LAARS Mighty Therm PH Installation Manual

Installation and Operation Instructions Document 1049E
Installation and Operation Instructions for
Mighty Therm
Hydronic Boilers
Models HH and PH
Sizes 500-1825
These instructions are to be stored in the pocket provided on the boiler
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H0117400E
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction...................................................3
1B. Boiler Identification .......................................3
1C. Flow Requirements.......................................3
1D. Variable Water Flow Systems.......................4
1E. Warning Regarding Chilled
Water Systems ............................................. 5
1F. Freeze Protection ......................................... 5
SECTION 2. Installation
2A. Boiler Placement ..........................................6
2B. Installation of Indoor Boilers..........................6
2B-1. Combustion Air Supply ................................. 6
2B-2. Venting .........................................................8
2C. Installation of Outdoor Boilers....................... 9
2D. Gas Supply and Piping ................................. 9
2E. Electrical Wiring .......................................... 10
2F. Water Piping of System .............................. 11
2G. Filling Fully-Connected System................... 11
SECTION 3. Operation
3A. Controls - General ...................................... 12
3B. Initial Start-Up ............................................. 13
3C. To Start Up System .................................... 13
3D. To Turn Off Boiler ....................................... 14
3E. To Shut Down System ................................ 14
SECTION 4. Maintenance
................................................................... 14
SECTION 5. Troubleshooting and Analysis of Service Problems
................................................................... 16
SECTION 6. Parts Descriptions and Order Numbers
................................................................... 18
SECTION 7. Outdoor Parts Descriptions and Order Numbers
................................................................... 26
SECTION 8. Optional Parts Descriptions and Order Numbers
................................................................... 28
Mighty Therm Hydronic Boiler
Page 3
SECTION 1. General Information
1A. Introduction
This manual provides information for the installation and operation of Laars hydronic boilers. It is strongly recommended that all application and installation procedures be reviewed completely before proceeding with the installation. Consult the Laars factory, or local factory representative with any problems or questions regarding this equipment. Experience has shown that most problems are caused by improper installation not system design.
Some accessory items are shipped in separate packages. Verify receipt of all items listed on the package slip. Inspect everything for possible damage upon delivery, and inform the carrier of any shortages or impairments. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
IMPORTANT WARNING:
The model HH and PH hydronic boilers must be installed in accordance with the procedures outlined in this manual. The warranty does not apply to boilers not installed or operated in accordance with these procedures. Consult local building and safety codes before proceeding with work. The installation must
conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest edition of the National Fuel Gas Code; ANSI Z223.1, National Electrical Code ANSI/NFPA 70 and/ or in Canada CAN 1 -13149 requirement.
When required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers safety codes for controls and safety devices for automatically fired boilers No. CSD-1, and in Canada CGA 3.3. Any modification to the boiler, its gas controls, gas orifices, wiring or draft diverter may void the Laars warranty. If field conditions require such modifications, consult factory.
1B. Boiler Identification
Consult rating plate on the boiler. The following example simplifies the boiler identification.
1 2 3456
PH 1670 I N 09 L
(1) Basic boiler model (see descriptions below). (2) Input rate X 1000 BTU/hr. (3) Indoor (1) or Outdoor (E) installation. (4) Gas type: Natural (N) or Propane (P). (5) Ignition system: I.I.D. (09) or continuous pilot
(16). Special option: I.I.D. (04) 115 volts.
(6) Firing modes:
On/Off (C) 2-stage (K) 4-stage (L) Mechanical Modulation (H) Motorized Modulation (F) Motorized On/Off (R) Motorized 2-stage (T).
Figure 1. Boiler Configuration.
Model HH hydronic heating boilers. There must be a field installed pump to circulate water.
Model PH hydronic heating boilers are basically the same as the HH models except that the PH boilers come with integrally mount pumps. Pumps are sized for pressure drop through the heat exchanger and short runs of pipe for primary-secondary systems.
