Keston RSM 20/FB Installation and Servicing Manual

COMBINATION WALL HUNG
GAS BOILER
MODEL RSM 20/FB
INSTALLATION & SERVICING
INSTRUCTIONS
DATA BADGE UNDER FRONT PANEL ON BURNER COVER
Manufactured by
THERMOMATIC SRL Casalecchio Di Reno Bologna Italy
exclusively for
High Efficiency Domestic & Commercial Boilers
34 West Common Road Hayes Bromley Kent BR2 7BX
Telephone : 020 8462 0262 Fax : 020 8462 4459
e-mail: info@keston.co.uk Web: www.keston.co.uk
Page 2
TECHNICAL DATA
Heal input (fixed) 26.2kW (89.400 Btu/h) Heal output 23kW (78.500 Btu/h) Burner pressure Burner
14mbar(5.6in.w.g.) Inlet 2Ombar Worgas Thermomatic 3 injector 2.35 - 2.70 - 2.35 n
Gas control valve Honeywell VK 4105G Control Box Honeywell VK 4105G Filling loop
Inter Albion with Alhilil double check valve
Boiler control thermostat Ranco K36 Y21 Bimetallic Priority thermostat Cewal 91931199 Overheat thermostat Ranco LM7 P5 043 Anticondensing Thermostat Imit TR2 Electrical supply 240V-50HZ Power consumption 180 W Internal fuse rating 3A Weight empty 77 kg (169.7 Ib) Weight full 92 kg (203.O Ib) CH max pressure 3 bar (44 psi) CH min working pressure 0.5 bar (7.4 psi) DHW max pressure 10 bar (146 psi) DHW min working pressure 0.6 bar (8.7 psi) CH expansion vessel 8 litres charged to 0.5 bar (7.4 psi) DHW expansion vessel
0.1 60 litres charged lo 3.5 L (51.5 psi)
CH max temperature 90°C Design temperature rise 11°C DHW flow at 30'c rise 11.0 l/min DHW flow at 35'c rise 9.21 l/min
Page 3
43
Contents Figures Section Page No. Page Technical Data Inside Internal Design 1.1 5 Front Cover Control Panel 2.1 6 General Description 1 5 Connections 3.1 6 Operating Sequence 2 6 Alternative top tip system 3.1. A 7 Related Documents 3.1 6 Sealed system filling & make-up 3.1. B 8 Gas Supply 3.2 6 Pump Performance 3.2 9 Water Systems 3.3 7 Typical Heating System 3.3 7 Flue Systems 3.4 9 Domestic Hot Water Supply 3.4 9 Appliance Location 3.5 10 Standard Flue Kit Components 3.5 9 Electrical 3.6 11 Optional Horizontal Extension
Flue Installation Procedures 4 13 Kit Components 3.6 9 Flue System: Cutting & Siting of Terminal 3.7 7 Assembly 4.7 13 Clearances 38 11 Connecting Services 4.8 18 Functional Flow Wiring Diagram 3.9 10 Filling Loop Assembly 4.9 18 Disassembly of panels 3.10 12 Commissioning 5 18 Wiring Diagram 3.11 38 Procedures for part replacement
Draining 6.3 20 Replacing Fan 6.5 20 Appliance Mounting 4.1 13 Replacing Air Pressure Switch 6.6 21 Flue Positioning 4.2 13 Replacing DHW Expansion Vessel Flue Connection 4.4 14 Replacing Automatic Air Vent 6.8 21 Flue Connection 4.5 14 Replacing CM Expansion Vessel Replacing Bimetallic Priority Vertical Flue Terminal Locations 4.7 16 Thermostat 6.10 21 Assembled Extended Vertical
Replacing Solenoid of Gas Kit 4.9 Control Valve 6.11 21 Replacing Multifunctional Filling Loop Assembly 4.11 18 Gas Control Valve 6.12 22 Gas Control Valve 5.1 19 Replacing Circulating Pump 6.13 22 Central Heating Expansion
Replacing thermostatic T/P Gauge 6.14 22 Thermostat Positions 6.4 22 Replacing Safety Valve 6.15 22 Pressure Relief Valve 6.5 22 Replacing Burner 6.16 23 6.7 23 Replacing Injectors 6.17 23 Top view of Boiler 8.1 32 Replacing Flame Sensing Ignition Electrodes 6.18 23 Replacing Electronic Control Box 6.19 23 Replacing Green Operating Light & Red Lockout Button 6.20 23 Replacing On/Off Summer/ Winter Switches 6.21 23 Replacing Filling Loop 6.22 23 Fault Finding Algorithm 7.1-12 24 – 31 Routine Servicing and Cleaning 8 32 Short Spare Parts List 34 – 36 Complete Boiler Wiring Schematic 37 Wiring Diagram 38 Manual Addendums 40 -
6 20 Time Clock Wiring 3.12 39
Honeywell T6360B Room Slat
Wiring 3.13 39
6.7 21 Flue Positioning 4.3 14
6.9 21 Vertical Flue Clearances 4.6 16
Flue
Vessel
Spare Parts
4.8 & 17
6.2 21
33, 34
Page 4
1 GENERAL DESCRIPTION (Fig.1.1)
The Thermomatic RSM 20/FB is a wall mounted water jacketed vertical tube Combination Boiler fitted with a copper coil to give an immediate supply of hot water. The appliance is room sealed and fitted with a coaxial duct for fan powered ventilation, designed for exit to either side or to the rear of the appliance. The copper coil containing 2 litres of hot water is indirectly heated, giving an immediate and continuous hot water supply.
