LAARS MAX 165 User Manual

Installation, Operation and Maintenance Instructions Document 1106D
Installation, Operation and Maintenance Instructions for
MAX
Residential Oil-Fired Boiler
MAX 100 (DV) MAX 120 (DV) MAX 140 (DV) MAX 165 (DV)
FOR YOUR SAFETY : This product must be installed and serviced by a professional service technician, qualified in boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
W ARNING
If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer , service agency , or fuel oil supplier.
READ AND SAVE THESE INSTRUCTIONS FOR REFERENCE
70-196D
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction...................................................3
SECTION 2. Technical Specifications
2A. Boiler Outputs ............................................... 5
SECTION 3. Installation
3A. Freight Claims............................................... 6
3B. Regulations ...................................................6
3C. Sizing the System ......................................... 6
3D. Location ........................................................6
3E. Clearance ..................................................... 6
3F. Combustion Air (other than direct vent) ......... 6
3G. Ventilation Air (conventional chimney
and direct vent) ............................................. 7
3H. Chimney Connection ..................................... 7
3I. Direct Vent Balanced Flue System................ 8
3J. Installation of Balanced Flue System ............ 9
3K. Boiler Piping..................................................9
3L. Freeze Protection ......................................... 9
3M. Indirect Hot Water Tank.............................. 10
3N. Burner Controls ........................................... 10
3O. Fuel System................................................ 10
3P. Gravity Head System .................................. 10
3Q. Suction Lift System ..................................... 10
3R. Oil Filter ...................................................... 10
3S. Wiring .........................................................10
SECTION 4. Operation
4A. Preliminary Burner Settings......................... 19
4B. Burner Adjustments..................................... 19
4C. Sequence of Operation ............................... 19
SECTION 5. Maintenance and Service
5A. Boiler .......................................................... 22
5B. Oil Burners.................................................. 22
5C. Oil Filter ...................................................... 22
5D. Cold Oil ....................................................... 22
SECTION 6. Homeowner Information
6A. Living With Your Boiler ................................ 22
6B. General Information .................................... 23
SECTION 7. Part Numbers
................................................................... 23
MAX Oil-Fired Boiler
SECTION 1. General Information
1A. Introduction
The MAX Boiler has been constructed to meet the stringent requirements of the ASME Boiler Codes and designed to provide a rapid response to hot water and heating demands at a very high thermal efficiency.
This is a low mass boiler. To take advantage of this feature, and prevent short cycling, always select the lowest firing rate satisfactory for the load requirement.
The boiler is supplied either for connection to a conventional chimney or comes complete with a balanced flue system for direct venting through the wall.
With the balanced flue system, air for combustion is drawn from outside through a terminal and ducted directly to the burner, making the boiler virtually room sealed. Flue gases are discharged through the same terminal so that wind pressures are applied equally to inlet and outlet, making it a true balanced flue system. A silencer is also incorporated in the terminal to reduce the flue gas discharge noise. This is a particularly useful feature if the terminal is located near a bedroom window or adjacent to neighboring properties.
The boiler is constructed with two concentric water jackets, the inner one forming the furnace tube and the outer the flue gas annulus. Flue gas retarders fitted around the annulus are specifically designed to extract the maximum heat from the gases with minimum pressure loss.
Page 3
The simple annular design also makes it possible to keep the water content to a minimum (only 3.2 gals. [12L] for the MAX (DV) 75, 100, 120 and 5.1 gals. [19L] for the MAX (DV) 140, 165). Because of this low mass, water is rapidly heated to the temperature demands. Another benefit of the low thermal mass is the insignificant level of standby loss when the burner shuts down.
To achieve the best possible heat transfer, the boiler is designed on the “Series Flow” principle whereby the return water is preheated by first passing through the outer water annulus before coming into contact with the furnace tube. This arrangement also provides a counter flow of flue gases and water so that the coolest gases come into contact with the coolest water for the most efficient heat transfer.
Heavily insulated doors at front and back of boiler, provide easy access for cleaning and inspection, with the burner being swung on the front door either left or right as required.
Accurate sensing of temperature and pressure is assured by grouping all controls and safety devices on a common supply manifold.
The use of the latest flame retention head burner allows the boiler to operate under a slight positive pressure which ensures stable combustion under virtually all operating conditions.
MAX (DV) GPH Nozzle Pump Input AFUE Heating Water Shipping
Model Rate Size Pressure MBTH/hr Rating Capacity Content Weight
75 0.72 0.65 140 101 87.0 85,900 3.0 12 324 147 100 1.00 0.85 140 140 86.5 121,200 3.2 12 324 147 120 1.20 1.00 140 168 86.0 141,600 3.2 12 324 147 140 1.40 1.20 150 196 85.6 166,000 5.1 19 431 196 165 1.65 1.35 150 231 85.0 192,400 5.1 19 431 196
GPH P.S.I. % BTU/h gal. L lbs. kg
Table 1. Boiler Specifications.
