Keston K170 Installation Manual

Page 1
WD51/2/1997 The Keston 170 Condensing Boiler
170,000 Btu/h (50 kW) Model
Fan Powered High Efficiency
Condensing Gas Boiler
Installation And Servicing Instructions
Keston 170 - GC No 41 930 04
CE No : 87AR50
These instructions must be left either
with the user or next to the site gas
34 West Common Road
Hayes, Bromley, Kent BR2 7BX
Tel. 0181 462 0262 Fax. 0181 462 4459
Page 2
WD51/2/1997 The Keston 170 Condensing Boiler
CONTENTS
Section Description 1 GENERAL INSTRUCTION
1.1 Description
1.2 Boiler Schematic
1.3 Related Documents
1.4 Performance Data
1.5 General Data
2 BOILER LOCATION
2.1 Dimensions & Minimum Clearances
2.2 Service Connections
2.3 Position
2.4 Electrical
2.5 Boiler Size Selection
2.6 Gas Supply
2.7 Water Systems
2.8 Flue System
2.9 Air Supply
2.10 Compartment Installation
2.11 Condensate Drainage
2.12 Radiant Floor Heating
2.13 Low Water Volume Boiler vs. Cast Iron Boiler
2.14 Determine Radiation Needed Room-By-Room
3 INSTALLATION OF THE BOILER
3.1 Wall Mounting Bracket
3.2 Mounting The Boiler
3.3 Assembly Practice
3.4 Installing Flue And Air Pipes
3.5 Condensate Drainage
3.6 Water System
3.7 Gas Supply
3.8 Electrical Supply
3.9 Exchanging A Boiler
4 COMMISSIONING OF THE BOILER
4.1 Initial Flushing
4.2 Gas Supply
4.3 Electrical Installation
4.4 LP Gas Conversion
4.5 Initial Firing
4.6 Hot Flushing
4.7 Checking The Gas Pressure
Page : i
Page 3
WD51/2/1997 The Keston 170 Condensing Boiler
4.8 Timing The Gas Meter
4.9 Handing Over To The User
5 FAULT FINDING
5.1 Electrical Control Sequence
5.2 Fault Finding Flow Chart
5.3 Continuity Checking
5.4 Functional Flow Wiring Diagram
5.5 Electrical Wiring Diagram
5.6 Illustrated Wiring Diagram
5.7 Exploded Assembly Diagrams
6 SERVICING
6.1 Pre Service Checks
6.2 Recommended Routine Service
7 REPLACEMENT OF PARTS
7.1 General
7.2 Precautions
7.3 Access
7.4 Electrical
7.5 Gas Orifice
7.6 Spark Ignition/Flame Detection Electrode
7.7 Burner Head & Burner
7.8 Heat Exchanger
7.9 Air Screen
7.10 Condensate Trap
7.11 Pressure Gauge
7.12 Sight Glass
7.13 HT Ignition Lead
7.14 Air Vent
7.15 Air Orifice
8 SPARE PARTS LISTINGS
BENCHMARK INITIATIVE
As part of the industry wide “Benchmark” Initiative all Kes ton 170 boilers now include a Benchmark Installation, Commiss ioning and Service Rec ord Log Book . Pleas e read this c aref ully and complete all sections relevant to the appliance installation. T he details of the Log Book will be required in the event of and warranty work being required. There is also a section to be completed after each regular service visit. The completed Log Book should be left with the customer.
CORGI CONTACT INFORMATION
The boiler should be installed and serviced only by CORGI registered operatives. All CORGI registered Installers carry a CORGI ID cad, and have a registration number. Both should be recorded in the Benchmark Log Book. You can call CORGI direct on 01256 372300.
Page : ii
Page 4
WD51/2/1997 Chapter 1 : General Instruction
1. GENERAL INSTRUCTION
1.1 DESCRIPTION
The Keston Condensing Boiler is unique in its concept and design. While the application for which the boiler was designed is the sam e as those which other boilers are us ed, the Keston boiler has the added advantage of very high efficiency, and small diameter plastic flue which can be extended to 15 metres horizontally or vertically.
