For use with Kohlerr Model RESA, RESAL, or RCL generator sets
equipped with RDC2 or DC2 generator/transfer switch controllers
TP-680712/11
Product Identification Information
Product identification numbers determine service parts.
Record the product identification numbers in the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Transfer Switch Identification Numbers
Record the product identification numbers from the
transfer switch nameplate.
Section 6 Diagrams and Drawings29..........................................................
Appendix A Abbreviations55..................................................................
TP-6807 12/11Table of Contents4
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanicalequipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcause severe
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
connected equipment, disable the
generator set as follows: (1) Move the
generator set master switch to the OFF
position. (2) Disconnect the power to
the battery charger. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent starting of
the generator set by an automatic
transfer switch, remotestart/stop
switch, or engine start command from a
remote computer.
Hazardous Voltage/
Moving Parts
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicablecodes andstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Makinglineorauxiliary
connections.Hazardous voltage
can cause severe injury or death. To
prevent electrical shock deenergize the
normal power source before making
any line or auxiliary connections.
TP-6807 12/115Safety Precautions and Instructions
Servicingthetransferswitch.
Hazardousvoltagecancause
severe injury or death. Deenergizeall
power sources before servicing. Turn
off the main circuit breakers of all
transfer switch power sources and
disable all generator sets as follows:
(1) Move all generator set master
controller switches to the OFF position.
(2) Disconnect power to all battery
chargers. (3) Disconnect all battery
cables, negative(--) leadsfirst.
Reconnect negative (--) leads last when
reconnecting the battery cables after
servicing. Follow these precautions to
prevent the starting of generator sets
by an automatic transfer switch, remote
start/stop switch, or engine start
command from a remote computer.
Before servicing any components
inside the enclosure: (1) Remove all
jewelry. (2) Stand on a dry, approved
electrically insulated mat.(3) Test
circuits with a voltmeter to verify that
they are deenergized.
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Use adequate lifting capacity.
Never leave the transfer switch
standing upright unless it is securely
bolted in place or stabilized.
Notice
NOTICE
Foreignmaterial contamination.
Cover the transfer switch during
installation to keep dirt, grit, metal drill
chips, and other debris out of the
components.Cover the solenoid
mechanism during installation. After
installation, use the manual operating
handle to cycle the contactor to verify
that it operates freely. Do not use a
screwdriver to force the contactor
mechanism.
NOTICE
Electrostatic discharge damage.
Electrostaticdischarge(ESD)
damages electronic circuit boards.
Preventelectrostaticdischarge
damage by wearing an approved
grounding wrist strap when handling
electronic circuit boards or integrated
circuits. An approved grounding wrist
strap provides a high resistance (about
1 megohm), not a direct short,to
ground.
TP-6807 12/116Safety Precautions and Instructions
This manual provides operation and installation
instructions for Kohlerr Model RXT automatic transfer
switches. See Figure 1 for typical Model RXT transfer
switches.
Model RXT transfer switches operate only with Kohlerr
Model generator sets equipped with the RDC2 or DC2
generator/transfer switch controller. See Figure 2 for
controller identification. The following Kohlerr model
generator sets can be used with the Model RXT transfer
switch:
D 14RESA
D 14RESAL
D 20RESA
D 20RESAL
D 48RCL
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this literature and the products represented
without notice and without any obligation or liability
whatsoever.
Introduction
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect parts often and
perform required service at the prescribed intervals.
Obtain service from an authorized service distributor/
dealer to keep equipment in top condition.
Figure 1Typical Model RXT Transfer Switches
(shown with optional status indicators)
RDC2DC2
GM77569
Figure 2RDC2 and DC2 Generator/Transfer Switch
Controllers (provided with and mounted on
the generator set)
TP-6807 12/117Introduction
Nameplate
n
A nameplate attached to the inside of the enclosure
cover or on the upper right side wall includes a model
designation, a serial number, ratings, and other
information about the transfer switch. See Figure 3.
Check the transfer switch model number from the
transfer switch nameplate and verify that it matches the
model shown on the front cover of this manual before
proceeding with installation.
TRANSFER SWITCH
FOR EMERGENCY SYSTEMS
VOLTS
PHASE
HERTZ
TYPE ENCLOSURE
MFG. DATE
ACCESSORIES:
1
MATERIAL
MODEL
2
SERIAL NO.
AMPS
WIRES
POLES
BAR CODE
3
Copy the model designation, serial number, and
accessory information from the nameplate to the spaces
provided in the Product Identification Information
section located inside the front cover of this manual for
use when requesting service or parts.
Current Rating: Numbers indicate the current rating
of the switch in amperes:
0100
0200
0400
Connections
A:No load center
B:With load center (100 amp single-phase only)
ASE: Service entrance rated
Figure 4Model Designation
TP-6807 12/118Introduction
Service Assistance
For professional advice on generator set power
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D VisittheKohler PowerSystemswebsite at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents
included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax:(33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6807 12/119Service Assistance
Notes
TP-6807 12/1110 Service Assistance
Section 1 Description
1.1Transfer Switch Description
An automatic transfer switch (ATS) transfers electrical
loads from a normal source of electrical power to an
emergency source when the normal source voltage or
frequency falls below an acceptable level. The normal
source is typically utility power. The emergency source
is usually a generator set.
