Kohler RXT Operation And Installation

Operation and
Installation
Automatic Transfer Switch
Model:
RXT
100--400 Amp Automatic Transfer Switches
For use with Kohlerr Model RESA, RESAL, or RCL generator sets
equipped with RDC2 or DC2 generator/transfer switch controllers
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Transfer Switch Identification Numbers
Record the product identification numbers from the transfer switch nameplate.
Model Designation
Serial Number
TP-6807 12/112
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 5........................................................
Introduction 7...............................................................................
Nameplate 8.................................................................
Model Designation 8..........................................................
Service Assistance 9........................................................................
Section 1 Description 11.....................................................................
1.1 Transfer Switch Description 11.............................................
1.2 Service Entrance Models 11...............................................
1.3 Load Centers 11.........................................................
1.4 Controller Interface Board 12..............................................
1.5 Optional LED Indicator Panel 12...........................................
Section 2 Installation 13......................................................................
2.1 Introduction 13..........................................................
2.2 Receipt of Unit 13........................................................
2.2.1 Inspection 13....................................................
2.2.2 Storage 13......................................................
2.2.3 Unpacking 13....................................................
2.2.4 Lifting 13........................................................
2.3 Installation 14...........................................................
2.4 Manual Operation Check 15...............................................
2.4.1 Manual Operation Procedure 1 15..................................
2.4.2 Manual Operation Procedure 2 15..................................
2.5 Electrical Wiring 16.......................................................
2.5.1 Load Center Circuit Breakers 16...................................
2.5.2 AC Power Connections 17........................................
2.5.3 Neutral Connection 18............................................
2.5.4 Neutral Bonding Jumper, Service Entrance Models 18................
2.5.5 Engine Start Function 18..........................................
2.5.6 Interface Module Connection 19....................................
2.5.7 Optional Load Control Connection 20...............................
2.5.8 Accessory Module Connections 20.................................
2.6 Test and Exercise 20.....................................................
2.7 Warranty Registration 20..................................................
Section 3 Operation 21.......................................................................
3.1 Model RXT Transfer Switch Operation 21...................................
3.2 Source Availability 21.....................................................
3.3 ATS Control Sequence of Operation 21.....................................
3.4 Time Delays 22..........................................................
3.5 Load Control Time Delay 22...............................................
Section 4 Service Disconnect, SE Model 23....................................................
4.1 Service Disconnect Procedure 23..........................................
4.2 Source Circuit Breaker Reset 23...........................................
Section 5 Scheduled Maintenance 25..........................................................
5.1 Introduction 25..........................................................
5.2 Testing 26..............................................................
5.2.1 Weekly Generator Set Exercise 26.................................
5.2.2 Monthly Automatic Control System Test 26..........................
TP-6807 12/11 Table of Contents 3
Table of Contents, continued
5.3 Inspection and Service 26.................................................
5.3.1 General Inspection 26............................................
5.3.2 Other Inspections and Service 27..................................
5.4 Service Schedule 27.....................................................
Section 6 Diagrams and Drawings 29..........................................................
Appendix A Abbreviations 55..................................................................
TP-6807 12/11Table of Contents4
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
DANGER
Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To
prevent electrical shock deenergize the normal power source before making any line or auxiliary connections.
TP-6807 12/11 5Safety Precautions and Instructions
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergizeall
power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.
Notice
NOTICE
Foreign material contamination.
Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. After installation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
NOTICE
Electrostatic discharge damage.
Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short,to ground.
TP-6807 12/116 Safety Precautions and Instructions
This manual provides operation and installation instructions for Kohlerr Model RXT automatic transfer switches. See Figure 1 for typical Model RXT transfer switches.
Model RXT transfer switches operate only with Kohlerr Model generator sets equipped with the RDC2 or DC2 generator/transfer switch controller. See Figure 2 for controller identification. The following Kohlerr model generator sets can be used with the Model RXT transfer switch:
D 14RESA
D 14RESAL
D 20RESA
D 20RESAL
D 48RCL
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this literature and the products represented without notice and without any obligation or liability whatsoever.
Introduction
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.
Figure 1 Typical Model RXT Transfer Switches
(shown with optional status indicators)
RDC2 DC2
GM77569
Figure 2 RDC2 and DC2 Generator/Transfer Switch
Controllers (provided with and mounted on the generator set)
TP-6807 12/11 7Introduction
Nameplate
n
A nameplate attached to the inside of the enclosure cover or on the upper right side wall includes a model designation, a serial number, ratings, and other information about the transfer switch. See Figure 3.