The Keston uses a high power combustion blower to deliver a pre-mix of gas and air to a downward firing burner in a high efficiency, single pass heat exchanger. Normally the combustion temper ature of the air gas mixtur e is around 1800
combustion at an amazing 1000 The flue system is room sealed and fan powered. The ignition is direct spark and fully
automatic. The boiler housing is not waterproof. The boiler should be installed in a position where it will always be dry. A small air intake point is incorporated within the appliance cabinet to ensure that the interior of the cabinet is maintained under a slight negative pressure. This is a safety feature to ensure no products may leak out of the cabinet into the installation space.
The boiler is suitable for c onnection to open vented or, preferably, sealed systems. The system must be pumped centra l heating or pum ped c entr al heating with combined indirec t sanitary hot water. Gravity circuits must not be used.
The Keston 170 Condensing Boiler
o
C thereby reducing the NO
o
C but the Keston achieves
x emissions.
Forming part of the boiler is the heat exchanger which is made f rom a highly corrosion resistant stainless steel, form ed into tightly wound coil. The hot combustion gases from the central down firing burner pass thr ough this coil im parting heat into the system water. Head characteristics of the boiler coil must be taken into consideration when calculating the pump size. The Keston boiler is not a high water content boiler and does not contain the metal mass , or water volume, of a cast iron or steel boiler . This boiler is of low mass and low water content and therefore responds f aster when there is a call for heat. This feature requires a higher water pum ping rate through the boiler otherwise localised boiling will occur within the boiler. Allow a pressure drop through the boiler of 13.75 ft head and a
water flow of 13.2 gallons (60 litres) per minute. The boiler selected m ust be sized relative to the total c alculated heat loss of the building.
The boiler rated output should not be greater than the total required to make up the calculated heat loss plus the heat required to provide sanitar y hot water, if the system is not hot water priority design. If there are special conditions such as excess ive sanitary hot water usage consult the manufacturer.
1.2 BOILER SCHEMATIC
Air is drawn into the boiler through a 50mm muPVC pipe. The air flow is proved by a differential pressur e across the air control orif ice. Gas is mix ed with combustion air at the inlet to the fan. The gas flow is r egulated by an orifice located in the housing downstr eam of the gas valve.
The gas and air are thoroughly mixed in the blower and f ed into the burner located at the top end of the heat exchanger module. The gas and air mixture is ignited by a direct spark ignition control system and burns with a blue flame j ust off the surface of the burner. As the hot products of combustion pass downwards, they are cooled by exchanging heat with the circulating water which enters the heat exchanger coil at the bottom of the heat exchanger.
Fig. 1.2 - Boiler Schematic
Installation & Servicing Instructions
Page : 1
Page 5
WD51/2/1997 Chapter 1 : General Instruction
The Keston 170 Condensing Boiler
When the return water temperature is below 54oC, part of the water vapour in the combustion products will condense ins ide the heat exchanger, thus increasing the boiler efficiency by releasing the latent heat of condensation. This condensate falls to the bottom of the heat exchanger where it is separated from the flue gases and exits from the boiler through the condensate drain. Any condensate formed in the flue runs back down the flueway and is drained at the base of the flue connection to the heat exchanger or drain points within the flue..
The condensate is very slightly acidic (about the same acidity as vinegar) and should be piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed of as normal waste water.
The flue gases are piped in a 50m m m uPVC pipe to the outside. The temper ature of the flue gases are usually around 10 pipe should be terminated outside the building from where they cannot re-enter the building or any other adjacent building.
The heating level may be controlled by room therm ostats, hot water cylinder therm ostats, programmer time clocks and energy management systems.
