Keston Q28H Installation Manual

Qudos 28h
User, Installation and Servicing
Instructions
FAN POWERED HIGH EFFICIENCY
GAS HEAT ONLY BOILER
CE/PI No. 86-CM-43
Qudos 28h - GC No. 41-930-19
Qudos 28hP - GC No. 41-930-20
These instructions must be left either with the
user or next to the site gas meter.
Keston Heating
PO Box 103, National Avenue, Kingston Upon Hull, HU5 4JN
Tel. +44 (0) 1482 443005 Fax. +44 (0) 1482 467133
email : info@keston.co.uk web : www.keston.co.uk
COMPLIANT WITH BUILDING REGULATION PART L1 & L2
SEDBUK A RATED
WD 440
issue 7 - 2011
CONTENTS
NB : These instructions are an integral part of the appliance. This document must be handed over to
the user on completion of the installation to ensure compliance with the Gas Safety (Installation & Use) Regulations
.
Section Description
0 HANDLING INSTRUCTIONS
0.1 List of contents
0.2 Recommended handling procedure
1 USER INSTRUCTIONS
1.1 Introduction
1.2 Maintenance
1.3 Boiler Setup and Operation
1.4 Safety Information
2 GENERAL INSTRUCTION
2.1 Description
2.2 Boiler Schematic
2.3 Related Documents
2.4 Physical Data
2.5 Optional Accessories
2.6 Performance Data
3 BOILER LOCATION
3.1 Dimensions & Minimum Clearances
3.2 Service Connections
3.3 Position
3.4 Electrical
3.5 Boiler Size Selection
3.6 Gas Supply
3.7 Water Systems
3.8 Flue System
3.9 Air Supply
3.10 Compartment Installation
3.11 Condensate Drainage
4 INSTALLATION OF THE BOILER
4.1 Wall Mounting Bracket
4.2 Mounting The Boiler
4.3 Assembly Practice
4.4 Installing Flue And Air Pipes
4.5 Condensate Drainage
4.6 Water System
4.7 Gas Supply
4.8 Electrical Supply
4.9 Exchanging A Boiler
5 COMMISSIONING OF THE BOILER
5.1 Initial Flushing
5.2 Gas Supply
5.3 Electrical Installation
5.4 LP Gas
5.5 Initial Firing
5.6 Hot Flushing
WD440/3/2007 The Keston Qudos 28h & Qudos 28hP Boilers
Page : i
5.7 Combustion Testing
5.8 Checking The Gas Pressure
5.9 Timing The Gas Meter
5.10 Handing Over To The User
6 FAULT FINDING
6.1 Electrical Control Sequence
6.2 Normal Operation
6.3 Fault Modes
6.4 Functional Flow Wiring Diagram
6.5 Electrical Wiring Diagram
6.6 Illustrated Wiring Diagram
6.7 Exploded Assembly Diagrams
7 SERVICING
7.1 Pre Service Checks
7.2 Recommended Routine Service
8 REPLACEMENT OF PARTS
8.0 General
8.1 Precautions
8.2 Access
8.3 Replacement Procedure
8.4 Electrical Components
8.5 Spark Ignition/Flame Detection Electrode
8.6 Burner
8.7 Heat Exchanger
8.8 Condensate Trap
9 SPARE PARTS LISTINGS
10 GAS BOILER COMMISSIONING CHECKLIST
WD440/3/2007 The Keston Qudos 28h & Qudos 28hP Boilers
Page : ii
0. HANDLING INSTRUCTIONS
0.1 LIST OF CONTENTS
The Keston Qudos 28h and Qudos 28hP are supplied almost totally pre-assembled. The units use standard 50 mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) pipe for the flue and air intake systems. The boiler is packed in a single box without additional flue kit. All additional components are packed inside the boiler cabinet itself. The following is a list of components and their location in the boiler cabinet
Equipment List Item Quantity Location
Wall Bracket Rawl Plugs 6 Inside accessories bag Wall Bracket Wall Fixing Screws 6 Inside accessories bag Wall Mounting Bracket 1 Secured to inside right
hand side of boiler case Wall Mounting Bracket Nuts 1 Inside accessories bag. Wall Mounting Bracket Washers 1+1 Inside accessories bag Wall Bracket Bolt Insulation 1 Inside accessories bag 50 mm muPVC Air/Flue Terminals 2 Inside accessories bag Air Inlet Spigot (50 mm) 1 Inside accessories bag Flue Outlet Spigot (50 mm) 1 Inside accessories bag Air Inlet Spigot Gasket 1 Inside accessories bag Air Inlet Spigot + Flue Outlet Spigot M6 Screws 4+2 Inside accessories bag Cabinet Cable Entry Clamps 2 Inside accessories bag Gas Isolating Cock 1 Inside accessories bag Condensate Trap 1 Inside accessories bag Condensate Trap fixing screws 2 Inside accessories bag Condensate Trap fixing washers 2 Inside accessories bag Condensate Trap Gasket 1 Inside accessories bag Outside Temperature Sensor 1 Inside accessories bag 50 mm muPVC Pipe 2 Inside boiler case 50 mm muPVC Elbow 2 Inside boiler case
Document List Item Quantity Location Boiler Warranty Registration Form 1 In document bag Installation Template 1 In document bag
Remove the cabinet shell by removing the two retaining screws in the top of the cabinet and the two retaining screws in the bottom of the cabinet.
