The Keston Condensing Boiler is unique in its concept and design. While the application
for which the boiler was designed is the same as those which other boilers are us ed the
Keston boiler has the added advantage of very high efficiency, and small diameter plastic
flue which can be extended to 10 metres horizontally or vertically.
The Keston uses a high power combustion blower to deliver a pre-mix of gas and air to a
downward firing burner in a high efficiency, single pass heat exchanger.
o
Normally the combustion temperature of the air gas mixture is around 1800
Keston achieves combustion at an am azing 1000
o
C thereby reducing the NOx emissions
down to an incredible less than 5 p.p.m.
The flue system is room sealed and fan powered. The ignition is direct spark and fully
automatic. The boiler housing is not waterproof. The boiler should be installed in a
position where it will always be dry. A small air intake point is incorporated within the
appliance cabinet to ensure that the interior of the cabinet is maintained under a slight
negative pressure. This is a safety feature to ensure no products may leak out of the
cabinet into the installation space.
C but the
s
The boiler is suitable f or connection to open vented or sealed s ystems. T he system mus t
be pumped central heating or pumped central heating with combined indirect domestic hot
water. Gravity circuits must not be used.
The boiler has a primary heat exchanger which, through its combustion chamber and
corrugated coil, transf ers the heat produced in the hot gas es of combus tion process into
the circulating water. Head characteristics of the boiler coil must be taken into
consideration when calculating the pump size.
The Keston boiler is not a high water content boiler and does not contain the metal mass ,
or water volume, of a cast iron or steel boiler. This boiler is of low mass and low water
content and therefore responds fast er when there is a call for heat. Th is f eatur e requir es a
higher water pumping rate thr ough the boiler otherwise localised boiling will occur within
the boiler.
Allow a pressure drop through the boiler of 3.2 ft head and a water flow of 4.2 gallons (19
litres) per minute f or the Keston 50, 4.3 f t head and 5 gallons (23 litres) per m inute for the
Keston 60 and 9 ft head and 6.7 gallons (30.5 litres) per minute for the Keston 80.
The boiler selected m ust be sized relative to the total c alculated heat loss of the building.
The boiler rated output should not be greater than the total required to make up the
calculated heat loss plus the heat required to provide domestic hot water. If there are
special conditions such as excessive domestic hot water usage consult the manufacturer.
1.2BOILER SCHEMATIC
Air is drawn into the boiler through a 40mm ( BS5255) m uPVC pipe. T he air f low is proved
by a differential pressure across the air control orifice.
Gas is mixed with com bustion air at the inlet to the fan. The gas flow is regulated by an
orifice located in the housing downstream of the gas valve.
The gas and air are thoroughly mixed in the blower and f ed into the burner located at the
top end of the heat exchanger module. The gas and air mixture is ignited by a direct spark
ignition control system and burns with a blue flame j ust off the surface of the burner. As
the hot products of com bustion pass downwards, they are cooled, exchanging heat with
the circulating water which enters the heat exchanger coil at the bottom of the heat
exchanger.
When the return water temperature is below 54oC, part of the water vapour in the
combustion products will condense ins ide the heat exchanger, thus increasing the boiler
efficiency. This condensate falls to the bottom of the heat exc hanger where it is s eparated
from the flue gases and exits from the boiler through the condensate drain. Any
condensate formed in the flue runs back down the flueway and is drained at the base of
the flue connection to the heat exchanger.
The condensate is very slightly acidic (about the same acidity as vinegar) and should be
piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed
of as normal waste water.
The flue gases are piped in a 40m m m uPVC pipe to the outside. The temper ature of the
flue gases are usually less than
10oC above the temperature of the retur n water. The flue
pipe should be terminated outside the building from where they cannot re-enter the
building or any other adjacent building or cause a nuisance by pluming.
s
The heating level may be controlled by room thermo stats, hot water cylinder thermostats
and programmer time clocks.
1.3RELATED DOCUMENTS
The Keston Condensing Boiler must be ins talled in accordance with the current issue of
the Gas Safety ( Installation and Use) Regulations, current IEE W iring Regulations, Safety
document no. 635 - The Electricity At Work Regulations 1989, Building Regulations,
Building Standards (Scotland) Consolidation, and the Bye Laws of the local Water
Undertaking.
In addition, due account must be taken to the following Codes Of Practice:
BS 6891:Gas Supplies
BS 6798:Installation Central Heating Boilers
BS 5449:Installation Pumped Central Heating
BS 5546:Installation Domestic Hot Water
BS 5440.1:Flues
BS 5440.2:Air Supply
BS 5482.1:Domestic Propane & Butane Burning Installations
BS 7074.1:Expansion Vessels
BS 7593:Treatment of Water in Hot Water Central Heating
BS 7671:Requirements for Electrical Installations. IEE Wiring
Systems
Regulations 16th Edition.
For Timber Framed Buildings, British Gas Publications DM2. Also British Gas
Publications 'Guidance Notes For The Installation Of Domestic G as Condensing
Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
The boiler must be installed in
minimum clearances shown to allow
subsequent servicing, and safe
operation.
254
2.2SERVICE CONNECTIONS
Gas, water, air and flue pipe,
condensation, and electrical
connections are as shown. Gas : 0.5
inch BSP male. Flow/Return : 28 mm
copper.
2.3POSITION
The Keston is not
suitable for external
installation. The boiler
may be installed in any
room or internal space,
although particular
attention is drawn to the
requirements of the
current IEE Wiring
Regulations and, in
Scotland, the electrical
provisions of the Building
Regulations applicable in
Scotland, with respect to
the installation of the
boiler in a room or
internal space containing
a bath or shower.
room containing a bath or shower, any electrical switch or appliance control, utilising
mains electricity, should be so situated that it cannot be touched by a person using the
bath or shower.
Compartment installation is permitted - such compartments must be constructed in
accordance with BS 6798.
The wall on which the boiler is mounted must be of suitable load bearing capacity and
must be non-combustible.
Important : It is not recommended to install the boiler on a studded wall or similar - it is
possible that the vibration from the fan would be amplified and transmitted to other parts
of the house.
[NB: Refer to
Section 2.8.3]
The Keston can be located virtually anywhere desired provided that all regulations are
met. Because of the boiler's compact size and venting flexibility, the installation is not
limited to a boiler room setting. Before locating the boiler near a living space consider
whether the sounds generated by the boiler will be objectionable. Sound levels from the
boiler are no greater than from any other type of high-efficiency boiler but even minimal
levels may be objectionable if located near a bedroom or in a living area.
2.4ELECTRICAL
2.4.1Electrical Connections
Chimneys not used for
venting any other
appliance may be used.
Secure air & flue pipes at
chimney outlet.
Figure 2.3
The boiler must be connected to a 230V ~ 50Hz supply, fused at 5A. All
external controls and wiring must be suitable for mains voltage. Wiring
external tothe boiler must be in accordance with current I.E.E wiring regulations
and local regulations.
The method of connection to the mains electricity supply must facilitate
complete electrical isolation of the boiler complying with the requirements of BS
1363.
The appliance must be connected to the supply via a fused double-pole switch,
having at least 3mm (1/8 inch) contact separation in both poles, serving only the
boiler and the system controls.
The connection point to the mains supply should be readily accessible and
adjacent to the boiler, except for rooms containing a bath or a shower. Refer to
section 2.3 Position.
2.4.2External Wiring & Controls
1.The boiler is deisgned so that all control wiring is external to the boiler.
Hence, any programmers or room thermostats etc must act by switching
the 230V supply to the boiler.
2.System designs which allow the boiler to fire when there is no pumped
circulation must NOT be used.
3.A programmer may be used with zone valves to give independent
control of central heating and hot water.
2.5BOILER SIZE SELECTION
The size of the boiler to be used is determined by the total calculated heat loss of the
building. Match the calculated heat loss with the boilers rated output. If a boiler is
installed with an output rating greatly exceeding the total capacity of the distribution
system the efficiency of the boiler will be reduced. If the boiler is to be used to heat
domestic hot water no additional capacity is normally needed for the average residential
installation since there is usually some excess capacity in the boiler as water heating is
an intermittent load.
