Kohler l654 Service Manual

RV GENERATOR
SERVICE MANUAL
3.5KW-7.5KW
(with relay controller)
KOHLER -
GENERATORS ,.’
Page
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . .
i
Section 1. Introduction and Specifications
l-l. l-2. l-3. l-4. l-5. 1-6. l-7. 1-8. 1-9.
Introduction
............................. l-l
Model 3.5 CM21-RV
...................... l-l
Model 4.5 CM21-RV (single)
.............. l-l
Model 4.5CKM21-RV (twin)
............... 1-I
Model 5.5 CM21-RV
......................
l-l
Model 7 CM21-RV
........................ l-l
Model 7.5 C21-RV
........................
1-2
Oil Specifications
........................ l-4
Fuel Specifications
.......................
l-5
Section 2. Operation
2-1. General.
......................... 2-1
2-2. Prestart Checklist
................... 2-1
2-3.
Operation
........................ 2-l
Section 3. Scheduled Maintenance
Governor
3-1.
General.
......................... 3-1
3-2.
Scheduled Maintenance
............... 3-I
Section 4. Troubleshooting
4-l. General.
........................ .4-l
4-2.
RV Systems Check
.................. 4-1
4-3. Troubleshooting
.................... 4-2
Section 5. Relay Controller
5-l. 5-2.
5-3. 5-4. 5-5.
Description
....................... 5-1
Sequence of Operation
............... 5-l
Fuses
........................... 5-4
REl Diode
....................... 5-5
Relays
.......................... 5-5
Page
Section 6. Generator
6-l. General
..........................
6-1
6-2. Troubleshooting .................... 6-1
6-3. Generator Disassembly ............... 6-l
6-4. Build-up Circuit
.................... 6-7
6-5. Brushes .......................... 6-8
6-6. Slip Rings
........................ 6-9
6-7. Exciter / Voltage Regulator ............ 6-9
6-8. Stator .......................... 6-I 1
6-9. Rotor. ......................... 6-11
6-10. Separate Field Excitation ............. 6-11
6-11. Voltage Sensing Relay ............... 6-12
6-l 2. Generator Reassembly ............... 6-12
Section 7. Choke, Shutdown Control and
7-1.
7-2.
7-3. 7-4. 7-5. 7-6 7-7. 7-8. 7-9.
Choke Testing and Adjustments
(3.5kW,4.5kW). . . . . . . . . . . . . . . . . . . . 7-1
Choke Testing and Adjustments
(4.5 twin, 5.5,7, 7.5kW) . . . . . . . . . . . . . 7-3
Positive Shutdown Control (3.5kW-7kW) . . . . 7-3
Crankcase Breather (3.5kW, 4.5kW) . . . . . . . 7-4
Governor (3.5kW, 4.5kW single). . . . . . . . . . 7-4
Governor Hunting Checks (4.5kW Only) . . . . 7-5
Governor (4.5kW twin). . . . . . . . . . . . . . . . 7-6
Governor (5.5kW, 7kW) . . . . . . . . . . . . . . . 7-6
Governor (7.5kW) . . . . . . . . . . . . . . . . . . . 7-7
Section 8. Wiring Diagrams
Appendix
Radio Frequency Interference Kit.. . . . . . . . . A-l
Safety Precautions
A Generator Set, like any other electro-mechanical device can pose potential dangers to life and limb if improperly maintained or imprudently operated. The best safeguards against accident are to be ever mindful of the potential dangers and to always use good common sense. In the interest of safety, some general precautions relating to operating of a Generator Set are presented below. Keep
these in mind.
A
WARNING
LETHAL EXHAUST GAS! An engine discharges deadly
carbon monoxide as part of the exhaust when operating.
Carbon monoxide is particularly dangerous in that it is an odorless, tasteless, and nonirritating gas, but be ever mindful that it can cause death if inhaled for even a short period of time. Have only qualified specialists install and replace exhaust system components and have the system inspected frequently. Be careful when parking your coach to avoid obstructing the exhaust outlet. The exhaust gasses must discharge freely, otherwise carbon monoxide may deflect under and into the vehicle or enter through open doors, windows, or vents. Also make sure that your exhaust cannot be discharged toward neighboring RV’s, campers, or any occupied building. Be especially watchful
for exhaust accumulation under calm, windless condi­tions.
A
WARNING
ELECTRICAL SHOCK! Battery can cause electrical burns
and shocks. Exercise reasonable care when working near the battery to avoid electrical connections through tools. Remove wristwatch, rings, and any other jewelry.
A
WARNING
HIGH VOLTAGE! Remember that the function of a genera-
tor set is to produce electricity and that wherever electric­ity is present, there is the potential danger of electrocu­tion. Take the same precautions with electrical appliances in your coach that you would observe in your home. Keep away from electrical circuits and wiring while the set is running and have electrical service performed only by qualified electricians. Make sure unqualified persons, especially children, cannot gain access to your set - keep the compartment door locked or securely latched at all times. Be sure that generator is properly grounded. Never touch electrical leads or appliances with wet hands, when standing in water, or on wet ground as the chance of electrocution is especially prevalent under such con­ditions.
A
WARNING
UNIT STARTS WITHOUT NOTICE! To prevent accidental
starting on units with a remote start/stop switch, always disconnect battery (remove negative lead first and recon­nect it last) to disable generator set before working on any equipment connected to generator.
