Kohler RXT Operation And Installation

Operation and
Installation
Automatic Transfer Switch
Model:
RXT
100--400 Amp Automatic Transfer Switches
For use with Kohlerr Model RESA, RESAL, or RCL generator sets
equipped with RDC2 or DC2 generator/transfer switch controllers
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Transfer Switch Identification Numbers
Record the product identification numbers from the transfer switch nameplate.
Model Designation
Serial Number
TP-6807 12/112
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 5........................................................
Introduction 7...............................................................................
Nameplate 8.................................................................
Model Designation 8..........................................................
Service Assistance 9........................................................................
Section 1 Description 11.....................................................................
1.1 Transfer Switch Description 11.............................................
1.2 Service Entrance Models 11...............................................
1.3 Load Centers 11.........................................................
1.4 Controller Interface Board 12..............................................
1.5 Optional LED Indicator Panel 12...........................................
Section 2 Installation 13......................................................................
2.1 Introduction 13..........................................................
2.2 Receipt of Unit 13........................................................
2.2.1 Inspection 13....................................................
2.2.2 Storage 13......................................................
2.2.3 Unpacking 13....................................................
2.2.4 Lifting 13........................................................
2.3 Installation 14...........................................................
2.4 Manual Operation Check 15...............................................
2.4.1 Manual Operation Procedure 1 15..................................
2.4.2 Manual Operation Procedure 2 15..................................
2.5 Electrical Wiring 16.......................................................
2.5.1 Load Center Circuit Breakers 16...................................
2.5.2 AC Power Connections 17........................................
2.5.3 Neutral Connection 18............................................
2.5.4 Neutral Bonding Jumper, Service Entrance Models 18................
2.5.5 Engine Start Function 18..........................................
2.5.6 Interface Module Connection 19....................................
2.5.7 Optional Load Control Connection 20...............................
2.5.8 Accessory Module Connections 20.................................
2.6 Test and Exercise 20.....................................................
2.7 Warranty Registration 20..................................................
Section 3 Operation 21.......................................................................
3.1 Model RXT Transfer Switch Operation 21...................................
3.2 Source Availability 21.....................................................
3.3 ATS Control Sequence of Operation 21.....................................
3.4 Time Delays 22..........................................................
3.5 Load Control Time Delay 22...............................................
Section 4 Service Disconnect, SE Model 23....................................................
4.1 Service Disconnect Procedure 23..........................................
4.2 Source Circuit Breaker Reset 23...........................................
Section 5 Scheduled Maintenance 25..........................................................
5.1 Introduction 25..........................................................
5.2 Testing 26..............................................................
5.2.1 Weekly Generator Set Exercise 26.................................
5.2.2 Monthly Automatic Control System Test 26..........................
TP-6807 12/11 Table of Contents 3
Table of Contents, continued
5.3 Inspection and Service 26.................................................
5.3.1 General Inspection 26............................................
5.3.2 Other Inspections and Service 27..................................
5.4 Service Schedule 27.....................................................
Section 6 Diagrams and Drawings 29..........................................................
Appendix A Abbreviations 55..................................................................
TP-6807 12/11Table of Contents4
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
DANGER
Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To
prevent electrical shock deenergize the normal power source before making any line or auxiliary connections.
TP-6807 12/11 5Safety Precautions and Instructions
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergizeall
power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.
Notice
NOTICE
Foreign material contamination.
Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. After installation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
NOTICE
Electrostatic discharge damage.
Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short,to ground.
TP-6807 12/116 Safety Precautions and Instructions
This manual provides operation and installation instructions for Kohlerr Model RXT automatic transfer switches. See Figure 1 for typical Model RXT transfer switches.
Model RXT transfer switches operate only with Kohlerr Model generator sets equipped with the RDC2 or DC2 generator/transfer switch controller. See Figure 2 for controller identification. The following Kohlerr model generator sets can be used with the Model RXT transfer switch:
D 14RESA
D 14RESAL
D 20RESA
D 20RESAL
D 48RCL
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this literature and the products represented without notice and without any obligation or liability whatsoever.
Introduction
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.
Figure 1 Typical Model RXT Transfer Switches
(shown with optional status indicators)
RDC2 DC2
GM77569
Figure 2 RDC2 and DC2 Generator/Transfer Switch
Controllers (provided with and mounted on the generator set)
TP-6807 12/11 7Introduction
Nameplate
n
A nameplate attached to the inside of the enclosure cover or on the upper right side wall includes a model designation, a serial number, ratings, and other information about the transfer switch. See Figure 3.
Check the transfer switch model number from the transfer switch nameplate and verify that it matches the model shown on the front cover of this manual before proceeding with installation.
TRANSFER SWITCH
FOR EMERGENCY SYSTEMS
VOLTS PHASE HERTZ
TYPE ENCLOSURE
MFG. DATE
ACCESSORIES:
1
MATERIAL MODEL
2
SERIAL NO.
AMPS WIRES POLES
BAR CODE
3
Copy the model designation, serial number, and accessory information from the nameplate to the spaces provided in the Product Identification Information section located inside the front cover of this manual for use when requesting service or parts.
1. Model designation
2. Serial number
3. Factory-installed accessory numbers
LISTED
R
TRANSFER SWITCH
FOR EMERGENCY SYSTEMS
GM21291-E
Figure 3 Typical Transfer Switch Nameplate
Model Designation
Figure 4 explains the model designation.
Model Controls Voltage Poles Enclosure Current Rating Connections
Record the transfer switch model designation in the boxes. The transfer switch model designation defines ratings a characteristics as explained below.