0.2 RECOMMENDED HANDLING PROCEDURE
NB : The following lift operation exceeds the recommended weight for a one-man lift as specified in the Manual Handling Operations 1992 Regulations.
For the carriage of carton it is recommended at least two people perform any lift. Clear the carriage route of the carton from point of delivery to point of installation. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. Always use assistance if required. If a sack truck is used it is recommended the carton is strapped to the truck.
For the unpacking of the appliance from the carton, it is recommended at least two people perform any lift. It is recommended to cut the base end of carton and open the carton flaps. Ensure the protective packing over the boiler tappings at the base of the boiler is kept in place,
WD440/3/2007 The Keston Qudos 28h & Qudos 28hP Boilers
Page : iii
then tilt the boiler forwards from its back onto its base and remove carton by sliding up over the boiler. When lifting this appliance the back should be kept straight at all times. Avoid twisting at the waist - reposition the feet instead. Avoid upper body bending when holding the appliance and keep the boiler as close to the body as possible.
Before hanging the appliance on the wall it is best to store the appliance laid on its back with the casing on. When ready to hang the boiler on the wall remove the casing and place to one side. At this stage it is assumed that the wall bracket is correctly positioned and secured on the wall face.
a) Have the wall bracket nut and washers to hand so that they can be accessed whilst
holding the boiler in position on its mounting bracket.
b) The boiler has a dry weight of 35 kg (77 lbs) and will therefore require at least two people
to lift without the use of lifting aids - ensure co-ordinated movements during lift. Always use assistance if required.
c) Lift the boiler by gripping at the four corners of the boiler back plate. When lifting this
appliance the back should be kept straight at all times. Avoid twisting at the waist ­reposition the feet instead. Avoid upper body bending when holding the appliance and
keep the boiler as close to the body as possible. d) Lift the boiler and locate onto the stud and the two pegs of the wall mounting bracket. e) Place the wall mounting bracket washers over the bracket stud protruding through the
back plate of the boiler. f) Secure the boiler onto the wall bracket by fixing the wall mounting bracket nut onto the
wall bracket stud. This must be tightened well.
Safety footwear and gloves are recommended PPE when lifting this appliance - to protect against sharp edges and ensure good grip.
The Qudos 28h and Qudos 28hP boilers can be fitted in compartments with very small clearances required around the appliance (refer to Section 3.1). Due consideration should therefore be given to access within the compartment for lifting and positioning.
WD440/3/2007 The Keston Qudos 28h & Qudos 28hP Boilers
Page : iv
1. USER INSTRUCTIONS
1.1 INTRODUCTION
Thank you for choosing this Keston Qudos 28h for your household heating. The boiler is designed to be very straightforward to operate and has no user serviceable parts inside the cabinet. The following instructions are to provide you with information on the operation and maintenance of your Qudos 28h and what to do in the unlikely event of a fault.
These user instructions should be read carefully to ensure safe and economical use of your Qudos 28h or Qudos 28hP. The Qudos 28h model is for use with natural gas only, the Qudos 28hP model is for use with LPG only.
1.2 MAINTENANCE Servicing
To ensure continual safe and efficient operation and to maintain product warranties it is a requirement that the appliance is checked and serviced at least once per year. It is the law that any servicing must be carried out by a competent person. Removal of the appliance
cabinet by anyone other than a competent person will automatically invalidate the appliance warranty.
Clearances
If fixtures are to be positioned close to the boiler, the following minimum clearances must be observed: Top 150mm, Left 5mm, Right 5mm, Base 200mm, Front 305mm. Extended clearance is required to the front for servicing.