Model RXT transfer switches must be connected to a
generator set equipped with the Kohlerr RDC2 or DC2
generator/transferswitchcontroller.Applicable
generator set models are listed in the Introduction.
Voltage sensing data from the ATS is continuously
transmitted to the RDC2/DC2 controller mounted on the
generator set.When the normal source fails, the
RDC2/DC2 controller signals the emergency source
generator set to start. When the emergency source
reaches acceptable levels and stabilizes, the ATS
transfers the electrical load to the emergency source.
The RDC2/DC2 controller signals the ATS to transfer
the load back when the normal source returns and
stabilizes.
Service Entrance Model
Figure 1-1 shows a typical installation block diagram.
Emergency
(Generator)
Normal
(Utility)
Power
Switching
Device
Power
Power
Automatic T ransfer Switch
To Load
Generator
Electrical
Controls
Interface
Board
TP-6751
Figure 1-1Typical ATS Block Diagram
Load Center ModelStandard Model
Figure 1-2Selected Transfer Switches
(covers removed)
1.2Service Entrance Models
Service entrance models use a circuit breaker to provide
the service disconnect for the utility source. A service
entrance model is shown in Figure 1-2.
1.3Load Centers
Model RXT 100 amp transfer switches are available with
a built-in load center. A model with a built-in load center
is shown in Figure 1-2. Models without load centers
require the installation of a separate load panel.
TP-6807 12/1111Section 1 Description
Loads. The transfer switch can be connected to supply
all of the electrical loads in the home, or only the
essential loads such as the furnace, refrigerator, well
pump, and selected light circuits. Identify the essential
circuits that must be supplied during a power outage.
Verify that the generator set and transfer switch are
adequately rated to supply all of the selected loads.
Circuit breakers. Because the size and number of
circuit breakers required will vary with each application,
circuit breakers are not provided with the transfer switch
load center.
Determine the circuits that will be connected to the
transfer switch (essential loads). Identify the breakers
for those circuits in the main distribution panel.
The ATS load center requires Square D type QO
breakers. If the main distribution panel uses the same
type of breakers, the breakers can be moved from the
main panel to the load center. Otherwise, obtain new
Square D type QO circuit breakers. For each circuit, the
rating of the load center circuit breaker must match the
rating of the existing breaker in the main panel.
1.5Optional LED Indicator Panel
A user interface panel that contains status-indicating
LEDs is available. See Figure 1-3. Source available
LEDs light to indicate that the utility and/or generator
sources are available. The utility or generator source
supplying load LED lights to show which source is
connected to the building load (i.e. contactor position,
normal or emergency).
If the status indicator is purchased as a loose kit (not
factory-installed), refer to the installation instructions
provided with the kit, TT-1585.
1
2
Up to 8 tandem breakers can be used. Use Square D
type QOT tandem breakers.
Verify that the total rating for all of the breakers used in
the load center does not exceed the rating of the transfer
switch.
1.4Controller Interface Board
All ATS control functions are performed by the
RDC2/DC2 controller mounted on the generator set and
communicated through the interface board.The
controller interface board sends voltage sensing data to
the RDC2/DC2 controller and receives transfer and load
control signals from the RDC2/DC2 controller.
3
4
1. Utility power available
2. Utility source supplying load
3. Generator source supplying load
4. Generator power available
Figure 1-3LED Indicators
GM78649
TP-6807 12/1112 Section 1 Description
Section 2 Installation
2.1Introduction
Kohlerr transfer switches are shipped factory-wired,
factory-tested, and ready for installation.Have the
equipment installed only by trained and qualified
personnel, and verify that the installation complies with
applicable codes and standards. Protect the switch
against damage before and during installation.
2.2Receipt of Unit
2.2.1Inspection
At the time of delivery, inspect the packaging and the
transfer switch for signs of shipping damage. Unpack
the transfer switch as soon as possible and inspect the
exterior and interior for shipping damage. If damage
and/or rough handling is evident, immediately file a
damage claim with the transportation company.
2.2.2Storage
Store the transfer switch in its protective packing until
final installation. Protect the transfer switch at all times
from moisture, construction grit, and metal chips. Avoid
storage in cold or damp areas where moisture could
condense on the unit. See Figure 2-1 for acceptable
storage temperatures.
ItemSpecification
Storage
Temperature
Operating
Temperature
Humidity5% to 95% noncondensing
Altitude0 to 3050 m (10000 ft.) without derating
Figure 2-1Environmental Specifications
2.2.3Unpacking
Allow the equipment to warm to room temperature for at
least24 hoursbeforeunpackingtoprevent
condensation on the electrical apparatus. Use care
when unpacking to avoid damaging transfer switch
components. Use a vacuum cleaner or a dry cloth to
remove dirt and packing material that may have
-- 4 0 °Cto85°C(--40°F to 185°F)
-- 2 0 °Cto70°C(--4°F to 158°F)
accumulated in the transfer switch or any of its
components.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris
to lodge in the components and damage the
switch.