Sample Model Designation: RXT-JFNC-0200A
Model
RXT: Kohler Automatic Transfer Switch
Controls
J: Interface for RDC2/DC2 Controller
Voltage/Frequency
C: 208 Volts/60 Hz (3-phase only) F: 240 Volts/60 Hz M: 480 Volts/60 Hz (3-phase only)
Number of Poles/Wires
N: 2-pole, 3-wire, solid neutral (120/240 V only) T: 3-pole, 4-wire, solid neutral V: 4-pole, 4-wire, switched neutral
Enclosure
C: NEMA 3R
Current Rating: Numbers indicate the current rating of the switch in amperes:
0100 0200 0400
Connections
A: No load center B: With load center (100 amp single-phase only) ASE: Service entrance rated
Figure 4 Model Designation
TP-6807 12/118 Introduction
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone: (33) 1 49 178300 Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6807 12/11 9Service Assistance
Notes
TP-6807 12/1110 Service Assistance
Section 1 Description
1.1 Transfer Switch Description
An automatic transfer switch (ATS) transfers electrical loads from a normal source of electrical power to an emergency source when the normal source voltage or frequency falls below an acceptable level. The normal source is typically utility power. The emergency source is usually a generator set.
Model RXT transfer switches must be connected to a generator set equipped with the Kohlerr RDC2 or DC2 generator/transfer switch controller. Applicable generator set models are listed in the Introduction.
Voltage sensing data from the ATS is continuously transmitted to the RDC2/DC2 controller mounted on the generator set. When the normal source fails, the RDC2/DC2 controller signals the emergency source generator set to start. When the emergency source reaches acceptable levels and stabilizes, the ATS transfers the electrical load to the emergency source.
The RDC2/DC2 controller signals the ATS to transfer the load back when the normal source returns and stabilizes.
Service Entrance Model
Figure 1-1 shows a typical installation block diagram.
Emergency (Generator)
Normal (Utility)
Power Switching Device
Power
Power
Automatic T ransfer Switch
To Load
Generator
Electrical
Controls
Interface
Board
TP-6751
Figure 1-1 Typical ATS Block Diagram
Load Center Model Standard Model
Figure 1-2 Selected Transfer Switches
(covers removed)
1.2 Service Entrance Models
Service entrance models use a circuit breaker to provide the service disconnect for the utility source. A service entrance model is shown in Figure 1-2.
1.3 Load Centers
Model RXT 100 amp transfer switches are available with a built-in load center. A model with a built-in load center is shown in Figure 1-2. Models without load centers require the installation of a separate load panel.
TP-6807 12/11 11Section 1 Description
Loads. The transfer switch can be connected to supply all of the electrical loads in the home, or only the essential loads such as the furnace, refrigerator, well pump, and selected light circuits. Identify the essential circuits that must be supplied during a power outage. Verify that the generator set and transfer switch are adequately rated to supply all of the selected loads.
Circuit breakers. Because the size and number of circuit breakers required will vary with each application, circuit breakers are not provided with the transfer switch load center.
Determine the circuits that will be connected to the transfer switch (essential loads). Identify the breakers for those circuits in the main distribution panel.
The ATS load center requires Square D type QO breakers. If the main distribution panel uses the same type of breakers, the breakers can be moved from the main panel to the load center. Otherwise, obtain new Square D type QO circuit breakers. For each circuit, the rating of the load center circuit breaker must match the rating of the existing breaker in the main panel.
1.5 Optional LED Indicator Panel
A user interface panel that contains status-indicating LEDs is available. See Figure 1-3. Source available LEDs light to indicate that the utility and/or generator sources are available. The utility or generator source supplying load LED lights to show which source is connected to the building load (i.e. contactor position, normal or emergency).
If the status indicator is purchased as a loose kit (not factory-installed), refer to the installation instructions provided with the kit, TT-1585.
1
2
Up to 8 tandem breakers can be used. Use Square D type QOT tandem breakers.
Verify that the total rating for all of the breakers used in the load center does not exceed the rating of the transfer switch.
1.4 Controller Interface Board
All ATS control functions are performed by the RDC2/DC2 controller mounted on the generator set and communicated through the interface board. The controller interface board sends voltage sensing data to the RDC2/DC2 controller and receives transfer and load control signals from the RDC2/DC2 controller.
3
4
1. Utility power available
2. Utility source supplying load
3. Generator source supplying load
4. Generator power available
Figure 1-3 LED Indicators
GM78649
TP-6807 12/1112 Section 1 Description
Section 2 Installation
2.1 Introduction
Kohlerr transfer switches are shipped factory-wired, factory-tested, and ready for installation. Have the equipment installed only by trained and qualified personnel, and verify that the installation complies with applicable codes and standards. Protect the switch against damage before and during installation.
2.2 Receipt of Unit
2.2.1 Inspection
At the time of delivery, inspect the packaging and the transfer switch for signs of shipping damage. Unpack the transfer switch as soon as possible and inspect the exterior and interior for shipping damage. If damage and/or rough handling is evident, immediately file a damage claim with the transportation company.
2.2.2 Storage
Store the transfer switch in its protective packing until final installation. Protect the transfer switch at all times from moisture, construction grit, and metal chips. Avoid storage in cold or damp areas where moisture could condense on the unit. See Figure 2-1 for acceptable storage temperatures.
Item Specification
Storage Temperature
Operating Temperature
Humidity 5% to 95% noncondensing
Altitude 0 to 3050 m (10000 ft.) without derating
Figure 2-1 Environmental Specifications
2.2.3 Unpacking
Allow the equipment to warm to room temperature for at least 24 hours before unpacking to prevent condensation on the electrical apparatus. Use care when unpacking to avoid damaging transfer switch components. Use a vacuum cleaner or a dry cloth to remove dirt and packing material that may have
-- 4 0 °Cto85°C(--40°F to 185°F)
-- 2 0 °Cto70°C(--4°F to 158°F)
accumulated in the transfer switch or any of its components.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris to lodge in the components and damage the switch.
2.2.4 Lifting
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.
See Figure 2-2 or the dimensional drawing for the weight of the transfer switch. Use a spreader bar to lift the transfer switch. Attach the bar only to the enclosure’s mounting holes or lifting brackets; do not lift the unit any other way. Close and latch the enclosure door before moving the unit.