Cleaning
Normal case cleaning only requires dusting with a dry cloth. To remove more stubborn marks wipe with a damp cloth and finish with a dry cloth.
1.3 BOILER SETUP & OPERATION
Check that the gas supply from the gas meter is turned on. Switch on the electrical supply to the boiler. The display will now run through a self check procedure. Set any controls to call for heat.
To light the boiler
The Qudos 28h features two temperature controls to allow different settings depending on the source of the demand, i.e. heating or hot water. Identify which setting is demanded. Using the “TTTT” on the left of the display, select the setpoint you wish to adjust, generally the one indicated by a radiator symbol with a “1” to the left. Set the required temperature using the “+” or “-” buttons associated with the heating zones or hot water temperature. After the selection of the desired temperatures press ENTER and then preset “RESET” to return to the normal display. If the actual temperature is less than the desired temperature the boiler will fire and, after a few seconds, a “flame” will appear on the display to show that the boiler is alight.
NB: Where the demand is via 0-10VDC or Opentherm the boiler setpoint is set using the external controller in use.
WD440/3/2007 Chapter 1 : User Instructions The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 1
Normal Operation
During normal operation the digital display will show the current boiler temperature and will show relevant operational symbols to confirm what action the boiler is taking. If the “radiator”,
or “
]]]]
” symbol is shown on the display the boiler is receiving a demand for that function.
Fault Modes
In the event that the boiler detects a situation which it considers to be a fault the display will change to show a flashing fault code starting with an “E” and then a two digit number. The table below explains these codes and the action you should take.
The cabinet has overheated - consult your Service Engineer before operating the boiler further - Service Reset Required
E70
Water pressure too high - check that the system water pressure top-up valve has not been left open or consult your installer to check the expansion vessel or the open vent.
E62
The flue temperature is too high. Consult your Service Engineer - Service Reset Required
E52
The system water pressure is too low. Check the system has water in and, for sealed systems, top up the system water pressure to restore a pressure of between 1 and 2 bar. (Consult your installer for instruction how to top up water pressure - repeated need for restoration of water pressure indicates a system leak which should be investigated)
E26
The boiler temperature is rising too fast - ask your Service Engineer to check for system blockage or pump failure.
E25
Flow overheat - the boiler has exceeded it maximum water temperature. Check that any by-pass is open and the controls are operating correctly
E12
Flame failure whilst running - the boiler is having difficulty maintaining the flame. Consult your Service Engineer and check for flue, gas supply or condensate drainage obstruction
E04
Ignition lockout - the boiler has attempted to light five times and not succeeded - check the gas supply is on.
E02
Description of faultDisplay
The above is an abbreviated list of possible error codes. If the code is not in the list above consult a GAS SAFE REGISTER registered engineer. A full list of codes can be found in Chapter 6 of this manual. If a code appears and you feel the original cause has been rectified and it is not designated as requiring a “Service Reset”, press the “Reset” button to resume boiler operation. Otherwise, or if the code persists consult a GAS SAFE REGISTER registered engineer. For sealed systems, raise up the system pressure until error E26 disappears from display (the boiler will enter in standby mode or will start to fire up if a heat demand exists). To check the system pressure press the “TTTT” button repeatedly until the display shows the water pressure, indicated by the word “bar” to the right of the number. To return to main screen press the RESET button.
Precautions
Care must be taken at all times to ensure that no blockage or obstruction is present in the condensate drainage line. In addition, the air intake and flue exhaust terminals must be free from obstruction at all times.
Care should be taken not to damage the
condensate trap protruding from the base of the boiler. Any sign of leakage of this part should be reported to a GAS SAFE REGISTER registered engineer immediately. If the part becomes broken the boiler should be turned off and a GAS SAFE REGISTER registered engineer contacted to make a repair.
Any indication of leakage from the boiler cabinet should be investigates by a GAS SAFE REGISTER engineer.
Frost Protection
The Qudos 28h has an integral frost protection function. However, care should also be taken that any exposed pipework is adequately insulated to prevent freezing.
WD440/3/2007 Chapter 1 : User Instructions The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 2
1.4 SAFETY INFORMATION
IF YOU SUSPECT A GAS LEAK TURN OFF THE APPLIANCE IMMEDIATELY, TURN OFF THE GAS TAP TO THE APPLIANCE (LOCATED UNDERNEATH) AND CONTACT YOUR GAS SUPPLIER WITHOUT DELAY.
