Keston Qudos 37, Qudos 37P User's Installation Manual

Q
QQ
Qudos
udosudos
udos
33
37
77
7
Fan Powered High Efficiency
Modulating Domestic Condensing Gas Boiler
User, Installation and Servicing Instructions
ISSUE: 3/2010
Q37 & Q37P Models
CE/PI No : 87BQ006
Q37 - GC No : 41-930-23
Q37P - GC No : 41-930-24
These instructions must be left either with
the user or next to the site gas meter.
34 West Common Road
Hayes, Bromley, Kent BR2 7BX
Tel. +44 (0)20 8462 0262 Fax. +44 (0)20 8462 4459
email : info@keston.co.uk web : www.keston.co.uk
COMPLIANT WITH BUILDING REGULATION PART L1 & L2
SEDBUK A RATED
WD500 The Keston Q37 & Q37P Boilers
CONTENTS
NB : These instructions are an integral part of the appliance. This document must be handed over to
the user on completion of the installation to ensure compliance with the Gas Safety (Installation & Use) Regulations
Section Description 0 HANDLING INSTRUCTIONS
0.1 List of contents
0.2 Recommended handling procedure
1 USER INSTRUCTIONS
1.1 Introduction
1.2 Maintenance
1.3 Boiler Setup and Operation
1.4 Safety Information
2 GENERAL INSTRUCTION
2.1 Description
2.2 Boiler Schematic
2.3 Related Documents
2.4 Physical Data
2.5 Optional Accessories
2.6 Performance Data Q37 and Q37P
3 BOILER LOCATION
3.1 Dimensions & Minimum Clearances
3.2 Service Connections
3.3 Position
3.4 Electrical
3.5 Boiler Size Selection
3.6 Gas Supply
3.7 Water Systems
3.8 Flue System
3.9 Air Supply
3.10 Compartment Installation
3.11 Condensate Drainage
4 INSTALLATION OF THE BOILER
4.1 Wall Mounting Bracket
4.2 Mounting The Boiler
4.3 Assembly Practice
4.4 Installing Flue And Air Pipes
4.5 Condensate Drainage
4.6 Water System
4.7 Gas Supply
4.8 Electrical Supply
4.9 Exchanging A Boiler
WD500 The Keston Q37 & Q37P Boilers
Page : i
5 COMMISSIONING OF THE BOILER
5.1 Initial Flushing
5.2 Gas Supply
5.3 Electrical Installation
5.4 LP Gas
5.5 Initial Firing
5.6 Hot Flushing
5.7 Combustion Testing
5.8 Checking The Gas Pressure
5.9 Timing The Gas Meter
5.10 Handing Over To The User
6 FAULT FINDING
6.1 Electrical Control Sequence
6.2 Normal Operation
6.3 Fault Modes
6.4 Functional Flow Wiring Diagram
6.5 Electrical Wiring Diagram
6.6 Illustrated Wiring Diagram
6.7 Exploded Assembly Diagrams
7 SERVICING
7.1 Pre Service Checks
7.2 Recommended Routine Service
8 REPLACEMENT OF PARTS
8.0 General
8.1 Precautions
8.2 Access
8.3 Replacement Procedure
8.4 Electrical Components
8.5 Spark Ignition/Flame Detection Electrode
8.6 Burner
8.7 Heat Exchanger
8.8 Condensate Trap
8.9 Pump
9 SPARE PARTS LISTINGS 10 GAS BOILER COMMISSIONING CHECKLIST
WD500 The Keston Q37 & Q37P Boilers
Page : ii
0. HANDLING INSTRUCTIONS
0.1 LIST OF CONTENTS
The Keston Q37 and Q37P are supplied almost totally pre-assembled. The units use standard 50 mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) pipe for the flue and air intake systems. The boiler is packed in a single box without additional flue kit. All additional components are packed inside the boiler cabinet itself. The following is a list of components and their location in the boiler cabinet
Equipment List Item Quantity Location
Wall Bracket Rawl Plugs 6 Inside accessories bag Wall Bracket Wall Fixing Screws 6 Inside accessories bag Wall Mounting Bracket 1 Secured to inside right
hand side of boiler case Wall Mounting Bracket Nuts 2 Inside accessories bag. Wall Mounting Bracket Washers 2+2 Inside accessories bag 50 mm muPVC Air/Flue Terminals 2 Inside accessories bag Gas Isolating Cock 1 Inside accessories bag 50 mm muPVC Pipe 2 Inside boiler case 50 mm muPVC Elbow 2 Inside boiler case Outside Temperature Sensor 1 Inside boiler case
Document List Item Quantity Location
Registration of Purchase 1 In A4 envelope 2 Year Warranty Plan 1 In A4 envelope Installation Template 1 In document bag
Remove the cabinet shell by removing the two retaining screws in the top of the cabinet and the two retaining screws in the bottom of the cabinet.