2.6GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas supplier or their
contractor. An existing meter should be checked preferably by the gas region to ensure
that the meter is adequate to deal with the rate of gas supply required. Installation pipes
should be fitted in accordance with BS 6891.
Minimum/Maximum Natural Gas Pressure:
Natural gas pressure before the gas valve must be maintained at 20 mbar (8 in w.g)
while the boiler is running.
Gas pressures above or below this level will lead to problems associated with the gas
valve's internal pressure regulator.
Minimum/Maximum L P Gas Pressure:
LPG pressure must be maintained between 31.5 mbar (12.4 in w.g) and 37.6 mbar (14.8
in w.g) while the boiler is running
Gas pressures above or below these levels will lead to problems associated with the gas
valve's internal pressure regulator.
.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (15 mm)
Due consideration must be given to the supply pressure to other gas appliances in the
premises.
A gas cock is supplied loose with the boiler. This cock should be fitted in the gas line to
the boiler as close to the boiler as possible so that it is easily identified as the cock to
isolate the boiler.
2.7WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply
Bylaws for forced hot water heating systems.
Consideration must be given to pipe capabilities and pressure drop through the piping.
Water treatment must be carried out to BS 7593 : Treament of Water in Hot Water
Central Heating Systems.
Pump isolating valves must be positioned as close to the pump as possible.
aThe Keston is suitable for use on open, vented water systems with combined feed
and vent.
bIt is preferable for use on sealed water systems, provided the appropriate
components required (see Section 2.7.2 Sealed Systems) are included in the
system.
cAny system must
connection with the boiler. A trap may be installed in the flow line to collect any
solder, or other debris, from the installation.
dAll water systems must be constructed to comply with requirements of the Local
Water Authority.
eOnly fully pumped systems can be used - gravity systems are strictly
suitable.
fAlways use a system complying with the requirements of BS 5449 and BS 6798.
gThe system must be so arranged that there shall always be a minimum flow of 4.2
(30.5 litres/min) [Keston 80] when the boiler is firing. This can be via a specially
installed by-pass arrangement.
hCopper tubing to BS 2871 Part 1 is recommended.
iJointing should be either with capillary or compression fittings. Pipes should have
a gradient to ensure air is passed easily to vent points and water flows readily to
drain points.
jDraining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 15
mm in nominal size and be in accordance with BS 2879.
AIR VENT POINTS
kThese must be fitted at all high points where air may collect.
be thoroughly flushed clean of grease, dirt and debris, prior to
not
2.7.1Open Vented Systems
A typical system is shown in Figure 2.7.1 which includes a combined feed and
vent. Note there must be no valve between the boiler flow and the open vent.
Note that the minimum static head required is 8 ft at the boiler flow pipe. If the
cold feed/vent is not brought to the flow pipe as shown, then the pressure loss
across the heat exchanger may have to be taken into account when estimating
the static pressure.
Although suitable for open vented systems with combined feed and vent
arrangements, the Keston is a low water content boiler. As such, any air
entrainement within the system water will produce boiler "kettling". It is
therefore recommended, if in any doubt, to consider the use of sealed
Sealed systems must be designed in accordance with BS 5449 and BS 7074 Pt1.
A typical sealed system is shown in Figure 2.7.2. It must include :
(i)A safety valve fitted on the flow, adjacent to the boiler. It must be non
adjustable and preset to 3 bar. A drain pipe must be attached, at least as
big as the valve connection, and routed to drain in any area not
hazardous nor where it may be subject to freezing.
(ii)An expansion vessel complying with BS 4814 and sized in accordance
with the requirements of BS 5449 and BS 7074 Pt 1. The vessel must be
positioned on the inlet to the pump.
(iii)A filling point, in accordance with local water authority requirements.
(iv)A method of system make-up (automatic or manual), in accordance with
local water authority requirements.
(v)There must be no permanent connection of mains water to the boiler
system.
(vi)The installation must be designed to work with flow temperatures of up to
110
o
C.
All components of the system including the heat exchanger of the indirect
cylinder must be suitable for a working pressure of 3 bar and a temperature of
o
C. Care should be taken in making all connections that the risk of leakage is
The hot water storage vessel must be of the indirect type (certain direct cylinders
can be used provided
they are suitably adapted by fitting an immersion
calorifier). DIRECT CYLINDERS MUST NOT BE USED. Further guidance is
provided in BS 1394. It is advisable to fit a lockshield valve on the cylinder return
to enable balancing of flow rate through the cylinder.
2.7.4Boiler By-pass Piping
Boiler water flows are critical to the operation of the boiler. If flow cannot be
maintained through the system piping to meet the minimums required by the
boiler (see paragraph 2.7 (g)). Insufficient water flows through the boiler will cause
the boiler to "kettle" or even produce steam which can damage the heat
exchanger and will invalidate the heat exchanger warranty.
It is normally advisable to incorporate a boiler by-pass in the system, especially if
thermostatic radiator valves are used. The by-pass should be fitted with a
lockshield valve to permit balancing of the by-pass flow rate. The flow/return
differential should be 10
o
C to 15oC. The lockshield valve can be adjusted to
maintain this condition with the radiators fully heated.
In the initial charge of water to the boiler system and in all subsequent additions
of water to the system some air will be dissolved in the water. As the water is
heated the air is driven out of the solution and will collect in high spots in the
system. These air bubbles can interfere with pumping and heat transfer and
must be eliminated.
Installation of air bleed valves at the high spot(s) in the system will allow for air
elimination when filling the system and will allow re-venting in a day or so after all
air has been driven out of solution.
Installation of an automatic air vent will ensure that any air, even minute
amounts, which subsequently enters the system will be automatically removed.
2.7.6Strainers
Debris in the heating system
can cause noise if it enters the
heat exchanger. Fitting of a
Y-strainer ahead of the
circulating pump will trap any
debris left in the system and
will protect the pump from
damage.
2.7.7Pump Selection
The Keston boilers have low
water content heat exchangers
with a high resistance to flow,
when compared with cast iron
heat exchanger boilers. As a
result selection of the correct
pump is essential
avoid localised boiling within
the heat exchanger. The
selected pump must be
capable of maintaining the
required flow rate for the boiler
against the pressure losses
contributed by the boiler and
the rest of the system.
Refer to the pressure loss/flow
rate Table 2.7.7 to determine
the pressure loss from the
boilers. Add this to the
pressure loss caused by the
rest of the system and select a
pump capable of meeting the
flow rate required at the total
pressure loss generated by the
boiler and the rest of the
system. The selected pump
must comply with BS 1394.
in order to
Y-Strainer will
collect an y loose
debris in the piping.
It is important to note that the minimum flow rate must be maintained whenever the
boiler is firing. Systems using zone valves must be specifically designed to only fire the
boiler when the pump is running and the minimum flow rate can be achieved.
The Wilo Salmson Gold Star pump, or the Grundfoss 15/60 pump is normally suitable for
use with the Keston condensing boiler range. However, in all cases due consideration
must be given to the resistance to flow offered by the rest of the system when making a
final pump selection. This is particularly important when using small bore underfloor
heating pipework.
Keston 80Keston 60Keston 50Boiler Model
Min Flow Rate
Required
Pressure Loss
Through
Boiler
4.2 GPM
19.1 litres/min
3.2 ft
0.97m
9.7 kPa
5.0 GPM
22.7 litres/min
4.3 ft
1.3m
13 kPa
6.7 GPM
30.5 litres/min
9.0 ft
2.75m
27.5 kPa
Table 2.7.7 Pump Selection
2.8FLUE SYSTEM
2.8.1Design
Individual air supply and flue outlet pipes are used. The material used for flue
outlet &/or air inlet must be muPVC to BS 5255 and of an internal diameter of 38
mm.