Page 4
LAARS Heating Systems
(127mm)
Side Front
Figure 1. Boiler Dimensions (refer to Table 2).
Table 2. Boiler Dimensions.
MAX Oil-Fired Boiler
Page 5
Auto Air Vent
Honeywell L4006E High Limit Aquastat (Manual Reset)
1¼" Supply
¾" Relief Valve
Honeywell L8148 Aquastat
Temperature / Pressure Gauge
1¼" Return
Flue Gas Sampling Plug
Figure 2. Controls Layout.
SECTION 2. Technical Specifications
2A. Boiler Outputs
Boiler constructed and hydrostatically tested in
accordance with ASME Boiler code Section IV.
Beckett / Carlin / Riello (model varies) Oil Burner complete with flame retention head, Honeywell control and cad. cell. or equivalent
(A post purge timer and oil solenoid valve is fitted to direct vent burners)
Honeywell L8148A Aquastat Relay.
Honeywell L4006E High Limit Aquastat (manual reset - direct vent boilers only)
Temperature and pressure gauge.
Pressure relief valve 3/4"
Automatic air vent
Air eliminator built into supply manifold
Boiler drain valve 1/2"
2500-004: 15-foot vent kit contains 15-feet of 5" stainless steel pipe (for vent) and 15-feet of 4" aluminum (for ducted air), with clamps, adapters, heatshield and silicone.
2500-009: Direct vent terminal (Univent terminal) to be used with either 10-foot or 15­foot vent kits, for all MAX DV boiler sizes.
In addition, the following vent terminal extensions
can be used to bring the terminal above grade level to meet code requirements:
2500-010: Vent terminal extension for 75, 100 and 120
2500-011: Vent terminal extension for 140 and 165
Balanced Flue System Kits (direct vent boilers only)
For direct venting, vent pipe kits and vent
terminals are available.
2500-002: 10-foot vent kit contains 10-feet of 5" stainless steel pipe (for vent) and 10-feet of 4" aluminum (for ducted air), with clamps, adapters, heatshield and silicone.
Page 6
LAARS Heating Systems
SECTION 3. Installation
3A. Freight Claims
The boiler and it's components should be inspected for damage upon arrival and any claim filed immediately against the carrier by the consignee. The carrier is responsible for taking prompt action on all claims.
3B. Regulations
THE BOILER INSTALLATION MUST BE CARRIED OUT BY A QUALIFIED INSTALLER IN ACCORDANCE WITH THE REGULATIONS OF AUTHORITIES HAVING JURISDICTION AND CSA STANDARD B139 or ANSI / NFPA 31
Installation of Oil Burning Equipment - latest edition, the
National Electrical Code ANSI / NFPA 70 - latest edition and local codes and authorities having jurisdiction. Such applicable requirements take precedence over the general requirements contained herein.
The installer must also be properly licensed and
experienced in all the codes and ordinances.
WARNING
In the interest of safety, gasoline or other flammable fluids or vapors must not be stored or used in the vicinity of the boiler.
3C. Sizing the System
Over sizing the boiler will cause short cycling and reduce its operational efficiency, so it is recommended that a building heat loss calculation is made to ensure that the correct size boiler is used (see Table 1).
3D. Location
The boiler should be mounted on a solid level floor and located as close as possible to the chimney or the position chosen for the direct vent terminal. The boiler can be mounted on a combustible floor due to its wet base construction, however, a check should be made to ensure the floor is capable of supporting the installed weight of the boiler including its water content.
A closet may be used to enclose the boiler, providing the enclosure is properly vented to ensure the controls do not become overheated (see Ventilation Air section). The boiler must also have the correct amount of air available for combustion when using a conventional chimney (see Combustion Air section).
When installed, necessary use metal shims under the base to level the
the boiler must be level. If
unit particularly front to back otherwise air could be trapped inside the boiler.
3E. Clearance
Adequate clearance should be allowed around the boiler for cleaning and servicing. The following minimum clearances are recommended:
Front - 24" (610mm) (for hinging door) Rear - 6" (152mm) Sides - 6" (152mm)
Clearance from combustible materials should be in accordance with local and national codes. Guidance is given in the National Fire Protection Bulletin NFPA, Installation of Oil Burning Equipment. All other applicable codes should also be followed.
3F. Combustion Air
(other than direct vent)
WARNING
As an additional measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.
AVERTISSEMENT
Laars recommande fortement, comme mesure de sécurité supplémentaire, l'installation de détecteurs de monoxyde de carbone adaptés dans le voisinage de l'appareil et dans chacune des pièces habitées adjacentes.