2.2.4Lifting
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Use adequate lifting capacity.
Never leave the transfer switch
standing upright unless it is securely
bolted in place or stabilized.
See Figure 2-2 or the dimensional drawing for the
weight of the transfer switch. Use a spreader bar to lift
the transfer switch.Attach the bar only to the
enclosure’s mounting holes or lifting brackets; do not lift
the unit any other way. Close and latch the enclosure
door before moving the unit.
AmpsDescription
Single phase7(14)
100
200
400
With load center8.2(18)
Three phase14(30)
Service Entrance10(22)
Single phase7(15)
Three phase14(30)
Service Entrance12(26)
Single phase36(80)
3-Pole/208--240 Volts41(90)
3-Pole/480 Volts59(130)
4-Pole59(130)
Service Entrance46(100)
Figure 2-2Approximate Weights
Weight, kg (lb.) [
TP-6807 12/1113Section 2 Installation
2.3Installation
NOTICE
Foreign material contamination. Cover the transfer switch
during installation to keep dirt, grit, metal drill chips, and other
debris out of the components. Cover the solenoid mechanism
during installation. Afterinstallation, use the manual operating
handle to cycle the contactor to verify that it operates freely.
Do not use a screwdriver to force the contactor mechanism.
NOTICE
Hardware damage.The transfer switch may use both
American Standard and metric hardware. Use the correct size
tools to prevent rounding of the bolt heads and nuts.
Check the system voltage and frequency. Compare
the voltage and frequency shown on the transfer switch
nameplate to the source voltage and frequency. Do not
install the transfer switch if the voltage and frequency
are different from the normal (utility) source voltage and
frequency or the emergency source voltage and
frequency shown on the generator set nameplate.
Plan the installation. Use the dimensions given on the
enclosure dimension (ADV) drawings in Section 6.
Select a mounting site that complies with local electrical
code restrictions for the enclosure type. Mount the
transfer switch as close to the load and power sources
as possible.Allow adequate space to open the
enclosure and service the switch.
Pull the bottom of the panel out and down until the top
clears the enclosure. Remove the inner panel to access
the transfer switch components.
NEMA 3R enclosures have locking tabs at the bottom of
the enclosure and the door. Whilethe enclosure is open,
turn the locking tab out so that the door can be locked
with a padlock after installation is complete.
Wall mounting. Mount the transfer switch to a wall or
other rigid vertical supporting structure. Refer to the
dimension drawings in Section 6 for hole locations. Use
shims to plumb the enclosure.
Cover or removethe transfer switch’s internal
components to protect them from drill chips or debris
during installation. Use a vacuum cleaner to remove
debris from the enclosure.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris
to lodge in the components and cause damage.
Tighten the mounting screws to 2.9 Nm (26 in. lb.) when
reinstalling the components.
Clearance holes through the back of each enclosure are
provided for mounting. The mounting holes on NEMA
3R enclosures have gaskets to seal out moisture. Use
washers with the mounting screws to protect the
gaskets.
NEMA 3R enclosures. To remove the enclosure’s front
panel, support the panel while removing the screws.
TP-6807 12/1114 Section 2 Installation
2.4Manual Operation Check
DANGER
CN
3
4
C
NO
NL1
NC
SCN
NL2
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
Check the manual operation before energizing the
transfer switch.Verify that the contactor operates
smoothly without binding. Do not place the transfer
switch into service if the contactor does not operate
smoothly.
After checking the manual operation, place the
contactor in the Normal (utility) position.
See Figure 2-3 to identify the manual operation
procedure for your transfer switch.
ATSProcedureFigure
100--200 amps, 1-phase2.4.1Figure 2-4
100--200 amps, 3-phase2.4.2Figure 2-6
400 amps, 1-phase2.4.1Figure 2-5
400 amps, 3-phase, 3-pole,
208--240 Volts
400 amps, 3-phase,
3-pole/480 Volt and 4-pole
2.4.1Figure 2-5
2.4.2Figure 2-7
Figure 2-3Manual Operation Procedure Guide
2.4.1Manual Operation Procedure 1
Note: Never manually operate the transfer switch when
the power is connected. Disconnect both power
sources before manually operating the switch.
1. 100-200 amp switches: These switches have an
attached handle as shown in Figure 2-4.
400 amp switches: Slide the detachable handle or
a wrench over the shaft. See Figure 2-5.
2. Move the handle up to place the transfer switch in
the Normal Source position or down to place the
contactor in the Emergency Source position. See
Figure 2-4 or Figure 2-5.
3. 400 amp switches: Remove the detachable handle
or wrench.
SCE
NC
NO
C
7
8
CE
EL2EL1
1
1. Handle (not detachable)
Figure 2-4Manual Operation, 100 and 200 Amp
Single-Phase Switches
1
GM80139
1. Shaft (attach handle or wrench here)
Figure 2-5Manual Operation, 400 Amp Single-
Phase and 208--240 Volt Switches
2.4.2Manual Operation Procedure 2
Note: Never use the maintenance handle to transfer the
load with the power connected. Disconnect both
power sources before manually operating the
switch.