0.2 RECOMMENDED HANDLING PROCEDURE
NB : The following lift operation exceeds the recommended weight for a one-man lift as specified in the Manual Handling Operations 1992 Regulations.
For the carriage of carton it is recommended at least two people perform any lift. Clear the carriage route of the carton from point of delivery to point of installation. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. Always use assistance if required. If a sack truck is used it is recommended the carton is strapped to the truck.
For the unpacking of the appliance from the carton, it is recommended at least two people perform any lift. It is recommended to cut the base end of carton and open the carton flaps. Ensure the protective packing over the boiler tappings at the base of the boiler is kept in place, then tilt the boiler forwards from its back onto its base and remove carton by sliding up over the boiler. When lifting this appliance the back should be kept straight at all times. Avoid twisting at the waist - reposition the feet instead. Avoid upper body bending when holding the appliance and keep the boiler as close to the body as possible.
Before hanging the appliance on the wall it is best to store the appliance laid on its back with the casing on. When ready to hang the boiler on the wall remove the casing and place to one side. At this stage it is assumed that the wall bracket is correctly positioned and secured on the wall face.
WD500 The Keston Q37 & Q37P Boilers
Page : iii
a) Have the wall bracket nuts and washers to hand so that they can be accessed whilst
holding the boiler in position on its mounting bracket.
b) The boiler has a dry weight of 41 kg (91 lbs) and will therefore require at least two people
to lift without the use of lifting aids - ensure co-ordinated movements during lift. Always use assistance if required.
c) Lift the boiler by gripping at the four corners of the boiler back plate. When lifting this
appliance the back should be kept straight at all times. Avoid twisting at the waist ­reposition the feet instead. Avoid upper body bending when holding the appliance and
keep the boiler as close to the body as possible. d) Lift the boiler and locate onto the two studs of the wall mounting bracket. e) Place the wall mounting bracket washers over the bracket stud protruding through the
back plate of the boiler. f) Secure the boiler onto the wall bracket by fixing the wall mounting bracket nuts onto the
wall bracket studs. This must be tightened well. Safety footwear and gloves are recommended PPE when lifting this appliance - to protect
against sharp edges and ensure good grip. The Q37 and Q37P boilers can be fitted in compartments with very small clearances required
around the appliance (refer to Section 3.1). Due consideration should therefore be given to access within the compartment for lifting and positioning.
WD500 The Keston Q37 & Q37P Boilers
Page : iv
1. USER INSTRUCTIONS
1.1 INTRODUCTION
Thank you for choosing this Keston Q37 for your household heating. The boiler is designed to be very straightforward to operate and has no user serviceable parts inside the cabinet. The following instructions are to provide you with information on the operation and maintenance of your Q37 and what to do in the unlikely event of a fault.
These user instructions should be read carefully to ensure safe and economical use of your Q37 or Q37P. The Q37 model is for use with natural gas only, the Q37P model is for use with LPG only.
1.2 MAINTENANCE Servicing
To ensure continual safe and efficient operation and to maintain product warranties it is a requirement that the appliance is checked and serviced at least once per year. It is the law that any servicing must be carried out by a competent person. Removal of the appliance
cabinet by anyone other than a competent person will automatically invalidate the appliance warranty.
Clearances
If fixtures are to be positioned close to the boiler, the following minimum clearances must be observed: Top 150mm, Left 5mm, Right 5mm, Base 100mm, Front 10mm. Extended clearance is required to the front for servicing (300mm).
Cleaning
Normal case cleaning only requires dusting with a dry cloth. To remove more stubborn marks wipe with a damp cloth and finish with a dry cloth.
1.3 BOILER SETUP & OPERATION
Check that the gas supply from the gas meter is turned on. Switch on the electrical supply to the boiler. The display will now run through a self check procedure. Set any controls to call for heat.