Amps Description
Single phase 7 (14)
100
200
400
With load center 8.2 (18)
Three phase 14 (30)
Service Entrance 10 (22)
Single phase 7 (15)
Three phase 14 (30)
Service Entrance 12 (26)
Single phase 36 (80)
3-Pole/208--240 Volts 41 (90)
3-Pole/480 Volts 59 (130)
4-Pole 59 (130)
Service Entrance 46 (100)
Figure 2-2 Approximate Weights
Weight, kg (lb.) [
TP-6807 12/11 13Section 2 Installation
2.3 Installation
NOTICE
Foreign material contamination. Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. Afterinstallation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
NOTICE
Hardware damage. The transfer switch may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
Check the system voltage and frequency. Compare the voltage and frequency shown on the transfer switch nameplate to the source voltage and frequency. Do not install the transfer switch if the voltage and frequency are different from the normal (utility) source voltage and frequency or the emergency source voltage and frequency shown on the generator set nameplate.
Plan the installation. Use the dimensions given on the enclosure dimension (ADV) drawings in Section 6. Select a mounting site that complies with local electrical code restrictions for the enclosure type. Mount the transfer switch as close to the load and power sources as possible. Allow adequate space to open the enclosure and service the switch.
Pull the bottom of the panel out and down until the top clears the enclosure. Remove the inner panel to access the transfer switch components.
NEMA 3R enclosures have locking tabs at the bottom of the enclosure and the door. Whilethe enclosure is open, turn the locking tab out so that the door can be locked with a padlock after installation is complete.
Wall mounting. Mount the transfer switch to a wall or other rigid vertical supporting structure. Refer to the dimension drawings in Section 6 for hole locations. Use shims to plumb the enclosure.
Cover or remove the transfer switch’s internal components to protect them from drill chips or debris during installation. Use a vacuum cleaner to remove debris from the enclosure.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris to lodge in the components and cause damage.
Tighten the mounting screws to 2.9 Nm (26 in. lb.) when reinstalling the components.
Clearance holes through the back of each enclosure are provided for mounting. The mounting holes on NEMA 3R enclosures have gaskets to seal out moisture. Use washers with the mounting screws to protect the gaskets.
NEMA 3R enclosures. To remove the enclosure’s front panel, support the panel while removing the screws.
TP-6807 12/1114 Section 2 Installation
2.4 Manual Operation Check
DANGER
CN
3
4
C
NO
NL1
NC
SCN
NL2
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Check the manual operation before energizing the transfer switch. Verify that the contactor operates smoothly without binding. Do not place the transfer switch into service if the contactor does not operate smoothly.
After checking the manual operation, place the contactor in the Normal (utility) position.
See Figure 2-3 to identify the manual operation procedure for your transfer switch.
ATS Procedure Figure
100--200 amps, 1-phase 2.4.1 Figure 2-4
100--200 amps, 3-phase 2.4.2 Figure 2-6
400 amps, 1-phase 2.4.1 Figure 2-5
400 amps, 3-phase, 3-pole, 208--240 Volts
400 amps, 3-phase, 3-pole/480 Volt and 4-pole
2.4.1 Figure 2-5
2.4.2 Figure 2-7
Figure 2-3 Manual Operation Procedure Guide
2.4.1 Manual Operation Procedure 1
Note: Never manually operate the transfer switch when
the power is connected. Disconnect both power sources before manually operating the switch.
1. 100-200 amp switches: These switches have an attached handle as shown in Figure 2-4. 400 amp switches: Slide the detachable handle or a wrench over the shaft. See Figure 2-5.
2. Move the handle up to place the transfer switch in the Normal Source position or down to place the contactor in the Emergency Source position. See Figure 2-4 or Figure 2-5.
3. 400 amp switches: Remove the detachable handle or wrench.
SCE
NC
NO
C
7
8
CE
EL2EL1
1
1. Handle (not detachable)
Figure 2-4 Manual Operation, 100 and 200 Amp
Single-Phase Switches
1
GM80139
1. Shaft (attach handle or wrench here)
Figure 2-5 Manual Operation, 400 Amp Single-
Phase and 208--240 Volt Switches
2.4.2 Manual Operation Procedure 2
Note: Never use the maintenance handle to transfer the
load with the power connected. Disconnect both power sources before manually operating the switch.
1. If the transfer switch is equipped with a maintenance handle, remove the handle from its storage location inside the enclosure. See Figure 2-7.
TP-6807 12/11 15Section 2 Installation
2. Insert the maintenance handle or a tool (such as a screwdriver) into the hole in the shaft on the left side of the operator as shown in Figure 2-6 or Figure 2-7.
3. Move the maintenance handle (or tool) up or down as shown to manually operate the transfer switch. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
2.5 Electrical Wiring
Refer to the connection diagrams on the transfer switch enclosure door and the wiring diagrams in Section 6 during installation.
All wiring must comply with applicable national, state, and local electrical codes. Use separate conduit for AC power wiring and low-voltage DC, control, and communication system wiring.
4. Return the transfer switch to the Normal position.
5. Remove the maintenance handle and return it to the storage location.
1
GM78867
1. Insert handle or tool here for manual operation
Figure 2-6 Manual Operation, 100--200 Amp
3-Phase Switches
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To prevent electrical
shock deenergize the normal power source before making any line or auxiliary connections.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
2.5.1 Load Center Circuit Breakers
1
2
1. Handle storage location
2. Insert handle here for manual operation
Figure 2-7 Manual Operation, 400 Amp 3-Phase
Switches
The 100 amp Model RXT transfer switch is available with a built-in load center with room for up to 16 single-pole circuit breakers. Up to 8 tandem breakers can be used for a maximum of 24 circuits.
The load center uses Square D type QO or QOT tandem breakers. In an essential load application, the breakers can be moved from the main panel to the load center if the main distribution panel uses the same type of breakers. Otherwise, obtain and install new Square D type QO circuit breakers. The rating of the load center circuit breaker must match the rating of the existing breaker in the main panel for each circuit. If circuit breakers are removed from the load panel, install cover plates over the vacant positions. Cover plates can be obtained from a local Square D supplier.
tp6225
Verifythat the total rating for all breakers used in the load center does not exceed the rating of the transfer switch.