The central heating pump will not operate until the boiler temperature reaches 60°C. The pump is
controlled by a capillary thermostat called the anti­condensing thermostat. In addition, a bimetallic priority thermostat will stop the pump as soon as domestic hot water is drawn. This allows the full heat output to be directed to supplying hot water only. The appliance jacket extends to burner level, so the walls of the combustion chamber are water-cooled. This prevents the intense local heating usually associated with combination boilers and considerably prolongs the appliance life. The domestic hot water, being indirectly healed through a coil of a larger diameter than normally used, is not so easily affected by calcium impurities that build up lime scale. This together with the flexing of the coil due to temperature changes, means calcium "build-up" is considerably lessened.
With the Summer/Winter switch set to Winter the appliance will automatically adjust to the central heating output, which may be a single radiator, ot any number within the heat ouput of the appliance. The Thermomalic does not require a 'by-pass' and all radiators can be fitted with thermostatic radiator valves. Unlike many other combination boilers, the Ther­momalic will operate on low water pressures. The boiler within the casing is cylinder shaped and fitted with vertical copper flue tubes through which the gas products pass. These tubes are fitted wiih stainless steel baffles to increase efficiency and to rapidly conduct the heat from the gas products to the water contained within the cylindrical heat exchanger. An extended copper coil fitted around the vertical flue tubes is within the water content. The water content connects to the central healing system and indirectly heats the domestic water passing through the coil. A SIT Controls multifunctional control with electric ignition is used and temperatures of both central heating and hot water ate controlled by capillary thermostats. The flue extract fan incorporates a pressure control switch which activates the gas control. In the case of a fan failure of any kind the gas control fails to safely.
It is recommended that a scale inhibitor should be fitted in hard water areas.
FIG.1.1 INTERNAL DESIGN
1 Manual air vent cock
2 Gas control valve
3 Stainless steel burners
4 Ignition electrode
5 Pocket for an anticondensing thermostat phial
6 Pocket For safety thermostat phial
7 Pocket for boiler healing thermostat phial
8 Water temperature gauge
9 Automatic air vent
10 Fan motor
11 Expansion vessel
12 Stainless steel Hue baffles
13 Boiler shell
14 Domestic hoi water copper coil
15 Circulating pump
16 Pressure relic! Safely valve
17 Water pressure gauge
18 Bimetallic priority thermostat
19 Air pressure microswitch
20 Air pressure switch body
21 Concentric flue/air pipe
22 Flue terminal
23 Flue hood
24 Electronic control box
25 Room sealed combustion chamber
26 Flame detection probe
27 Mini expansion vessel (Domestic)
Page 5
2 OPERATING SEQUENCE (Fig.2.1}
Red Light Central Heating Switch Temp. Press. Guage
Boiler Control Green Light Fuse On/Off Switch Overheat Switch
2.1 ON-OFF MAIN SWITCH
Allows the appliance to be manually switched on and off.
2.2 CENTRAL HEATING SWITCH (SUMMER­WINTER)
Allows the central heating and domestic hot water supply to be switched on. or domestic hot water only to be switched on.