Laars hydronic boilers are available in two configurations: an indoor version and an outdoor version. Both are available from the factory (see Figure 1).
1C. Flow Requirements
All low volume hydronic boilers must have continuous flow through the heat exchanger for proper operation. The system pump must be capable of developing sufficient pressure to overcome the
Page 4
Design T emperature Rise Across The Boiler
20°F 11°C 25°F 14°C 30°F 17°C 35°F 19°C
Indoor Outdoor Flow H/L Flow H/L Flow H/L Flow H/L
Sizes Sizes GPM l/s Ft. m GPM l/s Ft. m GPM l/s Ft. m GPM l/s Ft. m
500 38 2.4 1.4 0.4 31 2.0 1.1 0.3 26 1.6 0.9 0.3 22 1.4 0.6 0.2
500 41 2.6 1.7 0.5 33 2.1 1.1 0.3 27 1.7 0.9 0.3 23 1.5 0.7 0.2
600 49 3.1 2.3 0.7 39 2.5 1.6 0.5 32 2.0 1.1 0.3 28 1.8 0.9 0.3
600 49 3.1 2.3 0.7 39 2.5 1.6 0.5 32 2.0 1.1 0.3 28 1.8 0.9 0.3
715 56 3.5 2.5 0.8 45 2.8 1.9 0.6 37 2.3 1.5 0.5 32 2.0 1.0 0.3
715 58 3.7 3.2 1.0 47 3.0 2.2 0.7 39 2.5 1.6 0.5 33 2.1 1.1 0.3
850 66 4.2 3.4 1.0 53 3.3 2.5 0.8 44 2.8 2.0 0.6 38 2.4 1.4 0.4
850 69 4.4 3.6 1.1 55 3.5 3.1 0.9 46 2.9 2.2 0.7 39 2.5 1.6 0.5
1010 79 5.0 4.7 1.4 63 4.0 3.4 1.0 53 3.3 2.7 0.8 45 2.8 1.9 0.6
1010 82 5.2 5.0 1.5 66 4.2 3.6 1.1 55 3.5 3.1 0.9 47 3.0 2.2 0.7
1200 94 5.9 6.5 2.0 75 4.7 4.8 1.5 62 3.9 3.7 1.1 53 3.3 2.6 0.8
1200 98 6.2 6.9 2.1 78 4.9 4.9 1.5 65 4.1 3.6 1.1 56 3.5 3.1 0.9
1430 112 7.1 8.9 2.7 89 5.6 6.5 2.0 74 4.7 5.0 1.5 64 4.0 3.5 1.1
1430 117 7.4 9.5 2.9 93 5.9 6.7 2.0 78 4.9 5.0 1.5 67 4.2 3.7 1.1
1670 * * * * 102 6.4 8.8 2.7 85 5.4 6.7 2.0 73 4.6 4.7 1.4
1670 * * * * 109 6.9 9.1 2.8 91 5.7 6.8 2.1 78 4.9 5.0 1.5
1825 * * * * 114 7.2 10 3.0 95 6.0 8.0 2.4 81 5.1 5.5 1.7
1825 * * * * 119 7.5 10.4 3.2 99 6.2 8.3 2.5 85 5.4 5.7 1.7
LAARS Heating Systems
*Consult factory for recommendations
Table 1. Flow Requirements.
resistance of the boiler plus the entire circulating system at the designated GPM (see Table 1). The temperature rise across the boiler should never exceed 40°F (22°C). Primary-secondary pumping is the most effective way to assure proper flow through the boiler resulting in longer boiler life and greater system efficiency (see Figure 2).
1D. Variable Water Flow Systems
Heating systems using zone valves, zone pumps or 3-way valves can experience reduced water flow through the boiler. This can result in an excessive water temperature rise and unstable boiler operation. If the system water flow is variable, it must not be allowed to fall below 30% of full flow. The boiler must be equipped with staged or modulated fire with the temperature sensor installed in the outlet water. State variable flow when ordering. Laars recommends primary-secondary pumping for all variable flow systems. Primary-secondary pumping is mandatory for variable flow systems where minimum flows are less than 30% of full flow conditions. The boiler pump in a primary-secondary system maintains constant flow through the boiler even though the system flow is variable. In a primary-secondary system the pressure drop of the boiler is not added to the system (see Figure 2).