Both flue outlet terminal and air inlet terminal are supplied and are illustrated in
Figure 2.8.1.
2.8.2Maximum Lengths
The maximum lengths of both air inlet pipe and flue outlet pipe, when no bends
are used, are as detailed below.
Maximum Air Inlet Length:10.0 m
Maximum Flue Outlet Length:10.0 m
However, each bend used has an equivalent length that must be deducted from
the maximum straight length stated above.
A 92.5
Example:
o
sweep elbow is equivalent to 1.0m straight length.
Air inlet uses two 92.5o sweep elbows. Hence, maximum length permissible (ie
a+b in figure 2.8.2) = 10.0m - 1.0m - 1.0m = 8.0m
Flue outlet uses one 92.5
c+d in figure 7 = 10.0m - 1.0 m = 9.0m
Installation & Servicing Instructions
Page : 13
o
sweep elbow. Hence, maximum length permissible (ie
'Horizontal' flue outlet pipework
MUST slope at least 2.5
FLUE
degrees (45 mm per metre
run) downwards towards the
boiler. Pipework can be
vertical. Only swept elbows can
be used.
c
d
Air inlet pipework can be truly
horizontal or vertical, or
sloping in a downward direction
towards the boiler but in this
case rain, etc, must
be
prevented from entering the
pipe. There must be no
troughs in any of the
pipework, whether it be air
inlet or flue outlet. If a 45
Figure 2.8.2 : Flue & Air Maximum Length Example
Keston
mm per meter slope is not
possible, contact Keston Boilers Technical Department for further guidance.
Due the low temperature of
the flue gases further condensate
will form within the flue system. Drain
Figure 2.8.3 :
Flue Condensate Drain
Point Example
points, with suitable traps, must
therefore be incorporated within the
flue system at the base of vertical
flue sections in excess of 2m. These
additional condensate drains must
To Termina l
be run to discharge as detailed in
section 2.11. Such drain points can
To Boiler
40mm Tee Fitting
be formed using standard muPVC
fittings. Refer to the example in
Figure 2.8.3.
AIR
b
a
6 in min.
2.8.4Terminations
It is not advisable to terminate air
intake orflue within a car port area.
Air inlet terminals must be facing upwards and positioned to ensure only fresh air
is drawn into the boiler directly from outside the property.
The flue outlet terminal is designed to face outwards but can, if desired, be
adapted to face in any direction BUT
must not be directed in the region of the air
inlet.
The two terminals are subject to the requirements of BS 5440 Pt 1 for clearances
from features of the building although some can be decreased to the values
indicated. If either the air inlet or the flue outlet terminate at a height of less than
2m (6ft) above ground level the termination must be protected by a suitable
guard. The K4 terminal guard, manufactured by Tower Flue Components Ltd, is
suitable for this purpose and can be obtained from Keston Boilers.
The Keston Condensing Boiler, as with any condensing boiler, will generate a
condensate "plume" from the flue terminal in all weather conditions.
Consideration must therefore be given to the effect of this "plume" when
selecting a location for the flue terminal.
It is advisable for horizontal flue terminals to place a 45o elbow at the end of the
flue to direct the condensate plume up and away from the property.
Dimensions (mm)
170
O67
O43
Air Intake Terminal
Flue
Terminal
Air
Inlet
50300A Below openable window, air brick, etc.
7575B Below gutters, soil pipes, drain pipes.
50300C Below eaves.
50200D Below balconies.
5075E From vertical drain or soil pipes.
50600F From internal or external corner.
100300G Above ground or balcony or roof.
100600H From surface facing a terminal
1.21.2IFrom terminal facing a terminal.
1001.2J From opening in a car port.
1.51.5K Vertically from terminal on same wall.
300300L Horizontally from terminal on same wall.
Table 2.8.4Minimum Flue Terminations & Air Inlet Dimensions
2.8.5Clearances From Wall
Flue outlet and air inlet termination must be at least 60 mm and 95 mm
respectively from the wall face.
2.8.6Distance Between Flue Outlet & Air Inlet
There is no maximum - the terminations can be on opposite sides of the dwelling
if desired.
A minimum clearance of at least 350 mm must be left between the terminations.
2.8.7General Installations
All parts of the system must be constructed in accordance with BS 5440 Part 1,
except where specifically mentioned in these instructions.
All pipework must be adequately supported.
All joints other than push-on or plastic compression connectors must be made
and sealed
with solvent cement suitable for muPVC pipes and conforming to BS
6209: 1982.
External wall faces and any internal faces of cavity walls must be made good.
2.9AIR SUPPLY
The Keston is a room sealed appliance and therefore does not require purpose provided
ventilation for combustion air.
2.10COMPARTMENT INSTALLATION
Where the appliance is installed in a cupboard or compartment, no air vents are
required. The boiler will run sufficiently cool without ventilation.
2.11CONDENSATE DRAINAGE
Being a condensing boiler, the Keston is fitted with a condensate trap at the base of the
heat exchanger and flue assembly, with facility to connect to a drain point underneath the
appliance.
Use only plastic piping and do not reduce below 22mm internal diameter within the
dwelling. Condensate should preferably be drained into the house sanitary waste system
or, alternatively, the rainwater system. Termination of the pipe must be either at a branch
or stack internal to the house, or externally at an open gully. Alternatively, discharge into
a purpose made condensate soakaway can be considered. Existing or purpose built
drains must use suitable corrosion resistant material as condensate is mildly acidic.
A minimum slope downwards towards the drain of 2.5
Freezing of the termination and pipework must be prevented. Any drainage pipes outside
the house must be at least 32 mm inside diameter.
Further guidance is given in the British Gas Publication 'Guidance Notes for the
Installation of Domestic Gas Condensing Boilers'.
2.12RADIANT FLOOR HEATING
This type of heat distribution creates an exceptionally evenly heated environment and
since it is hidden beneath the finished flooring does not interfere with furniture
placement. The homeowner has complete freedom to decorate without having to
contend with any heating equipment visible in the homes interior. The low operating
temperatures of this type of system lead to very good operating efficiencies. In fact,
under floor heating can produce in excess of 95% operating efficiency from a Keston
condensing boiler. Water temperatures in radiant floor heating systems must be kept
relatively low, generally under 48
to the touch. If radiant heating is only one application for a multi-zone system which also
requires higher delivery water temperatures for other zones (i.e. water heating, skirting
heaters etc.) then the radiant floor zone temperature will need to be controlled separately
from the boiler.
o
(45mm fall in 1m) is essential.
o
C, so that surfaces do not become uncomfortably warm
If radiant floor heating is the only application of the boiler, the boilers temperature limits
can be lowered accordingly by introducing an external thermostat control mounted on the
return pipework into the boiler. This thermostat can then be used to interrupt power
supply to the boiler when the required temperature is reached. Mixing valves are also
available which will mix return water from the system with boiler output water to dilute the
temperature of water transmitted to the distribution system. Mixing valves may create
problems with low flow and high temperatures through the boiler unless care is taken to
design a system which will provide proper flows and will fully load the boiler. Keeping the
boiler's temperature high will prevent the boiler from operating at peak efficiencies.
Systems which maintain boiler temperatures in this way should be avoided.
If only a portion of the boiler's available output is to be used for radiant floor heating a
thermal storage tank will improve the boiler's operation and give adequate control of
temperature for the distribution system. By heating water to be distributed to the radiant
floor zone to the proper temperature in an indirect-fired water heater, full load conditions
will be available to the boiler because the heat exchanger in the tank can be sized to
match the boiler's output. The tank's thermostat can be set at the optimum operating
temperature needed by the distribution system and short-cycling of the boiler will be
prevented. In such insulations it is advisable to calibrate the thermal store's operating
thermostat to become the controlling thermostat of the boiler, ie the thermal store
operating thermostat is always activated to shut off the boiler before the boilers own
thermostat is activated. An insulated thermal storage tank without the heat exchanger may
also be used.