1. If thetransfer switch isequipped with a
maintenance handle, remove the handle from its
storage location inside the enclosure.See
Figure 2-7.
TP-6807 12/1115Section 2 Installation
2. Insert the maintenance handle or a tool (such as a
screwdriver) into the hole in the shaft on the left
side of the operator as shown in Figure 2-6 or
Figure 2-7.
3. Move the maintenance handle (or tool) up or down
as shown to manually operate the transfer switch. It
should operate smoothly without any binding. If it
doesnot,checkforshippingdamage or
construction debris.
2.5Electrical Wiring
Refer to the connection diagrams on the transfer switch
enclosure door and the wiring diagrams in Section 6
during installation.
All wiring must comply with applicable national, state,
and local electrical codes. Use separate conduit for AC
power wiring and low-voltage DC, control, and
communication system wiring.
4. Return the transfer switch to the Normal position.
5. Remove the maintenance handle and return it to the
storage location.
1
GM78867
1. Insert handle or tool here for manual operation
Figure 2-6Manual Operation, 100--200 Amp
3-Phase Switches
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
Making line or auxiliary connections. Hazardous voltage
can cause severe injury or death. To prevent electrical
shock deenergize the normal power source before making any
line or auxiliary connections.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set and related equipment and electrical circuits.
Turn off the main circuit breakers of all power sources before
servicing the equipment. Never contact electrical leads or
appliances when standing in water or on wet ground because
these conditions increase the risk of electrocution.
2.5.1Load Center Circuit Breakers
1
2
1. Handle storage location
2. Insert handle here for manual operation
Figure 2-7Manual Operation, 400 Amp 3-Phase
Switches
The 100 amp Model RXT transfer switch is available
with a built-in load center with room for up to 16
single-pole circuit breakers. Up to 8 tandem breakers
can be used for a maximum of 24 circuits.
The load center uses Square D type QO or QOT tandem
breakers. In an essential load application, the breakers
can be moved from the main panel to the load center if
the main distribution panel uses the same type of
breakers. Otherwise, obtain and install new Square D
type QO circuit breakers. The rating of the load center
circuit breaker must match the rating of the existing
breaker in the main panel for each circuit. If circuit
breakers are removed from the load panel, install cover
plates over the vacant positions. Cover plates can be
obtained from a local Square D supplier.
tp6225
Verifythat the total rating for all breakers used in the load
center does not exceed the rating of the transfer switch.
TP-6807 12/1116 Section 2 Installation
2.5.2AC Power Connections
Determine the cable size. Refer to Figure 2-8 or the
ADV drawings in Section 6 to determine the cable size
required for the transfer switch. Make sure the lugs
provided are suitable for use with the cables being
installed.
Conduit. Use separate conduit for AC power wiring
and low-voltage DC, control, and communication
system wiring. Watertight conduit hubs may be required
for outdoor use.
Select the proper cable clamp or use other approved
methods for securing the cable or conduit to the
enclosure.
Source and load connections. Clean cables with a
wire brush to remove surface oxides before connecting
them to the terminals. Apply joint compound to the
connections of any aluminum conductors.
Refer to the connection diagrams on the transfer switch
enclosure door and the wiring diagrams in Section 6.
The connection points on the transfer switch contactor
are labelled Normal, Emergency, and Load. Connect
the utility power to Normal. Connect the generator set to
Emergency.
Single phase. For single-phase models, connect to A
and C.
Three phase.For three-phase models, be sure to
follow the phase markings (A, B, C, and N).
Note: Connect the source and load phases as indicated
by the markings and drawings to prevent short
circuits and to prevent phase-sensitive devices
from malfunctioning or operating in reverse.
Service entrance models. Connect the utility source to
the lugs on the normal source disconnect circuit
breakers as shown in the service entrance switch wiring
diagram in Section 6.
Verify that all connections are consistent with drawings
before tightening the lugs.Tighten all cable lug
connections to the torque values shown on the label on
the switch.Carefully wipe off any excess joint
compound after tightening the terminal lugs.
On models with built-in load centers, the load lugs are
factory-wired to the load center. Connect the load leads
to the circuits in the load center and tighten the
connections. Check the labels on the breakers for the
tightening torques.
TP-6807 12/1117Section 2 Installation
2.5.3Neutral Connection
2.5.5Engine Start Function
Connect the neutral from the main panel to the neutral
lug in the ATS enclosure.
Ground the system according to NEC and local codes.
2.5.4Neutral Bonding Jumper, Service
Entrance Models
Thetransferswitchisshippedwiththe
neutral-to-ground jumper installed.For non-service
entrance applications, disconnect the neutral-to-ground
bonding jumper. See the transfer switch dimension
drawing.
Cable Sizes
AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections
The engine start function is controlled by the RDC2/DC2
controller on the generator set. There are no engine
start terminals on the Model RXT ATS.