To light the boiler
The Q37 features separate two temperature controls to allow different settings depending on the source of the demand, i.e. heating or hot water. To set these press the “+” or “-” buttons associated with the 1st stat or 2nd stat temperature and set the required temperature. After a few seconds the display stop flashing and will change back to show the actual boiler temperature. If the actual temperature is less than the desired temperature the boiler will fire and, after a few seconds, a “.” will appear in the lower right hand corner of the display to show that the boiler is alight. In summer you can switch the boiler to hot water only by pressing the “2nd STAT ONLY” button to that the green lamp above it is illuminated. In this mode the boiler will not respond to any demand for 1st stat. Press the
WD500 Chapter 1 : User Instructions The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 1
“2nd STAT ONLY” button again to extinguish the green light above and resume normal central heating operation.
Normal Operation
During normal operation the digital display will show the current boiler temperature and will show a “.” in the lower right corner of the display when the burner is alight. If the green lamp near the “1st STAT” or “2nd STAT” +/- keys is illuminated the boiler is receiving a demand for that function. If the green lamp is flashing the boiler is either up to temperature or shutting down following removal of the “1st STAT” or “2nd STAT” demand.
Fault Modes
In the event that the boiler detects a situation which it considers to be a fault the display will change to show a flashing fault code starting with an “E” and then a two digit number. The table below explains these codes and the action you should take.
Water pressure too high - You have put too much water pressure in your systemE40
Water pressure error - You must top up the water pressure for your systemE37
Mains supply frequency incorrect - There may be a problem with your power supply.E35
Mains supply voltage < 180V - There may be a problem with your power supplyE34
Flame drop out - Check for obstruction of the flue and/or air terminals, blockage/freezing of the drain pipe or a low gas supply (LPG).
E26
Water pressure losses - You have topped up the water pressure more than 4 times in 24 hours. You may have a leak on the system..
E24
Boiler overheat - Check that any valves to the heating circuit have not been shut down, that there is no air in the system and that the water pressure is correct..
E03
False flame - There is possibly a problem with the power supply.E02
Ignition failure - the boiler has attempted to light five times and not succeeded - check the gas supply is on.
E01
Description of faultDisplay
The above is an abbreviate list of possible error codes. If the code is not in the list above consult a GAS SAFE REGISTER registered engineer. A full list of codes can be found in Chapter 6 of this manual. If a code appears and you feel the original cause has been rectified, press the “Reset” button to resume boiler operation. If the code persists consult a GAS SAFE REGISTER registered engineer. When topping up the water pressure you can observe the actual pressure by pressing the “Installer” button repeatedly until the number “5” appears. After a few seconds the display with then change to show the system water pressure in bar. Set the water pressure to between 1.0 and 2.0 bar.
Precautions
Care must be taken at all times to ensure that no blockage or obstruction is present in the condensate drainage line. In addition, the air intake and flue exhaust terminals must be free from obstruction at all times.
Frost Protection
The Q37 has an integral frost protection function. However, care should also be taken that any exposed pipework is adequately insulated to prevent freezing.
1.4 SAFETY INFORMATION IF YOU SUSPECT A GAS LEAK TURN OFF THE APPLIANCE IMMEDIATELY, TURN OFF
THE GAS TAP TO THE APPLIANCE (LOCATED UNDERNEATH) AND CONTACT YOUR LOCAL GAS REGION WITHOUT DELAY.
WD500 Chapter 1 : User Instructions The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 2
Benchmark Initiative As part of the industry wide “Benchmark” initiative Q37 boiler manual includes Gas Boiler
Commissioning Checklist (Chapter 10). This form should be completed by your installer at
the end of the installation and commissioning process. The details of the Checklist will be required in the event of any warranty work being required. There is also Service Interval
Record (Chapter 10) to be completed after each annual service visit. These forms (Chapter 10) should be kept in a safe place for the life of the boiler.
The boiler should be installed and serviced only by GAS SAFE REGISTER registered operatives. All GAS SAFE REGISTER registered Installers carry a GAS SAFE REGISTER ID card and have a registration number. Both should be recorded in your boiler manual (Chapter 10: GAS BOILER COMMISSIONING CHECKLIST). You can check your installer by calling GAS SAFE REGISTER direct on 0800 408 5500.
IMPORTANT This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
WD500 Chapter 1 : User Instructions The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 3
2. GENERAL INSTRUCTION
2.1 DESCRIPTION
The KESTON Q37 and Q37P boilers utilize the latest in condensing technology to produce a high efficiency boiler with SEDBUK A rated efficiency plus advanced controls to maximize operational efficiency.