Check the transfer switch model number from the transfer switch nameplate and verify that it matches the model shown on the front cover of this manual before proceeding with installation.
TRANSFER SWITCH
FOR EMERGENCY SYSTEMS
VOLTS PHASE HERTZ
TYPE ENCLOSURE
MFG. DATE
ACCESSORIES:
1
MATERIAL MODEL
2
SERIAL NO.
AMPS WIRES POLES
BAR CODE
3
Copy the model designation, serial number, and accessory information from the nameplate to the spaces provided in the Product Identification Information section located inside the front cover of this manual for use when requesting service or parts.
1. Model designation
2. Serial number
3. Factory-installed accessory numbers
LISTED
R
TRANSFER SWITCH
FOR EMERGENCY SYSTEMS
GM21291-E
Figure 3 Typical Transfer Switch Nameplate
Model Designation
Figure 4 explains the model designation.
Model Controls Voltage Poles Enclosure Current Rating Connections
Record the transfer switch model designation in the boxes. The transfer switch model designation defines ratings a characteristics as explained below.
Sample Model Designation: RXT-JFNC-0200A
Model
RXT: Kohler Automatic Transfer Switch
Controls
J: Interface for RDC2/DC2 Controller
Voltage/Frequency
C: 208 Volts/60 Hz (3-phase only) F: 240 Volts/60 Hz M: 480 Volts/60 Hz (3-phase only)
Number of Poles/Wires
N: 2-pole, 3-wire, solid neutral (120/240 V only) T: 3-pole, 4-wire, solid neutral V: 4-pole, 4-wire, switched neutral
Enclosure
C: NEMA 3R
Current Rating: Numbers indicate the current rating of the switch in amperes:
0100 0200 0400
Connections
A: No load center B: With load center (100 amp single-phase only) ASE: Service entrance rated
Figure 4 Model Designation
TP-6807 12/118 Introduction
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone: (33) 1 49 178300 Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6807 12/11 9Service Assistance
Notes
TP-6807 12/1110 Service Assistance
Section 1 Description
1.1 Transfer Switch Description
An automatic transfer switch (ATS) transfers electrical loads from a normal source of electrical power to an emergency source when the normal source voltage or frequency falls below an acceptable level. The normal source is typically utility power. The emergency source is usually a generator set.
Model RXT transfer switches must be connected to a generator set equipped with the Kohlerr RDC2 or DC2 generator/transfer switch controller. Applicable generator set models are listed in the Introduction.
Voltage sensing data from the ATS is continuously transmitted to the RDC2/DC2 controller mounted on the generator set. When the normal source fails, the RDC2/DC2 controller signals the emergency source generator set to start. When the emergency source reaches acceptable levels and stabilizes, the ATS transfers the electrical load to the emergency source.
The RDC2/DC2 controller signals the ATS to transfer the load back when the normal source returns and stabilizes.
Service Entrance Model
Figure 1-1 shows a typical installation block diagram.
Emergency (Generator)
Normal (Utility)
Power Switching Device
Power
Power
Automatic T ransfer Switch
To Load
Generator
Electrical
Controls
Interface
Board
TP-6751
Figure 1-1 Typical ATS Block Diagram
Load Center Model Standard Model
Figure 1-2 Selected Transfer Switches
(covers removed)
1.2 Service Entrance Models
Service entrance models use a circuit breaker to provide the service disconnect for the utility source. A service entrance model is shown in Figure 1-2.
1.3 Load Centers
Model RXT 100 amp transfer switches are available with a built-in load center. A model with a built-in load center is shown in Figure 1-2. Models without load centers require the installation of a separate load panel.
TP-6807 12/11 11Section 1 Description
Loads. The transfer switch can be connected to supply all of the electrical loads in the home, or only the essential loads such as the furnace, refrigerator, well pump, and selected light circuits. Identify the essential circuits that must be supplied during a power outage. Verify that the generator set and transfer switch are adequately rated to supply all of the selected loads.
Circuit breakers. Because the size and number of circuit breakers required will vary with each application, circuit breakers are not provided with the transfer switch load center.
Determine the circuits that will be connected to the transfer switch (essential loads). Identify the breakers for those circuits in the main distribution panel.
The ATS load center requires Square D type QO breakers. If the main distribution panel uses the same type of breakers, the breakers can be moved from the main panel to the load center. Otherwise, obtain new Square D type QO circuit breakers. For each circuit, the rating of the load center circuit breaker must match the rating of the existing breaker in the main panel.