Range of Wire Sizes, Cu/Al
per customer-supplied
circuit breaker
(1) #6 – 250 MCM(3) #6 – 250 MCM(3)#14–1/0AWG
(2) #6 – 250 MCM
(1) #4 – 600 MCM
(2) #6 – 250 MCM
(1)#2–2/0AWG(9)#4–14AWG
(3) #4 AWG – 600 MCM
(6) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3) #4 – 600 MCM
(6) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3)#6–3/0AWG
(3)#14–1/0AWG
TP-6807 12/1118 Section 2 Installation
2.5.6Interface Module Connection
See Figure 2-9 and Figure 2-10. Use 20 AWG Belden
#9402, 8723, or equivalent shielded, twisted-pair cable
The interface module must be connected to a Kohlerr
generator set equipped with the RDC2 or DC2
controller. The generator set is typically equipped with a
field-connection terminal block. See the generator set
to connect P10-1 through P10-4 on the controller
interface module to the generator set terminal block
connections A, B, PWR, and COM. The maximum cable
length is 61 meters (200 ft.).
Installation Manual for the location of the terminal block.
Alternatively, 12--14 AWG wire can be used for the PWR
Note: This document gives connection information for
one Model RXT transfer switch connected to a
generator set equipped with an RDC2 or DC2
controller. If additional accessory modules such
as a programmable interface module (PIM) or a
and COM connections only. If 12--14 AWG wire is used
for the PWR and COM connections, the maximum cable
length is 152 m (500 ft.) if one Model RXT transfer
switch and no accessory modules are connected to the
generator set.
load control module (LCM) are connected, refer
to the generator set installation manual for cable
requirements and connection instructions.
Note: Connections 3 and 4 on the generator set are not
used with the Model RXT transfer switch.
20 AWG shielded twisted-pair,
Belden 9402, 8723, or equivalent
20 AWG shielded twisted-pair Belden 9402
or 12--14 AWG wire
Figure 2-9Controller Interface Connections
Connect one end of each cable shield to
GROUND at the generator set.
GND
Generator Set
A
B
PWR
COM
4
3
TB1
Generator Set Terminal Block TB1.
See the generator set manuals for location.
Check the decal on the generator set for terminal
block connections.
A
B
PWR
COM
1
Note: Generator set terminal block connections 3 and 4 are
NOT USED with the Model RXT ATS.
Interface Board on the Model
RXT Transfer Switch
A
B
PWR
COM
Leave one end of each cable shield disconnected.
If accessory modules are connected in series, connect
the cable shields as shown below and refer to the
generator set installation manual.
RXT
RXT
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
Figure 2-10 Interface Module Connection to Generator Set Field-Connection Terminal Block
TP-6807 12/1119Section 2 Installation
2.5.7Optional Load Control Connection
2.5.8Accessory Module Connections
Connector P11 on the interface module provides a
connection point for optional load control circuits. The
load control contact provides a delayed contact closure
to allow startup of selected loads 5 minutes after transfer
to the emergency power source (generator set). Use
this contact to delay startup of equipment with large
motor-starting loads such as air conditioners.
See Figure 2-11 for the location of load control
connector P11. See Figure 2-12 for contact ratings,
connection, and wire size information.
Note: An optional load control module is available for
generator sets equipped with the RDC2 or DC2
controller.The load control module allows
management of up to six separate loads (two
HVAC thermostat connections and four other
non-essential loads). See TT-1574, Load Control
Module Instructions.
For connection of the optional load control module
(LCM) or programmable interface module (PIM), refer to
the instructions provided with the modules and to the
generator set installation manual.
2.6Test and Exercise
Refer to the generator set Operation Manual for
instructions to test the power system operation and to
set the RDC2 or DC2 controller for weekly exercise runs
to keep the power system in good operating condition.
2.7Warranty Registration
Startup Notification Form. The Startup Notification
Form covers all equipment in the standby system.
Complete the Startup Notification Form and register the
equipment in the Kohler online warranty system within
60 days of the initial startup date. Standby systems not
registered within 60 days of startup are automatically
registered using the manufacturer’s ship date as the
startup date.
The Model RXT transfer switch must be connected to a
generator set equipped with the RDC2 or DC2
controller.The RDC2/DC2 generator set/transfer
switch controller manages automatic transfer switch
(ATS) functions when connected to a Kohlerr Model
RXT transfer switch through the ATS interface board.
The controller receives voltage sensing data from the
Model RXT ATS and operates the generator set and
transfer switch to provide standby power when utility
power is lost.
See the generator set operation manual for:
D ATS status screens and configuration menus.
D Information about loaded exercise.
3.2Source Availability
The Model RXT transfer switch supplies voltage
sensing data to the RDC2 or DC2 controller through the
ATS interface board. If the source voltage falls below
the undervoltage dropout setting, the source is
considered to have failed. See Figure 3-1.
Voltage Sensing ParameterSetting
Accuracy±5%
Undervoltage Dropout90% of Pickup
Undervoltage Pickup90% of Nominal
3.3ATS Control Sequence of
Operation
See Figure 3-2 for time delay settings.