TP-6807 12/1116 Section 2 Installation
2.5.2 AC Power Connections
Determine the cable size. Refer to Figure 2-8 or the ADV drawings in Section 6 to determine the cable size required for the transfer switch. Make sure the lugs provided are suitable for use with the cables being installed.
Conduit. Use separate conduit for AC power wiring and low-voltage DC, control, and communication system wiring. Watertight conduit hubs may be required for outdoor use.
Select the proper cable clamp or use other approved methods for securing the cable or conduit to the enclosure.
Source and load connections. Clean cables with a wire brush to remove surface oxides before connecting them to the terminals. Apply joint compound to the connections of any aluminum conductors.
Refer to the connection diagrams on the transfer switch enclosure door and the wiring diagrams in Section 6. The connection points on the transfer switch contactor are labelled Normal, Emergency, and Load. Connect the utility power to Normal. Connect the generator set to Emergency.
Single phase. For single-phase models, connect to A and C.
Three phase. For three-phase models, be sure to follow the phase markings (A, B, C, and N).
Note: Connect the source and load phases as indicated
by the markings and drawings to prevent short circuits and to prevent phase-sensitive devices from malfunctioning or operating in reverse.
Service entrance models. Connect the utility source to the lugs on the normal source disconnect circuit breakers as shown in the service entrance switch wiring diagram in Section 6.
Verify that all connections are consistent with drawings before tightening the lugs. Tighten all cable lug connections to the torque values shown on the label on the switch. Carefully wipe off any excess joint compound after tightening the terminal lugs.
On models with built-in load centers, the load lugs are factory-wired to the load center. Connect the load leads to the circuits in the load center and tighten the connections. Check the labels on the breakers for the tightening torques.
TP-6807 12/11 17Section 2 Installation
2.5.3 Neutral Connection
2.5.5 Engine Start Function
Connect the neutral from the main panel to the neutral lug in the ATS enclosure.
Ground the system according to NEC and local codes.
2.5.4 Neutral Bonding Jumper, Service Entrance Models
The transfer switch is shipped with the neutral-to-ground jumper installed. For non-service entrance applications, disconnect the neutral-to-ground bonding jumper. See the transfer switch dimension drawing.
Cable Sizes
AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections
Switch
Size,
Amps
100
200
400
Figure 2-8 Cable Sizes
Switch Phases Normal and Emergency Load Neutral Ground
Standard 1 (1) #14 -- 1/0 AWG (1)#14–1/0AWG (3)#12–1/0AWG (9)#4–14AWG
With load
center
Service
Entrance
3-Phase 3 (1)#8–3/0AWG (1)#8–3/0AWG (3)#6AWG–3/0AWG (3)#6–3/0AWG
Standard 1 (1) #6 AWG – 250 MCM (1) #6 AWG – 250 MCM (3) #6 AWG – 250 MCM (9)#4–14AWG
Service
Entrance
3-Phase 3 (1) #6 AWG – 250 MCM (1) #6 AWG – 250 MCM
Standard 1 (2) #6 – 250 MCM (2) #6 – 250 MCM
Service
Entrance
3-pole
208-240 V
3 or 4 pole
480 V
1 (1)#14–1/0AWG
Normal: (1) #12 – 2/0
1
1
1
3 (2) #6 – 250 MCM (2) #6 – 250 MCM
3
AWG
Emerg: (1) #6 – 250
MCM
Normal: (1) #4 – 300
MCM
Emerg: (1) #6 -- 250
MCM
Normal: (2) 3/0 – 250
MCM
Emerg: (2) #6 -- 250
MCM
(1) #4 – 600 MCM (2) #6 – 250 MCM
(1) #6 AWG – 250 MCM (3) #6 AWG – 250 MCM (3)#14–1/0AWG
The engine start function is controlled by the RDC2/DC2 controller on the generator set. There are no engine start terminals on the Model RXT ATS.
Range of Wire Sizes, Cu/Al
per customer-supplied
circuit breaker
(1) #6 – 250 MCM (3) #6 – 250 MCM (3)#14–1/0AWG
(2) #6 – 250 MCM
(1) #4 – 600 MCM (2) #6 – 250 MCM
(1)#2–2/0AWG (9)#4–14AWG
(3) #4 AWG – 600 MCM
(6) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3) #4 – 600 MCM
(6) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3)#6–3/0AWG
(3)#14–1/0AWG
TP-6807 12/1118 Section 2 Installation
2.5.6 Interface Module Connection
See Figure 2-9 and Figure 2-10. Use 20 AWG Belden #9402, 8723, or equivalent shielded, twisted-pair cable
The interface module must be connected to a Kohlerr generator set equipped with the RDC2 or DC2 controller. The generator set is typically equipped with a field-connection terminal block. See the generator set
to connect P10-1 through P10-4 on the controller interface module to the generator set terminal block connections A, B, PWR, and COM. The maximum cable length is 61 meters (200 ft.).
Installation Manual for the location of the terminal block.
Alternatively, 12--14 AWG wire can be used for the PWR
Note: This document gives connection information for
one Model RXT transfer switch connected to a generator set equipped with an RDC2 or DC2 controller. If additional accessory modules such as a programmable interface module (PIM) or a
and COM connections only. If 12--14 AWG wire is used for the PWR and COM connections, the maximum cable length is 152 m (500 ft.) if one Model RXT transfer switch and no accessory modules are connected to the generator set.
load control module (LCM) are connected, refer to the generator set installation manual for cable requirements and connection instructions.
Terminal Block Connection Designation Description Wire Size
P10-1 A Communication Line
P10
P10-2 B Communication Line
P10-3 PWR 12 VDC
P10-4 COM 12 VDC
Note: Connections 3 and 4 on the generator set are not
used with the Model RXT transfer switch.