2.13LOW WATER VOLUME BOILER VS. CAST IRON BOILER
Because of their high water content and mass of metal, cast iron and steel boilers are less
responsive but somewhat more forgiving of design errors. Short-cycling of the
burner on the temperature limit control is less pronounced, though no less detrimental to
operation, because the boiler itself will absorb and radiate a significant amount of heat.
Low water volume boilers respond more quickly to a call for heat, can be made more
compact and lightweight, but must have adequate heat delivery systems to avoid
short-cycling of the burner on the temperature limit control. The heat delivery system's
output must be equal to or greater than the boiler's output to fully load the boiler or
short-cycling will occur.
Likewise, pumping rates of water through low water volume boilers must be maintained so
that water is moved through the boiler fast enough so as not to reach boiling
temperatures. The slower the water moves through the boiler the more heat it will absorb
and the higher the temperatures will rise. Consequently, the pump selected must be
adequate to maintain that critical flow of water.
2.14DETERMINE RADIATION NEEDED ROOM-BY-ROOM
A radiator or convector's ability to deliver heat is related to the water temperature and the
rate of delivery to the unit. Most systems in the past have been rated at about 80
Higher efficiencies can be gained from a condensing boiler if ratings published at lower
temperatures are used. However, this is not imperative. With normal 80
condensing boiler will still deliver significantly higher efficencies than a non-condensing
boiler. Lower water temperatures in the system tend to increase the efficiency of the
boiler and will help assure that the boiler is subjected to a sufficient load to avoid
short-cycling.
o
C.
o
C ratings used a
The Keston boilers are capable of temperatures of up to 80
temperature of the return water, the lower the efficiency of the system. This is true of all
boilers, though all non-condensing boiler must be kept at higher temperatures to avoid
condensation in the boiler which destroys such boilers quickly. Materials used in the
Keston are made to withstand the condensates corrosive nature.
Read Chapter 2 - Boiler Location and decide upon the position of the boiler.
Installation of the boiler is straightf orward but consideration m ust be given to access to allow f lue
and air pipes to be pushed through walls and ceilings. The order in which the components are
installed will depend upon particular site conditions, but in general it will be easiest and most
accurate to install the boiler and then build up the flue outlet and air inlet pipes to the terminal this is the sequence described.
3.1WALL MOUNTING BRACKET
aPlace the bracket on the wall
horizontally with the pre-drilled
holes at the bottom.
bDrill through the centre hole of
the bracket, plug the hole and
fix in position.
cUsing a spirit level make sure
the bracket is completely level
and mark the position of the
other screw holes.
dRemove the bracket and drill the
holes in the positions marked.
Plug these holes.
eScrew the bracket to the wall
using screws of an appropriate
size for the wall type (No. 12 x 2
inch wood screws normally
suffice).
fMark the bottom fixing hole and
drill for a No 8 x 1 inch wood
screw. Insert plug.
All dimensions in mm.
110
285
250
Figure 3.1 Wall Mounting Fixing Locations
3.2MOUNTING THE BOILER
aLift and locate the upper rear lip on the boiler to the boiler wall bracket.
bMove the boiler sideways to centralise the boiler on the bracket.
cScrew in the lower fixing screw.
3.3ASSEMBLY PRACTICE
Remove all plastic debris and burrs when installing air intake piping. Plastic filings
caused by cutting muPVC pipe must not be allowed to be drawn into the filter or
combustion air blower. Prevent dust entering the air intake when cutting on building sites.
Blower failure which is determined to be caused by plastic filings or other debris will not
be covered by guarantee.
Combustion air filters are fitted to the Keston condensing boilers as standard. This
filter must be examined at least once every year, and more often in particularly
dusty and dirty areas.
The combustion air filter will prevent plugging of the burner caused by dirt being trapped
in the burner's outer mesh. The filter element supplied with the boiler is obtainable from
Keston Boilers or its distributors.
3.4INSTALLING FLUE AND AIR PIPES
Remember the flue pipe must
achieved using 92.5
o
bends.
slope downwards back towards the boiler and this is best
aFrom the two connections on the boiler, mark the positions of the two holes for
the flue and air pipes on the wall(s) or ceiling. To allow access to drill the holes it
may be necessary to temporarily remove the boiler. If the boiler stays put then it
is imperative that the front panel and top access plate are replaced and the two
plastic pipes capped off whilst drilling. Under no circumstances must debris from
the wall or cut pipes be allowed to enter the appliance or the plastic pipework.
bDrill the two holes in the wall/ceiling, preferably using a core drill.
3.4.1Diameter of holes.
i)Allowance must be made for
socketed lengths if these are
to be passed through the
holes :
du = unsocketted
T
d
D
diameter
= 43 mm
ds= socketed
diameter
= 50 mm
L
u
T
ii)For 'horizontal' runs of flue
pipe the holes must either be
oversized or cut at a 5
(the latter may be difficult on
long holes).
3.4.2Oversizing
For every 1m length of run, L, the minimum diameter of the horizontal hole, D,
must be du + 10 mm or ds + 10 mm respectively, assuming the pipe touches the
wall at points T otherwise D will have to be increased by clearance from T. See
Section 3.4.3 - Examples.
c.Measure, cut and check the air and flue pipes to pass to the exit from the
wall(s) or ceiling.
Always thoroughly deburr all pipes and, most important, remove shavings from
within the pipe.
d.Assemble, using adhesive, the pipework from the boiler connections to
the exit from the first wall/ceiling (remount the boiler if removed). When
pushing pipe through walls, ensure grit and dust is not allowed to enter
the pipe.
Ensure pipes are fully engaged into
sockets.
Connect the condensate drainage
system and fill the condensate trap by
pouring water down the boiler flue
spigot ( See Section 3.5 Condensate
Drainage).
Make the final connection of flue
and air pipe to the boiler using push
on, or plastic compression
couplings. Ensure that the connectors
are set vertically otherwise leakage of
condensate may occur which will corrode the casing. Do not use
adhesive on the 'push on' end of the connecting couplings.
Adhesive
Fully Engaged
FA
e.Using the same methods drill any further holes (always covering existing
pipework), cut and assemble the pipework.
f.From outside, complete the two terminations - See Section 2.8 Flue
System and make good all holes.
g.Support any pipes whose route could be displaced either of its own
accord or by accident. Any horizontal run over 1m or vertical runs of any
length must always be supported.
h.Check all connections for security and re-seal any joints using sovent
cement where soundness may be in doubt.
Note:It is equally important to seal the air inlet with solvent cement as
the flue outlet pipe joints.
3.5CONDENSATE DRAINAGE
Connect the condensate drainage system to the boiler. It is advisable to use a
detachable fitting at connection to the boiler to enable easy removal for servicing.
Fill the condensate trap by pouring water into the boiler flue spigot until water is seen to
flow freely from the condensate drainage system. Make the final connection of flue pipe to
the boiler.
Details are provided in Chapter 2 - Section 2.11 Condensate Drainage
Connection : 22 mm plastic pipe.
Connect the flow and return pipework to the boiler. Ensure a detachable coupling is used
at connection to the boiler (ie compression fitting) to enable heat exchanger removal if
required. Details of system requirements are given in Chapter 2 - Section 2.7 Water
Systems.
Connections: 28mm copper
3.7GAS SUPPLY
Connect the gas supply to the appliance. Details of gas supply requirements are given in
Chapter 2 - Section 2.6 Gas Supply.
Connections: 0.5 inch BSP male. (15mm connection to gas cock).
3.8ELECTRICAL SUPPLY
The entry point for the electrical supply cable is in the base of the appliance (see Section
2.2 Service Connections fig. 2.1.2) via a cordgrip bush. Feed the cable through this bush
and route inside the cabinet to the connection strip located to the front bottom right of the
cabinet.
1.The electrical supply must be as specified in Chapter 2 - Section 2.4 Electrical
Supply.
WARNING : THIS APPLIANCE MUST BE EARTHED.
2.All external controls and wiring must be suitable for mains voltage. Wiring should
be in 3 core PVC insulated cable not less than 24/0.2 mm (0.75mm) to BS 6500
Table 16.