A
WARNING
DANGEROUS ACID! Avoid contact with battery electro-
lyte. It contains acid which can eat holes in clothing, burn skin, and cause permanent damage to eyes. Always wear splash-proof safety goggles when working around the battery. If battery electrolyte is splashed in the eyes or on skin, immediately flush the affected area for 15 minutes with large quantities of clean water. In the case of eye contact, seek immediate medical aid. Never add acid to a battery once the battery has been placed in service. Doing so may result in dangerous spattering of electrolyte.
.A WARNING
EXPLOSIVE t3ATTERY GASES! The gases generated by a battery being charged are highly explosive. Do not smoke
or permit flame or spark to occur near a battery at any time, particularly when it is being charged. Avoid contact­ing terminals with tools, etc., to prevent burns and to prevent sparks that could cause an explosion. Remove wristwatch, rings, and any other jewelry before handling battery. Any compartment containing batteries should be
...
well ventilated to prevent accumulation of explosive gases. To avoid sparks, do not disturb battery charger connec­tions while battery is being charged and always turn charger off before disconnecting battery connections. Turn automotive test equipment off when connecting or removing battery clips. When removing or reconnecting battery cables, make sure ignition switch and all accesso­ries are turned off.
A
WARNING
EXCESSIVE NOISE! Never operate without adequate
muffler or with faulty exhaust system - exposure to excessive noise is not only tiring but can lead to impair­ment of hearing.
A
WARNING
HOT PIPING! An engine gets hot while running and
exhaust system components get extremely hot. Do not work on generator set until unit is allowed to cool.
A
WARNING
DANGEROUS FUELS! Use extreme caution when hand-
ling, storing, and using fuels - all fuels are highly explosive in a vapor state. Store fuel in a well-ventilated area away from spark producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running to prevent spilled fuel from igniting on contact with hot parts or from ignition spark. Keep fuel lines and connections tight and in good condition - don’t replace flexible fuel lines with rigid lines. Flexiblesections
are used to avoid breakage due to vibration. Should any fuel leakage, fuel accumulation, or electrical sparks be noted, DO NOT OPERATE GENERATOR SET. Have sys-
terns repaired by qualified specialists before resuming generator operation. Additional precautions should be taken when using the following fuels:
Gasoline-Store gasoline only in approved red containers clearly marked GASOLINE. Don’t store gasoline in .any occupied building.
Propane (LP)-Adequate ventilation is mandatory. Pro- pane is heavier than air; install gas detectors low in room. Inspect detectors often.
A
WARNING
UNINTENTIONAL STARTING! To prevent accidental
starting when checking choke operation, remove spark plug lead(s) at spark plug(s).
A
WARNING
FLASH FIRE! A sudden flash fire can cause serious burns.
To avoid the possibility of a flash fire, do not smoke or permit flame or spark to occur near carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuel or fuel vapors.
A
WARNING
ELECTROCUTION! Your RV generator set must not be
used to “backfeed” by connecting it to building/camp­ground electrical circuits. Doing so can cause serious injury or death to utility personnel working on utility transmission lines and may also seriously injure persons in your household. Unauthorized connection may be unlawful in some states and/or localities. A transfer switch must be installed in the RV to prevent interconnection of generator and outside source of power.
A
WARNING
BACKFIRE! A sudden backfire can cause serious burns.
Keep hands and face away from the carburetor when the air cleaner is removed.
A
WARNING
FIRE HAZARD! Keep the compartment and generator set
clean and free of debris to minimize chances of fire. Also remember that hot exhaust gases and exhaust system parts could start grass fires. Keep away from hot engine and generator parts’to avoid burning yourself.
A
WARNING
MOVING PARTS! Do not open generator set compartment
door when unit is running, except for servicing by quali­fied specialists. Replace guards, covers, and screens (if used) before operating generator set.
A
WARNING
HIGH VOLTAGE! When the power cord is plugged in
during voltage regulator test, the AC pins become “hot” and there is danger of electrocution.
A
WARNING
EXPLOSION! Use generator sets specified for RV use in RV
installations only.
Section 1.
Introduction and Specifications
l-l. INTRODUCTION
This manual covers operation, scheduled maintenance troubleshooting and corrective maintenance for Kohler gen­erator sets designed and built for recreational vehicles. The
six standard models are the 3.5CM21 -RV, 4.5CM21-RV,
4.5CKM21 -RV, 5.5CM21 -RV, 7CM21 -RV and 7.5C21 -RV. These models are referred to by their kilowatt output,
3.5kW, 4.5kW (single), 4.5kW (twin), 5.5kW, 7kW and
7.5kW. Differences between models are noted throughout
the manual. All models feature Kohler designed and built 4-cycle gasoline engines, rotating field generators and relay
controllers. See Table l-l for specifications and model vari­ations, Table 1-2 for dimensions and weight, and Table l-3
for engine specifications. Refer to the wiring diagrams in
the back of the manual. I-2. MODEL 3.5CM21-RV The 3500 watt generator set is powered by a single
cylinder model K181 QS engine. The set produces 120 volt, 29 amp alternating current. It has a rotor with two magnetic poles and operates at 3600 R.P.M., producing 60 hertz or 3000 R.P.M., producing 50 hertz, 13 amp current. A 30 amp circuit breaker protects the set from overload damage. Due to its compact size and lightweight, it is installed in RV’s with limited suspension support and compartment space. See Figure l-l for major components.
