
2 (51)
2
(51)
Dimensions shown in inches (mm).
Page 4
Page 4
Check Valve
Tank
Pump
.75
(19)
24
(610)
Domestic
Hot Water
Outlet
Cold Water
Inlet
32.5
(826)
62.5
(1588)
41.5
(1054)
Tank
Aquastat
Drain Valve
LAARS Heating Systems
Boiler Flue Collar 4 (102)
60
(1521)
Tank Relief Valve
24
(610)
7
(178)
(610)
Figure 2. Dimensional Information.
Dimensions inches mm
Size A
50 14 356
75 15 381 100 16 406 125 17 432
Boiler In/Out NPT
(all sizes)
Gas NPT (all sizes) ½* Domestic Hot Water (all sizes)
Inlet/Outlet NPT ¾
Minimum clearances from
combustible surfaces:
Left Side: 2" 51mm
Right Side: 2" 51mm
Rear: 2" 51mm
Front: 4" 102mm Top: 23" 584mm
Service clearances:
Allow 4" 102mm on each side
for piping access.
7
(178)
24
Side View Front View
Hot
Water
Supply
Cold
Water
Supply
28
(711)
Figure 3. Piping Schematic.
Dimensions shown in inches (mm).
Space Heating -
Refer to Doc u me n t 1 080
Boiler
Tank
*¾" for model 125 Natural.
Figure 4. Typical Expansion Tank Installation.
Page 5
Mini-Combo id
Page 5
2B. Heater Placement
The heater must be placed to provide clearances on all sides for maintenance and inspection. Allow 4 inches on each side for piping access. There must also be minimum distances maintained from combustible surfaces. Figure 1 shows minimum clearance from combustible surfaces. The Mini-Combo unit can be installed in a closet, as long as the minimum clearances are maintained. Special attention should be paid to the air supply opening to the closet. Refer to Table 1.
Net Free Area — square inches sq. cm
Model Inside Air Outside Air
MC50 100 645 15 97
MC75 100 645 20 129 MC100 100 645 25 161 MC125 125 806 32 206
Area indicated is for one of two openings: One at floor level and one at the ceiling, so the total free area would be double the figures indicated. Refer to Document 1080 for more information.
Table 1. Minimum Recommended Air Supply.
persons. Attach run-off tube to T&P valve and run tube within 6" (152mm) from floor. No reducing couplings, valves, or any other type of restriction is to be installed in this line. This run­off tube must be installed to allow free and complete drainage of both valve and run-off tube.
Filling Storage Water Tank
1. Open hot water faucet in house to allow air in the tank and in piping to escape.
2. Open shut-off valve(s) in cold water supply line.
3. Open shut-off valve(s) in hot water supply line.
2C. Piping
• To prevent damage to the unit, all soldering is to be done prior to assembling the cold and hot water, and any other connections to the tank.
• Use suitable pipe dope or tape.
• Before piping the boiler to the heating system, be sure to install the system check valve (provided with the unit) onto the inlet (return) tee of the boiler with arrow pointed downward (see Figure 3).
• If anti-freeze is used in boiler system, local codes may require a backflow preventer on cold supply line. Use anti-freeze specifically intended for hydronic heating system. Inhibited propylene glycol is recommended.
WARNING
Do not use automotive or ethylene glycol anti­freeze, or any undiluted anti-freeze. This can cause severe personal injury, death or substantial property damage.
If a backflow preventer, pressure reducing valve
or check valve is in cold water supply, install an expansion tank on cold water supply line (see Figure 4) to prevent normal thermal expansion from repeatedly forcing open the T&P relief valve.
T&P relief valve's discharge piping must be directed so that hot water flows away from all
Figure 5. MCH Schematic.
Page 6
Page 6
LAARS Heating Systems
WALL
THERMOSTAT
(FIELD
SUPPLIED)
R
W
A
TERMINAL
STRIP
BL
SENSOR
R
AQUASTAT
(OPTIONAL)
BK - BLACK W-WHITE R-RED Y-YELLOW BL - BLUE BR - BROWN O-ORANGE P-PURPLE G-GREEN BL/Y - BLUE/YELLOW STRIPE BR/Y - BROWN/YELLOW STRIPE
IF ANY OF THE ORIGINAL WIRE (AS SUPPLIED WITH THE APPLIANCE) MUST BE REPLACED, IT MUST BE REPLACED WITH APPLIANCE WIRING MATERIAL SUITABLE FOR 105 DEGREES C OR ITS EQUIVALENT
115V-FACTORY WIRED 115V-FIELD WIRED 24V-FACTORY WIRED 24V-FIELD WIRED
Figure 6. Wiring Diagram.