3.The supply connection must be via a 5 amp fused double pole switch, serving
only the boiler and system controls. (Refer to Chapter 2 - Section 2.4 Electrical
Supply).
4.Securely tighten the terminal screws and route the cable through the re-openable
cable clips. Ensure all cables are secured and that the cord grip bush is tightened
to securely grip the main cable at entry to the cabinet.
The mains cable must be connected to the terminals as follows:-
N-Blue wire (Neutral)
L-Brown wire (Live)
-Yellow/Green Wire (Earth)
Ensure connection is made such that if the cable slips in its anchorage the current
carrying conductors become taut before the earthing conductor.
3.9EXCHANGING A BOILER
Before removing an existing boiler add Fernox Supafloc , or equivalent cleaning agent,
in accordance with the manufacturers instructions. Open all radiator valves and fire the
boiler. When the system is fully heated, shut off the gas supply and drain down the central
heating system.
Important
The Keston condensing boiler contains components which could be damaged or
blocked by grease, dirt or solder etc. It is essential that sludge or scale is removed
from an existing system.
Connect the new boiler as instructed in this manual and fit in accordance with Sections
3.1 to 3.8
For sealed systems, fill to a pressure of about 2.7 bar. Check the complete system for
water soundness. If leaks need to be rectified using flux or solder the system must be
flushed cold again before proceeding.
Reduce the pressure to the Initial System Design Pressure for sealed systems, if
applicable. Vent the system.
Gas Supply
The complete gas installation up to the boiler service cock must be checked for
soundness. BS 6891.
Electrical Installation
Carry out preliminary electrical safety checks, i.e. Earth continuity, Polarity, Resistance
to Earth, Short Circuit using a suitable test meter.
Initial Firing
Checking The Gas Pressure At The Burner Pressure Test Nipple
The gas burner pressure must be checked at the burner pressure test nipple (Figure 5.7.3
item 54). Full details of this procedure
are given in Section 4.7 Checking The
Gas Pressure.
The gas pressure setting is factory
adjusted to within the required range
and should not normally need
re-adjustment. If the reading is incorrect
then check such factors as soundness of
the air and flue pipe joints, pressure
sensible joints and the gas inlet pressure
(20 mbar required). If all joints are sound
and the gas inlet pressure is satisfactory
set the gas pressure to the required
Important:
This condensing boiler c ontains components which could be dam aged or block ed by grease, dirt,
solder etc., from the water system. The following commissioning procedures must be followed
precisely.
4.1INITIAL FLUSHING
All waterways within the Keston are either copper or high alloy stainless steel. As a result
standard water treatment chemicals for conventional central heating boilers are suitable.
In any event reference must be made to BS 7593 : Treatment Of Water In Hot Water
Central Heating Systems.
a.Disconnect the boiler from the system at the flow and return connections and
temporarily
b.Flush the entire system until clean water is discharged, free from dirt, flux, solder
etc. The use of a flushing chemical is recommended, e.g. Fernox Supafloc.
Sludge and scale must be removed from an existing system.
c.Connect the system to the boiler and fill in accordance with Section 2.7 - Water
Systems. At this stage, for sealed systems, fill to a pressure of about 2.7 bar.
link the flow and return pipes on the system.
d.Check the complete system for water soundness. If leaks need to be rectified
using flux and solder, the system must be flushed cold again before proceeding.
e.Reduce the pressure to the Initial System Design Pressure for sealed systems, if
applicable. Vent the system
4.2GAS SUPPLY
The complete gas installation up to the boiler service cock must be checked for
soundness. BS 6891.
4.3ELECTRICAL INSTALLATION
Carry out preliminary electrical safety checks, i.e. Earth continuity, Polarity, Resistance to
Earth, Short Circuit using a suitable test meter.
4.4LP GAS CONVERSION
All Keston condensing boilers are built and shipped as natural gas fired units. Field
conversion kits are available to convert Keston condensing boilers to use LPG. Suitable
instructions are supplied with the LPG field conversion kits.
4.5INITIAL FIRING
Important
Checking the gas pressure to the pre-mix burner requires a special procedure, outlined
below, which must be carried out.
a.Purge the gas supply in accordance with BS 6891.
b.Turn the gas service cock OFF.
c.Loosen the screw in the burner pressure test point (Figure 5.7.3 item 106A) on
d.Turn on the electrical supply, setting any external controls to call for heat.
e.ON/OFF switch - select 'ON'. The amber 'run' light will illuminate on the ON/OFF
switch, the red 'lockout' light will illuminate, the blower and pump will start and,
after about 15 seconds, a spark will attempt to light gas at the burner. With the
gas service cock off, the boiler will go to lockout - red light illuminated, but the
blower and pump will continue to run. At intervals of approximately 1 minute the
boiler will make two further attempts to fire. After the final attempt the blower will
run for a further 20 seconds before shutting down.
f.Vent the water system.
Important:
Keston heat exchanger consists of a single coil which can trap an air pocket.
The
Great care must be taken to ensure that water flow has been established through
the heat exchanger and thus ensuring no air pockets remain in the heat
exchanger and pipe work. Firing the boiler while an air pocket exists in the heat
exchanger could damage it.
g.Note the reading on the pressure gauge caused by the suction of the blower. This
should be approximately minus 12 mbar for the Keston 80, minus 26 mbar for the
Keston 60 and minus 32mbar for the Keston 50. If it is not, check the system as
follows:
If the negative pressure exceeds the required figure, then it suggests
that there is a possible restriction in the air inlet pipework.
If the negative pressure is less than required figure, then it suggests
that there is a possible restriction in the flue outlet pipework. Note the
exact reading.
h.Turn the gas service cock to ON.
i.Turn off the electricity supply, wait 10 seconds and turn back on. The boiler will
again go through its ignition sequence but this time the main burner will light,
provided all air has been purged from the gas supply to the boiler. When the
burner is lit and the boiler is operating normally the the green (run) lamp, the
upper lamp adjacent to the flame symbol, will also be illuminated indicating
successful ignition.(If it does not, air is indicated - turn off and repeat the
procedure).
If this does not occur, the green (run) lamp, the upper lamp adjacent to the flame
symbol, will be extinguished and, at approximately 1 minute intervals, the
electronic ignition system will make two further attempts to light the burner.
If the ignition is successful and the boiler is operating normally, the green (run)
lamp, the upper lamp adjacent to the flame symbol, and the red (lockout) lamp will
be illuminated simultaneously.
If, after three automatic attempts, the boiler still fails to ignite, the green (run)
lamp, the upper lamp adjacent to the flame symbol, will be extinguished and the
red (lockout) lamp will remain illuminated.
If, after five manual attempts (to allow for purging of any air in the gas line), the
boiler still fails to ignite (indicated by the red (lockout) lamp) refer to Section 5.2 Fault Finding Flow Chart.
j.Check for gas soundness between the gas service cock and connection to the
the cleaning agent, ie Fernox
Supafloc. Turn off the boiler and
flush the water system while still
hot. Thoroughly flush the system
with clear water.
c.Refill the system using a quality water treatment such as Fernox MB1 or Fernox
Super Concentrate. If aluminium radiators are used then Fernox Copal should be
used. For sealed systems, fill to the required Initial Design Pressure.
4.7CHECKING THE GAS PRESSURE
With the boiler running measure the burner pressure at the burner pressure test nipple.
The gas setting is factory adjusted to within the required range and should not normally
need re-adjustment unless the unit has also been converted to LPG as part of the
installation. If the reading is incorrect then check such factors as soundness of the air and
flue pipe joints and the gas inlet pressure (20 mbar required). If all joints are sound and
the gas inlet pressure is satisfactory remove the brass dust cap covering the burner
pressure adjustment screw on the gas valve (See fig. 4.7). Set the gas pressure to the
required value as stated in table 1.4 by turning the exposed burner pressure adjustment
screw (clockwise will increase burner pressure, anti-clockwise will decrease burner
pressure). Replace the brass dust cap to cover the burner pressure adjustment screw.