2.3 BOILER CONTROL THERMOSTAT Controls the temperature of the water fed to the
central healing system. The temperature can be man­ually adjusted between approximately 50" - 90*C ± 2°C.
2.4 OVERHEAT SWITCH
A boiler overheat switch will operate if the boiler thermostat exceeds 90*C ± 3%. After determining the season (of the boiler overheat thermostat operating, the thermostat can be manually re-set. Note: thermo­stat control cannot be re-set until boiler temperature falls below 80"C.
2.5 PRESSURE AND TEMPERATURE GAUGE
A combined boiler pressure and temperature gauge indicates the pressure and temperature of the water in the boiler. As a guide the pressure of water in the boiler, with a pressurised system, can be set at 1 bar when the water is cold.
2.6 BIMETALLIC PRIORITY THERMOSTAT
A bimetallic priority thermostat is fitted al the connec­tion of the domestic cold water inlet to the boiler. When a hot lap is opened, the bimetallic priority thermostat is operated by the flow of cold water into the boiler.
If the central heating switch (summer/winter switch) is in the Winter position (i.e. central heating ON) the bimetallic priority thermostat turns off the central healing circulating pump.
When the domestic hoi water demand is satisfied the bimetallic priority thermostat allows the pump to restart.
When only a small domestic hot water flow is drawn the bimetallic priority thermostat does not intervene.
2.7 ANTICONDENSING THERMOSTAT
This thermostat prevents the central heating emula­ting pump from operating until the boiler water temperature reaches 60"C
3 GENERAL REQUIREMENTS
3.1
RELATED DOCUMENTS
It is the law that gas appliances be fitted by a competent person. Failure to do so could lead to prosecution. It is in your own interest, and that of safety, to ensure compliance with the law. Installation shall be in accordance with the following documents:
- Gas Safety (Installation and Use) Regulation 1984
- Building Regulations
- Building Standards (Scotland) Consolidation
- Current IEE Wiring Regulations
- By-Laws of the Local Water Authority
- BS.6798: Boilers of rated input not exceeding 60KW
- BS5449: Forced circulation hot water systems
- BS.5546: Gas hot water supplies
- BS.5440: Part 1: Flues
- BS.5440: Part 2: Ventilation
- BS.6891: Gas supply
- Where the appliance is installed in a timber framed
building, reference should be made to the British Gas Publication reference DM2.
3.2 GAS SUPPLY See fig.3.1 for connection
Fig. 3.1
A gas meter can only be connected by local gas legions or by a local gas region contractor. An existing meter should be checked, preferably by the gas region, to ensure the meter is adequate to deal with the rate of gas supply. Installation of pipes should be in accordance with BS.6891. Pipework from the meter to the appliance must be of adequate size. Do not use pipes of a smaller size than the appliance gas inlet connection.
The complete installation must be tested for sound­ness and purged as described in the above code
Page 6
3.3 WATER SYSTEMS
Fig. 3.3 TYPICAL HEATING SYSTEM
3.3.1 Central heating
See Fig.3. f for connections
WARNING: When radiator(s) are at a higher level than the boiler. A NON-RETURN VALVE MUST BE FITTED lo the central healing systems flow pipe.
A. Old systems. These* are likely to contain sludge and debris which, if passed into the appliance, may cause irreparable damage to the pump and other components. It is. therefore, highly recommended that the old system be thoroughly flushed using such as Fernox cleaner - use in accordance with the manufacturer's instructions.
B. New systems Must always be flushed of debris.
C. Design of system The primary system must be of the sealed type, the designed temperature rise should be 1 PC.
The following sealed system components are included on the appliance:
i. Double check valve, stop valve and filling loop,
ii. 8 lilre central heating expansion vessel,
iii. Circulating pump.
iv. CALEFFI relief (safety) valve.
v. D.H.W, Expansion Vessel
vi. Combined temperature and pressure gauge.
D. Expansion vessel/sizing of system Guidance is provided in BS.7074. Part 1 and BS.5449. The maximum permissible capacity of the system, including the appliance, will depend upon the initial design pressure. As an example, for an initial design pressure of 1 bar the maximum permitted capacity, including the appliance, is 70 titles.
For calculation purposes: Existing vessel capacity - 8 litres (charged at 0.5 bar) Capacity of appliance - 15 litres Safely valve setting - 3 Bar
If the system capacity exceeds the allowed value then an additional vessel must be provided, connected as close as possible to the appliance heating return.