1-3. MODEL 4.5CM21-RV
The 4500 watt generator set is powered by a single cylinder Kohler Model K341QS engine. The set produces
Model
3.5CM21-RV
3.5CM61-RV
3.5CFM21-RV
3.5CFM61-RV
4.5CM21:RV
4.5CM61 -RV
4.5CFM21-RV
4.5CFM61-RV
4.5CKM21 -RV
4.5CKM61 -RV
5.5CM21
5.5CM61
5.5CFM21
5.5CFM61 7CM21 7CM61
7.5C21
7.5C61
Volts
Amps Per
Term in al Watts Freq. (HZ) RPM
120
29
3500 60 3600
120/240
14.5 3500 60
3600
120
26.6
3200 50
3000
120/240
13.3
3200
50
3000
120
37.5 4500 60
1800
120/240 18.8
4500 60 *
1800
120
30
3600 50 1500
120/240
15
3600
SO
1500
120 37.5 4500 60
1800
1201240
18.8
4500 60
1800
120
46
5500 60
1800
120/246 23 5500 . 60 1800
120 37.5 4500 50 1500
120/240
18.8 4500 ,50 1500
120 58
7000 60 1800
120/240 26
7000
60 ’ 1800
120
62.5
7500
60 1.800
120/240
31.3 7500
60 1800
120 volt, 37.5 amp alternating current. It has a rotor with four magnetic poles and operates at 1800 R.P.M., produc­ing 60 hertz. A 40 amp line circuit breaker protects generator against damage due to overload. See Figure l-2 for major components.
1-4. MODEL 4.5CKM21-RV
The 4500 watt generator set is powered by a two cylinder Kohler Model KT17 engine. The set produces 120 volts,
37.5 amp alternating current. It has a rotor with four mag­netic poles and operates at 1800 R.P.M., producing 60 hertz. Two 20 amp circuit breakers protect against damage due to overload. See Figure l-3 for major components.
1-5. MODEL 5.5CM21-RV
The 5500 watt generator set is powered by a two cylinder Kohler Model K582QS engine. The set produces 120 volt, 46 amp alternating current. It has a rotor with four magne-
tic poles and operates at 1800 R.P.M., producing 60 hertz.
A 50 amp circuit breaker (on most models) protects against damage due to overload. See Figure I-4for major compon­ents.
1-6. MODEL 7CM21-RV
The 7000 watt generator set is powdered by a two cylinder
Kohler Model K582QS engine. The’set produces 120 volt, 58 amp alternating current. It has a rotor with four magne­tic poles and operates at 1800 R.P.M., producing 60 hertz. A 60amp circuit breaker (on most models) protects against damage due to overload. See Figure I-4for major compon­ents.
. .
Wires, I
2 3
‘2
3 2 3 2 3 2 3
2 3 2 3 2 3
2 3
Phase
1
1
1
1 1 1 1 1
1 1
1 1 1 1 1 1
1 1
Table l-l. Generator Specifications
l-l
1-7. MODEL 7.5CZl-RV
The 7500 watt generator set is powered by a four cylinder
Kohler Model L654 liquid-cooled engine. Two 30 Amp circuit breakers protect the rotating field 60 Hertz genera-
torfrom overload. On the 7.X21 model-s, the set produces
120 volt, 62.5 amp alternating current. On the 7.5661 models, 120/240 volt, 31.3 Amp alternating current is produced. See Figure 1-5 for major components.
Specification
Weight (approximate)
3.5 Model
150 lb.
(68.0 kg)
4.5 Model (Single)
235 lb.*
(106.6 kg)
,
4.5 Model
KT17
Series II
5.5 Model 7.0 Model
7.5 Model
4
230 lb.**
315 lb. 334 lb.
470 lb.
(104.3 kg)
(142.9 kg)
(151.5 kg) (213.2 kg)
Length - Overall 22” 23- 13/26”
28-5/l 6”
26”
27-l/2”
43-l /4”
(55.9cm)
(60.5cm) (71.9 cm)
(66.Ocm)
(69.8cm) (109.8cm)
Width - Overall 13-3/4” 18-3/l 6” 1 20-3/4” 21-l/2”
(34.9cm) (46.2cm) 1 (52.7 cm)
(54.6cm)
Height - Overall 15-314” 19-l /I 6” 17-9/l 6”
20-3/8”
20-3/8” 25-l /4”
(40.0cm) (48.4cm) (44.6 cm)
(51.8cm)
(51.8cm) (64.1cm)
A
A
**KT17 Series I
*Earlier Models 250 I b.
235 lb. (106.3 kg)
(113.4 kg)
Table l-2. Dimensions and Weight
Specifications
Fuel Inlet Connection
Size
Battery Voltage Battery Amp Hr. Battery Ground
Battery Cranking
Current
3.5 Model
l/4” I.D.
12v
55
Negative
40 amps
4.5 Model (Single)
l/4” I.D.
12v
55 Negative
76 amps
4.5 Model (Twin)
7/l 6-20
U.N.F.
12v
55
Negative
76 amps
5.5 Model 7.0 Model
l/4” I.D. l/4” I.D.
12v
12v
55
55
Negative Negative
98 amps 98 amps
.
7.5 Model
7/l 6-20
U.N.F.
12v
90
Negative
120 amps
Battery Charging
Current
15 amps
7 amps
7 amps
7 amps 7 amps 4 amps
Engine Model
K181QS K34 1 QS KTI 7 K582QS K582QS L654
Breaker Point Gap
0.020” 0.016” to 0.012” to
0.020” 0.020” 0.015”
(0.51 mm)
0.020”
0.018”
(0.51 mm) (0.51 mm)
(.381mm)
(0.41 mm to
(0.30mm to
0.51 mm)
0.45mm)
RPM
3600 1800
1800
1800
1800
1800
Fuel System Choke
Automatic
Automatic
Automatic
Automatic Automatic
Automatic
Thermal/Electric Thermal/Electric Thermal/Electric Thermal./Electric Thermal/Electric Thermal/Electric
Spark Plug Gap
0.035” 0.035”
0 -025”
0.035” 0.035” .0.025”
(0.89mm)
(0.89mm)
(0.64mm) (0.89mm) (0.89mm)
(0.64mm)
Total Air
376cfm
396cfm
417cfm
675cfm
675cfm 1777cfm
Requirements ( 10.7m3/min.)