1.3 RELATED DOCUMENTS
The Keston Condensing Boiler must be ins talled in accordance with the current issue of the Gas Safety (Installation and Use) Regulations, current IEE Wiring Regulations,
Building Regulations, Building Standards (Scotland) Consolidation, and the Bye Laws of the local Water Undertaking.
o
C above the temperature of the return water. T he flue
In addition, due account must be taken to the following Codes Of Practice:
BS 6891 : Gas Supplies BS 6798 : Installation Central Heating Boilers BS 5449 : Installation Pumped Central Heating BS 5546 : Installation Domestic Hot Water BS 5440.1 : Flues
Installation & Servicing Instructions
Page : 2
Page 6
WD51/2/1997 Chapter 1 : General Instruction
BS 5440.2 : Air Supply BS 5482.1 : Domestic Propane & Butane Burning Installations BS 7074.1 : Expansion Vessels BS 7593 : Treatment of Water in Hot Water Central Heating
BS 7671 : Requirments for Electrical Installations.IEE Wiring For Timber Framed Buildings, British Gas Publications DM2. Also British Gas
Publications 'Guidance Notes For The Installation Of Domestic G as Condensing Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
1.4 PERFORMANCE DATA
The Keston 170 Condensing Boiler
Systems Regulations 16th Edition.
Boiler Input (gross) kW 55.0 Btu/h 187,600
Boiler Output To Water kW 49.8
o
C Flow 60oC Return) Btu/h 170,000
(80 Boiler Output To Water kW 52.4
o
C Flow 40oC Return) Btu/h 179,000
(60 Boiler Output To Water kW 54.5
o
C Flow 30oC Return) Btu/h 186,000
(50 Burner Setting Pressure mbar 10.0
(Hot) in wg 3.94 Gas Comsumption After l/s 1.42
10 mins Running Ft (CV of Gas - 38.7 MJ/m (1038 Btu/Ft
3
)
3
)
3
/hr 180.73
1.5 GENERAL DATA
Max. Operating Flow Temp.
o
C 80.00
Max. Head (Open Systems) m 30.50
Ft 100.0 Max. Press. (Sealed Sys.) Bar 2.70 Min. Head (Open Systems) m 2.5
Ft 8.0 Inlet Gas Pressure mbar 20.0
in wg 8.0 Gas Orifice Size mm 4.5 Air Orifice Size mm 23.0
o
Recommended Temperature
C 10 to 15
Differential
Main Burner Keston Premix Gas Control White Rogers 36E Series Combustion Fan Keston
Type LPB 103 220/240
0.6 kW 2900 RPM
Direct Spark RAM ElectronicsIgnition Ignition Full Sequence Control
Air Press. Switch Tridelta FS6717-1428 Filter Keston Filter Gas Supply 0.75 inch BSPT Male
Connection (22mm to gas cock)
Installation & Servicing Instructions
Flow Connection 35mm Copper Return Connection 35mm Copper Power Supply 230V 50Hz Pwr Consumption 610 W Ext Fuse Rating 10 Amps Weight - Full 68 kg (150 lbs)
Weight - Empty 61 kg (134 lbs) Data Badge Posn Right Hand Panel Inside
Case
Water Content 7.0 litres
Page : 3
Page 7
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
2. BOILER LOCATION
All dimensions in mm.
2.1 DIMENSIONS AND MINIMUM CLEARANCES
The boiler must be installed in m inim um clearances shown to allow subsequent servicing, and safe operation.
2.2 SERVICE CONNECTIONS
254
Gas, water, air and flue pipe, condensation, and electrical connections are as shown. Gas :7 0.5 inch BSP male. Flow/Return 35 mm
copper.
2.3 POSITION
The Keston is not suitable for external installation. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Figure 2.1.2 Dimensions
Air Intake
Return
50
Flow
Flue
1
1
305
Figur e 2.1.1
127
Minimum Clearances
All dimensions in mm.
890
Condense
Gas
Where a room-sealed appliance is installed in a
50
244
190
263
405
Top View
Installation & Servicing Instructions
113
152
65
37
Service Connection Locations
97
500
7
2
3
35
85
50
30
44
Base View
All dimensions are in mm.
Page : 4
Page 8
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
room containing a bath or shower, any electrical switch or appliance control, utilising mains electricity, should be so situated that it cannot be touched by a person using the bath or shower.
Compartment installation is permitted - such compartments must be constructed in accordance with BS 6798.