The Q37 is unique in concept and design. It comprises a high efficiency stainless steel
heat exchanger coupled with a low emissions burner to deliver ultra high efficiency
condensing mode operation within a compact wall hung cabinet. The unit automatically
adjusts gas and air rate according to demand to give a heating input in the range of 9.2kW
to 38.0kW (GCV). The integral pump assembly, in the Q37, is automatically speed
controlled to best match water flow rate to heat output & further increase appliance
efficiency.
In addition, the boiler feature a connection for an optional outside sensor to enable the
boilers inbuilt weather compensation option which delivers enhanced user comfort levels
with peak operating efficiency due to the lower flow temperatures involved. The boiler also
features an “Opentherm” connection point for the Keston Room Control module which
provides further advanced user control for room temperature compensation and optimum
start. The boiler fascia provides separate user controls for 2 stats (e.g. central heating and
domestic hot water temperatures). The boilers have the added advantage of very high
efficiency, and small diameter muPVC plastic flue which can be extended up to 20
metres horizontally or vertically.
The Keston Q37 uses a variable speed combustion blower to deliver a premix of gas and
air to a downward firing burner in a high efficiency, single pass heat exchanger. The flue
system is room sealed and fan powered. The ignition is direct spark and fully automatic.
The boiler housing is not waterproof and should be installed in a position where it will
always be dry. Combustion air is drawn from the cabinet which is connected to outside
atmosphere via a small diameter plastic intake pipe. The cabinet therefore remains under
negative pressure at all times the boiler is operating.
The boiler is suitable for connection to open vented or, preferably, sealed systems. The
pump is fitted within the boiler.
The boiler heat exchanger is made from highly corrosion resistant stainless steel in
corrugated pipe form which provides massive surface area within a compact dimension.
The hot combustion gases from the down firing burner pass around the stainless steel
pipes imparting heat into the system water. The integral variable speed pump within the
appliance cabinet ensures the heat exchanger receives correct water flow when firing.
The Q37 is not a high water content boiler and does not contain the metal mass, or water
volume, of a cast iron or steel boiler. This boiler is of low mass and low water content and
therefore responds faster when there is a call for heat. The Q37 features full user
diagnostics, integral frost protection function, automatic pump and fan exercise in periods
of inactivity, anti cycle control and dry fire protection.
2.2 BOILER SCHEMATIC
Air is drawn into the boiler through a 50 mm muPVC (BS5255 and/or BSEN1566-1 and
BSEN1329) plastic pipe or, alternatively, via a 75mm Keston composite plastic pipe. Gas
is mixed with combustion air at the inlet to the fan. The gas flow is automatically regulated
by the gas valve according to the air flow generated by the fan. The gas and air are
thoroughly mixed in the blower and fed into the burner located at the top end of the heat
exchanger module. The gas and air mixture is ignited by a direct spark ignition control
system and burns with a blue flame just off the surface of the burner. As the hot products
of combustion pass downwards, they are cooled by exchanging heat with the circulating
water which enters the heat exchanger at the bottom of the heat exchanger. The optimum
heat input is detected by monitoring flow and return temperatures and is adjusted by
WD500 Chapter 2 : General Instruction The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 4
controlling the speed of the fan. The optimum pump speed is also detected and automatically selected by the boiler.
When the return water temperature is below 55oC, part of the water vapour in the combustion products will condense inside the heat exchanger, thus increasing the boiler efficiency further by releasing the latent heat of condensation. This condensate falls to the bottom of the heat exchanger where it is separated from the flue gases and exits from the boiler through the condensate drain. Any condensate formed in the flue runs back down the flueway and is drained at the base of the flue connection to the heat exchanger or drain points within the flue.
The condensate is very slightly acidic (about the same acidity as vinegar) and should be piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed of as normal waste water.
The flue gases are piped in a 50 mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) plastic or, alternatively, 75mm Keston composite plastic pipe to outside. The temperature of the flue gases are usually around 5oC to 10oC above the temperature of the return water. The flue pipe should be terminated outside the building from where they cannot re-enter the building or any other adjacent building.
The heating level may be controlled by room thermostats, programmer time clocks and compatible energy management systems. An optional Keston room controller can
WD500 Chapter 2 : General Instruction The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 5
be connected which will provide enhanced controls such as room compensation to further
increase efficiency and comfort levels on heating only systems. Once the controls are set
the boiler operates automatically. Further, a Keston outside sensor can be connected to
the boiler which will automatically invoke weather compensated heating which further
boosts user comfort and boiler efficiency.