Preferred Source Fails:
1. The load control contact opens.
2. The engine start time delay times out.
3. The generator set is signaled to start.
4. The generator starts and the emergency source
becomes available.
5. The normal-to-emergency time delay times out.
6. The transfer switch transfers to the emergency
source.
7. The load control contact time delay times out.
8. The load control contact closes.
Normal Source Returns:
1. The emergency-to-normal time delay times out.
2. The contactor transfers to the normal source.
3. The engine cooldown time delay times out.
4. The generator is signaled to stop.
Figure 3-1Voltage Sensing Parameters
TP-6807 12/1121Section 3 Operation
3.4Time Delays
3.5Load Control Time Delay
Time delays are factory-set to the values shown in
Figure 3-2. An authorized distributor/dealer can adjust
time delays using a personal computer and Kohlerr
SiteTecht software.
The load control time delay allows delayed starting of
large motor loads (such as air conditioners), preventing
simultaneous starting of large motors after transfer to
the generator set. The load control time delay is fixed at
5 minutes. It is not adjustable.
Time delays described in this section operate only when
the RDC2 or DC2 generator set controller is connected
to a Kohlerr Model RXT transfer switch.
The load must be connected to the load control output
on the interface board of the Model RXT transfer switch.
See the transfer switch operation and installation
The engine start and load transfer time delays prevent
manual for connection instructions.
engine start and load transfer caused by brief variations
in the utility power source.
Note: A separate load control module (LCM) that
provides four power relays and two HVAC relays
is available for generator sets equipped with the
RDC2 or DC2 controller. See LCM Specification
Sheet G6-120 for more information.
Time DelaySettingDescription
Engine Start3 secondsTime delay after utility source is lost until the engine start cycle begins.
Transfer, Normal to Emergency3 secondsTime delay after emergency source becomes available until transfer to
Transfer, Emergency to Normal2 minutesTime delay after the utility source returns until transfer back to normal.
Load Control5 minutesAllows delayed connection of selected loads to the generator set.
Guards against starting the generator set because of a brief change in
the utility source.
emergency source.
Ensures that the the utility source is stable before transferring from the
emergency source.
Prevents simultaneous starting of large motors after transfer to the
emergency source. Recommended for delayed starting of air
conditioners.
Figure 3-2Time Delays
TP-6807 12/1122 Section 3 Operation
Section 4 Service Disconnect, SE Model
Note: This section applies only to service entrance
model transfer switches, which are identified with
the letters ASE at the end of the model
designation.
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
4.1Service Disconnect Procedure
Use the following procedure to disconnect the utility
source on service entrance model transfer switches.
Note: Power is still present on the input side of the utility
source circuit breaker after this procedure.
4.2Source Circuit Breaker Reset
The utility source circuit breaker can trip due to an
overcurrent condition. Identify and correct the cause of
the overcurrent condition before resetting the circuit
breaker. Contact a local distributor/dealer for service if
necessary.
When the circuit breaker trips, the handle moves to an
intermediate position. To reset a tripped circuit breaker,
move the handle to the extreme OFF position and then
to the ON position.
1
1. Prevent the emergency generator set from
starting:
a. Press the OFF button on the generator set
controller.
b. Disconnect power to the generator set battery
charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
2. On the transfer switch, remove the outer enclosure
door only.
3. Move the utility source circuit breaker to the OFF
position.
Note: Power is still present on the input side of the
utility source circuit breaker. Do not remove
the protective barrier around the utility
source connection lugs.
4. To lock out the transfer switch, replace the outer
door and attach a padlock to the hasp.
GM80015
2
1. Normal/utility circuit breaker
2. Padlock hasp
Figure 4-1Service Entrance Model, Door Removed
TP-6807 12/1123Section 4 Service Disconnect, SE Model
Notes
TP-6807 12/1124 Section 4 Service Disconnect, SE Model
Section 5 Scheduled Maintenance
5.1Introduction
Regular preventive maintenance ensures safe and
reliable operation and extends the life of the transfer
switch.Preventive maintenance includes periodic
testing, cleaning, inspection, and replacement of worn
or missing components. Section 5.4 contains a service
schedule for recommended maintenance tasks.
A local authorized distributor/dealer can provide
complete preventive maintenance and service to keep
the transfer switch in top condition. Unless otherwise
specified, have maintenance or service performed by an
authorized distributor/dealer in accordance with all
applicable codes and standards.See the Service
Assistance section in this manual for how to locate a
local distributor/dealer.
Keep records of all maintenance or service.
Replace all barriers and close and lock the enclosure
door after maintenance or service and before reapplying
power.
WARNING
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnectthe power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Grounding the transfer switch. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Open main circuit breakers of
all power sources before servicing equipment. Configure the
installation to electrically ground the transfer switch and
related equipment and electrical circuits to comply with
applicable codes and standards. Never contact electrical
leads or appliances when standing in water or on wet ground,
as the chance of electrocution increases under such
conditions.
Moving parts.