20 AWG shielded twisted-pair,
Belden 9402, 8723, or equivalent
20 AWG shielded twisted-pair Belden 9402
or 12--14 AWG wire
Figure 2-9 Controller Interface Connections
Connect one end of each cable shield to GROUND at the generator set.
GND
Generator Set
A
B
PWR
COM
4
3
TB1
Generator Set Terminal Block TB1.
See the generator set manuals for location. Check the decal on the generator set for terminal block connections.
A
B
PWR
COM
1
Note: Generator set terminal block connections 3 and 4 are
NOT USED with the Model RXT ATS.
Interface Board on the Model
RXT Transfer Switch
A
B
PWR
COM
Leave one end of each cable shield disconnected.
If accessory modules are connected in series, connect the cable shields as shown below and refer to the generator set installation manual.
RXT
RXT
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
Figure 2-10 Interface Module Connection to Generator Set Field-Connection Terminal Block
TP-6807 12/11 19Section 2 Installation
2.5.7 Optional Load Control Connection
2.5.8 Accessory Module Connections
Connector P11 on the interface module provides a connection point for optional load control circuits. The load control contact provides a delayed contact closure to allow startup of selected loads 5 minutes after transfer to the emergency power source (generator set). Use this contact to delay startup of equipment with large motor-starting loads such as air conditioners.
See Figure 2-11 for the location of load control connector P11. See Figure 2-12 for contact ratings, connection, and wire size information.
Note: An optional load control module is available for
generator sets equipped with the RDC2 or DC2 controller. The load control module allows management of up to six separate loads (two HVAC thermostat connections and four other non-essential loads). See TT-1574, Load Control Module Instructions.
For connection of the optional load control module (LCM) or programmable interface module (PIM), refer to the instructions provided with the modules and to the generator set installation manual.
2.6 Test and Exercise
Refer to the generator set Operation Manual for instructions to test the power system operation and to set the RDC2 or DC2 controller for weekly exercise runs to keep the power system in good operating condition.
2.7 Warranty Registration
Startup Notification Form. The Startup Notification Form covers all equipment in the standby system. Complete the Startup Notification Form and register the equipment in the Kohler online warranty system within 60 days of the initial startup date. Standby systems not registered within 60 days of startup are automatically registered using the manufacturer’s ship date as the startup date.
3
2
1. ATS/generator set interface connection P10
2. Load control connection P11
3. Factory connections
1
GM80663
Figure 2-11 Interface Module Connections
Terminal Block Connection Designation Description Contact Rating Wire Size
P11
P11-1 LC1
P11-2 LC2
Load Control Output
10 A @ 250 VAC
1A@30VDC
#12--18 AWG
Figure 2-12 Load Control Contact P11 Connections
TP-6807 12/1120 Section 2 Installation
Section 3 Operation
3.1 Model RXT Transfer Switch
Operation
The Model RXT transfer switch must be connected to a generator set equipped with the RDC2 or DC2 controller. The RDC2/DC2 generator set/transfer switch controller manages automatic transfer switch (ATS) functions when connected to a Kohlerr Model RXT transfer switch through the ATS interface board. The controller receives voltage sensing data from the Model RXT ATS and operates the generator set and transfer switch to provide standby power when utility power is lost.
See the generator set operation manual for:
D ATS status screens and configuration menus.
D Information about loaded exercise.
3.2 Source Availability
The Model RXT transfer switch supplies voltage sensing data to the RDC2 or DC2 controller through the ATS interface board. If the source voltage falls below the undervoltage dropout setting, the source is considered to have failed. See Figure 3-1.
Voltage Sensing Parameter Setting
Accuracy ±5%
Undervoltage Dropout 90% of Pickup
Undervoltage Pickup 90% of Nominal
3.3 ATS Control Sequence of Operation
See Figure 3-2 for time delay settings.
Preferred Source Fails:
1. The load control contact opens.
2. The engine start time delay times out.
3. The generator set is signaled to start.
4. The generator starts and the emergency source becomes available.
5. The normal-to-emergency time delay times out.
6. The transfer switch transfers to the emergency source.
7. The load control contact time delay times out.
8. The load control contact closes.
Normal Source Returns:
1. The emergency-to-normal time delay times out.
2. The contactor transfers to the normal source.
3. The engine cooldown time delay times out.
4. The generator is signaled to stop.
Figure 3-1 Voltage Sensing Parameters
TP-6807 12/11 21Section 3 Operation
3.4 Time Delays
3.5 Load Control Time Delay
Time delays are factory-set to the values shown in Figure 3-2. An authorized distributor/dealer can adjust time delays using a personal computer and Kohlerr SiteTecht software.
The load control time delay allows delayed starting of large motor loads (such as air conditioners), preventing simultaneous starting of large motors after transfer to the generator set. The load control time delay is fixed at 5 minutes. It is not adjustable.
Time delays described in this section operate only when the RDC2 or DC2 generator set controller is connected to a Kohlerr Model RXT transfer switch.
The load must be connected to the load control output on the interface board of the Model RXT transfer switch. See the transfer switch operation and installation
The engine start and load transfer time delays prevent
manual for connection instructions.
engine start and load transfer caused by brief variations in the utility power source.
Note: A separate load control module (LCM) that
provides four power relays and two HVAC relays is available for generator sets equipped with the RDC2 or DC2 controller. See LCM Specification Sheet G6-120 for more information.
Time Delay Setting Description
Engine Start 3 seconds Time delay after utility source is lost until the engine start cycle begins.
Transfer, Normal to Emergency 3 seconds Time delay after emergency source becomes available until transfer to
Transfer, Emergency to Normal 2 minutes Time delay after the utility source returns until transfer back to normal.
Load Control 5 minutes Allows delayed connection of selected loads to the generator set.
Guards against starting the generator set because of a brief change in the utility source.
emergency source.
Ensures that the the utility source is stable before transferring from the emergency source.
Prevents simultaneous starting of large motors after transfer to the emergency source. Recommended for delayed starting of air conditioners.