(11 .2m3/min.) (11 .7m3/min.) (19.1m3/min.)
(19.1 m3/min.) (49.75m3/min.)
Frequency Regulation
5% 5%
5%
5%
5% 5%
25% Load 0.35 gal/hr
0.52 gal/hr
0.40 gal/hr
0.55 gal/hr 0.56 gal/hr
0.7 gal/hr
g
(1.3 lts/hr) (2.0 lts/hr)
(1.5lts/hr)
(2.1 lts/hr)
(2.1 lts/hr)
(2.6 lts/hr)
._
‘;
5
50% Load
0.46 gal/hr 0.60 gal/hr
0.50 gal/hr
0.61 gal/hr
0.66 gal/hr 0.8 gal/hr
(1.7 lts/hr) (2.3 lts/hr)
(1 .9lts/hr)
(2.3 lts/hr)
(2.5 lts/hr)
(3.0 lts/hr)
v) c
s
75% Load 0.57 gal/hr
0.73 gal/hr
0.60 gal/hr
0.73 gal/hr 0.84 gal/hr
1.1 gal/hr
z
(2.2 lts/hr) (2.8 lts/hr) (2.3lts/hr)
(2.8 lts/hr)
(3.2 Its/h r)
(4.2 Its/hr)
l? .
100% Load
0.74 gal/hr
0.92 gal/hr
0.80 gal/hr
0.88 gal/hr 1.08 gal/hr
1.4 gal/hr
I I
(2.8 Itslhr) I
(3.5 Its/hr)
I
(3.0lts/hr) I
(3.3 lts/hr) ,
(4.1 lts/hr) ,
(5.3 lts/hr) ,
Table 1.3 Engine Specifications
1-2
AIR COOLING
SPARK
SHROUD
REMOTE
CIRCUIT
CL
CONTROL PROTECTOR
CONTROLLER
(HIDDEN) I
INTAKE
BATTERY -+@ /
POSITIVE
CONNECTION
GROUND STRAP
AIR EANER
BATTERY CHARGING RECTIFIER
REGULATOR
INTAKE
TIMING
SIGHT
HOLE
Figure 1-1. Service Side View of a Kohler 3500 Watt RV Generator Set
AIR
COOLING SHROUD
SPARK PLUG
DRY ELEMENT
AIR CLEANER
CIRCUIT
GOVERNOR
_
PROTECTORS\
REGULAT(
REMOTE CONTROL EC EPTAC L
iONTROLLER
START-STOP
SWITCH
BATTERY
POSITIVE
CONNECTION
I
STRAP
HARNESS PLUG
BREAKER POINT
FUEL
PUMP
AIR INTAKE
/ SCREEN
TIMING
SIGHT
HOLE
OIL FILL TUBE
AND DIPSTICK
,
AIR DISCHARGE
0lL DRAIN (UNDER UNIT)
Figure l-2. Service Side View of a Kohler 4500 Watt Single Cylinder RV Generator Set
BREATHER_
AIR DUCT
/
IGNITION
thtMtNT
EXHAUST
.d
~.
TUBE
..”
FUEL
LINE
i OIL FILL
CIRCUIT
?OTECTOR
FINS
VOLTAGE / EGULATOR
c
&j \ FUEL
PUMP
COOLING SLOTS
/
EQUIPMENT
GROUND
$p”
.:’ ,::. : ,, :.:::::,A~
:i:::::
,:*.
r
“’ :
./: >::: ;,.. 1’
,;:z>
. . .
..,,,,,.
’ CONTROLLER
Figure 1-3. Service Side View of a Kohler 4500 Watt Twin Cylinder RV Generator Set
AIR CLEANER
.
CARBURETOR
UST ES
CIRCUIT PROTECTORS
/
b=AA9TE CONTROL
ICEPTACLE
BREAKER POINT
COVER (ON
GOVENOR)
BATTERY
CHARGING
VOLTAGE
REGULATOR
GOVERNOR
EGULATOR
FULL-FLOW
OIL FILTER
CONTROLLER
OIL FILL TUBE
& DIPSTICK
‘OP
BLOWER
, Ah I I
HOUSING
/
SWITCH
GROUNDING
AIR
I
“ISCHARGE
BATTERY POSITIVE
Y
CONNECTION
MOUNTI
OIL DRAIN LOCATED
UNDER UNIT
Figure I-4. Service Side View of a Kohler 5500 or 7000 Watt RV Generator Set
I-4
l-8 OIL SPECIFICATIONS Use high quality detergent oil of API (American Petroleum
Institute) service class SF. Select viscosity based on the air temperature at the time of operation as shown below:
RECOMMENDED SAE VISCOSITY GRADES
!
I
I
I
I
I 1 I
'F -50 6
T 1 r I I
20
32 40 60 80 100
t
I I
T
I
I I
I
c-30 -20 -10
0 10 20 30 40
TEMPERATURE RANGE EXPECTED BEFORE NEXT OIL CHANGE
l
Straight 30 weight oil is preferred. If multi-viscosity is used, be aware of the resulting increase in oil consump­tion and combustion deposits when used in temperatures above 32’ F (0” C).