A Special Note About 3-Way Water Valves
3-way water valves (2 position or proportional) are sometimes used to divert water around a boiler and control the temperature of water being supplied to the system. Valves installed in this manner must be supplied with an end switch or some other suitable control to shut off the boiler when the flow is reduced to 30%. The boiler must be supplied with staged or modulated fire as indicated in Section 1D, Variable Water Flow Systems.
It is often possible to accomplish excellent water temperature control without 3-way valves through proper application of staged or modulated firing systems. Consult the factory or local Laars representative for assistance with such systems.
System Pressure Requirements
The model HH and PH boilers are designed to operate on closed, pressurized systems. A minimum of 12 psi should be maintained on the system where boiler supply water temperatures are 200°F (93°C) or less. If higher temperatures are required, the minimum system pressure should be at least 15 psi above the water vapor pressure corresponding to the elevated water temperature.
The hydronic boilers are not suitable for open systems unless the supply water temperatures are kept below 180°F (82°C), and minimum of 5 psi static head is maintained within the boiler.
Mighty Therm Hydronic Boiler
Page 5
Figure 2. Typical Schematic for a Primary-Secondary System.
1E. Warning Regarding Chilled
Water Systems
When a boiler is connected to an air conditioning system where the same water is used for heating and cooling, chilled water must be prevented from entering the boiler. When changing such a system from cooling to heating, the chilled water should be allowed to circulate through the building (after the chiller has been turned off) for a period long
Suggested Wiring Diagram For Tempering System Water at Change-over From Heating to Cooling.
Figure 3. Boiler-Chiller Installation.
enough for the water to warm up to at least 70°F (21°C) before the water is allowed to flow into the boiler. It is equally important to prevent hot water from entering the chiller. The system shown in Figure 3 is suggested to make sure that the system water is neither too hot nor too cold when a changeover from heating to cooling, or vice versa, takes place. When a boiler is connected to heating coils located in air handling units (where they may be exposed to refrigerated air circulation), the boiler piping system shall be equipped with a flow control valve or other automatic means to prevent gravity circulation of chilled water through the boiler. Chilled water in the boiler will create condensation on the boiler tubes which will drip on the burners and may extinguish the pilot.
Boilers installed in violation of either of the
above requirements may void the warranty.
1F. Freeze Protection
Boiler installations are not recommended in areas where the danger of freezing exists unless proper precautions are taken for freeze protection. The preferred method of freeze protection is by maintaining a mixture of no more than 50% properly inhibited HVAC glycol. This mixture will protect the boiler to temperatures of about -35°F (-37°C). To get the desired temperature rise across the boiler when this mixture is used, increase the water flow by 15% above the original recommendation. Increase the head loss requirement by 20%.
Page 6
LAARS Heating Systems
SECTION 2. Installation
2A. Boiler Placement
The boiler must be placed to provide specific clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces. These clearances also apply to non-combustible materials, because the boiler requires air circulation for proper operation.
Boiler should be mounted on a level surface. An integral combustible flooring base is provided as standard equipment on all outdoor models. models can be installed on a combustible floor with a special base assembly which is available from the factory, or with a base that complies with local code requirements. See rating plate for part number of the base assembly.
Do not install boiler on carpeting.
Under the National Fuel Gas Code, ANSI Z223.1, it is permissible to place the boiler on floors other than non-combustible when the installation complies with the American Insurance Code. Figures 5, 6, 7, and 8 show common installation on combustible flooring.
