Keston Rigs User Manual

Prefabricated Plant Rigs
Installation & Control
Instructions
34 West Common Road
Hayes, Bromley, Kent BR2 7BX
Tel. +44 (0)20 8462 0262 Fax. +44 (0)20 8462 4459
WD309/0/2003 The Keston Prefabricated Plant Rigs
1.0 INTRODUCTION The Keston Pre-Fabricated Plant Rigs are designed as complete heating plant packages for rapid site installation and commissioning. The units are supplied to site pre-piped and pre-wired on a floor standing frame (a wall hung option is available for the two boiler rigs). The rigs are supplied complete with a Keston Rig Controller module.
2.0 PIPE CONNECTIONS Although most pipework is already complete within the rig. The final connections for gas, condensate, flue exhaust and air supply will need to be made to each boiler. The connections should be made following all requirements laid out in the boilers Installation & Servicing Instructions.
The rigs are provided complete with a balance header which is prepiped to each boiler. A pair of system tappings, flow and return, are provided on the header plus connection points for fill point, expansion vessel, air vent and drain off. The diagram below shows the relative position of these connection points and their intended purpose.
3.0 CONTROL MODULE
The Keston Rig Controller is a comprehensive controller offering a wide range of facilities to the end user. However, it is recognised that customers control requirements vary widely and that some functions are not always required. The rigs are supplied preset for option 1) Basic Sequence Control. To enable modes 2), 3) or
4) additional sensors may be required. In addition, commissioning set-up will be required by Keston Boilers Ltd, or its approved agents.
Installation & Control Instructions
Page 2 of 10
WD309/0/2003 The Keston Prefabricated Plant Rigs
3.1 AVAILABLE FUNCTIONS
To enable simple application the functionality is divided into four distinct groups as detailed below:
3.1.1 Entry Level (Factory Default)
This is the mode in which all rig controllers are set by the factory, and therefore no further components or action are necessary to realise these facilities.
Boiler Sequencing In this mode the controller sequences the operation of the boilers to ensure the required flow temperature is maintained with the minimum boiler operation. The required flow temperature is set by the user. Boiler Load Averaging The switching order of the boilers is changed once per week, based on the hours each boiler has run, to ensure even usage of each boiler over time. Frost Protection The Controller also provides frost protection, which will fire the boiler(s) in the event the main flow temperature falls below 5OC. The boiler will remain on until the flow temperature is raised above 15OC. System Pump Overrun & Seizure Protection The controller also provides a 230VAC output for connection to a system pump. The pump is run when the rig is enabled and will also provide a 2 minute overrun on shutdown. The controller will also operate the system pump at least once daily to prevent seizure. Fault Signal A volt free pair of contacts are provided which move the closed circuit in the event of a fault being identified Control Signal The Controller will fire the boiler(s) when enabled via a volt free contact pair.
3.1.2 Compensated Heating & Time Control This mode provides all the features detailed in “Basic Sequence Control” plus the additional features detailed below. However, to access this mode an outside temperature sensor (part no C.17.4.17.00.0) is required. These are available from Keston Boilers Ltd via your preferred stockist.
Weather Compensated Heating Control The boiler flow temperature is adjusted automatically according to the outside temperature. This provides even building temperatures and maximises boiler efficiency. Comprehensive Heating Time Control The controller features an integral time programmer for heating periods permitting a different heating pattern for each day of the week with up to two heating periods per day. Holiday dates can also be programmed. The user may then specify three temperature levels – day, night and holiday. The room temperature is estimated based on outside temperature, boiler flow temperature and the building construction. DHW Override In the event a volt free signal is received from the hot water system the weather compensated heating control is suspended and the unit runs at the specified flow temperature until the volt free signal is removed. Outside Temperature Frost Protection The outside temperature is constantly monitored such that, in the event the outside temperature falls below 3OC the boiler is fired to maintain a boiler flow temperature of 20OC. Once the outside temperature rises to 4OC or above this action is stopped. This feature is design to ensure protection of system pipes against freezing. However, it can be disabled if required.
Installation & Control Instructions
Page 3 of 10
Loading...
+ 7 hidden pages