I
Using other than service class SF oil, or extending oil change intervals longer than recommended could cause engine damage which is not covered by the engine warranty. On a new engine, change the oil after the first five hours of operation, and thereafter on K181QS and K341 QS change oil every 25 hours. On KT17, K582QS and L654, change oil every 50 hours.
I-9. FUEL SPECIFICATIONS For best results, use only clean, fresh, regular grade unleaded gasoline with a pump sticker octane rating of 87 or higher in the U.S.A. In countries using the Research
MODEL
CAPACITY
35kW
1 Quart (0.95 Iitres)
4.5kW (Single)
2 Quarts (1.89 litres)
4.5kW (KT17 Series I)
3.8 Quarts (3.6 litres)
4.5kW (KT17 Series II)
1.5 Quarts (1.4 litres)
5.5kW
4 Quarts (3.78 litres) (Additional
l/2 quart (0.47 litres) when filter
is replaced)
7kW
4 Quarts (3.78 litres) (Additional
l/2 quart (0.47 litres) when filter
is replaced)
7.5kW
5 U.S. Quarts (4.73 Iitres)
Unleaded is recommended since it leaves less combus-
tion chamber deposits. Regular grade leaded gasoline
may also be used; however, be aware that the combustion chamber and cylinder head will require more frequent service.
Use fresh gasoline to ensure it is blended for the season,
and to’ reduce the possibility of gum deposits forming which could clog the fuel system. Do not use gasoline left
over from the previous season.
Gasohol containing no more than 10% ethanol can be
used if unleaded gasoline is unavailable. Never use gas-
ohol containing more than 10% ethanol or gasoline con-
Table 1-5. Oil Capacity
rating method, it should be 90 octane minimum.
taining methanol. Do not add oil to the gasoline.
RADIATOR FILL
\
SPARK
PLUGS
CRANKCASE
A
BREATHER
\ /I\\
(HIDDEN)
I
CIjRBURETOR
VALVE
TAPPET,
COVER
BELTTENSION ADJUSTMENT
GOVERNOR
ADJUSTMEN
OIL PRE
GAUGE
/
/
OIL
FILL/CHECK
MOUNTING
I /
OIL PRESSURE
ADJUSTMENT
\
\
CONTROLLER
\
GROUN
FUEL
OIL
FUEL
DRAIN
STRAF
TRAY
SOLENOID
PUMP
C
REMO’
CONTR
:ONNEC
TE
OL
TOR
Figure 1-5. Service Side View of Kohler 7500 Watt RV Generator Set
c
l-5
Section 2
Operation
2-l. GENERAL
Operation of the generator set is controlled by a single switch on the controller (Figure 2-l). This switch is a
momentary contact, three-position, start-run-stop switch.
It is spring loaded to return to the center (run) position when released from either the start or stop position. This switch must be held in the desired position until the unit
is running or has come to a complete stop. The controller
includes a keyed connector for starting and stopping the set at an optional remote switch located inside the vehicle.
2-2. PRESTART CHECKLIST
Refer to Table 2-l for all prestart checks.
CHECK REQUIREMENT
Oil Level Near Full (Not Over)
Air Inlets Unobstructed Compartment Clean Air Cleaner Clean, Properly Installed Air Shrouding
Tight, Proper Position
Exhaust System Unobstructed, Properly
lnstal led
Electrical Connections Clean and Tight
Table 2-I. Prestart Checklist
2-3. OPERATION
NOTE If the generator set shuts itself down due to high engine temperature or low oil pressure, the cause must be located and eliminated before the set can be restarted. Also, make sure the circuit breaker(s) is in the “on” posi­tion so generator output is transferred to the load.
CAUTION
In the event of a “false start”, that is, the en­gine gets up sufficient speed to disengage the starter but fails to continue running, allow the engine to come to a complete halt before making a restart attempt. If the flywheel is still rotating when the starter is engaged, the starter pinion and ring gear will clash which may damage the ring gear teeth.
Figure 2-I. Controller
‘I. Move the START-STOP switch on the controller to
START position and hold until the engine is running but
not more than 10 seconds. Normally the engine will start within five seconds. If the engine does not start in 10 sec­onds, release the switch and wait a few seconds before mov­ing back to START position. This allows the choke to reset in the full choke position.
2. Whenever possible allow a brief cooling period by run­ning the set at low or no load for a few minutes just prior to shutdown. To stop, move the switch to STOP position and hold until the set comes to a complete halt.
2-I
Section 3
Scheduled Maintenance
3-l. GENERAL Scheduled maintenance is “preventive” maintenance. Major repair can be avoided by correcting problems when they are small. When performing maintenance, always look for signs of potential trouble, such as loose connec­tions or dirty components. When running the set, listen for any unusual noises.
NOTE - Oil Change
3-2. SCHEDULED MAINTENANCE Refer to Table 3-1 for scheduled maintenance requirements.
Perform each function at the indicated time interval. For each function, refer to the applicable paragraph for instruc­tions.
NOTE
On a new engine change the oil after the first five hours of operation, and thereafter on K181QS and K341QS change oil every 25 hours. On KT17, K582QS & L654 change oil every 50 hours.
For maintenance work on engine components, refer to the Kohler engine service manual
which covers the engine model.
Every
1
Before Every Every Every
.
Each
25 50
100 500
Function Startup Hours
Hours Hours Hours
.