Benchmark Initiative
As part of the industry wide “Benchmark” initiative Qudos 28 boiler manual includes Gas Boiler Commissioning Checklist (Chapter 10). This form should be completed by your installer at the end of the installation and commissioning process. The details of the Checklist will be required in the event of any warranty work being required. There is also Service Interval
Record (Chapter 10) to be completed after each annual service visit.
These forms (Chapter 10) should be kept in a safe place for the life of the boiler.
The boiler should be installed and serviced only by GAS SAFE REGISTER registered operatives. All GAS SAFE REGISTER registered Installers carry a GAS SAFE REGISTER ID card and have a registration number. Both should be recorded in your boiler manual (Chapter 10: GAS BOILER COMMISSIONING CHECKLIST). You can check your installer by calling GAS SAFE REGISTER direct on 0800 408 5500.
IMPORTANT This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
WD440/3/2007 Chapter 1 : User Instructions The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 3
2. GENERAL INSTRUCTION
2.1 DESCRIPTION
The KESTON Qudos 28h and Qudos 28hP boilers utilise the latest in condensing technology to produce a high efficiency boilers with SEDBUK A rated efficiency plus advance controls to maximise operational efficiency.
The Qudos 28h is unique in concept and design. It comprises a high efficiency stainless steel heat exchanger coupled with a low emissions burner to deliver ultra high efficiency condensing mode operation within a compact wall hung cabinet. The unit automatically adjusts gas and air rate according to demand to give a heating input in the range of 7.8kW to 29.4kW (GCV).
The Qudos 28h has been developed to embrace the concept of advanced controls to ensure the ultra high performance burner and heat exchanger system is run to optimum performance levels whilst provided or exceeding the comfort levels demanded. As a result the boilers feature a host of additional connections for:
- an optional outside sensor to enable the boilers inbuilt weather compensation option which delivers enhanced user comfort levels with peak operating efficiency due to the lower flow temperatures involved.
- an optional “Opentherm” connection point for the Keston Room Control module which provides further advanced user control for room temperature compensation and optimum start.
- optional 0-10VDC input where temperature control is provided by external 3rd party intelligent controls
- optional connection of a DHW thermistor to enable modulated reheat of DHW and optional legionella prevention function
Further, the Qudos 28h is developed with the concept that the gas boiler in the modern home is often supplemented by alternative or renewable energy sources. As a result the Qudos 28h features:
- optional connection of a solar thermal system, pump, panel and DHW sensor, for direct control of solar thermal system from the boiler. Other additional energy source systems, such as Ground Source Heat Pump, will be accommodated soon.
The boilers have the added advantage of very high efficiency, and small diameter muPVC plastic flue which can be extended up to 20 metres horizontally or vertically.
The Keston Qudos 28h uses a variable speed combustion blower to deliver a premix of gas and air to a downward firing burner in a high efficiency, single pass heat exchanger. The flue system is room sealed and fan powered. The ignition is direct spark and fully automatic. The boiler housing is not waterproof and should be installed in a position where it will always be dry. Combustion air is drawn from the cabinet which is connected to outside atmosphere via a small diameter plastic intake pipe. The cabinet therefore remains under negative pressure at all times the boiler is operating.
These boilers are designed for use as part of a sealed or open vented water central heating system with fully pumped circulation.
The boiler heat exchanger is made from highly corrosion resistant stainless steel in corrugated pipe form which provides massive surface area within a compact dimension. The hot combustion gases from the down firing burner pass around the stainless steel pipes imparting heat into the system water. The Qudos 28h is not a high water content boiler and does not contain the metal mass, or water volume, of a cast iron or steel boiler. This boiler is of low mass and low water content and therefore responds faster when there is a call for heat. The Qudos 28h features full user diagnostics, integral frost protection
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 4
function, automatic pump and fan exercise in periods of inactivity, anti cycle control and dry fire protection.
2.2 BOILER SCHEMATIC
Air is drawn into the boiler through a 50 mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) plastic pipe or, alternatively, via a 75mm Keston composite plastic pipe. Gas is mixed with combustion air at the inlet to the fan. The gas flow is automatically regulated by the gas valve according to the air flow generated by the fan. The gas and air are thoroughly mixed in the blower and fed into the burner located at the top end of the heat exchanger module. The gas and air mixture is ignited by a direct spark ignition control system and burns with a blue flame just off the surface of the burner. As the hot products of combustion pass downwards, they are cooled by exchanging heat with the circulating water which enters the heat exchanger at the bottom of the heat exchanger. The optimum heat input is detected by monitoring flow and return temperatures and is adjusted by controlling the speed of the fan.