E. Pressure relief (safety) valve The valve outlet must be routed to a suitable point of drainage where there will be no hazard to occupants and where freezing will not take place.
F. Filling the system A double check valve, stop valve and filling loop are supplied. Before using ensure that the arrangement complies with the requirements of the Local Water Authority. Alternatively BS 5449:1990 (fig 3.1A) shows other methods of filling.
Fig. 3.1.A ALTERNATIVE TOP UP SYSTEM
G. System make up There must be no direct permanent connection to the mains water supply, hence the filling loop must be disconnected at one end alter use. If an automatic top up method is required, then this must be done via either a cistern which has no other purpose or a top up bottle. Full details are provided in BS.5449:! 990 (fig 3.1 B) Again, always check local Water By-laws before installation. See also Fig.3. l.A.
H. Pump performance Fig.3.2 shows the pump performance characteristics and values given take due account of the losses through the appliance.
I. Thermostatic radiator valves A by-pass is not required and such valves can be fitted on all radiators if desired.
J. Drain points Drain taps should be lilted on the lowest point of the system, the taps complying with BS.2879
K. Vents Although an automatic air vent & manual air vent is provided on the appliance, further facility to vent the system should be provided.
L. All components and fillings used should be suitable for temperatures of up to 11O°C and pressures of up to 3 bar.
All syslem components added must be in occoidance with US 5-149 and BS.G798.
Page 7
Position 1
1000
30-
35 016
Position It
170O
45-
60 025 Position III
2450
72.92
038
Speed RPM Watts
Input
Full Load Current in Amps
Fig. 3-2 PUMP PERFORMANCE
M. Central heating pressure We recommended that the initial design pressure, i.e. when cold, be 1 bar When fully heated and drawing a full load, the resultant hot pressure must not exceed 2.7 bar. The safety valve will discharge at 3 bar ± 0.3 bar.
N. System design A typical sealed system is shown in Fig.3.3.
3.3.2 Domestic hot water circuit See Fig.3.1 for connections An extended copper coil is filled which is healed from the primary water. Starting from cold, the appliance should be fully heated before full capacity hot water supply is obtained
IMPORTANT To conform to the requirements of the National Water Council, il the main water pressure is at any lime in excess of 73 psi. (5 bars) {1 69(1) a Pressure Limiting or Pressure Reducing Valve must be fined by the installer into the mains supply in an inconspicuous approved by Ihe NWC and must not allow more than 73 psi. (5 bars) pressure to the appliance.
Page 8
Fig. 3.4 DOMESTIC HOT WATER SUPPLY
3.4 FLUE SYSTEM
3.4.1 The standard balanced flue system can be directed to the right, left or rear of the appliance.
3.4.2 As supplied, the standard horizontal flue assembly will cover a distance of up to 910 mm from the centre line of (he appliance for side flues. for rear flues, a wall thickness of up to 800mm can be accommodated. Both dimensions are to the outside wall face.
An optional 1m extension flue system kit (Pan No R3000050) is available which allows the maximum lengths to be increased to 1840 mm and 1730 mm respectively. An optional 2m extension flue system kit (Pan No R3000014) is available which allows the maximum lengths to be increased lo 2840 and 2730 respective­ly
3.4.4 If a vertical flue is required an optional vertical flue system kit (Part No R3000030) is available which replaces the standard 1m horizontal Hue assembly supplied. The vertical flue assembly will cover a distance of up to 1m from the top of the boiler flue hood to the end of the air pipe and comes complete with a terminal rain hood. Optional extension flue system kits are available to allow the maximum vertical lengths lo be increased lo 1975mm (Part No 3OO0050) or 2975mm (Part No
3000014).
Fig. 3.5 STANDARD HORIZONTAL FLUE SYSTEM KIT COMPONENTS
Fig. 3.6 OPTIONAL HORIZONTAL
EXTENSION FLUE SYSTEM KIT COMPONENTS
Page 9
3.4.5 The flue system must be installed in accordance with BSS440 Part 1.
3.4.6 Siting of flue terminal It is essential that products of combustion cannot enter any building through such as openable windows, doors, air bricks, etc. Fig 3.7 gives details of the minimum required spacing of the 'terminal from building features.
3.4.7 Terminal guard Where the terminal is fitted within 2m of a walkway. a balcony or a fiat roof to which people have access, then a terminal guard, model C.1 must be fitted centrally over the terminal. This guard is available from KESTON BOILERS.