BR
P
R
PRESSURE
SWITCH
ROLL-OUT
SAFETY SWITCH
AQUASTAT
R
HIGH LIMIT
TANK
24V COM
SEN
NC
P
GAS VAL VE MOLEX
COM
BL
TRANSFORMER
R
NO
P
O
BL
Y
R
O
Y
Y
P
24V 115V
G
Y
R
R
Y
R
R
BL
Y
R
R
R
4
265
4
265
4
265
ZONE PUMP
RELAY
1
3
1
3
TANK
PUMP
RELAY
1
INDUCER MOTOR RELAY
3
BK
W
BK
BK
BR
BK
BR
PUMP
(FIELD
SUPPLIED)
BR
INDUCER
W
W
Y
W
HOT
115/60HZ
POWER SUPPLY
NEUTRAL
GROUNDING
CONDUCTOR
TANK
PUMP
MODEL MCH
H2021000A
4. When water discharges from the faucet, close it. Check for system leaks and repair if necessary.
Filling and connecting boiler pipes: Consult the JV boiler manual, Document 1080.
Caution
Never use water heater/boiler unless it is completely filled with water.
2D. Wiring
Priority System: Under this wiring the storage
tank will be supplied before space heating. This will insure that it gets adequate hot water flow from the boiler to maintain a fully rated delivery of domestic hot water.
Caution
In this priority mode, any demand for space heating is postponed until the storage water tank has reached set temperature. This delay in supplying the space heating zones is usually not noticed by the inhabitants of the living spaces. However, in the event of certain storage water tank malfunctions, space heating could be delayed indefinitely. If undetected and un-corrected, freezing damage to piping could result.
WARNING
Electrical shock can cause severe personal injury or death. Disconnect power supply to the boiler before doing any electrical work.
Electrical Connection (see Figures 5 and 6).
1. Remove the two screws attaching the front cover of the control box.
2. There are six wires coiled in the area on the right side of the control box, supplied with wire nuts: 2 black wires twisted together, 3 white wires twisted together, and a brown wire.
3. Follow the schematics in Figures 5 and 6. Remove the wire nut from the two black wires, and connect the hot lead from a 115 volt power supply to both wires. Secure the three wires in the wire nut.
4. The three white, neutral wires should be joined to the other neutral lead coming from the 115 volt power supply, and the neutral lead coming from the pump (space heating).
5. The brown wire attaches to the hot side of the space heating pump.
Page 7
Mini-Combo id
Page 7
115 Volts Supply
Transformer
Sequence of Operation
Tank Stat
(common)
Domestic Demand
(N.C.)
Tank Pump (energized)
Heating Demand
(N.O.)
Heating Pump
(energized)
High Limit
Switch
Inducer
Energized
Fan Proving
Switch
Flame Roll-Out
Safety Switch
Main Gas Valve
(energized)
Figure 7. Sequence of Operation.
Boiler On
Page 8
Page 8
LAARS Heating Systems
Figure 8. Parts Identification.
Page 9
Mini-Combo id
# Qty Part # Description
1 1 20085700 Weldment, Panel, Base 2 1 20085600 Weldment, Panel, Top 3 1 20086300 Weldment, Panel, Door 4 1 20086400 Panel, Side, Right 5 1 20127900 Weldment, Panel, Side, Left 6 1 20085900 Panel, Rear 7 1 20086500 Panel, Access 8 1 20084000 Bracket, Mounting, Left 9 4 20085400 Bracket, Support, Tank 10 2 P2019200 Cross, Black Iron, 1¼" NPT 11 4 P2014800 Fitting, Brass Compression,
7
/8" OD x ¾"
12 1 A2085600 Valve, Check, ¾" NPT
7
13 7.2ft P2015000 Tubing, Copper, Type “L”,
/8" OD 14 1 A2085700 Valve, Drain, Tank, ¾" NPT 15 1 E0205000 Temperature Control, Electronic 16 1 A2085400 Valve, Relief, Temp & Pressure 17 1 A2085301 30 Gal. Water Tank,
Double Wall HX
1 A2085300 30 Gal. Water Tank,
Single Wall HX 18 2 20087300 Door Latch Assembly 19 1 A0066500 Pump, Circulator 20 1 A2086600 Valve, Check, 1¼" NPT 21 1 A2087600 Handle, Door 22 2 A2086700 Flange, Pump, ¾" NPT 23 1 A2085900 Well, Immersion, ¾" NPT 24 1 A2000400 Gauge, Pressure/Temperature 25 1 A2000600 Gauge, Temperature 26 1 20084001 Bracket, Mounting, Right 27 1 E2103100 Sensor
Page 9
Page 10
Page 10
LAARS Heating Systems
Page 11
Mini-Combo id
Page 11
Page 12
Laars Heating Systems Company reserves the right to change specifications, components, features, or to discontinue products without notice.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 603.335.6300 • Fax 603.335.3355 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 905.238.0100 Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 0806 Document 2101B
H2100200B
Loading...