TP-6807 12/1125Section 5 Scheduled Maintenance
Servicing the transfer switch. Hazardous voltage can
cause severe injury or death. Deenergize all power sources
before servicing. Turn off the main circuit breakers of all
transfer switch power sources and disable all generator sets
as follows: (1) Move all generator set master controller
switches to the OFF position. (2) Disconnect power to all
battery chargers. (3) Disconnect all battery cables, negative
(--) leads first. Reconnect negative (--) leads last when
reconnecting the battery cables after servicing. Follow these
precautions to prevent the starting of generator sets by an
automatic transfer switch, remote start/stop switch, or engine
start command from a remote computer. Before servicing any
components inside the enclosure: (1) Remove all jewelry. (2)
Stand on a dry, approved electrically insulated mat. (3) Test
circuits with a voltmeter to verify that they are deenergized.
Short circuits.Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
NOTICE
Hardware damage.The transfer switch may use both
American Standard and metric hardware. Use the correct size
tools to prevent rounding of the bolt heads and nuts.
NOTICE
Electrostatic discharge damage. Electrostatic discharge
(ESD) damages electronic circuit boards.Prevent
electrostatic discharge damage by wearing an approved
grounding wrist strap when handling electronic circuit boards
or integrated circuits. An approved grounding wrist strap
provides a high resistance (about 1 megohm), not a directshort, to ground.
Screws and nuts are available in different hardness
ratings.To indicate hardness, American Standard
hardware uses a series of markings and metric
hardware uses a numeric system. Check the markings
on the bolt heads and nuts for identification.
5.2Testing
5.2.1Weekly Generator Set Exercise
D Watch and listen for signs of excessive noise or
vibration during operation.
D After the switch transfers the load to the standby
source, end the test and verify that the expected
sequence of operations occurs as the transfer switch
retransfers to the preferred source.
5.3Inspection and Service
Contact an authorized distributor/dealer to inspect and
service the transfer switch annually and also when any
wear, damage, deterioration, or malfunction of the
transfer switch or its components is evident or
suspected.
5.3.1General Inspection
External Inspection. Keep the transfer switch clean
and in good condition by performing a weekly general
external inspection of the transfer switch. Check for any
condition of vibration, leakage, excessive temperature,
contamination, or deterioration. Remove accumulations
of dirt, dust, and other contaminants from the transfer
switch’s external components or enclosure with a
vacuum cleaner or by wiping with a dry cloth or brush.
Note: Do not use compressed air to clean the transfer
switch because it can cause debris to lodge in the
components and damage the switch.
Tighten loose external hardware. Replace worn, missing,
or broken external components with manufacturerrecommendedreplacementparts.Contactan
authorizeddistributor/dealerforspecificpart
information and ordering.
Internal Inspection. Disconnect all power sources,
open the transfer switch enclosure door, and inspect
internal components monthly or when any condition
noticed during an external inspection may have affected
internal components.
Use the exerciser or a manual test to start and run the
generator set under load once a week to maximize the
reliability of the emergency power system.
5.2.2Monthly Automatic Control
System Test
Test the transfer switch’s automatic control system
monthly. Refer to the RDC2/DC2 controller operation
manual for the test procedure.
D Verify that the expected sequence of operations
occurs as the switch transfers the load to the
emergency source when a preferred source failure
occurs or is simulated.
Contact an authorized distributor/dealer to inspect and
service the transfer switch if any of the following
conditions are found inside the transfer switch.
D Accumulations of dirt, dust, moisture, or other
contaminants.
D Signs of corrosion.
D Worn, missing, or broken components.
D Loose hardware.
D Wire or cable insulation deterioration, cuts, or
abrasion.
TP-6807 12/1126 Section 5 Scheduled Maintenance
D Signsofoverheatingorlooseconnections:
discoloration of metal, melted plastic, or a burning
odor.
operation of the transfer switch.See Section 5.4,
Service Schedule, for the recommended maintenance
items and service intervals.
D Other evidence of wear, damage, deterioration, or
malfunction of the transfer switch or its components.
Have an authorized distributor/dealer repair or replace
damagedorworninternalcomponentswith
manufacturer-recommended replacement parts.
If the application does not allow a power interruption for
the time required for the internal inspection, have an
authorized distributor/dealerperformthe internal
inspection.
5.4Service Schedule
Follow the service schedule in Figure 5-1 for the
recommended service intervals.Have all service
performed by an authorized distributor/dealer except for
activities designated by an X, which may be performed
by the switch operator.
maintenance that ensures the safe and reliable
Adjust,
Repair,
Replace
CleanTestFrequency
D (clean
and lube)
Y
System Component or Procedure
See
Section
Visually
Inspect
Check
Electrical System
Check for signs of overheating or loose connections:
discoloration of metal, melted plastic, or a burning odor
Check the contactor’s external operating mechanism
for cleanliness; clean and relubricate if dirty *
Inspect wiring insulation for deterioration, cuts, or
abrasion. Repair or replace deteriorated or damaged
wiring
Tighten control and power wiring connections to
specifications
Check the transfer switch’s main power switching
contacts’ condition; clean or replace the main contacts
or replace the contactor assembly as necessary
5.3.1XXY
5.3.1X
5.3.1XDDY
2.5DDY
S/MDDDY
General Equipment Condition
Inspect the outside of the transfer switch for any signs
of excessive vibration, leakage, high temperature,
contamination, or deterioration *
Check that all external hardware is in place, tightened,
and not badly worn
Inspect the inside of transfer switch for any signs of
excessive vibration, leakage, high temperature,
contamination, or deterioration *
Check that all internal hardware is in place, tightened,
and not badly worn
* Service more frequently if the transfer switch is operated in dusty or dirty areas.