The wall on which the boiler is mounted must be of suitable load bearing capacity and must be non-combustible.
Important : It is not recommended to install the boiler on a studded wall or similar - it is possible that the vibration from the fan would be amplified and transmitted to other parts of the property.
[NB: Refer to Section 2.8.3]
The Keston can be located virtually anywhere desired provided that all regulations are complied with. Because of the boiler's compact size and venting flexibility, the installation is not limited to a boiler room setting. Before locating the boiler near a living space
consider whether the sounds generated by the boiler will be objectionable.
2.4 ELECTRICAL
2.4.1 Electrical Connections
The boiler must be connected to a 230V ~ 50Hz supply, fused at 10A. All external controls and wiring must be suitable for mains voltage. Wiring
external to the boiler must be in accordance with current I.E.E wiring regulations and local regulations.
Chimneys not used for venting any other
appliance may be used.
Secure air & flue pipes at chimney outlet.
Figure 2.3
The method of connection to the mains electricity supply must facilitate complete electrical isolation of the boiler, preferably by the use of a fused,
Installation & Servicing Instructions
Page : 5
Page 9
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
unswitched three pin plug and a shuttered socket-outlet, both complying with the requirements of BS 1363.
The appliance must be connected to the supply via a fused double pole switch having at least 3mm (1/8 inch) contact separation in both poles, serving only the boiler and the system.
The connection point to the mains supply should be readily accessible and adjacent to the boiler, except for rooms containing a bath or a shower. Refer to section 2.3 Position.
2.4.2 External Wiring & Controls
1. The boiler is deisgned so that all control wiring is external to the boiler. Hence, any programmers or room thermostats etc must act by switching the 230V supply to the boiler.
2. System designs which allow the boiler to fire when there is no pumped circulation must NOT be used.
3. A programmer may be used with zone valves to give independent control of central heating and hot water.
2.5 BOILER SIZE SELECTION
The size of the boiler to be used is determined by the total calculated heat loss of the building. Match the calculated heat loss with the boilers rated output. If a boiler is installed
with an output rating greatly exceeding the total capacity of the distribution system the efficiency of the boiler will be reduced.
2.6 GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas region or their contractor. An existing meter should be checked preferably by the gas region to ensure that the meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891.
Minimum/Maximum Natural Gas Pressure:
Natural gas pressure before the gas valve must be maintained at 20 mbar (8 in WG) while the boiler is running.Gas pressures above or below this level will lead to problems associated with the gas valve's internal pressure regulator.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (22 mm). Due consideration must be given to the supply pressure to other gas appliances in the premises. Reduction in dynamic gas supply pressure will result in intermittent ignition failures. Ensure gas supply pipe work is adequately sized for the length of run from the meter to the boiler.
A gas cock is supplied loose with the boiler. This cock should be fitted in the gas line to the boiler as close to the boiler as possible so that it is easily identified as the cock to isolate the boiler.
2.7 WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply Bylaws for forced hot water heating systems. Consideration must be given to pipe capabilities and pressure drop through the piping.
Installation & Servicing Instructions
Page : 6
Page 10
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
Water treatment must be carried out to BS 7593 : Treatment of Water in Hot Water Central Heating Systems. Pump isolating valves must be positioned as close to the pump as possible.
a The Keston 170 is suitable for use on open vented water systems with combined
feed and vent.
b It is preferable for use on sealed water systems, provided the appropriate
components required (see Section 2.7.2 Sealed Systems) are included in the system.
c Any system must
connection with the boiler. A trap should be installed in the flow line to collect any solder, or other debris, from the installation.
d All water systems must be constructed to comply with requirements of the Local
Water Authority. e Only fully pumped systems can be used - gravity systems are strictly f Always use a system complying with the requirements of BS 5449 and BS 6798. g The system must be so arranged that there shall always be a minimum flow of
13.2 gpm (60 litres/min) when the boiler is firing.
be thoroughly flushed clean of grease, dirt and debris, prior to
not suitable.