Indoor
2B-1. Combustion Air Supply
1. The boiler location must provide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223.1 and/or in Canada CAN 1 - B1 49 requirements, and any local codes that may be applicable. Inadequate combustion air supply may result in incomplete combustion, sooting of the heat exchanger, and unsafe operation of the boiler.
2. (a.) In the United States, the general requirements specify that boiler rooms should be provided with two permanent air supply openings communicating
directly through the wall to outside air; one within 12 inches (305mm) of the ceiling, and the other within 12 inches (305mm) of the floor. Each opening should have a minimum free area of one square inch per 4,000 BTUH input of the total input rating of all appliances in the enclosed area. See Table 3 for recommended air supply for each model. An improperly ventilated equipment room can get excessively hot and cause accelerated deterioration of controls and electrical components.
2B. Installation of Indoor Boilers
1. Locate the boiler to provide adequate clearance for inspection and service on all sides (see Table 2). from front (for proper access to and service of controls) and 18" at water connection end. For alcove installation, see Figure 9.
Clearance Indoor Outdoor From inches mm inches mm
Top 30 762 unobstruct Water Conn. Side 12 305 24 610 Opposite Side 6 152 24 610 Front Alcove Unobstruct Rear 8 203 24 610 Vent Pipe* 6 152 Hot Water Pipes Per Code Per Code
*1" when using type B Vent (refer to Manufacturer's Instructions
Table 2. Minimum Boiler Clearances
2. Install the boiler on a waterproof floor with an adequate floor drain and a 6" (152mm) minimum curb on all four sides to protect the building if boiler repairs are required. The
manufacturer will not be held liable for any water damage in connection with this boiler.
We recommend minimums of 24"
From Combustible Surfaces.
Boiler Each Opening*
Model Sq. Inches Sq. cm
500 125 806.5 600 150 967.8 715 179 1154.9
850 213 1374.3 1010 253 1632.4 1200 300 1935.6 1430 358 2309.8 1670 418 2696.9 1825 457 2948.6
*Net Free Area in Square Inches
Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area could be double the figures indicated. For special conditions refer to the latest edition of ANSI Z223.1.
Consult factory if not communicating directly through the walls with the outdoors.
Note: Check with louver manufacturers for net free area of louvers. Correct for screen resistance to the net free area if a screen is installed. Check all local codes applicable to combustion air.
Table 3. Minimum Recommended
Air Supply to Boiler.
Mighty Therm Hydronic Boiler
Figure 4. Base for Combustible Floors.
Page 7
Figure 7. Typical Boiler Installation on Roof Using a
4 x 4 Stringer.
Figure 5. Typical Boiler Installation on Concrete Slab.
Figure 6. Typical Boiler Installation on Raised Platform
(Wood).
Figure 8. Installation on Concrete Blocks or Tile.
(b.) In Canada, consult local building and safety codes or, in the absence of such requirements, follow CGA requirements and/or CAN 1 - B149 standard. (Table 3 does not apply).
3. Exhaust Fans or Vents: Any equipment which exhausts air from the boiler room can deplete the combustion air supply or reverse the natural draft action of the venting system.
The boiler must be completely isolated and this could cause flue products to accumulate in the room. Additional air must be supplied to compensate for such exhaust. The information in Table 3 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
Page 8
Figure 9. Alcove Installation.
4. If a blower or fan is used to supply air to the heater room, the installer should make sure it does not create drafts which could cause nuisance shutdowns of the pilot. If a blower is necessary to provide adequate combustion air to the boiler, a suitable switch or equivalent must be wired into the boiler control circuit to prevent the boiler from firing unless the blower is operating.
5. The boiler must be completely isolated and protected from any source of corrosive chemical fumes such as trichlorethylene, perchlorethylene, chlorine, etc.
2B-2. Venting
1. Laars boilers have built-in draft diverters for natural draft operation and must not be connected to any portion of a mechanical draft system under positive pressure. The flue outlet must be connected to a clear, unobstructed vent of adequate capacity ending above the highest point of the building with an approved vent cap. The venting system should be installed according to the latest edition of ANSI Z223.1 and/or, in Canada, CAN1-13149 requirement and any local codes having jurisdiction.