See Section: Read these sections carefully for additional information before attempting maintenance or service.
Visually Inspect: Examine these items visually.
Check: Requires physical contact with or movement of system components, or the use of nonvisual indications.
Adjust, Repair, Replace: Includes tightening hardware and lubricating the mechanism. May require replacement of components
depending upon the severity of the problem.
Clean: Remove accumulations of dirt and contaminants from external transfer switch’s components or enclosure with a vacuum cleaner or
by wiping with a dry cloth or brush. Do not use compressed air to clean the switch because it can cause debris to lodge in the components
and cause damage.
Test: May require tools, equipment, or training available only through an authorized distributor/dealer.
Symbols used in the chart:
X=The transfer switch operator can perform these tasks.
D=Authorized distributor/dealer must perform these tasks.
W=Weekly
M=Monthly
5.3XXM
5.3XXXM
5.3DDDY
5.3XDDY
Q=Quarterly
S=Semiannually (every six months)
Y=Yearly (annually)
W/D=Wiring diagram
Figure 5-1Service Schedule
TP-6807 12/1127Section 5 Scheduled Maintenance
Notes
TP-6807 12/1128 Section 5 Scheduled Maintenance
Section 6 Diagrams and Drawings
Diagram or DrawingDrawing NumberPage
Single-Phase
Enclosure Dimension Drawings
100--200 Amp Single-Phase
Sheet 1ADV-8190 1 of 230........................................................
Sheet 2ADV-8190 2 of 231........................................................
100 Amp Single-Phase with Load CenterADV-819741..............................
Figure 6-23 Wiring Diagram, 100 Amp Single-Phase with Load Center, GM80675
TP-6807 12/1152 Section 5 Diagrams and Drawings
Figure 6-24 Schematic Diagram, 100 Amp Single-Phase with Load Center, GM80676
TP-6807 12/1153Section 5 Diagrams and Drawings
Notes
TP-6807 12/1154 Section 5 Diagrams and Drawings
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCadvanced digital control;
adj.adjust, adjustment
ADVadvertising dimensional
Ahamp-hour
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APDCAir Pollution Control District
APIAmerican Petroleum Institute
approx.approximate, approximately
AQMDAir Quality Management District
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CANcontroller area network
CARBCalifornia Air Resources Board
CBcircuit breaker
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American
Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dB(A)decibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., °degree
dept.department
DFMEADesign Failure Mode and
EPSemergency power system
ERemergency relay
ESengineering special,
ESDelectrostatic discharge
substrate (semiconductor)
Association
Laboratories
Laboratories
Effects Analysis
e. V. (also Deutsche Industrie
Normenausschuss)
engine control module
Association
Association
Agency
engineered special
est.estimated
E-Stopemergency stop
etc.et cetera (and so forth)
exh.exhaust
ext.external
FFahrenheit, female
fglass.fiberglass
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ftpfile transfer protocol
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temp., high
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPiron pipe
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
ground
engine temp.
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
TP-6807 12/11Appendix 55
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
10
bytes)
KBusKohler communication protocol
kgkilogram
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, kΩ kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
kWthkilowatt-thermal
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
ld. shd.load shed
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
LWLlow water level
sound power level, A weighted
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
3
m
3
m
3
m
units), male
cubic meter
/hr.cubic meters per hour
/min.cubic meters per minute
bytes)
MCCBmolded-case circuit breaker
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mΩ milliohm
MOhm, MΩmegohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
msmillisecond
m/sec.meters per second
MTBFmean time between failure
MTBOmean time between overhauls
mtg.mounting
MTUMotoren-und Turbinen-Union
MWmegawatt
mWmilliwatt
μFmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
NCnormally closed
NECNational Electrical Code
NEMANational Electrical
Manufacturers Association
NFPANational Fire Protection
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
(screw)
PHHPhillipsr hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
psigpounds per square inch gauge
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTUremote terminal unit
RTVroom temperature vulcanization
RWread/write
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SNserial number
SNMPsimple network management
protocol
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
specspecification
specsspecification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SSstainless steel
std.standard
stl.steel
tach.tachometer
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
THDtotal harmonic distortion
TIFtelephone influence factor
TIRtotal indicator reading
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
w/owithout
wt.weight
xfmrtransformer
TP-6807 12/1156 Appendix
Notes
TP-6807 12/1157
Notes
TP-6807 12/1158
TP-680712/11
E 2011 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.