When the return water temperature is below 55
o
C, part of the water vapour in the combustion products will condense inside the heat exchanger, thus increasing the boiler efficiency further by releasing the latent heat of condensation. This condensate falls to the bottom of the heat exchanger where it is separated from the flue gases and exits from the boiler through the condensate drain. Any condensate formed in the flue runs back down the flueway and is drained at the base of the flue connection to the heat exchanger or drain points within the flue.
The condensate is very slightly acidic (about the same acidity as vinegar) and should be piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed of as normal waste water.
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 5
ENTER RESET
The flue gases are piped in a 50 mm muPVC (BS5255 and/or and BSEN1329) plastic or, alternatively, 75mm Keston composite plastic pipe to outside. The temperature of the flue gases are usually around 5
o
C to 10oC above the temperature of the return water. The flue pipe should be terminated outside the building from where they cannot re-enter the building or any other adjacent building.
The heating level may be controlled by room thermostats, programmer time clocks and compatible energy management systems. An optional Keston room controller can be connected which will provide enhanced controls such as room compensation to further increase efficiency and comfort levels. However, this is only recommended for heating only applications. Once the controls are set the boiler operates automatically. Further, a Keston outside sensor can be connected to the boiler which will automatically invoke weather compensated heating which further boosts user comfort and boiler efficiency.
In the event of the boiler overheating the safety devices will cause a safety shutdown.
The Qudos 28h features an integral frost protection function which will operate the system pump, regardless of the external controls, should the boiler temperature fall below 10oC.
In the event the boiler temperature falls below 5oC the boiler will also fire. This is to avoid damage to the boiler through freezing of boiler water. The boiler will turn off when the flow temperature exceeds 15oC.
The Qudos 28h features a system pump exercise function which will run the pump, without firing the boiler, for 10 seconds in the event the boiler is on standby for in excess of 24 hours without firing. This is to help prevent seizing of the system pump due to long periods of inactivity.
2.3 RELATED DOCUMENTS
The Keston Qudos 28h and Qudos 28hP Condensing Boilers must be installed in accordance with the current issue of the Gas Safety
(Installation and Use) Regulations 1996, current IEE Wiring Regulations, Building Regulations, Building Standards (Scotland) Consolidation, and the Bye Laws of the local Water Undertaking.
It is the law that ALL gas appliances are installed by a competent person in accordance with the above regulations.
In addition, due account must be taken to the following Codes Of Practice:
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 6
(
, +
1
0
"
BS 6891 : Low Pressure Installation Pipes BS 6798 : Installation of Gas Fired Hot Water Boilers of
Rated Input Not Exceeding 70kW BS 5449 : Installation Pumped Central Heating BS 5546 : Installation of Gas Hot Water Supplies for
Domestic Purposes (2nd family gases) BS 5440.1 : Flues (for gas appliances of rated input not
exceeding 70kW) BS 5440.2 : Air Supply (for gas appliances of rated input not
exceeding 70kW)
BS 5482.1 : Domestic Propane and Butane Burning
Installations BS 7074.1 : Expansion Vessels BS 7593 : Treatment of Water in Hot Water Central
Heating Systems BS 7671 : Requirements for Electrical Installations. IEE
Wiring Regulations 16th Edition.
BSEN 12828:2003 : Heating Systems in Buildings: Design for water
based heating systems BSEN 12831:2003 : Heating Systems in Buildings: Method for
calculation of design heat load BSEN 14336:2004 : Heating Systems in Buildings: Installation and
commissioning of water based heating systems For Timber Framed Buildings, British Gas Publications DM2. Also British Gas Publications 'Guidance Notes For The Installation Of Domestic Gas Condensing Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
In IE, the installation must be carried out by a competent person and installed in accordance with the current edition of IS813 “Domestic Gas Installations”, the current Building Regulation and reference should be made to the current ETC1 rules for electrical installations.
No alterations should be made to the boiler without written permission from KESTON Heating. Any unauthorised modification will invalidate the warranty and may affect the safe and efficient operation of the boiler.