In the event of the boiler overheating the safety devices will cause a safety shutdown.
The Q37 features an integral frost protection function which will operate the pump,
regardless of the external controls, should the boiler temperature fall below 10oC. In the
event the boiler temperature falls below 5oC the boiler will also fire. This is to avoid
damage to the boiler through freezing of boiler water. The boiler will turn off when the flow
temperature exceeds 15oC.
The Q37 features an integral pump exercise function which will run the pump, without
firing the boiler, for 10 seconds in the event the boiler is on standby for in excess of 24
hours without firing. This is to help prevent seizing of the pump due to long periods of
inactivity.
2.3 RELATED DOCUMENTS
The Keston Q37 and Q37P Condensing Boiler must be installed in accordance with the
current issue of the Gas Safety (Installation and Use) Regulations 1996, current IEE
Wiring Regulations, Building Regulations, Building Standards (Scotland) Consolidation,
and the Bye Laws of the local Water Undertaking. It is the law that ALL gas appliances
are installed by a competent person in accordance with the above regulations.
In addition, due account must be taken to the following Codes Of Practice:
BS 6891 : Low Pressure Installation Pipes BS 6798 : Installation of Gas Fired Hot Water Boilers of
Rated Input Not Exceeding 70kW BS 5449 : Installation Pumped Central Heating BS 5546 : Installation of Gas Hot Water Supplies for
Domestic Purposes (2nd family gases) BS 5440.1 : Flues (for gas appliances of rated input not
exceeding 70kW) BS 5440.2 : Air Supply (for gas appliances of rated input not
exceeding 70kW) BS 5482.1 : Domestic Propane and Butane Burning
Installations BS 7074.1 : Expansion Vessels BS 7593 : Treatment of Water in Hot Water Central Heating
Systems BS 7671 : Requirements for Electrical Installations. IEE
Wiring Regulations 16th Edition.
BSEN 12828:2003 : Heating Systems in Buildings: Design for water
based heating systems BSEN 12831:2003 : Heating Systems in Buildings: Method for
calculation of design heat load BSEN 14336:2004 : Heating Systems in Buildings: Installation and
commissioning of water based heating systems For Timber Framed Buildings, British Gas Publications DM2. Also British Gas Publications 'Guidance Notes For The Installation Of Domestic Gas Condensing Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
In IE, the installation must be carried out by a competent person and installed in accordance with the current edition of IS813 “Domestic Gas Installations”, the current Building Regulation and reference should be made to the current ETC1 rules for electrical installations.
WD500 Chapter 2 : General Instruction The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 6
No alterations should be made to the boiler without written permission from Keston Boilers Ltd. Any unauthorised modification will invalidate the warranty and may affect the safe and efficient operation of the boiler.
2.4 PHYSICAL DATA - Q37 & Q37P
Cabinet Height mm 780 Cabinet Width mm 500 Cabinet Depth mm 304
Top Clearance mm 150 Side Clearance mm 5 Base Clearance mm 100 Front Clearance (for servicing) mm 300
Weight - Full kg / (lbs) 46/(101) Weight - Empty kg / (lbs) 41/(90)
Flow and Return Connection 28mm pipe Gas Connection 22mm pipe Condensate Connection overflow 22mm plastic
IP Rating IP20 (IPX0) Flue and Air Intake Material 50mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329)
Flue Pipe Size (nominal bore) mm / (in) 50 / (2) Air Intake Pipe Size (nominal bore) mm / (in) 50 / (2) Max. Air Intake Length m 39 Max. Flue Outlet Length m 20* Max. Total Flue Outlet and Air Intake Length m 40 * Flue lengths between 16 and 20m will create a 1% reduction in output. Flue and Air Intake Material 75mm Keston Composite Flue Pipe Size (nominal bore) mm / (in) 75 / (3) Air Intake Pipe Size (nominal bore) mm / (in) 75 / (3) Max. Air Intake Length m 117 Max. Flue Outlet Length m 60** Max. Total Flue Outlet and Air Intake Length m 120 ** Flue lengths between 48 and 60m will create a 1% reduction in output
2.5 OPTIONAL ACCESSORIES
A range of accessories are available from Keston Boilers Ltd to compliment an installation. Terminal wall sealing collars are available to make good the external all face whilst working from the inside of the building using 50mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) pipe. Stand-off frame is available to leave a 50mm gap behind the boiler to allow routing of pipes behind the boiler.