4.8TIMING THE GAS METER - NATURAL GAS
Burner pressure
Adjustment
Burner pressure
test nipple.
NB:
Table 4.8 Meter Timings
After the boiler has been started, and with no other appliances using gas, time the gas
meter to be certain that the unit is running at the proper gas input. Determine the cubic
feet of gas passing through the meter and determine the input in Btu per hour. Input must
be within plus or minus 5% of the rated input.
Time, in seconds, the time taken to pass 2 cubic feet of gas through the meter (ie one
revolution of a 2 cu ft dial) or 0.1 cubic metres if the meter is of the new metric digital type.
Refer to table 4.8 to determine the input to the boiler and the time required for 2 ft
0.1m3) of natural gas. Adjust the gas valve screw clockwise to increase the input (speed
up the meter) or anticlockwise to decrease the input(slow down the meter) accordingly.
4.9HANDING OVER TO THE USER
It is important to fully explain the following :
a.Procedure to light and turn off the boiler, including isolation of the electrical supply
if necessary.
b.The function of the lockout feature must be explained :
If the red light only is illuminated for more than four minutes, this means that the
boiler has failed to light. Turn off the electrical supply and wait 20 seconds. Turn
ON again and wait.
i)If lockout recurs immediately then the gas supply should be checked as
ON, otherwise consult a Service Engineer.
ii)If it is not possible to relight, the boiler must be isolated and a Service
Engineer called in to rectify the fault.
c.Advise that a reduction in the water pressure reading on the gauge for sealed
systems indicates a leak which should be rectified before further use.
d.Advise that the appliance should be serviced by a competent person at least once
a year.
e.Advise on frost precautions.
f.Hand over User Instructions.
When the external controls are calling for heat, power will be fed to the boiler connection
strip at terminals L (Live) and N (Neutral). If the ON/OFF switch is also in the ON position
the boiler ON lamp (amber) will be illuminated. Provided all temperature thermostats and
pressure switches are closed, power will be fed to pin 2 on the control box, initiating the
following sequence.
(1)The boiler lockout lamp (red) will be illuminated
(2)The fan will start.
(3)When the fan reaches running speed, the Air Pressure switch, normally open, will
close which will start the ignition sequence.
(4)After a pre-purge period of about 15 seconds, the gas valve will open to allow gas
to mix with the air at the suction side of the fan and the ignition spark will occur at
the main burner.
(5)When the burner ignites, the flame is detected by the control box through the
combined flame sensor/ignitor and the ignition spark is stopped. Both the lockout
lamp (red) and the boiler run lamp (green), the upper lamp adjacent to the flame
symbol, will be illuminated. The boiler is now in its normal run condition.
(6)The burner will continue to operate until the gas valve interrupts the gas supply.
The gas valve will be closed by the control box if power is interrupted to the boiler
by any external control or the boiler thermostat. If an interruption to the gas supply
causes loss of the flame the control box with pause for approximately 10 seconds
and then attempt to re-ignite the unit. If this attempt fails, ie due to lack of gas
supply, the boiler will make two further attempts to ignite at intervals of
approximately 1 minute and will then go into a lockout state (red lamp illuminated
only). Once gas supply has been resumed the boiler can be reset by turning the
boiler off and then on again via the on/off switch on the boiler control panel.
(7)The boiler can also be shut down by any of the flow limit, flow overheat and the
flue overheat thermostats, gas low pressure switch and by the low water pressure
switch.
In such an event the green (run) lamp, the upper lamp adjacent to the flame
symbol, will be extinguished and only the red (lockout) lamp will be illuminated.
Any failure of the boiler to sequence in the above manner should be investigated using the
following trouble shooting flow diagram.
Before attempting any electrical fault finding, always carry out preliminary electrical system
checks. On completion of any service/fault finding task which has required the breaking
and remaking of electrical connections, the checks, earth continuity, polarity, short circuit,
resistance to earth must be repeated.
To ensure the continued safe and efficient operation of the boiler it is necessary to carry out
routine servicing at regular intervals. The frequency of the servicing will depend upon the particular
operating conditions, but it is recommended that an annual service should be carried out by a
competent engineer.
The appliance has an integral air filter, mounted at the top right hand side of the boiler, to which
the air intake pipe is connected. This filter should be ex amined every time the boiler is servic ed. It
may need more frequent inspection ac cording to the condition of the atm osphere in which the air
intake terminates.
Note:The air filter can be easily blocked if the boiler is running on or near a building site having
an excess of airborne dust. It is essential, with a premix gas burner, that the air is clean
and free of dust.
It is the law that any service work must be carried out by competent qualified persons.
6.1Pre-Service Checks
It is recommended that an inspection should be carried out prior to shutting down the unit
for servicing. Remove the front cover by releasing the 2 slotted screws on the top and
lifting the cover from the base (Front cover located by two pegs). The following items
should be observed:
a.Smooth starting and running of the blower.
b.Smooth lighting of the burner.
c.Check for leakage of gas, gas/air or combustion products.
d.Check for condensate leaks.
e.Check the colour and appearance of the flame. A sky blue flame slightly off the
burner gauze is normal. The burner itself should appear dark. Any glow on the
burner indicates gauze blockage requiring cleaning, an incorrect gas flow or an air
intake blockage.
f.Check that the temperature differential between the flow and return pipes is less
than 15
o
C. The temperature difference should be between 10oC and 15oC.
g.Check for water soundness.
h.Inspect the flue vent and air intake pipework. Joints must be sound and all
pipework well bracketed.
i.Check that there is a steady fall back to the boiler from the flue pipe to allow
condensate to run back into the boiler (See Section 2.8.3 Slope).
j.With the boiler operating at a low return temperature (i.e. less than 50
o
C) check
that the condensate flows freely from the condensate line.
6.1.1Burner & Heat Exchanger Blockage Checks
i)Turn off the boiler & shut off the gas supply to the boiler.
ii)Remove the pressure point screws from points A & B. Attach a differential
gauge.
iii)Turn on the boiler and wait for the fan to reach full speed. Obviously the
burner will not light.
iv)The pressure difference should be lower than : 8 mbar on the Keston 50,
8.4 mbar on the Keston 60 and 11.2 mbar on the Keston 80. If not, clean
the burner.
v)Turn off the electrical supply to the boiler.
vi)Remove the pressure point screw from point C and transfer the tube from
vii)Turn on the electrical supply to the boiler (gas still off), wait for the fan to
Pressure Test
Point A
Heat
Exchanger
Shell
Fig 6.1.1 Pressure Test Point Loc ations
point A to C, replacing the screw on point A.
reach full speed.
Flue
Flue Overheat
Thermostat
Combustion
Test Point
&
Pressure Test
Point C
viii)The pressure difference should be below 11 mbar. If not, clean heat
exchanger.
ix)Disconnect the gauge from point B. Refit the screw.
x)Read pressure of point C.
xi)The maximum pressure should be 3 mbar. If the pressure is greater than
this, check the flue for blockage.
xii)Turn off the electrical supply to the boiler.
xiii)Remove the pressure gauge tube and refit the screw.
xiv)Open the gas service cock.
6.2Recommended Routine Service
a.Inspect the air filter located at the top right hand side of the boiler. Release the
projecting leaf on the filter box and slide out the filter.
If the filter looks dirty remove the dirt with a vacuum cleaner or by other means. If
in any doubt renew the filter element.
b.Remove the burner head (Section 7.7) and inspect the burner appearance. Black
markings or other discolourations on the gauze indicate too much gas or a lack of
air possibly due to a blocked air filter. Any breakages or damage to the burner
mesh indicate the burner must be replaced.
c.If necessary, either due to discolouration or a high pressure differential between
points A & B in the pre-service checks, clean the burner with a mild
detergent and rinse under a hot running tap.
d.If necessary, either from visual inspection or a high pressure differential between
points B & C in the pre-service checks, clean the heat exchanger using a suitable
stiff plastic bristle brush, vacuum out any large particles and flush the heat
exchanger with fresh water until the water flowing from the condensate drain is
clear. When brushing the heat exchanger take care not to damage the
condensing plug in the lower half of the heat exchanger.
e.Remove the condensate trap (Section 7.10) and unscrew the cap. Clean by
flushing through with clean running water. Reassemble in reverse order.
f.Check the electrodes mounted on the burner head. If the points are damaged or
burnt replace them.