This can be via a specially
installed by-pass arrangement.
h Copper tubing to BS 2871 Part 1 is recommended. i Jointing should be either with capillary, threaded or compression fittings. Pipes
should have a gradient to ensure air is passed easily to vent points and water
flows readily to drain points. j Draining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 22 mm in
nominal size and be in accordance with BS 2879.
AIR VENT POINTS k These must be fitted at all high points where air will naturally collect and must be
sited to allow complete draining of the system.
2.7.1 Open Vented Systems
A typical system is shown in Figure 2.7.1 which includes a combined feed and
vent. Note there must be no valve between the boiler flow and the open vent.
Note that the minimum static head required is 9 ft at the boiler flow pipe. If the
cold feed/vent is not brought to the flow pipe as shown, then the pressure loss
across the heat exchanger may have to be taken into account when estimating
the static pressure.
Although suitable for open vented systems with combined feed and vent
arrangements, the Keston is a low water content boiler. As such, any air
entrainement within the system water will produce boiler “kettling”. It is
therefore recommended, if in any doubt, to consider the use of sealed
systems where possible.
Installation & Servicing Instructions
Page : 7
Page 11
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
Boiler
Expansion Pipe
28mm
Minimum
Keston
Strainer
Rad. 2 Rad. 1
Expansion Tank
Pump
Minimum 9ft Heig ht
By-pass Bal. Valve
Valve
Cylinder
L/S Valve
Valve
2.7.2 Sealed Systems
Sealed systems must be designed in accordance with BS 5449 and BS 7074 Pt1. A typical sealed system is shown in Figure 2.7.2. It must include :
(i) A safety valve fitted on the flow, adjacent to the boiler. It must be non
(ii) An expansion vessel complying with BS 4814 and sized in accordance
(iii) A filling point, in accordance with local water authority requirements. (iv) A method of system make-up (automatic or manual), in accordance with
(v) There must be no permanent connection of mains water to the boiler
(vi) The installation must be designed to work with flow temperatures of up to
Figure2.7.1 : Open Vented System Diagram
adjustable and preset to 3 bar. A drain pipe must be attached, at least as big as the valve connection, and routed to drain in any area not hazardous nor where it may be subject to freezing.
with the requirements of BS 5449 and BS 7074 Pt 1. The vessel must be positioned on the inlet to the pump.
local water authority requirements.
system.
o
C.
110
Installation & Servicing Instructions
Page : 8
Page 12
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
k
Make -up vessel. Max. capacity of
Air Vent
3 lt. (5pt)
Boiler
Drain Coc
Keston
Safety Valve
Expansion Vessel
Pressure Guage
Strainer
By-pass Bal. Valve
Pump
Doubl e Check Valve
Figure 2.7.2 : Sealed System Diagram
L/S
Test Cock
RETURN
HEATING CIRCUIT
FLOW
BS 1010:2 Stop T ap
Non-Return Valve
Auto Air Vent
Hose Union bib tap
Hosepipe (disconnected after filling)
Hose Connector
All components of the system including the heat exchanger of the indirect cylinder
must be suitable for a working pressure of 3 bar and a temperature of 110
Care should be taken in making all connections that the risk of leakage is
minimised.
2.7.3 Hot Water System (if applicable)
The hot water storage vessel must be of the indirect type (certain direct cylinders
can be used provided
they are suitably adapted by fitting an immersion calorifier).
DIRECT CYLINDERS MUST NOT BE USED. Further guidance is provided in BS
1394. It is advisable to fit a lockshield valve on the cylinder return to enable
balancing of the flow rate through the cylinder.
2.7.4 Boiler By-pass Piping
Boiler water flows are critical to the operation of the boiler. If flow cannot be
maintained through the system piping to meet the minimums required by the
boiler (see paragraph 2.7 (g)). Insufficient water flows through the boiler will cause
the boiler to "kettle" or even produce steam which can damage the heat
exchanger and will invalidate the heat exchanger warranty.