3.4.8 Air supply This appliance is room sealed and. when installed in a room or space, requires no ventilation. If installed in a cupboard/compartment, air is required for cooling purposes, as follows:
Fig. 3.7 SITING OFTHE TERMINAL
Position of Air Vents
Air from Room or Internal
Air Direct from Outside
Space
High level 236 cm²
36-6 ins²
Low level
36.6 ins²
236 cm²
18.3 ins²
1 1 8 cm²
18.3 ins² 1 1 8 cm²
Both air vents must communicate with the same room or space, or both must be on the same wall to outside air.
3.5 APPLIANCE LOCATION
3.5.1 This appliance is not suitable for external installation.
3.5.2 The wall on which the appliance is mounted must be of suitable load bearing capacity
3.5.3 Installation in a compartment is permitted (full guidance is provided in BS.6798).
3.5.4 Adequate space must be allowed for installa­tion, subsequent servicing, and safe operation. Appliance dimensions and the minimum allowable clearances required are shown in Figs. 3. t and 3.8
TERMINAL POSITION Minimum distance
Fanned draught.
A. Directly below an openable window or other opening. e.g. an air brick 300 mm B. Below gutters, soil pipes or drain pipes 75 mm C. Below eaves 200 mm D. Below balcony 200 mm E. From vertical drain pipes and soil pipes 75 mm F. From internal or external corners 300 mm
TERMINAL POSITION Minimum distance
Fanned draught.
G. Above ground or balcony level 300 mm H. From a surface facing a terminal 600 mm I. From a terminal facing a terminal 1200 mm J. Vertically from a terminal on the
same wall 1500 mm K. Horizontally from a terminal on the same wall 300 mm
Page 10
A flexible three-core PVC insulated cable must be used between the isolator and terminal block with a minimum cable size of 0.75 mm1 (24 x 0.2 mm) BS.6500 Table 16 Ensure all cables are secure.
3.6.3 ELECTRICITY SUPPLY
WARNING: THIS APPLIANCE MUST BE EARTHED.
Connection shall be made to a 240 Volts 50 Hz ­supply. K a mains plug connection is used it must be of a three-pin type and fused to 3 Amps.
To connect a plug
Fig. 3.8 MINIMUM CLEARANCES
3.5.6 The position must allow for correct termination of the flue system (see Section 3.4).
3.5.6 The combination boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combination boiler in a room or internal space containing a bath or shower.
Where a room-sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
3.6 ELECTRICAL
3.6.1 Electrical connections and installation must conform to current IEE Regulations and. in Scotland, the electrical provisions of the Building Regulations.
The appliance must be earthed.
Wiring external to the appliance MUST be carried out by a competent person in accordance with the current IEE Regulations and Local Regulations which apply. The Thermornatic Combination Boiler is supplied for connection to a 240V-50Hz single phase. The appliance is fused at 3A
3.6.2 The method of connection to the electricity supply MUST provide means of completely isolating the electricity supply to the boiler and its ancillary control, preferably by using a 3A fused three-pin plug and unswitched shuttered socket outlet both complying with the requirements of 8S.1
363. or alternately a 3A fused double-pole switch having n 3 mm contact separation on both poles.
As the colour of the wires in the mains lead of (he appliance may not correspond with the coloured markings identifying the terminals in your plug, proceed as follows:— The wire which is coloured green-and-yellow must be connected to the terminal in the plug which is marked with the letter E or by the earth symbol or coloured green or green-and-yellow. The wire which is coloured blue must be connected to the terminal which is marked with the tetler:N or coloured black. The wire which is coloured brown must be connected to the terminal which is marked with the letter L or coloured red.
ELECTRICAL CONNECTIONS
3.6.4 To gain access to the terminal block remove me four screws fixing (he base panel with the attached front door and remove the panel (see Fig. 3.10, item 9'1
3.6.5Thread the main supply cable through the cable restraining clamp, leave enough cable for removal of control panel to replace any boiler controls.
3.6.6 Ensure earth wire is longer than current carrying conductors so that if cables are strained or slip in their anchorage, the current carrying conductors become taut before the earth wire.