Figure 3-2 Time Delays
TP-6807 12/1122 Section 3 Operation
Section 4 Service Disconnect, SE Model
Note: This section applies only to service entrance
model transfer switches, which are identified with the letters ASE at the end of the model designation.
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
4.1 Service Disconnect Procedure
Use the following procedure to disconnect the utility source on service entrance model transfer switches.
Note: Power is still present on the input side of the utility
source circuit breaker after this procedure.
4.2 Source Circuit Breaker Reset
The utility source circuit breaker can trip due to an overcurrent condition. Identify and correct the cause of the overcurrent condition before resetting the circuit breaker. Contact a local distributor/dealer for service if necessary.
When the circuit breaker trips, the handle moves to an intermediate position. To reset a tripped circuit breaker, move the handle to the extreme OFF position and then to the ON position.
1
1. Prevent the emergency generator set from starting:
a. Press the OFF button on the generator set
controller.
b. Disconnect power to the generator set battery
charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
2. On the transfer switch, remove the outer enclosure door only.
3. Move the utility source circuit breaker to the OFF position.
Note: Power is still present on the input side of the
utility source circuit breaker. Do not remove the protective barrier around the utility source connection lugs.
4. To lock out the transfer switch, replace the outer door and attach a padlock to the hasp.
GM80015
2
1. Normal/utility circuit breaker
2. Padlock hasp
Figure 4-1 Service Entrance Model, Door Removed
TP-6807 12/11 23Section 4 Service Disconnect, SE Model
Notes
TP-6807 12/1124 Section 4 Service Disconnect, SE Model
Section 5 Scheduled Maintenance
5.1 Introduction
Regular preventive maintenance ensures safe and reliable operation and extends the life of the transfer switch. Preventive maintenance includes periodic testing, cleaning, inspection, and replacement of worn or missing components. Section 5.4 contains a service schedule for recommended maintenance tasks.
A local authorized distributor/dealer can provide complete preventive maintenance and service to keep the transfer switch in top condition. Unless otherwise specified, have maintenance or service performed by an authorized distributor/dealer in accordance with all applicable codes and standards. See the Service Assistance section in this manual for how to locate a local distributor/dealer.
Keep records of all maintenance or service.
Replace all barriers and close and lock the enclosure door after maintenance or service and before reapplying power.
WARNING
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
DANGER
Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnectthe power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding the transfer switch. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open main circuit breakers of all power sources before servicing equipment. Configure the installation to electrically ground the transfer switch and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground, as the chance of electrocution increases under such conditions.
Moving parts.
TP-6807 12/11 25Section 5 Scheduled Maintenance
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources
before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
NOTICE
Hardware damage. The transfer switch may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
NOTICE
Electrostatic discharge damage. Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground.
Screws and nuts are available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
5.2 Testing
5.2.1 Weekly Generator Set Exercise
D Watch and listen for signs of excessive noise or
vibration during operation.
D After the switch transfers the load to the standby
source, end the test and verify that the expected sequence of operations occurs as the transfer switch retransfers to the preferred source.
5.3 Inspection and Service
Contact an authorized distributor/dealer to inspect and service the transfer switch annually and also when any wear, damage, deterioration, or malfunction of the transfer switch or its components is evident or suspected.
5.3.1 General Inspection
External Inspection. Keep the transfer switch clean and in good condition by performing a weekly general external inspection of the transfer switch. Check for any condition of vibration, leakage, excessive temperature, contamination, or deterioration. Remove accumulations of dirt, dust, and other contaminants from the transfer switch’s external components or enclosure with a vacuum cleaner or by wiping with a dry cloth or brush.
Note: Do not use compressed air to clean the transfer
switch because it can cause debris to lodge in the components and damage the switch.
Tighten loose external hardware. Replace worn, missing, or broken external components with manufacturer­recommended replacement parts. Contact an authorized distributor/dealer for specific part information and ordering.
Internal Inspection. Disconnect all power sources, open the transfer switch enclosure door, and inspect internal components monthly or when any condition noticed during an external inspection may have affected internal components.
Use the exerciser or a manual test to start and run the generator set under load once a week to maximize the reliability of the emergency power system.
5.2.2 Monthly Automatic Control System Test
Test the transfer switch’s automatic control system monthly. Refer to the RDC2/DC2 controller operation manual for the test procedure.
D Verify that the expected sequence of operations
occurs as the switch transfers the load to the emergency source when a preferred source failure occurs or is simulated.
Contact an authorized distributor/dealer to inspect and service the transfer switch if any of the following conditions are found inside the transfer switch.
D Accumulations of dirt, dust, moisture, or other
contaminants.
D Signs of corrosion.
D Worn, missing, or broken components.
D Loose hardware.
D Wire or cable insulation deterioration, cuts, or
abrasion.
TP-6807 12/1126 Section 5 Scheduled Maintenance
D Signs of overheating or loose connections:
discoloration of metal, melted plastic, or a burning odor.
operation of the transfer switch. See Section 5.4, Service Schedule, for the recommended maintenance items and service intervals.
D Other evidence of wear, damage, deterioration, or
malfunction of the transfer switch or its components.
Have an authorized distributor/dealer repair or replace damaged or worn internal components with manufacturer-recommended replacement parts.
If the application does not allow a power interruption for the time required for the internal inspection, have an authorized distributor/dealer perform the internal inspection.