It is normally advisable to incorporate a boiler by-pass in the system, especially if
thermostatic radiator valves are used. The by-pass should be fitted with an
automatic by-pass valve to permit balancing of the by-pass flow rate. The
flow/return differential should be 10
maintain this condition with all thermostatic radiator valves closed.
o
C.
o
C to 15oC. The valve should be adjusted to
Installation & Servicing Instructions
Page : 9
Page 13
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
2.7.5 Air Elimination
In the initial charge of water to the boiler system and in all subsequent additions of water to the system some air will be dissolved in the water. As the water is heated the air is driven out of the solution and will collect in high spots in the system. These air bubbles can interfere with pumping and heat transfer and
must be eliminated.
Installation of air bleed valves at the high spot(s) in the system will allow for air elimination when filling the system and will allow re-venting in a day or so after all air has been driven out of solution.
2.7.6 Strainers
Debris in the heating system can cause noise if it enters the heat exchanger. Fitting of a Y-strainer ahead of the circulating pump will trap any debris left in the system and will protect the pump from damage. The boiler guarantee does not cover heat exchanger failure due to debris abrasion within the
system.
Y-Strainer will collect an y loose debris in the piping.
Figure 2.7.6 Strainers
2.7.7 Pump Selection
The Keston boilers have low water content heat exchangers with a high resistance to flow, when compared with cast iron heat exchanger boilers. As a result selection of the correct pump is essential localised boiling within the heat exchanger. The selected pump must be capable of maintaining the required flow rate for the boiler against the pressure losses contributed
by the boiler.
The Keston 170 condensing boiler offers a hydraulic resistance of
4.2m (13.75ft) water at the required flow rate of 60 l/m (13.2 gpm).
If a single pump is to be used for the entire installation the boiler resistance must be added to the pressure loss caused by the rest of the
in order to avoid
Static Pressure - m WC
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
20 30 40 50 60
10
Water Flow - L/min
Figure 2.7.7 : Pressure Loss Gra ph
70
Installation & Servicing Instructions
Page : 10
Page 14
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
g
system and a pump selected that is capable of meeting the flow rate required at
the total pressure loss generated by the boiler and the rest of the system. The
selected pump must comply with BS 1394. It is important to note that the
minimum flow rate must be maintained whenever the boiler is firing. Systems
using zone valves must be specifically designed to only fire the boiler when the
pump is running and the minimum flow rate can be achieved.
2.8 FLUE SYSTEM
2.8.1 Design
Individual air supply and flue outlet pipes are used. The material used for flue
outlet &/or air inlet must be muPVC to BS 5255 an of an internal diameter of 51
mm.
O56
40
87
80
Flue Outlet Terminal
Both flue outlet terminal and air inlet terminal are supplied and are illustrated in
Figure 2.8.1 above.
2.8.2 Maximum Lengths
The maximum lengths of both air inlet pipe and flue outlet pipe, when no bends
are used, are as detailed below.
Maximum Air Inlet Length : 15.0 m
Maximum Flue Outlet Length : 15.0 m
However, each bend used has an equivalent length that must be deducted from
the maximum straight length stated above. Knuckle bends must not be used.
Fi
ure 2.8.1 : Terminals
211
O83
O56
Air Intake Terminal
o
A 92.5
sweep elbow is equivalent to 1.0m straight length. Example: Air inlet uses two one 92.5o sweep elbows. Hence, maximum length permissible
(ie a+b in figure 2.8.2) = 15.0m - 1.0m - 1.0m = 13.0m
o
Flue outlet uses one 92.5
sweep elbow. Hence, maximum length permissible (ie
c+d in figure 2.8.2) = 15.0m - 1.0 m = 14.0m
Installation & Servicing Instructions
Page : 11
Page 15
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
2.8.3 Slope
FLUE
d
c
AIR
b
a
Keston
Figure 2.8.2 : Flue & Air Maximum Length Example
'Horizontal' flue outlet pipework MUST slope at least 5 degrees (80 mm per metre run) downwards towards the boiler. Pipework can be vertical. Only swept elbows can be used. Air inlet pipework can be truly horizontal or vertical, or sloping in a downward direction towards the boiler but in this case rain, etc, must
be prevented from entering the pipe. There must be no troughs in any of the pipework, whether it be air inlet or flue outlet. If a 80 mm per meter slope is not possible, contact Keston Boilers Technical Department for further guidance.
