:
II TS_619_00 PW9000DPA S2 User Manual 13/3/17
3.4.4 UPS Power connections 3-32
3.4.5 Battery configuration 3-33
External battery enclosure with separate battery configuration 35
External battery enclosure with common battery configuration 36
3.5 UPS Cabling procedure 3-37
3.5.1 Safety notes 3-37
3.5.2 Preparing the UPS power cabling 3-37
3.5.3 Connecting the UPS AC power cables 3-37
3.5.4 Connecting the battery cables 3-38
3.6 Customer Interface Board 3-38
3.6.1 Customer dry-port interface terminal block – X1 3-38
3.6.2 Customer interface output terminals – X2, X3, X4 3-39
3.7 Parallel-cabinet control and configuration 3-40
3.7.1 Parallel control bus 3-40
3.7.2 Multidrop 3-40
Operating Procedures 41
4.1 Introduction 4-41
4.1.1 Commissioning 4-41
4.1.2 Operating procedure summary 4-41
4.1.3 General warnings 4-42
4.2 Operating instructions 4-42
4.3 How to start the UPS system from a fully powered-down condition 4-42
4.4 How to start the UPS system from the maintenance bypass 4-44
4.5 How to transfer the load to maintenance bypass 4-45
4.6 How to shut down the complete UPS system 4-46
4.7 Operating in ‘on bypass’ mode 4-47
4.7.1 How to Turn ON the UPS in ‘on bypass’ mode 4-47
4.7.2 How to Turn OFF the UPS in ‘on bypass’ mode 4-47
4.7.3 How to transfer between ‘on bypass’ and ‘on inverter’ mode 4-47
Maintenance 48
5.1 Introduction 5-48
5.2 Scheduled maintenance 5-48
5.2.1 Preventative maintenance inspection 5-48
5.2.2 System calibration 5-48
5.2.3 Battery maintenance and testing 5-49
Troubleshooting 50
6.1 Alarms 6-50
6.2 Menu, Commands, Event Log, Measurements, 6-50
6.3 Fault identification messages and alarms 6-51
6.4 Contacting service 6-51
Options 52
7.1 Introduction 7-52
7.2 Customer interface board 7-53
7.2.1 Remote shut down customer input 7-53
7.2.2 Generator ON customer input 7-53
7.2.3 Battery temperature sensor 7-54
7.2.4 RS232 Computer serial interface – JD11 & USB 7-54
7.2.5 RS232 Interface for multidrop – JD12 7-54
7.2.6 SNMP/ CS141 slots – SLOT 1/ SLOT 2 7-55