Check that the spark gap measures 4 mm.
g.Replace the burner head, renewing any gasket as necessary, and reconnect the
gas/air supply and the ignition lead. Ensure the flanged gas/air supply joint is air
tight.
h.Turn on the electrical supply to the boiler and allow the boiler to reach operating
temperature levels.
household
i.Check for gas leakage around the burner head, air/gas flexible hose to the burner
head and ignitor plug if they have been removed.
j.Visually inspect the burner through the glass spy hole at the burner head (a small
mirror will prove useful).
k.Recheck the burner pressure by following the procedure detailed in Section 4.7
The following must always be carried out by a competent/qualified person.
7.1PRECAUTIONS
i)Always switch off the mains electricity supply and disconnect the plug at the
isolating switch and socket. (If a switch only is used then remove the fuse.)
ii)Gain access to the appliance (Section 7.2) and turn off the gas supply at the
appliance service cock.
7.2ACCESS
i)Remove the front door by releasing the two slotted screws to the front of the top
panel. The front panel may then be removed by tilting forward and lifting vertically
to disengage the two locating studs in the base of the front panel.
ii)Access to the burner head can be gained by removing the access plate in the top
panel of the appliance.
7.3REPLACEMENT PROCEDURES
i)Always replace in the reverse order unless otherwise stated.
ii)Electrical connections must be remade in accordance with the Wiring Diagram
(Section 5.5).
iii)Test the soundness of any gas carrying or water carrying joint broken during the
service procedures.
7.4ELECTRICAL COMPONENTS
7.4.1On/Off Switch (Fig. 5.7.1 item 115)
i)Isolate the appliance (Section 7.1)
ii)Gain access (Section 7.2)
iii)Remove the push on connectors from the switch taking note of the
correct positions.
iv)Press in the catches and push the switch forwards through the control
panel.
v)Reassemble (Section 7.3)
vi)Check for correct operation of the switch.
ii)Gain access (Section 7.2)
iii)Remove the push on connectors from the thermostat taking note of the
correct positions.
iv)Unscrew the two retaining screws and remove the thermostat.
v)Reassemble (Section 7.3)
NB:When fitting the new thermostat it is a requirement to smear a
thin film of heat sink compound between the thermostat and
plate. This, combined with fitting the new thermostat tightly to the
plate, ensures a good contact.
i)Isolate the appliance (Section 7.1)
ii)Gain access (Section 7.2)
iii)Remove the push on connectors from the thermostat taking note of the
correct positions.
iv)Unscrew the two retaining screws and remove the thermostat.
v)Flue protection thermostat only
The thermostat seal is maintained via a small 'O' ring between thermostat
and flue pipe. If this is damaged on removal it must be replaced.
vi)Reassemble (Section 7.3)
NB:When fitting the new thermostat it is a requirement to smear a
thin film of heat sink compound between the thermostat and
plate. This, combined with fitting the new thermostat tightly to the
plate, ensures a good contact.
ii)Shut off the water supply to the appliance.
iii)Gain access (Section 7.2)
iv)Drain the system to below the level of the appliance using the drain off
tap at the base of the heat exchanger.
v)Remove the push on connectors from the water pressure switch taking
note of the correct positions.
vi)Unscrew the pressure switch.
vii)Reassemble (Section 7.3).
NB:Use a little jointing compound or PTFE tape on the thread.
viii)Refill the system (See Section 4 - Commissioning).
7.4.6Ignition Control Box (Fig. 5.7.1 item 108)
i)Isolate the appliance (Section 7.1)
ii)Gain access (Section 7.2)
iii)Remove the HT ignition lead.
iv)Pull off the multi-pin connector away from the box.
v)Unscrew the two screws securing the control box to the casing and
ii)Gain access (Section 7.2)
iii)Remove the cover plate to the electrical connections on the blower motor
by removing the four retaining screws.
iv)Disconnect the wires to the combustion blower taking note of the correct
positions.
v)Remove the allen screws fixing the air intake pipe flange and the gas/air
mixture pipe flange to the blower.
vi)Undo the two nuts securing the combustion blower base plate to the
cabinet base and lift out the combustion blower.
vii)Unscrew the three bolts fixing the base plate and anti-vibration mounts to
the combustion blower.
viii)Reassemble (Section 7.3)
NB:When reassembling inspect any gaskets for damage and replace
if necessary.
ix)Reset the gas rate (See Section 4 - Commissioning)
7.4.9Gas Control Valve (Fig. 5.7.3 item 95)
i)Isolate the appliance (Section 7.1)
ii)Gain access (Section 7.2)
iii)Remove the cover concealing the electrical connections on the front of
the gas valve.
iv)Remove the push on connectors exposed taking note of the correct
positions.
v)Remove the push on connectors to the gas low pressure switch taking
note of the correct positions.
vi)Remove the earth connection to the side of the gas valve.
vii)Remove the four allen bolts securing the gas inlet flanged connections to
the gas control valve.
viii)Undo the four bolts fixing the base of the gas control valve to the gas
outlet block.
ix)Remove the gas valve.
x)Unscrew the gas low pressure switch at its connection to the gas control
valve body.
xi)Reassemble (Section 7.3)
xii)Reset the gas rate (See Section 4 - Commissioning)
ii)Gain access (Section 7.2)
iii)Unscrew and remove the brass plug from the gas outlet block.
iv)Remove the rubber seal from the injector housing.
v)Insert a flat blade screwdriver into the exposed hole and unscrew the gas injector.
vi)Check the injector is the correct size for the boiler size and fuel type.
vii)Reassemble (Section 7.3)
NB : When fitting the new gas injector ensure that the injector is screwed fully
home past the gas port into the chamber from the gas valve.
viii)Reset the gas pressure (See Section 4 - Commissioning)
ii)Gain access (Section 7.2)
iii)Remove the pull off HT lead to the spark ignition electrode.
iv)Remove the burner head (Section 7.7 steps iv) to vii).
v)Undo the screws to the spark ignition electrode flange located on the burner
head and withdraw the spark ignition electrode.
vi)Reassemble (Section 7.3)
NB:When reassembling inspect the gasket for damage and replace if
necessary. With the new spark ignition electrode in place it is essential to
ensure the gap between the tip of the electrode and the burner surface is
4 mm. Distance above or below 4 mm will affect the ignition performance.
If necessary gently bend the electrode taking care not to damage the
ceramic insulator.