5.4 Service Schedule
Follow the service schedule in Figure 5-1 for the recommended service intervals. Have all service
5.3.2 Other Inspections and Service
Have an authorized distributor/dealer perform scheduled maintenance, service, and other
performed by an authorized distributor/dealer except for activities designated by an X, which may be performed by the switch operator.
maintenance that ensures the safe and reliable
Adjust, Repair,
Replace
Clean Test Frequency
D (clean
and lube)
Y
System Component or Procedure
See
Section
Visually
Inspect
Check
Electrical System
Check for signs of overheating or loose connections: discoloration of metal, melted plastic, or a burning odor
Check the contactor’s external operating mechanism for cleanliness; clean and relubricate if dirty *
Inspect wiring insulation for deterioration, cuts, or abrasion. Repair or replace deteriorated or damaged wiring
Tighten control and power wiring connections to specifications
Check the transfer switch’s main power switching contacts’ condition; clean or replace the main contacts or replace the contactor assembly as necessary
5.3.1 X X Y
5.3.1 X
5.3.1 X D D Y
2.5 D D Y
S/M D D D Y
General Equipment Condition
Inspect the outside of the transfer switch for any signs of excessive vibration, leakage, high temperature, contamination, or deterioration *
Check that all external hardware is in place, tightened, and not badly worn
Inspect the inside of transfer switch for any signs of excessive vibration, leakage, high temperature, contamination, or deterioration *
Check that all internal hardware is in place, tightened, and not badly worn
* Service more frequently if the transfer switch is operated in dusty or dirty areas.
See Section: Read these sections carefully for additional information before attempting maintenance or service. Visually Inspect: Examine these items visually. Check: Requires physical contact with or movement of system components, or the use of nonvisual indications. Adjust, Repair, Replace: Includes tightening hardware and lubricating the mechanism. May require replacement of components
depending upon the severity of the problem. Clean: Remove accumulations of dirt and contaminants from external transfer switch’s components or enclosure with a vacuum cleaner or
by wiping with a dry cloth or brush. Do not use compressed air to clean the switch because it can cause debris to lodge in the components
and cause damage.
Test: May require tools, equipment, or training available only through an authorized distributor/dealer.
Symbols used in the chart:
X=The transfer switch operator can perform these tasks. D=Authorized distributor/dealer must perform these tasks. W=Weekly M=Monthly
5.3 X X M
5.3 X X X M
5.3 D D D Y
5.3 X D D Y
Q=Quarterly S=Semiannually (every six months) Y=Yearly (annually) W/D=Wiring diagram
Figure 5-1 Service Schedule
TP-6807 12/11 27Section 5 Scheduled Maintenance
Notes
TP-6807 12/1128 Section 5 Scheduled Maintenance
Section 6 Diagrams and Drawings
Diagram or Drawing Drawing Number Page
Single-Phase
Enclosure Dimension Drawings
100--200 Amp Single-Phase
Sheet 1 ADV-8190 1 of 2 30........................................................
Sheet 2 ADV-8190 2 of 2 31........................................................
100 Amp Single-Phase with Load Center ADV-8197 41..............................
400 Amp Single-Phase ADV-8193 36.............................................
Wiring Diagrams
100--400 Amp Single-Phase GM80663 42........................................
100 Amp Single-Phase with Load Center GM80675 52..............................
Schematic Diagrams
100--400 Amp Single-Phase GM80664 43........................................
100 Amp Single-Phase with Load Center GM80676 53..............................
Service Entrance
Enclosure Dimension Drawings
100--200 Amp Single-Phase Service Entrance
Sheet 1 ADV-8192 1 of 3 33........................................................
Sheet 2 ADV-8192 2 of 3 34........................................................
Sheet 3 ADV-8192 3 of 3 35........................................................
400 Amp Single-Phase Service Entrance Switch
Sheet 1 ADV-8196 1 of 2 39........................................................
Sheet 2 ADV-8196 2 of 2 40........................................................
Wiring Diagrams
100--400 Amp Service Entrance GM80665 44......................................
Schematic Diagrams
100--400 Amp Service Entrance GM80666 45......................................
Three-Phase
Enclosure Dimension Drawings
100--200 Amp Standard, Three-Phase, 3- and 4-Pole ADV-8191 32...................
400 Amp Standard, Three-Phase, 3-pole 208--240 V ADV-8194 37....................
400 Amp Standard, Three-Phase, 4-pole and 3-Pole/480 V ADV-8195 38..............
Wiring Diagrams
100--200 Amp Standard, Three-Phase, 3- and 4-Pole GM80667 46...................
400 Amp Standard, Three-Phase, 3-pole 208--240 V GM80669 48....................
400 Amp Standard, Three-Phase, 4-pole and 3-Pole/480 V GM80671 50..............
Schematic Diagrams
100--200 Amp Standard, Three-Phase, 3- and 4-Pole GM80668 47...................