Description Part Number
Flue Terminal Wall Sealing Collar (50mm) C.08.0.00.07.0 Air Terminal Wall Sealing Collar (50mm) C.08.0.00.07.0 50/75mm Flue Adapter C.17.2.00.60.0 Flue Outlet Terminal (75mm) C.17.2.26.00.0 Air Inlet Terminal (75mm) C.17.2.26.00.0 Keston Chronotherm Room Controller C.17.4.21.00.0
WD500 Chapter 2 : General Instruction The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 7
2.6 PERFORMANCE DATA - Q37 & Q37P
Seasonal Efficiency (SEDBUK) = 90.4 (Q37) & 92.4 (Q37P) This value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by Advantica Technologies Ltd
Keston Boilers Ltd declare that there are no substances harmful to health within the appliance or used during the production of the appliance.
The Q37 is intended for domestic and commercial EMC environments and on a governed G20 meter supply.
The Q37P is intended for domestic and commercial EMC environments and on a governed G31 supply.
WD500 Chapter 2 : General Instruction The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 8
Q37 Q37P NG (G20) LPG (G31)
Min. Input (Gross CV) kW/(Btu/h) 9.2/(31,400) 9.0/(30,700) Max. Input (Gross CV) kW/(Btu/h) 38.0/(129,700) 37.0/(126,300)
Max. Output To Water
(80/60oC Flow/Return) kW/(Btu/h) 33.6/(114,700) 33.6/(114,700) (50/30oC Flow/Return) kW/(Btu/h) 37.0/(126,300) 37.0/(126,300)
Min. Output To Water
(80/60oC Flow/Return) kW/(Btu/h) 8.1/(27,600) 7.4(25,250) (50/30oC Flow/Return) kW/(Btu/h) 9.0/(30,700) 8.1/(27,600)
Max. Burner Press.-Hot
(Factory Preset)
mbar/(in w.g) 0/(0) 0/(0) Max. Gas Cons. After 10 mins l/s / (Ft3/hr) 1.00/(127) 0.38/(49) Max. Operating Flow Temp.
o
C 82 82
Max. Press. (Sealed System) bar 2.50 2.50 Inlet Gas Pressure mbar/(in w.g) 20.0 / (8.0) 37.0/(14.8)
Recommended Temp Diff.
o
C 8 to 20 8 to 20
Electrical Supply 230V 50Hz 230V 50Hz Power Consumption (Max) W 198 198 Power Consumption (Standby) W 4 4
Type of Gas G20 Natural Gas G31 LPG Optimum Flue Gas CO2 Level (at max CH rate, case on) 9.1±0.2 10.5±0.2
Expected CO/CO2 Ratio (at max CH rate, case on) 0.0006 0.001 Destination Countries GB/IE GB/IE
SEDBUK Efficiency 90.4 92.4 NOx Class 5 5 Heating System Minimum Press. bar / (lbf/sq in) 0.7 / ( 10.1)
This boiler meets the requirements of SI 3083 The Boiler (Efficiency) Regulations and is therefore deemed to meet the requirements of Directive 92/42/EEC. The CE mark on the appliance shows compliance with Directives 90/396/EEC, 73/23/EEC and 89/336/EEC.
IMPORTANT This product contains ceramic fibre boards, which although not regarded as a risk, contain ceramic fibre which may cause temporary irritation to eyes, skin and respiratory tract. The fibres are held in place by inorganic binders. Therefore as long as the boards are not disturbed they will not be released. Since the boards are non-serviceable parts there should be no risk. Under no circumstances should the user interfere with any sealed parts.
To ensure that the release of fibres from these RCF articles is kept to a minimum, during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust accumulated in and around the appliance before and after working on the appli­ance. When replacing these articles we recommend that the replaced items are not broken up, but are sealed within heavy duty polythene bags, and clearly labelled as RCF waste. RCF waste is classed as a stable, non-reactive hazardous waste and may be disposed at a landfill licensed to accept such waste. Protective clothing is not required when handling these articles, but we recommend you follow the normal hygiene rules of not smoking, eating or drinking in the work area and always wash your hands before eating or drinking.
BENCHMARK INITIATIVE As part of the industry wide “Benchmark” initiative Q37 boiler manual includes Gas Boiler
Commissioning Checklist (Chapter 10). This form should be completed by your installer at the
end of the installation and commissioning process. The details of the Checklist will be required in the event of any warranty work being required. There is also Service Interval Record (Chapter
10) to be completed after each annual service visit. These forms (Chapter 10) should be kept in a safe place for the life of the boiler.