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 7
2.4 PHYSICAL DATA - Qudos 28h & Qudos 28hP
Cabinet Height mm 680 Cabinet Width mm 390 Cabinet Depth mm 280 Top Clearance mm 150 Side Clearance mm 5 Base Clearance mm 200 Front Clearance (for servicing) mm 300 Weight - Full kg / (lbs) 39(86) Weight - Empty kg / (lbs) 35(77) Flow and Return Connection G3/4 Gas Connection G1/2 Condensate Connection overflow 22mm plastic IP Rating IP20 (IPX0)
Flue and Air Intake Material
50mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) Flue Pipe Size (nominal bore) mm / (in) 50 / (2) Air Intake Pipe Size (nominal bore) mm / (in) 50 / (2) Max. Air Intake Length m 39 Max. Flue Outlet Length m 20 Max. Total Flue Outlet and Air Intake Length m 40
Flue and Air Intake Material
75mm Keston Composite Flue Pipe Size (nominal bore) mm / (in) 75 / (3) Air Intake Pipe Size (nominal bore) mm / (in) 75 / (3) Max. Air Intake Length m 117 Max. Flue Outlet Length m 60 Max. Total Flue Outlet and Air Intake Length m 120
2.5 OPTIONAL ACCESSORIES
A range of accessories are available from KESTON Heating to compliment an installation. Terminal wall sealing collars are available to make good the external all face whilst working from the inside of the building using 50mm muPVC (BS5255 and/or BSEN1566-1 and BSEN1329) pipe. Stand-off frames are available to leave a 50mm gap behind the boiler to allow routing of pipes behind the boiler.
Description Part Number
Flue Terminal Wall Sealing Collar (50mm) C.08.0.00.07.0 Air Terminal Wall Sealing Collar (50mm) C.08.0.00.07.0 50/75mm Flue Adapter C.17.2.00.60.0 Flue Outlet Terminal (75mm) C.17.2.26.00.0 Air Inlet Terminal (75mm) C.17.2.26.00.0 Stand Off Back Plate Q.10H.0.01.00.0 Keston Chronotherm Room Controller C.17.4.21.00.0 DHW Tank Sensor Q.10S.0.04.00.0 Solar Sensors Kit (Panel sensor and 2 x DHW Tank Sensors) Q.10S.0.05.00.0
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 8
2.6 PERFORMANCE DATA - Qudos 28h & Qudos 28hP
Seasonal Efficiency (SEDBUK) = 91.1 (Qudos 28h) & 93.1 (Qudos 28hP) This value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by Advantica Technologies Ltd
KESTON Heating declare that there are no substances harmful to health within the appliance or used during the production of the appliance.
The Qudos 28h is intended for domestic and commercial EMC environments and on a governed G20 meter supply.
The Qudos 28hP is intended for domestic and commercial EMC environments and on a governed G31 supply.
This boiler meets the requirements of SI 3083 The Boiler (Efficiency) Regulations and is therefore deemed to meet the requirements of Directive 92/42/EEC. The CE mark on the appliance shows compliance with Directives 90/396/EEC, 73/23/EEC and 89/336/EEC.
IMPORTANT This product contains ceramic fibre boards, which although not regarded as a risk, contain ceramic fibre which may cause temporary irritation to eyes, skin and respiratory tract. The fibres are held in place by inorganic binders. Therefore as long as the boards are not disturbed they will not be released. Since the boards are non-serviceable parts there should be no risk. Under no circumstances should the user interfere with any sealed parts. To ensure that the release of fibres from these RCF articles is kept to a minimum, during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust accumulated in and around the appliance before and after working on the
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 9
Qudos 28h Qudos 28hP Nat. Gas (G20) LPG (G31)
Min. Input (Gross CV) kW/(Btu/h) 7.8/(26,600) 7.6/(26,000) Max. CH Input (Gross CV) kW/(Btu/h) 29.4/(100,300) 28.8/(98,300) Max. CH Output To Water
(80/60oC Flow/Return) kW/(Btu/h) 26.4/(90,500) 26.4/(90,500) (50/30oC Flow/Return) kW/(Btu/h) 28.4/(96,900) 28.4/(96,900)
Min. CH Output To Water
(80/60oC Flow/Return) kW/(Btu/h) 7.0/(24,900) 7.0/(24,900) (50/30oC Flow/Return) kW/(Btu/h) 7.8/(26,600) 7.6/(26,000)
Max. Burner Press.-Hot
(Factory Preset)
mbar/(in w.g) 0/(0) 0/(0) Max. Gas Cons. After 10 mins (DHW) l/s / (Ft3/hr) 0.76/(96.6) 0.35/(45.0) Max. Operating Flow Temp.