400 Amp Standard, Three-Phase, 3-pole 208--240 V GM80670 49....................
400 Amp Standard, Three-Phase, 4-pole and 3-Pole/480 V GM80672 51..............
TP-6807 12/11 29Section 6 Diagrams and Drawings
Figure 6-1 Enclosure Dimensions, 100--200 Amp Single-Phase, ADV-8190, Sheet 1 of 2
TP-6807 12/1130 Section 5 Diagrams and Drawings
Figure 6-2 Enclosure Dimensions, 100--200 Amp Single-Phase, ADV-8190, Sheet 2 of 2
TP-6807 12/11 31Section 5 Diagrams and Drawings
Figure 6-3 Enclosure Dimensions, 100--200 Amp Three-Phase, 3- and 4-Pole, ADV-8191
TP-6807 12/1132 Section 5 Diagrams and Drawings
Figure 6-4 Enclosure Dimensions, 100--200 Amp Single-Phase, Service Entrance, ADV-8192, Sheet 1 of 3
TP-6807 12/11 33Section 5 Diagrams and Drawings
Figure 6-5 Enclosure Dimensions, 100--200 Amp Single-Phase, Service Entrance, ADV-8192, Sheet 2 of 3
TP-6807 12/1134 Section 5 Diagrams and Drawings
Figure 6-6 Enclosure Dimensions, 100--200 Amp Single-Phase, Service Entrance, ADV-8192, Sheet 3 of 3
TP-6807 12/11 35Section 5 Diagrams and Drawings
Figure 6-7 Enclosure Dimensions, 400 Amp Single-Phase, ADV-8193
TP-6807 12/1136 Section 5 Diagrams and Drawings
Figure 6-8 Enclosure Dimensions, 400 Amp Three-Phase, 3-Pole/208--240 Volts, ADV-8194
TP-6807 12/11 37Section 5 Diagrams and Drawings
Figure 6-9 Enclosure Dimensions, 400 Amp Three-Phase, 3-Pole/480 Volt and 4-Pole, ADV-8195
TP-6807 12/1138 Section 5 Diagrams and Drawings
Figure 6-10 Enclosure Dimensions, 400 Amp Single-Phase, Service Entrance, ADV-8196, Sheet 1 of 2
TP-6807 12/11 39Section 5 Diagrams and Drawings
Figure 6-11 Enclosure Dimensions, 400 Amp Single-Phase, Service Entrance, ADV-8196, Sheet 2 of 2
TP-6807 12/1140 Section 5 Diagrams and Drawings
Figure 6-12 Enclosure Dimensions, 100 Amp Single-Phase with Load Center, ADV-8197
TP-6807 12/11 41Section 5 Diagrams and Drawings
Figure 6-13 Wiring Diagram, 100--400 Amp Single-Phase, GM80663
TP-6807 12/1142 Section 5 Diagrams and Drawings
Figure 6-14 Schematic Diagram, 100--400 Amp Single-Phase, GM80664
TP-6807 12/11 43Section 5 Diagrams and Drawings
Figure 6-15 Wiring Diagram, 100--400 Amp Service Entrance, GM80665
TP-6807 12/1144 Section 5 Diagrams and Drawings
Figure 6-16 Schematic Diagram, 100--400 Amp Service Entrance, GM80666
TP-6807 12/11 45Section 5 Diagrams and Drawings
Figure 6-17 Wiring Diagram, 100--200 Amp Three-Phase, 3- and 4-Pole, GM80667
TP-6807 12/1146 Section 5 Diagrams and Drawings
Figure 6-18 Schematic Diagram, 100--200 Amp Three-Phase, 3- and 4-Pole, GM80668
TP-6807 12/11 47Section 5 Diagrams and Drawings
Figure 6-19 Wiring Diagram, 400 Amp Three-Phase, 3-Pole/208--240 Volts, GM80669
TP-6807 12/1148 Section 5 Diagrams and Drawings
Figure 6-20 Schematic Diagram, 400 Amp Three-Phase, 3-Pole/208--240 Volts, GM80670
TP-6807 12/11 49Section 5 Diagrams and Drawings
Figure 6-21 Wiring Diagram, 400 Amp Three-Phase, 3-Pole/480 Volts and 4-Pole, GM80671
TP-6807 12/1150 Section 5 Diagrams and Drawings
Figure 6-22 Schematic Diagram, 400 Amp Three-Phase, 3-Pole/480 Volts and 4-Pole, GM80672
TP-6807 12/11 51Section 5 Diagrams and Drawings
Figure 6-23 Wiring Diagram, 100 Amp Single-Phase with Load Center, GM80675
TP-6807 12/1152 Section 5 Diagrams and Drawings
Figure 6-24 Schematic Diagram, 100 Amp Single-Phase with Load Center, GM80676
TP-6807 12/11 53Section 5 Diagrams and Drawings
Notes
TP-6807 12/1154 Section 5 Diagrams and Drawings
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC advanced digital control;
adj. adjust, adjustment ADV advertising dimensional
Ah amp-hour AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only APDC Air Pollution Control District API American Petroleum Institute approx. approximate, approximately AQMD Air Quality Management District AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for Testing
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CAN controller area network CARB California Air Resources Board CB circuit breaker cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cert. certificate, certification, certified cfh cubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfm cubic feet per minute CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
cogen. cogeneration com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CRT cathode ray tube CSA Canadian Standards
CT current transformer Cu copper cUL Canadian Underwriter’s
CUL Canadian Underwriter’s
cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dB(A) decibel (A weighted) DC direct current DCR direct current resistance deg., ° degree dept. department DFMEA Design Failure Mode and
dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator E, emer. emergency (power source) ECM electronic control module,
EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge
substrate (semiconductor)
Association
Laboratories
Laboratories
Effects Analysis
e. V. (also Deutsche Industrie Normenausschuss)
engine control module
Association
Association
Agency
engineered special
est. estimated E-Stop emergency stop etc. et cetera (and so forth) exh. exhaust ext. external F Fahrenheit, female fglass. fiberglass FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lb. foot pounds (torque) ft./min. feet per minute ftp file transfer protocol ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temp., high
hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lb. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP iron pipe ISO International Organization for
J joule JIS Japanese Industry Standard
ground
engine temp.
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
TP-6807 12/11 Appendix 55
k kilo (1000) K kelvin kA kiloampere KB kilobyte (2
10
bytes) KBus Kohler communication protocol kg kilogram
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
LWL low water level
sound power level, A weighted
LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
3
m
units), male
cubic meter
/hr. cubic meters per hour /min. cubic meters per minute
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCCB molded-case circuit breaker MCM one thousand circular mils meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, mmilliohm MOhm, MΩmegohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard ms millisecond m/sec. meters per second MTBF mean time between failure
MTBO mean time between overhauls mtg. mounting MTU Motoren-und Turbinen-Union MW megawatt mW milliwatt μF microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas NBS National Bureau of Standards NC normally closed NEC National Electrical Code NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillipsr head Crimptiter
(screw) PHH Phillipsr hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch psig pounds per square inch gauge pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay
rms root mean square rnd. round ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTU remote terminal unit RTV room temperature vulcanization RW read/write SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SN serial number SNMP simple network management
protocol SPDT single-pole, double-throw SPST single-pole, single-throw spec specification specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SS stainless steel std. standard stl. steel tach. tachometer TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal THD total harmonic distortion TIF telephone influence factor TIR total indicator reading tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with w/o without wt. weight xfmr transformer
TP-6807 12/1156 Appendix
Notes
TP-6807 12/11 57
Notes
TP-6807 12/1158
E 2011 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...