The boiler should be installed and serviced only by GAS SAFE REGISTER registered operatives. All GAS SAFE REGISTER registered Installers carry a GAS SAFE REGISTER ID card and have a registration number. Both should be recorded in your boiler manual (Chapter 10: GAS BOILER COMMISSIONING CHECKLIST). You can check your installer by calling GAS SAFE REGISTER direct on 0800 408 5500.
WD500 Chapter 2 : General Instruction The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 9
3. BOILER LOCATION
3.1 DIMENSIONS AND MINIMUM CLEARANCES
The boiler must be installed in minimum clearances shown to allow subsequent servicing, and safe operation. However, larger clearances may be required during installation.
3.2 SERVICE CONNECTIONS
Gas, water, air and flue pipe, condensation,
and electrical connections are as shown. Gas : 22mm pipe. Flow/Return 28mm pipe.
The Q37 is equipped with both top and bottom outlet connections for flow and return. The outlet connection which is not used should be capped.
An optional stand-off frame is also available which mounts behind the boiler to leave a 50mm deep space behind the boiler. This is to permit pipe routing behind the boiler if required. See Section 2.5 - Optional Accessories.
3.3 POSITION
The Q37 and Q37P are not suitable for external installation. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Where a room-sealed appliance is installed in a room containing a bath or shower, any
electrical switch or appliance control, utilising
WD500 Chapter 3 - Boiler Location The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 10
All dimensions in mm.
150
300 When servicing appliance
100
Figure 3.1.1
Minimum Clearances
55
10 When appliance is operating
All dimensions in mm.
500
3
0
4
Figure 3.1.2 Dimensions
Flue
Air Intake
780
mm
mains electricity, should be so situated that it cannot be touched by a person using the bath or shower. The Q37 and Q37P are classified as IP20 (IPX0) and are therefore suitable for installation in Zone 3 areas, unless subject to hose down.
Compartment installation is permitted - such compartments must be constructed in accordance with BS 6798. The wall on which the boiler is mounted must be of suitable load bearing capacity and must be non-combustible. The Keston Q37 can be located virtually anywhere desired provided that all regulations are complied with. Because of the boiler's compact size and venting flexibility, the installation is not limited to a boiler room setting. Before locating the boiler near a living space consider whether the sounds generated by the boiler will be objectionable. The boiler may be located within a cupboard enclosure to reduce noise levels if located within a living space. LPG boilers must not be installed in a cellar.
3.4 ELECTRICAL
3.4.1 Electrical Connections
The boiler must be connected to a permanent 230V ~ 50Hz supply, fused at 3A.
The boiler can be wired to a single switched live 230VAC input. However, the boiler has TWO thermostats, and will therefore accept up to TWO switched live 230VAC signal inputs, such as heating and hot water or radiators and underfloor heating zones. 2nd STAT demand will always take priority over a 1st STAT demand. Alternatively, a Keston Room Controller can be connected directly, via two core low voltage cable, to the terminals marked “OT”. The Keston Room Controller will then provide fully room compensated control to ensure the boiler output is matched to the rooms requirements at optimum boiler efficiency. This is only recommended for heating only applications. Wiring external to the boiler must be in accordance
with current I.E.E wiring regulations and local regulations.
WD500 Chapter 3 - Boiler Location The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 11
Chimneys not used for venting any other
appliance may be used.
Figure 3.3
Secure air & flue pipes at chimney outlet.
[NB: Refer to Section 3.8.3]
The method of connection to the mains electricity supply must facilitate complete electrical isolation of the boiler, preferably by the use of a fused, unswitched three pin plug and a shuttered socket-outlet, both complying with the requirements of BS 1363. There must be only one common method of isolation for the boiler and its control system. The appliance must be connected to the 3A supply via a fused double-pole switch having at least 3 mm (1/8 inch) contact separation in both poles, serving only the boiler and the system controls. The connection point to the mains supply should be readily accessible and adjacent to the boiler, except for rooms containing a bath or a shower. Refer to section 3.3 Position.