Compartment - Remove dirt. Blow dry compressed air through cooling inlets
(set running).
X
I
Air Inlet and Outlet - Clean.
X
Oil Level - Check.
X
Check Exhaust Pipe. X
I
Oil - Change.
See note above.
. Oil Filter - Change.
X
Air Cleaner Element - Clean
(change every 200 hrs.).
X
Fuel Sediment Bowl or Filter (if equipped) - Remove and clean.
X
Clean Electric Fuel Pump Filter ­See owner’s manual.
X Check Coolant Level In Radiator (7.5KW) X Check Fan Belt Tension (7.5KW)
X Spark Plug - Clean and regap.
X
Point Contacts - Service or replace.
X
Brushes and Collector Rings ­Check and service.
X
Ignition Timing -
Check and correct.
X
Rectifier
- Regulator - Check
condition and battery charging.
X
Alternator Stator - Check leads and connections. X
Starting Motor - Check brushes & commutator.
X
Engine External Surface - Clean screen,
cooling fins, block, oil fill area.
X
Valve Clearance
- Check and adjust
valve stems and tappets. X
I
Crankcase Breather - Check valve and gaskets, clean filter, check hoses.
X
Cylinder Head - Remove, clean
and inspect.
X
.
Electric Fuel Pump - Service filter.
X
1-i: 50 hours.
Check Electrolyte Level in Battery
---_--.-_ . ..-_ _
Table 3-1. Scheduled Maintenance
3-1
Section 4
Troubleshooting
4-l. GENERAL
CAUTION
When troubleshooting a generator set, always consider the simplest causes first. Narrow the problem down to a func­tional system, such as fuel or ignition. To operate efficient­ly, an engine must have sufficient fuel, a good ignition spark and good compression. All adjustments must be correct. For a generator to produce the required electricity, all parts must be clean, all connections tight, and all com­ponents in working order. See Table 4-l for Engine Trou­bleshooting and Table 4-2 for Generator Troubleshooting.
4-2. RV SYSTEMS CHECK
The “RV Systems Check” is designed to check the electri­cal status of an RV generator set prior to connecting and testing with the controller. If the generator does not check out in each step, correct the malfunction before proceeding to the next step.
Do not push the V.B.U. button after the “GEN ON” lamp is on. Voltage regulator damage may resu It.
CAUTION
Do not use the RV Systems Check as a replace­ment for the controller. The hi-temp and low oil pressure switches will not shut the machine
down in the event of a malfunction. Generator
damage will result.
1. Make sure the battery is properly connected and oil is at proper level.
CAUTION
Do not push the CRANK button after the en-
2. Check the three fuses in the RV Systems Check tester
gine is running. Starter damage will result.
(Figure 4-l). Replace any blown fuses.
RV
‘II I
SYSTEMS CHECK
GEN
POL. CRANK ON’ SAFETY
IGNITION
ON OFF
CRANK CHOKE
V. B.U.
“RV SYSTEMS CHECK”
CONNECT TO RV GENERATOR
*WIRING HARNESS PLUG
SWITCHES
“Ignition” -
Supplies battery voltage to ignition coil, choke heater, fuel control solenoid, fuel valve and fuel pump.
“Crank” -
Supplies battery voltage to starter relay. Note: May be actuated with ignition switch on or off.
“Choke” - Supplies battery voltage to choke plate
solenoid. Note: May only be actuated during cranking.
“V.B.U.” -
Voltage Build Up, supplies battery vol-
tage to excite field. VISUAL INDICATORS “Pol” - Green -
Indicates battery polarity correct.
“GEN. ON” -. DOES NOT FUNCTION ON SETS
EQUIPPED WITH RELAY CONTROLLERS.
“Crank” - Amber -’
Indicates battery voltage signal
present during cranking.
“Safety Switch” - Amber - Indicates safety circuit
wiring correct. Operator must manually short temperature switch to ground to obtain this
indication.
[Check Tester Fuses First In Case Of Malfunction 1
FUSES
15 AMP - IGN/CRK
1 AMP -CHOKE
3 AMP - V.B.U.
Figure 4-1. RV Systems Check
4-1
3. Remove the
12 pin connector
plug it into the
tester.
from the controller and NOTE
4. Observe the POL (polarity) lamp. Green light indicates battery polarity is correct. If lamp does not light, check for correct battery connection to the generator set.
NOTE
On 5.5kW, 7kW and 7.5kW sets the SAFETY lamp will also be on. This indicates the low oil pressure switch is functioning properly.
5. With the IGNITION switch in OFF position, press the
CRANK button. The CRANK lamp should light and the engine should crank. If the lamp does not light, no voltage from the battery is present.
On 5.5kW, 7kW and 7.5kW sets, the SAFETY lamp will go off after the engine has reached
sufficient operating oil pressure.
IO. To check the high temperature cutout, low oil pressure cutout and/or the oil level cutout for proper operation, start the generator set and connect a jumper wire from the cutout device to ground. The “amber” safety lamp should light, indicating the protective circuit is functioning prop­erly.
11. If all checks are OK, connect the 12 pin connector to the generator set controller.
If the 15 amp fuse blows, check for defective cranking solenoid, fuel pump or fuel solenoid, ignition coil, choke heater, fuel shutdown control or shorted wiring.
6. Remove the air cleaner cover to observe the choke plate
during the next step.
If the 1 amp fuse blows, check for defective choke sol­enoid or wiring.
7. Again, with the IGNITION switch in OFF position press
the crank button. While the engine is cranking, press the
CHOKE button to supply battery voltage to the choke
plate solenoid. Make sure the choke plate is functioning
properly. If not, see Section 7. Release the CRANK and
CHOKE buttons.