1.5 Optional LED Indicator Panel
A user interface panel that contains status-indicating LEDs is available. See Figure 1-3. Source available LEDs light to indicate that the utility and/or generator sources are available. The utility or generator source supplying load LED lights to show which source is connected to the building load (i.e. contactor position, normal or emergency).
If the status indicator is purchased as a loose kit (not factory-installed), refer to the installation instructions provided with the kit, TT-1585.
1
2
Up to 8 tandem breakers can be used. Use Square D type QOT tandem breakers.
Verify that the total rating for all of the breakers used in the load center does not exceed the rating of the transfer switch.
1.4 Controller Interface Board
All ATS control functions are performed by the RDC2/DC2 controller mounted on the generator set and communicated through the interface board. The controller interface board sends voltage sensing data to the RDC2/DC2 controller and receives transfer and load control signals from the RDC2/DC2 controller.
3
4
1. Utility power available
2. Utility source supplying load
3. Generator source supplying load
4. Generator power available
Figure 1-3 LED Indicators
GM78649
TP-6807 12/1112 Section 1 Description
Section 2 Installation
2.1 Introduction
Kohlerr transfer switches are shipped factory-wired, factory-tested, and ready for installation. Have the equipment installed only by trained and qualified personnel, and verify that the installation complies with applicable codes and standards. Protect the switch against damage before and during installation.
2.2 Receipt of Unit
2.2.1 Inspection
At the time of delivery, inspect the packaging and the transfer switch for signs of shipping damage. Unpack the transfer switch as soon as possible and inspect the exterior and interior for shipping damage. If damage and/or rough handling is evident, immediately file a damage claim with the transportation company.
2.2.2 Storage
Store the transfer switch in its protective packing until final installation. Protect the transfer switch at all times from moisture, construction grit, and metal chips. Avoid storage in cold or damp areas where moisture could condense on the unit. See Figure 2-1 for acceptable storage temperatures.
Item Specification
Storage Temperature
Operating Temperature
Humidity 5% to 95% noncondensing
Altitude 0 to 3050 m (10000 ft.) without derating
Figure 2-1 Environmental Specifications
2.2.3 Unpacking
Allow the equipment to warm to room temperature for at least 24 hours before unpacking to prevent condensation on the electrical apparatus. Use care when unpacking to avoid damaging transfer switch components. Use a vacuum cleaner or a dry cloth to remove dirt and packing material that may have
-- 4 0 °Cto85°C(--40°F to 185°F)
-- 2 0 °Cto70°C(--4°F to 158°F)
accumulated in the transfer switch or any of its components.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris to lodge in the components and damage the switch.
2.2.4 Lifting
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.
See Figure 2-2 or the dimensional drawing for the weight of the transfer switch. Use a spreader bar to lift the transfer switch. Attach the bar only to the enclosure’s mounting holes or lifting brackets; do not lift the unit any other way. Close and latch the enclosure door before moving the unit.
Amps Description
Single phase 7 (14)
100
200
400
With load center 8.2 (18)
Three phase 14 (30)
Service Entrance 10 (22)
Single phase 7 (15)
Three phase 14 (30)
Service Entrance 12 (26)
Single phase 36 (80)
3-Pole/208--240 Volts 41 (90)
3-Pole/480 Volts 59 (130)
4-Pole 59 (130)
Service Entrance 46 (100)
Figure 2-2 Approximate Weights
Weight, kg (lb.) [
TP-6807 12/11 13Section 2 Installation
2.3 Installation
NOTICE
Foreign material contamination. Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. Afterinstallation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
NOTICE
Hardware damage. The transfer switch may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
Check the system voltage and frequency. Compare the voltage and frequency shown on the transfer switch nameplate to the source voltage and frequency. Do not install the transfer switch if the voltage and frequency are different from the normal (utility) source voltage and frequency or the emergency source voltage and frequency shown on the generator set nameplate.
Plan the installation. Use the dimensions given on the enclosure dimension (ADV) drawings in Section 6. Select a mounting site that complies with local electrical code restrictions for the enclosure type. Mount the transfer switch as close to the load and power sources as possible. Allow adequate space to open the enclosure and service the switch.
Pull the bottom of the panel out and down until the top clears the enclosure. Remove the inner panel to access the transfer switch components.
NEMA 3R enclosures have locking tabs at the bottom of the enclosure and the door. Whilethe enclosure is open, turn the locking tab out so that the door can be locked with a padlock after installation is complete.
Wall mounting. Mount the transfer switch to a wall or other rigid vertical supporting structure. Refer to the dimension drawings in Section 6 for hole locations. Use shims to plumb the enclosure.