Page 11
Page 12
4. INSTALLATION PROCEDURES
4.1 Unpack the appliance, check the contents:
Combination
i
boiler Wall plugs
ii
Fixing brackets
iii
Connection
iv
plate with ball valves
T-bar template
v
Flue assembly with
vi
elbow Wall liner with flexible
vii
washer Filling loop with double
vii
check valve
i
4.2 Select the appliance position, taking due account of Section 3.
4.3 PREPARATION FOR MOUNTING THE APPLIANCE
The Thermomatic Combination Boiler is supplied with a connection plate with ball valves and a T-bar template that allow the installer to make all water and
f Insert the plastic plugs and screw in the fixing brackets to within 2 of 3 mm ol the wall face.
4.3 Hang the T-bar template on the fixing brackets and check that it is perfectly horizontal and seated on the fixing brackets.
4.4.1 Hang the connection plate carrying the valves on the T-bar template hung on the wall in 4.4 and fix together using the screws. Drill four holes in the wall for fixing the connection plate to the wall, using the existing holes on the connection plate as a template. Fix the connection plate to the wall using lour screws in the holes drilled.
4.4.2 Once the T-bar template and connection plate have been fixed securely lo the wall make all the gas and water connections.
4.4.3 Remove the T-bar template and hang the appliance on the fixing brackets via the two square cut outs on the top of the appliance.
4.5 Remove the base panel. 4 screws (see fig. 3.10 item 91 Exploded drawing of disassembling the boiler panels).
4.6Remove the front panel. 2 screws (see fig 3.10 item
93). lift and disengage. Remove the plugs from the cold water inlet and domestic hot water outlet
4.7 FLUE SYSTEM: CUTTING AND ASSEMBLY
4.7.1 Standard Flue Systems When fully assembled, the standard flue system will be shown, side or rear flue (fig. 4.2).
gas connections and test the system before hanging the boiler. Hence, the boiler itself need only be hung at the final stage of the works.
a Mark a vertical line for the centre of the appliance b Mark a horizontal line for the top of the appliance. c Lay the top edge of the T-bar template onto the horizontal line and mark two holes on the wall for the fixing brackets. d Mark the flue hole centre, either on the rear wall. ceiling or extended to the required side wall as shown. e For standard flue systems, drill the flue hole 130mm diameter, preferably using a core drill. For extended Flue systems, drill the Flue hole 145 mm diameter
IMPORTANT: The plastic liner must always be used and the air pipe fixed at the appliance elbow ONLY.
Page 13
Fig. 4.3
a Measure the wall thickness T (fig. 43). b Maximum available lengths of plastic liner: Rear flue Maximum wall thickness (standard liner):
580 mm (T) Maximum wall thickness (optional extension liner) 828 mm (T).
Side flue Maximum distance from appliance side to
outer wail face: 680 mm (T+ C) (with maximum wall thickness T as for rear flues)
When measuring and cutting, always separate the inner (flue) pipe wiih terminal from the outer (air) pipe.
c Cut the air pipe fig. 3.5 — cut from the plain end. Rear Flue To overall length (L) oFT + 62 mm. Side Flue To overall length (L) ofT + C+ 180mm
When cutting the air pipe, take care not to ovalise it and remove the internal sharp edges produced when cutting the pipe. Drill again a hole (4 mm diameter) at a distance of 7mm from the pipe end F) Fig 3 5 to [he hole center
d Cut the flue pipe — cut from the plain end. Any Flue Cut off exactly the same amount as removed from the air pipe. Drill again a hole (3mm diameter) at a distance of 16 mm from the end of pipe to the centre of hole
e Cut the plastic- liner (S)
f Insert the flue pipe/terminal F) into the elbow A) and secure with the specific screw.
g Insert the terminal into the plain, i.e. unchannelled end of the air pipe E).
h IMPORTANT Before inserting the air pipe into the elbow. LUBRI­CATE THE ELBOW SEAL WITH OIL. then insert the air pipe completely into the elbow. If the elbow seal is not lubricated, it is not possible to insert the air pipe into the elbow. Take care to let the holes correspond, then insert the clevis pin (fig 4.4).
i Pass the flue/air pipe assembly through the plastic liner S).
j Fully insert the elbow A) into the fan socket, ensuring that the elbow seal is correctly located.
k Check that the terminal protrudes the correct amount from the wall face (fig. 4.3.).
4.7.2 HORIZONTAL EXTENSION FLUE SYSTEM a Measure wall thickness T (rig. 4.3)
Page 14
Loading...
+ 30 hidden pages