If the 3 amp fuse blows, check for shorted or grounded generator rotor or defective voltage regulator.
8. With the IGNITION switch ON, start the engine, using CRANK and CHOKE buttons as needed. If engine does not
start, see Engine Troubleshooting, Table 4-l. With engine at operating speed, press V.B.U. (voltage build-up) button
momentarily. Check for generator output voltage. If no output voltage is available, see Troubleshooting Gen­erator., Table 4-2.
9. Turn the IGNITION switch to OFF position to stop the engine.
4-3. TROUBLESHOOTING
Refer to Table 4-l for engine troubleshooting. To make
engine repairs, refer to the Kohler engine service manual
which covers the engine model. A troubleshooting chart
cannot cover every possible cause of malfunction. Always consider every possible cause of malfunction. Knowledge of four cycle engines and battery ignition systems can be applied. Refer to Table 4-2 to troubleshoot the genera­tor. The table refers to applicable paragraphs in the manual.
4-2
CONDITION
A. Hard Starting or Loss of Power
B. Overheating
C. Backfiring
D.
Occasional “skip” at High Speed
E. Operating Erratically
POSSIBLE CAUSE
1. Faulty Ignition. a. Loose or grounded high tension or breaker point leads.
b. Improper breaker point gap and timing. c. Defective breaker points. d. Faulty spark plug or improper gap.
e. Faulty condenser or coil.
f. Weak battery.
2. Faulty Fuel System. a. Gasoline not getting to carburetor.
A. Dirt or gum in fuel line.
B. Fuel pump faulty. b. Dirt in carburetor. c. Carburetor improperly adjusted. d. Choke faulty or improperly adjusted. e. Stale fuel. f. Carbon build up. g. Possible intake manifold vacuum leak.
3. Valve maintenance.
4. Defective Automatic Compression Release (ACR).
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Insufficient available cool air. Dirty air intake screen, shroud or cooling fins.
Stale fuel.
Fuel mixture too lean. Improper ignition timing. Engine overloaded.
Tight tappet clearance.
Insufficient hot-air discharge opening. Loose or broken fan belt (7.5kW).
Low coolant level (7.5kW). Too much lube oil. Summer/Winter air baffle in wrong position.
‘I. Fuel mixture too lean.
2. Improper timing.
3. Valve “sticking”.
4. Possible intake manifold vacuum leak.
1. Spark plug gap too wide.
2. Improper carburetor setting or lack of fuel.
3. Wrong type spark plug. Use resistor type plug.
4. Improper timing.
5. Faulty condenser.
1:
2.
3.
4.
5.
6.
7.
8.
9.
IO.
Clogged fuel line. Water in fuel.
Faulty choke control. Improper fuel mixture. Loose ignition connections. Vacuum leaks in manifold or carburetor connection. Vent in gas cap plugged. Fuel pump faulty.
4CR installed upside down. Solenoid should be to the bottom.
Improper ground on anti-dieseling device.
Table 4-1. Engine Troubleshooting
Refer to Kohler Engine Service Manual for Repair.
defer to Generator Owner’s Manual for Adjustments.
4-3
CONDITION
1. Engine will not crank.
POSSIBLE CAUSE/CORRECTION (SECTION)
1. Battery cable connections reversed. (Must be negative ground.)
2. 10 amp fuse in controller blown (5-3).
3. Defective start switch or “C” relay (5-2).
4. Open circuit in wiring harness or connector.
5. Faulty starter motor.
6. Open circuit in REI diode (5-4).
7. Normally closed 3CR contacts, open (5-5).
8. Busted or loose ground strap.
2. Engine cranks but will not start.
1. Choke not operating or out of adjustment (7-1, 7-2).
2. Check fuel supply to carburetor.
3. Faulty fuel shut-down control (7-3).
4. Faulty fuel pump.
5. Dirty or stuck ignition points.
6. Faulty condenser.
7. Faulty spark plug.
3. Engine starts, then stops when switch is closed.
8. 2CR relay not functioning. Must have battery voltage on positive connection of ignition coil (5-5).
9. Fuel mixture. Replace.
1. No AC generator output.
2. Faulty 3CR interlock relay (5-5).
3. Faulty 4CR voltage sensing relay (5-5).
4. Faulty exciter voltage regulator (6-7).
4. No AC output.
1. Circuit breakers in the off position (2-3).
2. Generator brushes not making contact on slip rings (6-5).
3. Faulty build-up circuit. Battery voltage must be present at terminal “B” of regulator during cranking (6-7).
4. Open connection in wiring harness or plug connector (5-2).
5. Faulty exciter voltage regulator (6-7).
6. Circuit protector tripping due to overload, reduce load.
5. Low output or excessive drop in voltage (below 1 IO volts).
1. Generator set overloaded.
2. Engine rpm set too low (7-5 thru 7-9).
3. Faulty exciter voltage regulator (6-7).
4. Poor stator coil connections, use a clamp-on ammeter and check
each connection. .
6. High AC voltage (above 125 volts AC).
1. Faulty exciter voltage regulator.
2. Stator reconnected improperly.
7. Engine shuts down for no apparent reason.
1. Generator set overheated
- improper installation. Refer to RV
installation manual or 75kW Owner’s Manual.
2. No fuel.
3. Oil level or oil pressure system failure.
4. Faulty shutdown solenoid.
8. Unit will not operate with remote switch - OK at controller.
I. Incorrect wiring of remote switch to remote plug assembly. Center
pole of remote switch must connect to terminal 4 of remote harness plug, Figure 5-2.