o
C 82 82 Max. Press. (Sealed System) bar 2.70 2.50 Min. Press/Head (Open System) bar 0.25 (8 feet) 0.25 (8 feet) Inlet Gas Pressure mbar/(in w.g) 20.0 / (8.0) 37.0/(14.8)
Recommended Temp Diff.
o
C 8 to 20 8 to 20 Electrical Supply 230V 50Hz 230V 50Hz Power Consumption (Max) W 80 80 Power Consumption (Standby) W 8.5 8.5 Type of Gas G20 Natural Gas G31 LPG Optimum Flue Gas CO2 Level (at max CH rate, case on) 9.1±0.2 10.5 ±0.2 Expected CO/CO2 Ratio (at max CH rate, case on) 0.0007 0.001 Destination Countries GB/IE GB/IE SEDBUK Efficiency 91.1 93.1
NOx
Class
5
5
appliance. When replacing these articles we recommend that the replaced items are not broken up, but are sealed within heavy duty polythene bags, and clearly labelled as RCF waste. RCF
waste is classed as a stable, non-reactive hazardous waste and may be disposed at a landfill licensed to accept such waste. Protective clothing is not required when handling these articles, but we recommend you follow the normal hygiene rules of not smoking, eating or drinking in the work area and always wash your hands before eating or drinking.
Benchmark Initiative As part of the industry wide “Benchmark” initiative Qudos 28h boiler manual includes Gas Boiler Commissioning Checklist (Chapter 10). This form should be completed by your installer at the
end of the installation and commissioning process. The details of the Checklist will be required in the event of any warranty work being required. There is also Service Interval Record (Chapter
10) to be completed after each annual service visit.
These forms (Chapter 10) should be kept in a safe place for the life of the boiler.
The boiler should be installed and serviced only by GAS SAFE REGISTER registered operatives. All GAS SAFE REGISTER registered Installers carry a GAS SAFE REGISTER ID card and have a registration number. Both should be recorded in your boiler manual (Chapter 10: GAS BOILER COMMISSIONING CHECKLIST). You can check your installer by calling GAS SAFE REGISTER direct on 0800 408 5500.
WD440/3/2007 Chapter 2 : General Instruction The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 10
IN THE EVENT OF A GAS LEAK
Turn off the gas isolation valve to the property immediately. Extinguish all naked flames or other sources of ignition. Do not operate electrical switches on or off. Open all doors and windows to ventilate the area.
3. BOILER LOCATION
3.1 DIMENSIONS AND MINIMUM CLEARANCES
The boiler must be installed in minimum clearances shown to allow subsequent servicing, and safe operation. However, larger clearances may be required during installation.
3.2 SERVICE CONNECTIONS
Gas, water, air and flue pipe, condensation, and electrical connections are as shown in the diagram below. Gas : 15mm compression. Flow/Return 0.75 inch BSP male, Gas 0.5 inch BSP male, PRV 15mm copper pipe and Condensate 21.3mm plastic pipe .
An optional stand-off frame is also available which mounts behind the boiler to leave a 50mm deep space behind the boiler. This is to permit pipe routing behind the boiler if required. See Section 2.5 - Optional Accessories.
3.3 POSITION
The Qudos 28h and Qudos 28hP Combi are not suitable for external installation. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a room-sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control, utilising mains electricity, should be so situated that it cannot be touched by a person using the bath or shower. The Qudos 28h and Qudos 28hP are classified as IP20 (IPX0) and are therefore suitable for installation in Zone 3 areas, unless subject to hose down.
WD440/3/2007 Chapter 3 - Boiler Location The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 11
$OOGLPHQVLRQVLQPP

:KHQVHUYLFLQJDSSOLDQFH

)LJXUH
0LQLPXP&OHDUDQFHV
:KHQDSSOLDQFHLVRSHUDWLQJ
$OOGLPHQVLRQVLQPP

2
8
0
Figure 3.1.2 Dimensions
)OXH([KDXVW
$LU,QWDNH

mm
Compartment installation is permitted - such compartments must be constructed in accordance with BS 6798. The wall on which the boiler is mounted must be of suitable load bearing capacity and must be non-combustible. The Keston Qudos 28h can be located virtually anywhere desired provided that all regulations are complied with. Because of the boiler's compact size and venting flexibility, the installation is not limited to a boiler room setting. Before locating the boiler near a living space consider whether the sounds generated by the boiler will be objectionable. The boiler may be located within a cupboard enclosure to reduce noise levels if located within a living space. LPG boilers must not be installed in a cellar.