Cover or remove the transfer switch’s internal components to protect them from drill chips or debris during installation. Use a vacuum cleaner to remove debris from the enclosure.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris to lodge in the components and cause damage.
Tighten the mounting screws to 2.9 Nm (26 in. lb.) when reinstalling the components.
Clearance holes through the back of each enclosure are provided for mounting. The mounting holes on NEMA 3R enclosures have gaskets to seal out moisture. Use washers with the mounting screws to protect the gaskets.
NEMA 3R enclosures. To remove the enclosure’s front panel, support the panel while removing the screws.
TP-6807 12/1114 Section 2 Installation
2.4 Manual Operation Check
DANGER
CN
3
4
C
NO
NL1
NC
SCN
NL2
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Check the manual operation before energizing the transfer switch. Verify that the contactor operates smoothly without binding. Do not place the transfer switch into service if the contactor does not operate smoothly.
After checking the manual operation, place the contactor in the Normal (utility) position.
See Figure 2-3 to identify the manual operation procedure for your transfer switch.
ATS Procedure Figure
100--200 amps, 1-phase 2.4.1 Figure 2-4
100--200 amps, 3-phase 2.4.2 Figure 2-6
400 amps, 1-phase 2.4.1 Figure 2-5
400 amps, 3-phase, 3-pole, 208--240 Volts
400 amps, 3-phase, 3-pole/480 Volt and 4-pole
2.4.1 Figure 2-5
2.4.2 Figure 2-7
Figure 2-3 Manual Operation Procedure Guide
2.4.1 Manual Operation Procedure 1
Note: Never manually operate the transfer switch when
the power is connected. Disconnect both power sources before manually operating the switch.
1. 100-200 amp switches: These switches have an attached handle as shown in Figure 2-4. 400 amp switches: Slide the detachable handle or a wrench over the shaft. See Figure 2-5.
2. Move the handle up to place the transfer switch in the Normal Source position or down to place the contactor in the Emergency Source position. See Figure 2-4 or Figure 2-5.
3. 400 amp switches: Remove the detachable handle or wrench.
SCE
NC
NO
C
7
8
CE
EL2EL1
1
1. Handle (not detachable)
Figure 2-4 Manual Operation, 100 and 200 Amp
Single-Phase Switches
1
GM80139
1. Shaft (attach handle or wrench here)
Figure 2-5 Manual Operation, 400 Amp Single-
Phase and 208--240 Volt Switches
2.4.2 Manual Operation Procedure 2
Note: Never use the maintenance handle to transfer the
load with the power connected. Disconnect both power sources before manually operating the switch.
1. If the transfer switch is equipped with a maintenance handle, remove the handle from its storage location inside the enclosure. See Figure 2-7.
TP-6807 12/11 15Section 2 Installation
2. Insert the maintenance handle or a tool (such as a screwdriver) into the hole in the shaft on the left side of the operator as shown in Figure 2-6 or Figure 2-7.
3. Move the maintenance handle (or tool) up or down as shown to manually operate the transfer switch. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
2.5 Electrical Wiring
Refer to the connection diagrams on the transfer switch enclosure door and the wiring diagrams in Section 6 during installation.
All wiring must comply with applicable national, state, and local electrical codes. Use separate conduit for AC power wiring and low-voltage DC, control, and communication system wiring.
4. Return the transfer switch to the Normal position.
5. Remove the maintenance handle and return it to the storage location.
1
GM78867
1. Insert handle or tool here for manual operation
Figure 2-6 Manual Operation, 100--200 Amp
3-Phase Switches
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To prevent electrical
shock deenergize the normal power source before making any line or auxiliary connections.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
2.5.1 Load Center Circuit Breakers
1
2
1. Handle storage location
2. Insert handle here for manual operation
Figure 2-7 Manual Operation, 400 Amp 3-Phase
Switches
The 100 amp Model RXT transfer switch is available with a built-in load center with room for up to 16 single-pole circuit breakers. Up to 8 tandem breakers can be used for a maximum of 24 circuits.
The load center uses Square D type QO or QOT tandem breakers. In an essential load application, the breakers can be moved from the main panel to the load center if the main distribution panel uses the same type of breakers. Otherwise, obtain and install new Square D type QO circuit breakers. The rating of the load center circuit breaker must match the rating of the existing breaker in the main panel for each circuit. If circuit breakers are removed from the load panel, install cover plates over the vacant positions. Cover plates can be obtained from a local Square D supplier.
tp6225
Verifythat the total rating for all breakers used in the load center does not exceed the rating of the transfer switch.