3.4.2 External Wiring & Controls
1. The boiler is designed so that all control wiring is external to the boiler.
2. Heating control signal inputs must the 230VAC "switched live" type unless using a Keston Room Controller (see below)
3.4.2.1 Enhanced Control Options
Room Compensation (Opentherm) A Keston Room Controller may be used to provide room compensated control to ensure the boiler output is matched to the rooms requirements at optimum boiler efficiency. This is only recommended for heating only applications.
Weather Compensation A Keston outside temperature sensor may be connected as an option. The boiler will automatically detect this connection and will operate on a "weather compensation" basis when receiving a heating demand signal from the SL1 terminal or from a Keston Room Controller. Screened cable (80% density) must be used to connect the outside temperature sensor.
3.5 BOILER SIZE SELECTION
The Q37 will automatically adjust heat output and pump speed to match the system requirements at any given time. Efficiency and combustion levels are maintained at optimum levels throughout the possible output range. The Q37 is therefore suitable for all systems with a total heat load within the maximum range of the boiler.
3.6 GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas region or their contractor. An existing meter should be checked preferably by the gas region to ensure that the meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891.
Minimum/Maximum Gas Pressure:
Natural gas pressure before the gas valve must be maintained at between 18 mbar (7.2 in WG) and 22 mbar (8.8 in) while the boiler is running
.
WD500 Chapter 3 - Boiler Location The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 12
Live Neutral Earth
Mains Supply 230V
Fused @ 3A
Room Thermostat T6360B1028
1 2 3
KESTON
Qudos 37
L N E
SL1
Alarm
SL2
3.4.2 Wiring Example
OTC OTC
To Keston Ext. Sensor [Optional]
OT OT
To Keston Room Controller [Optional - instead of room thermostat]
LPG pressure must be maintained between 31.5 mbar (12.4 in w.g) and 37.6 mbar (14.8 in w.g) while the boiler is running. Gas pressures above or below these levels will lead to problems associated with the gas valve's internal pressure regulator.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (22mm). Due consideration must be given to the supply pressure to other gas appliances in the premises. Reduction in dynamic gas supply pressure will result in intermittent ignition failures. Ensure gas supply pipe work is adequately sized for the length of run from the meter to the boiler at a supply rate of 38kW (i.e. a natural
gas supply should be considered to be a minimum of 22mm diameter. If gas runs greater than 14m, including the allowance for bends, are involved the pipe size should be increased further).
3.7 WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply Bylaws for forced hot water heating systems. Consideration must be given to pipe capabilities and pressure drop through the piping when selecting pipe sizes. The primary pipe connections to the boiler must be sized according to the system load, not dictated by the boiler connection sizes. Water treatment must be carried out to BS 7593 : Treatment of Water in Hot Water Central Heating Systems. In IE the requirements given in the current edition of IS813 and the current Building Regulations must be followed.
a The Q37 is suitable for use on open, vented water systems with combined feed
and vent fitted to the boiler return.
b It is preferable for use on sealed water systems, provided the appropriate
components required (see Section 3.7.2 Sealed Systems) are included in the system.
c Any system must be thoroughly flushed clean of grease, dirt and debris, prior to
connection with the boiler. A trap may be installed in the flow line to collect any solder, or other debris, from the installation.
d All water systems must be constructed to comply with requirements of the Local
Water Authority. e Always use a system complying with the requirements of BS 5449 and BS 6798. f System design must ensure an open circuit is always available to ensure
circulation when the pump overrun function is operating after boiler shutdown. f Isolation valves must be fitted on the flow and the return to enable isolation when
maintaining the boiler. g Copper tubing to BS 2871 Part 1 or barrier plastic pipe suitable to 110 oC, such as
Unipipe, is recommended. h Jointing should be either with capillary, threaded or compression fittings. Pipes
should have a gradient to ensure air is passed easily to vent points and water
flows readily to drain points. i Draining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 22 mm in
nominal size and be in accordance with BS 2879.
AIR VENT POINTS j These must be fitted at all high points where air will naturally collect and must be
sited to allow complete draining of the system. k. Where thermal stores are to be used the thermal store supplier should be
consulted as to the compatibility of the thermal store with a Keston Q37. Thermal
store units where the boiler directly heats an open vented thermal store are not
suitable for use with the Q37.
3.7.1 Open Vented Systems
A typical system is shown in Figure 3.7.1 which includes a combined feed and
vent. Note that the combined feed and vent must be fitted to the primary
WD500 Chapter 3 - Boiler Location The Keston Q37 & Q37P Boilers
Installation & Servicing Instructions Page : 13
Loading...
+ 40 hidden pages