3.4 ELECTRICAL
3.4.1 Electrical Connections
The boiler must be connected to a permanent 230V ~ 50Hz supply, fused at 3A.
The boiler can be wired to a single switched live 230VAC signal input. However, the boiler has TWO thermostats, and will therefore accept up to TWO switched live 230VAC signal inputs, such as heating and hot water. Alternatively, a Keston Room Controller can be connected directly, via two core low voltage cable, to the terminals marked “OT”. The Keston Room Controller will then provide fully room compensated control to ensure the boiler output is matched to the rooms requirements at optimum boiler efficiency. This is only recommended for heating only applications. Further, the boiler can be driven by an external 0-10VDC input.
Wiring external to the boiler must be in accordance with current I.E.E wiring regulations and local regulations. The method of connection to the mains electricity supply must facilitate complete electrical isolation of the boiler, preferably by the use of a fused, unswitched three pin plug and a shuttered socket-outlet, both complying with the requirements of BS 1363. There must be only one common method of isolation for the boiler and its control system.
WD440/3/2007 Chapter 3 - Boiler Location The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 12
&KLPQH\VQRWXVHGIRU YHQWLQJDQ\RWKHU
DSSOLDQFHPD\EHXVHG
)LJXUH
6HFXUHDLUIOXHSLSHVDW FKLPQH\RXWOHW
[NB: Refer to Section 3.8.3]
The appliance must be connected to the 3A supply via a fused double-pole switch having at least 3 mm (1/8 inch) contact separation in both poles, serving only the boiler and the system controls. The connection point to the mains supply should be readily accessible and adjacent to the boiler, except for rooms containing a bath or a shower. Refer to section 3.3 Position.
3.4.2 External Wiring & Controls
1. The boiler is designed so that all control wiring is external to the boiler.
2. Heating control signal inputs must the 230VAC "switched live" type unless using a Keston Room Controller (see below) or 0-10VDC input.
3. The system pump must also be wired back to the boiler to enable the boiler to provide pump overrun and pump exercise function.
3.4.2.1 Enhanced Control Options
The Qudos 28h can be wired into a conventional heating installation using only
permanent and switched live connections and pump connection.
However, the Qudos 28h features a wide range of OPTIONAL control features
normally associated with commercial boilers installations at additional cost. These are provided as standard in the Qudos 28h and require low costs sensors to be added to activate them. The features provided are detailed below. Refer to Chapter 4.8 for further wiring detail.
Room Compensation (Opentherm) A Keston Room Controller may be used to provide room compensated control to ensure the boiler output is matched to the rooms requirements at optimum boiler efficiency. This is only recommended for heating only applications
Weather Compensation (Ext Sensor) A Keston outside temperature sensor may be connected as an option. The boiler will automatically detect this connection and will operate on a "weather compensation" basis when receiving a heating demand signal from the SL terminal or from a Keston Room Controller. Screened cable (80% density) must be used to connect the outside temperature sensor.
Solar Control Where a solar thermal system is in use, with a twin coil cylinder such as the Keston qSpa Twin, the Qudos 28h will control operation of the solar pump in conjunction with the boiler. The boiler requires connection to the solar tank sensor, solar panel sensor and solar pump
Modulating
DHW Reheat The Qudos 28h can provide direct modulation to maximise the re-heat performance of the DHW cylinder. A DHW cylinder sensor can be connected directly to the Qudos 28. A DHW demand input can also be provided to control DHW reheat activity, perhaps in conjunction with Solar Thermal. With this facility connected an automatic anti-legionnella facility can also be provided.
Analog
ue Demand (0-10VDC) Where external control panels are used, in boiler room applications, a 0-10VDC input can be connected to the boiler, in place of the SL1 switched live demand. The 0-10VDC signal will drive the first setpoint at 1VDC = 10C setpoint (NB: <0.5VDC is off, >8.0 VDC is 80C)
External Lockout Signal Where remote monitoring and/or alarms are installed the boiler offers a
volt-free lockout signal output. The boiler will provide a closed circuit
across the two output points when the boiler is in lockout.
WD440/3/2007 Chapter 3 - Boiler Location The Keston Qudos 28h & Qudos 28hP Boilers
Installation & Servicing Instructions Page : 13
Loading...
+ 41 hidden pages