2. Open connection in wiring.
Table 4-2. Troubleshooting Generator
Section 5
Relay Controller
5-I. DESCRIPTION
All generator set functions are dependent upon the control-
ler. See Figure 5-l for parts identification. For operation instructions refer to Section 2. The controller includes a keyed connector for installing a remote switch and hour­meter panel. This optional remote switch allows the oper­ator to start and stop the generator set from another loca­tion in the vehicle. The hourmeter records the hours of generator set operation (Figure 5-2). The controller can be removed by removing the two snap connectors and two capscrews underneath the controller. This section covers sequence of operation, and fuse, diode, and relay replace­ment.
5-2. SEQUENCE OF OPERATION
The Relay Controller is the controlling point for generator set operation. The following is the sequence of operations controlled by the Relay Controller. See Figures 5-3 through 5-7.
.
REMOTE CONTROL
/
WIRING HARNESS
CONNECTOR
PLUG
IGNITION RELAY
REI
3CR
DIODE INTERLOCK RELAY
Figure 5-1. Controller
12 VOLT
GENERATOR
“ON” LIGHT
12 VOLT
HOURMETER
Lead Designation
. .
Pin No. Color Gauge of Wire
1 Red
18
2 White
22
3 Brown
22
4 Black
18
5
6 Blue
22
REMOTE CONTROL CONNECTOR
(ON CONTROLLER)
HARNESS
/
PLUG
SPRING LOADED
START-STOP
APPLIES TO SWITCH A-269299 ONLY
KOHLER PART NO. PA-269966
Figure 5-2. Remote Control Connections
5-l
l lO AMP
lN.LINE
FUSE
I
CHOKE HTR.
ZCR
I I
*EARLIER MODELS ONLY
238760
\;/-
.
d
2CR
8 /
*EARLIER MODELS ONLY
238749
Figure 5-3. Sequence of Operation
Schematic 3.5kW
Figure 5-4. Sequence of Operation
Schematic 4.5kW (Single)
52
5 II
-STARTER 1
REuOTE SW.
+ YLL
2CR
2 + ICN -
EINTS
OIL
e
II
LIITLUI I
BREAKER
4
“EARLIER MODELS ONLY
277948
STD. ON 7kW
OPTION 5.5kW
. :
Q%. Qb +O-.
.
I, 1
.
.
*EARLIER MODELS ONLY
277931
Figure 5-5. Sequence of Operation
Schematic 4SkW (KT17 Series I)
Figure 5-6. Sequence of Operation
Schematic 5.5 & 7kW
5-3
I2 VOLT
3CRT
La?-
FUEL ‘PUMP
.
I
TRANSFORMER
Y
r
CEN:: ATOR
i t
L2 LI
LO
“EARLIER MODELS ONLY
241753
Figure 5-7. Sequence of Operation
Schematic 7.5kW
1. Pressing the start-stop switch to the start position ener­gizes both the cranking contactor “C” and the 2CR relay. (Diode REI will prevent this from happening if the battery is connected in reverse.)
5-4
2. Energizing the 2CR relay will allow current to flow through the 10 Amp in-line fuse to the ignition coil, choke heater, carburetor shut-down solenoid and electric fuel pump (if equipped).
3. Energizing cranking contactor “C” will allow current to flow to the starter motor and crank the engine. The car­buretor choke solenoid will also be energized and current can flow through the normally closed 4CR contacts to the “B” terminal of the aenerator voltage regulator for the initial voltage build-up.
4. When the engine starts and the generator is producing AC output, the 4CR relay (mounted in the generator end bracket) will energize.
5. The normally CLOSED contacts in the V.B.U. (voltage
. .
bui,ld-up) circuit will then open and disconnect the battery supply from the generator voltage regulator.
6. The normally OPEN 4CR contacts will close and allow the 3CR relay to become energized. All the 3CR contacts will then change positions, the normally open contacts will close and the normally closed contacts will open.
7. The normally closed 3CR contacts in series with the “C” cranking contactor will open deenergizing the “C” contactor. This offers protection from engaging the starter motor while the unit is operating.
8. The 3CR contacts in series with the 2CR relay coil will close, maintaining current flow to the 2CR relay coil. The 2CR relay controls current flow to the engine ignition circuit.
9. The now closed 3CR contacts in series with the ICR relay coil and engine safety cutouts will allow the ICR relay to become energized if the safety cutout contacts close. The ICR relay also energizes when the start-stop switch is placed in the stop position.
10. Energizing the ICR relay, either by the engine safety cutouts or by placing the start-stop switch to the stop posi­tion will disrupt current flow to the 2CR relay coil and in turn prevent current flow to the ignition circuit when the 2CR contacts in this circuit open.
5-3. FUSES
A
WARNING
UNIT STARTS WITHOUT NOTICE! To prevent accidental
starting on units with a remote start/stop switch, always disconnect battery (remove negative lead first and recon­nect it last) to disable generator set before working on any equipment connected to generator.
There is one IO Amp fuse inside the controller (Figure 5-l). This fuse protects the controller against damage in the
event a short develops in the engine wiring. If this fuse “blows” the set will stop. If the set has stopped due to
causes other than lack of fuel, engine malfunction, or low
oil pressure, remove the cover of the controller and check the fuse. If blown, replace the fuse then attempt to restart the generator set. If the set will not start, or if the fuse
blows again, locate and correct the cause.
Loading...
+ 43 hidden pages