Chimney Vent: For boilers installed in basements, infiltration may be adequate to provide combustion air. For buildings of exceptionally tight construction, the boiler must be installed in an unconfined space, or in an area which directly communicates with an unconfined space. An unconfined space is a space whose volume is 50 cubic ft. (1.4m3) or more per 1,000 BTU (293kW) of the aggregate input of all appliances in that space. Two openings to the space, one 6" (152mm) from the floor and one 6" (152mm) from the ceiling of the enclosure must be provided. Each opening must have at least 168 square inches (1084 sq.cm) of free area.
Chimney Vent with outside air duct connected directly to burner: In an installation of exceptionally tight construction, intake air may be ducted directly to the burner from the outdoors. On an AF2 burner remove the black air intake shroud to connect the 4" (102mm) aluminium duct (up to 15 equivalent ft. [4.6m] maximum). Terminate the duct on the outside of the building with a suitable protective cover. This cover must be located at least 16" (406mm) above grade or above an anticipated snow line.
MAX Oil-Fired Boiler
Page 7
On Carlin EZ-1 burners install model # 97406
combustion air intake system.
3G. Ventilation Air
(conventional chimney and direct vent)
Where the boiler is installed in a basement there is normally sufficient air infiltration to provide adequate ventilation.
Where the boiler is installed in a closet or otherwise confined space ventilation must be provided to keep the controls from overheating. This is accomplished by providing two openings to the space, one 6" (152mm) from the floor and one 6" (152mm) from the ceiling.
3H. Chimney Connection
Caution
An oil-fired unit shall be connected to a vent having sufficient draft at all times to ensure sfe and proper operation of the unit.
The chimney must be inspected and thoroughly cleaned before connecting boiler. Most local codes require the chimney to be lined when using an oil fired boiler in order to protect the bricks and mortar from the
condensation produced by modern high efficient boilers.
The chimney must terminate at least 3 ft. (0.9m) above the point where it passes through the roof and be in a position free from down draft.
The boiler should be connected to the chimney with the shortest possible run of 5 in. flue pipe and be located above the chimney base to allow a drop leg for scale accumulation to avoid blocking flue pipe entrance.
Horizontal runs should be pitched up towards chimney at approximately 1/4 inch per foot.
Install balanced damper on chimneys higher than 20 feet (6.1m).
Install "Blocked Vent Switch" provided in accordance with attached instructions. Follow all Warnings, Cautions and Maintenance Instructions for safe, trouble free operation.
IMPORTANT: Max 75-140 may condense when vented into an outside chimney. To minimize potential for condensing, install either thermostatic union or recirc bypass, shown in Figures 12 and 13.
As the boiler and flue pipe are under slight positive pressure on start-up, it is necessary to seal all pipe joints with high temperature tape or silicone sealant to avoid any flue gas leakage into room.
5" diameter flue pipe ­secure both ends of pipe with clamps and seal with silicone
Oil Burner
Burner Intake Air & Adaptor
Balanced Flue T erminal
10" max.
Flange Fix to Wall
Ð
Ï
6½"
Gas Flue Discharge
Air Intake Screen
4" pipe adapter
4" diameter air pipe - secure both ends with clamps
Figure 3. Direct Vent Balanced Flue System.
Page 8
³
Minimum 1.5
(0.5)
LAARS Heating Systems
3
³
4
(1.2)
(0.9)
³
³
7
(2.1)
Figure 4. Terminal Locations - Minimum Distances.
1
(0.3)
3I. Direct Vent Balanced Flue System
With this system flue gases are vented directly through the wall and fresh air for combustion is drawn in through the same terminal, thus ensuring wind pressures are equal to the intake and flue gas discharge to create a balanced flue condition.
The terminal also incorporates a silencer to reduce the flue gas discharge noise and a specially designed end cap which throws the flue gases clear of the wall to avoid surface discoloration.
NOTE: If the burner is not correctly adjusted it is possible that surface discoloration may occur. Laars will not accept any responsibility for such discoloration.
The position chosen for the Balanced Flue Terminal must conform to the following guidelines:
1. The terminal shall not be less than 3 ft. (0.9m)
above or 10 ft. (3m) horizontally from any forced
air inlet into the building.
1.5
(0.5)
1
(0.3)
Gravity Air Inlet
1 (0.3)
4
(1.2)
3
(0.9)
Forced Air Inlet
Dimensions shown in feet (m).
2. The terminal shall not be less than 4 ft. (1.2m) below, 4 ft. (1.2m) horizontally or 1 ft. (0.3m) above any door, window, or gravity air inlet into the building.
3. The terminal shall not be less than 3 ft. (0.9m) from an inside corner of an L shaped building.
4. The terminal shall not be less than 7 ft. (2.1m) above grade when located adjacent to public walkways.
5. The terminal shall not be less than 2 ft. (0.6m) from an adjacent building.
6. IMPORTANT: The terminal shall be located at a height not liable to blockage from leaves, snow or other debris,
at least one foot (0.3m) above
grade level.
7. The terminal shall be positioned so that flue gases are not directed where they can jeopardize people, overheat combustible structures, or enter buildings.
Loading...
+ 16 hidden pages