7.7 BURNER HEAD & BURNER (Fig. 5.7.2 items 46 & 48)
i)Isolate the appliance (Section 7.1)
ii)Gain access (Section 7.2)
iii)Remove the pull off HT lead to the spark ignition/flame detection electrode head.
iv)Remove the four screws retaining the access panel (Fig. 5.7.4 item 6) and
remove the access panel from the top of the cabinet.
v)Remove the two allen screws fixing the flange gas/air mixture pipe connection to
the burner head.
vi)Remove the four allen screws fixing the burner head to the top of the heat
exchanger.
vii)Withdraw the burner & burner head from the top of the heat exchanger through
the access panel opening in the top of the cabinet.
viii)Unscrew the burner from the burner head taking care not to damage the burner
mesh.
ix)Reassemble (Section 7.3)
NB:When reassembling inspect any gaskets for damage and replace if
necessary. Set the spark gas as detailed in Section 7.6.
x)Reset the gas rate (see Section 4 - Commissioning)
ii)Gain access (Section 7.2)
iii)Shut of the water supply to the appliance.
iv)Remove the burner head (Section 7.7)
v)Drain the system to below the level of the appliance using the drain off tap at the
base of the heat exchanger.
vi)Remove the boiler thermostat (Section 7.4.2)
vii)Remove the push on connectors to the water pressure switch, flow overheat
thermostat, flow high limit thermostat and flue protection thermostat taking note of
the correct positions.
viii)Remove the condensate trap (Section 7.10)
ix)Remove the pressure gauge phial located next to the drain off tap.
x)Disconnect the flow and return compression couplings to the flow and return
pipes exiting the top of the boiler.
xi)Remove the push on flue connection to the flue pipe exiting the top of the boiler.
xii)Remove the complete air filter assembly and flexible air pipe.
xiii)Remove the nut fixing the strap retaining the base of the heat exchanger and pull
out the strap by unhooking it from its fixing behind the heat exchanger.
xiv)Remove the allen screw securing the top of the heat exchanger to its mounting
bracket.
xv)Remove the five screws fixing the top of the cabinet.
xvi)Remove the heat exchanger, with pipework attached, & the top of the cabinet.
xvii)Separate the top of the cabinet from the combined assembly.
xviii)Remove the flow and flue pipework from the heat exchanger (Replacement heat
exchangers are supplied with return pipework attached).
xix)Reassemble (Section 7.3)
xx)Recommission (Section 4 - Commissioning)
ii)Gain access (Section 7.2)
iii)Drop the lower section of the air filter housing by pulling forward the securing flap.
iv)Open the lower section as far as possible and pull out the combined paper filter
element with rubber seal.
v)Reassemble (Section 7.3)
NB:When fitting the new air filter take care to ensure that the new filter is
placed to cover completely the air intake entry into the boiler cabinet.
ii)Gain access (Section 7.2)
iii)Disconnect the condensate line from the base of the heat exchanger.
iv)Disconnect the condensate line from the base of the flue assembly.
v)Disconnect the condense lines from the projection of the condensate trap from
the base of the cabinet.
vi)Withdraw the condensate trap.
vii)Mop up any spilled condensate.
viii)Reassemble (Section 7.3)
NB:When re-fitting condensate trap pour water into the condensate hose
from the base of the heat exchanger until nearly full. Then reconnect the
condensate hose to the base of the heat exchanger.
ii)Gain access (Section 7.2)
iii)Shut off the water supply to the appliance.
iv)Gain access (Section 7.2)
v)Drain the system to below the level of the appliance using the drain off tap at the
base of the heat exchanger.
vi)Unscrew the air vent.
vii)Reassemble (Section 7.3)
viii)Refill the system (See Section 4 - Commissioning)
ii)Gain access (Section 7.2)
iii)Disconnect the flexible air intake hose from the air inlet manifold (Fig 5.7.3 item
102)
iv)Unscrew the air orifice grub screw (Fig 5.7.3 item 83) to release the air orifice.
v)Lift the air orifice from its seat in the air inlet manifold.
vi)Reassemble (Section 7.3)
NB:When replacing the air orifice ensure that the new orifice is seated with the
For open systems ensure that there is at least 8 feet head of
water pressure at the top of the boiler.
DO NOT remove the dust caps from the air and exhaust pipes
until ready to connect.
Ensure that ALL dust particles, filings , plastic chips etc. are
removed from the inlet pipe.
If the installation is a replacement the system must be flushed
clean. System should be drained hot, then refilled, then drained
again until the water is clean.
Ensure that there is a proper electrical supply ie 230V fused at
5A.
Take great care with pipe connections to ensure that no
damage is done to the internal pipework.
Ensure that the 22mm condensate pipe is not exposed to
freezing conditions.
†
†
†
†
†
†
†
†
†
Make sure that the exhaust pipe terminates away from windows
or vents and is out of reach.
Make sure that the air inlet and exhaust pipe outlets are at least
350mm apart.
Check tightness of all connections in the boiler before firing.
Ensure that the terminals supplied are fitted to both the exhaust
and air inlet pipes.
Ensure that the air inlet terminal is facing upwards to prevent
entry of rain.
The system must be free from air before firing.
The pump must always run when the boiler is firing.
Gravity circuits are not allowed.
If TRV's are installed on radiators ensure that a bypass is
installed to maintain required flow.
Page 57
WD 62/1/1997
KESTON CONDENSING BOILER
Users Instructions
The Gas Safety (Installation And Use) Regulations: 1994 im pose certain statutory obligations on
gas users. Further information regarding these regulations can be obtained from your Gas Region.
All gas appliances must be installed by competent persons by law in accordance with these
regulations. Membership of CORGI is indication of such a competent person with regard to gas
installation.
It is in your interests, and that of safety, to ensure that the appliance is installed correctly and that the
law is complied with. Failure to do so could lead to prosecution.
Introduction
These instructions should be carefully read to ensure safe and economical
use of your boiler.
The Keston Condensing Boiler series are high efficiency central heating
condensing boilers designed to provide central heating and indirect domestic
hot water supply. They are designed for use with fully pumped systems only.
These boilers are supplied for natural gas use but may be converted for use
with LPG by installing the appropriate conversion kit. This conversion must be
carried out by a competent person.
Servicing
To ensure continual safe and efficient operation of the boiler it is
recommended that the appliance be checked and serviced as necessary at
regular intervals. Generally once per year will be sufficient. It is the law that
any servicing must be carried out by a competent person.
Clearances
If fixtures are to positioned close to the boiler the following minimum
clearances must be observed: Top : 254 mm, Bottom : 127 mm, Left : 1 mm,
Right : 1 mm & Front : 305 mm. Extended clearance is required to the front to
allow for access for servicing.
Cleaning
Normal casing cleaning only requires dusting with a dry cloth. To remove
more stubborn marks wipe with a damp cloth and finish with a dry cloth.
Boiler Setup
1)Check that the gas supply from the gas meter is turned ON
2)Check that the gas tap to the boiler is in the ON position (i.e. the screwdriver
slot is aligned with the gas tap).
3)Switch on the electric supply to the boiler and controls and set the heating
controls to call for heat.
4)Check the pressure gauge, to the right on the control panel on the front of the
boiler. This should show around 1 to 2 bar pressure for pressurised systems.
Page 58
WD 62/1/1997
Warning:If there is no pressure indicated and the system if of the pressurised
type do not attempt to light the boiler. Send for your Installer or Service
Engineer to re-pressurise the system.
To Light The Boiler
On/Off
Switch
Green
0
I
Lamp
Red
Lamp
2
31
0
Pressure
Gauge
Fig 1: Boiler Control Panel
Switch the On/Off switch, to the left of the control panel on the front of the boiler, to
the ON position. The following sequence will occur:
1)In the On position the On/Off switch will be lit with an amber light If the switch
does not illuminate check that the electricity supply to the heating system is
on and that the controls are calling for the boiler to fire.
2)At the same time the red (lockout) light will illuminate. If neither the red
(lockout) lamp nor green (run), the upper lamp adjacent to the flame symbol,
illuminate then the boiler is up to temperature and will automatically start
when the heating temperature drops sufficiently.
3)After about 15 seconds the boiler will ignite and the green (run) lamp, the
upper lamp adjacent to the flame symbol, will also be illuminated.
The boiler is now running correctly and will proceed to switch itself on and off as the
heating reaches its operating temperature.
If the green (run) lamp, the upper lamp adjacent to the flame symbol, goes out and
the red light remains illuminated for more than two minutes, due to a failure to ignite
or an interruption to the gas supply, turn the boiler off, wait for 10 seconds and turn
the boiler on again as described above in To Light The Boiler. If the boiler still fails
to ignite after three successive attempts contact your Installer or Service Engineer.
NB:The Keston boiler is designed for simplicity and hence has no user
adjustment.
Gas Leak or Fault
If you suspect a gas leak turn off the appliance immediately and contact your
local gas region without delay.
If you suspect a fault with the appliance it must not be used until the fault has
been corrected by a competent person.
In the unlikely event of a breakdown consult your Installer or Service Engineer
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.