TP-6807 12/1116 Section 2 Installation
2.5.2 AC Power Connections
Determine the cable size. Refer to Figure 2-8 or the ADV drawings in Section 6 to determine the cable size required for the transfer switch. Make sure the lugs provided are suitable for use with the cables being installed.
Conduit. Use separate conduit for AC power wiring and low-voltage DC, control, and communication system wiring. Watertight conduit hubs may be required for outdoor use.
Select the proper cable clamp or use other approved methods for securing the cable or conduit to the enclosure.
Source and load connections. Clean cables with a wire brush to remove surface oxides before connecting them to the terminals. Apply joint compound to the connections of any aluminum conductors.
Refer to the connection diagrams on the transfer switch enclosure door and the wiring diagrams in Section 6. The connection points on the transfer switch contactor are labelled Normal, Emergency, and Load. Connect the utility power to Normal. Connect the generator set to Emergency.
Single phase. For single-phase models, connect to A and C.
Three phase. For three-phase models, be sure to follow the phase markings (A, B, C, and N).
Note: Connect the source and load phases as indicated
by the markings and drawings to prevent short circuits and to prevent phase-sensitive devices from malfunctioning or operating in reverse.
Service entrance models. Connect the utility source to the lugs on the normal source disconnect circuit breakers as shown in the service entrance switch wiring diagram in Section 6.
Verify that all connections are consistent with drawings before tightening the lugs. Tighten all cable lug connections to the torque values shown on the label on the switch. Carefully wipe off any excess joint compound after tightening the terminal lugs.
On models with built-in load centers, the load lugs are factory-wired to the load center. Connect the load leads to the circuits in the load center and tighten the connections. Check the labels on the breakers for the tightening torques.
TP-6807 12/11 17Section 2 Installation
2.5.3 Neutral Connection
2.5.5 Engine Start Function
Connect the neutral from the main panel to the neutral lug in the ATS enclosure.
Ground the system according to NEC and local codes.
2.5.4 Neutral Bonding Jumper, Service Entrance Models
The transfer switch is shipped with the neutral-to-ground jumper installed. For non-service entrance applications, disconnect the neutral-to-ground bonding jumper. See the transfer switch dimension drawing.
Cable Sizes
AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections
Switch
Size,
Amps
100
200
400
Figure 2-8 Cable Sizes
Switch Phases Normal and Emergency Load Neutral Ground
Standard 1 (1) #14 -- 1/0 AWG (1)#14–1/0AWG (3)#12–1/0AWG (9)#4–14AWG
With load
center
Service
Entrance
3-Phase 3 (1)#8–3/0AWG (1)#8–3/0AWG (3)#6AWG–3/0AWG (3)#6–3/0AWG
Standard 1 (1) #6 AWG – 250 MCM (1) #6 AWG – 250 MCM (3) #6 AWG – 250 MCM (9)#4–14AWG
Service
Entrance
3-Phase 3 (1) #6 AWG – 250 MCM (1) #6 AWG – 250 MCM
Standard 1 (2) #6 – 250 MCM (2) #6 – 250 MCM
Service
Entrance
3-pole
208-240 V
3 or 4 pole
480 V
1 (1)#14–1/0AWG
Normal: (1) #12 – 2/0
1
1
1
3 (2) #6 – 250 MCM (2) #6 – 250 MCM
3
AWG
Emerg: (1) #6 – 250
MCM
Normal: (1) #4 – 300
MCM
Emerg: (1) #6 -- 250
MCM
Normal: (2) 3/0 – 250
MCM
Emerg: (2) #6 -- 250
MCM
(1) #4 – 600 MCM (2) #6 – 250 MCM
(1) #6 AWG – 250 MCM (3) #6 AWG – 250 MCM (3)#14–1/0AWG
The engine start function is controlled by the RDC2/DC2 controller on the generator set. There are no engine start terminals on the Model RXT ATS.
Range of Wire Sizes, Cu/Al
per customer-supplied
circuit breaker
(1) #6 – 250 MCM (3) #6 – 250 MCM (3)#14–1/0AWG
(2) #6 – 250 MCM
(1) #4 – 600 MCM (2) #6 – 250 MCM
(1)#2–2/0AWG (9)#4–14AWG
(3) #4 AWG – 600 MCM
(6) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3) #4 – 600 MCM
(6) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3)#6–3/0AWG
(3)#14–1/0AWG
TP-6807 12/1118 Section 2 Installation
Loading...
+ 42 hidden pages