IMPORTANT NOTE: Do not use sheet metal screws at the snap lock joints of Type B gas vents.
LAARS Heating Systems
2. Do not weld or fasten the vent pipe to the boiler draft hood. The weight of the stack must not rest on the boiler.
The draft hood and boiler top must be easily removable for normal boiler service and inspection.
3. Avoid using long horizontal runs of the vent pipe, and too many 90° elbows, reductions or restrictions. Horizontal runs should have at least a 1/4" rise per foot in the direction of flow. A vent connector should be supported for the design and weight of the material used to maintain clearances and prevent physical damage and separation of joints.
4. Avoid ending heater vents near air conditioning or air supply fans. The fans can pick up exhaust flue products from the boiler and return them inside the building, creating a possible health hazard. A minimum of 4 feet (1.2m) horizontal distance must be maintained from electrical meters, gas meters, and relief equipment.
5. Always use double-wall or insulated vent pipe (Type B or equivalent). In cold weather, uninsulated outside vents can chill the rising flue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling flue products into the boiler room.
6. Avoid oversize vent piping or extremely long runs of the pipe which may cause excessive cooling and condensation. Rule of Thumb: The total length of the vent, including the connector and any offset, should not exceed 15 feet (4.6m) for every inch of vent diameter. Longer total lengths shown in venting tables are based on maximum capacity, not condensation factors.
7. When the installation of a draft fan is necessary in connecting a venting system to a Laars boiler, the installation should be engineered by competent personnel following good engineering practices. The draft fan supplier should be consulted for correct size. The installation should be in accordance with the latest edition of ANSI Z223.1 and/or, in Canada, CAN 1-B149 requirement and any local codes having jurisdiction. When a draft fan is installed, a suitable draft switch must be wired into the boiler control circuit at terminal designated “Field Interlock” to prevent firing of the boiler unless a positive draft has been established.
8. When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the
Mighty Therm Hydronic Boiler
Page 9
other appliances remaining connected to the common venting system are not in operation.
(a) Seal any unused openings in the common
venting system.
(b) Visually inspect the venting system for
proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building
doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
(d) Place in operation the appliance being
inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
(e) Test for spillage at the draft hood relief open-
ing after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each
appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gasburning appliance to their previous conditions of use.
(g) Any improper operation of the common
venting system should be corrected so the installation conforms with the latest edition of the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223. 1.
2C. Installation of Outdoor Boilers
1. Locate the boiler to provide the minimum clearances as listed in Table 2, “Boiler Clearances.”
2. Do not place the boiler in an enclosure or wall recess. Avoid locations where wind deflection
See Service Clearance, 2 B.1.
off structures might cause a down draft. When such wind conditions are possible, place the boiler at least three (3) feet (0.9m) from the structures.
3. Never install the boiler under any kind of roof overhang. Do not place the boiler below or adjacent to any doors, windows, louvers, grills, etc. which connect in any way with an inhabited area of a building. This includes other structures such as garages or utility rooms (see Figure 10).
Figure 10. Incorrect Outdoor Installation.
4. Although these models are AGA designed certified for outdoor installations, such installations are not recommended in areas where the danger of freezing exists unless proper precautions are taken for freeze protection.
Caution
Outdoor installations are not recommended
in areas where the danger of
snow blockage exists.
2D. Gas Supply and Piping
Review the following instructions before
proceeding with the installation.
1. Verify that the boiler is fitted for the proper type of gas by checking the rating plate. Laars boilers are normally equipped to operate below a 2000 foot (610m) altitude. Boilers equipped to operate at higher altitudes have appropriate stickers or tags attached.
2. Use the figures in Table 4 to provide adequate gas piping from the gas meter to the boiler.
3. A trap (drip leg) must be provided ahead of the gas controls (see Figure 11). A manual gas
Loading...
+ 19 hidden pages