Due the low temperature of the flue gases further condensate will form within the flue system. Drain points, with suitable traps, must therefore be incorporated within the flue system at the base of vertical flue sections in excess of 2m. These additional condensate drains must be run to discharge as detailed in section 2.11. Such drain points can be formed using standard muPVC fittings. Refer to the example in Figure 2.8.3.
2.8.4 Terminations Air inlet terminals must be
facing upwards and positioned to ensure only fresh air is drawn into the boiler. The air terminal must be located outside of the building. Drawing of combustion air directly from a ventilated boiler room will invalidate the heat exchanger warranty. The air intake terminal must face upwards to prevent entry of rain into the air intake pipework.
The flue outlet terminal is designed to face outwards but can, if desired, be
Figure 2.8.3 :
Flue Condensate Drain Point Example
To Terminal
To Boiler
50mm Tee Fitting
6 in min.
Installation & Servicing Instructions
Page : 12
Page 16
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
adapted to face in any direction BUT must not be directed in the region of the air inlet.
Dimensions (mm)
Flue
Terminal
Air
Inlet
50300A Below openable window, air brick, etc. 7575B Below gutters, soil pipes, drain pipes. 50300C Below eaves. 50200D Below balconies or car port roof. 5075E From vertical drain or soil pipes.
50600F From internal or external corner. 100300G Above ground or balcony or roof. 100600H From surface facing a terminal
1,2001,200I From terminal facing a terminal.
1001,200J From opening in a car port.
1,5001,500K Vertically from terminal on same wall.
300300L Horizontally from terminal on same wall.
Table 2.8.4 Minimum Flue Terminations & Air Inlet Dimensions
The two terminals are subject to the requirements of BS 5440 Pt 1 for clearances from features of the building although some can be decreased to the values indicated. If either the air inlet or the flue outlet terminate at a height of less than 2m (6ft) above ground level the termination must be protected by a suitable guard. The K4 terminal guard, manufactured by Tower Flue Components Ltd, is suitable for this purpose and can be obtained from Keston Boilers. The Keston condensing boiler, as with any condensing boiler, will generate a condensate “plume” from the flue terminal in all weather conditions. Consideration must therefore be given to the effect of this “plume” when selecting a location for the flue terminal. It is advisable, for horizontal flue terminals, to place a 45
O
elbow at the end of the flue to direct the condensate plume up and away from the property,
2.8.5 Clearances From Wall
Flue outlet and air inlet terminations must be at least 60 mm and 95 mm respectively from the wall face.
2.8.6 Distance Between Flue Outlet & Air Inlet
There is no maximum - the terminations can be on opposite sides of the dwelling if desired. A minimum clearance of at least 500 mm must be left between the terminations.
2.8.7 General Installations
All parts of the system must be constructed in accordance with BS 5440 Part 1, except where specifically mentioned in these instructions. All pipework must be adequately supported.
Installation & Servicing Instructions
Page : 13
Page 17
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
All joints other than push-on or plastic compression connectors must be made and sealed
with solvent cement suitable for muPVC pipes and conforming to BS 6209: 1982. External wall faces and any internal faces of cavity walls must be made good.
2.9 AIR SUPPLY
The Keston is a room sealed appliance and therefore does not require purpose provided ventilation for combustion air.
2.10 COMPARTMENT INSTALLATION
The casing temperature of the Keston 170 is very low. Due to this fact, no compartment ventillation is required for cooling purposes.
2.11 CONDENSATE DRAINAGE
Being a condensing boiler, the Keston is fitted with a condensate trap at the base of the heat exchanger and flue assembly, with facility to connect to a drain point underneath the appliance.
Use only plastic piping and do not reduce below 15mm internal diameter within the dwelling. Condensate should preferably be drained into the sanitary waste system or, alternatively, the rainwater system of the property.
Termination of the pipe must be either at a branch or stack internal to the house, or externally at an open gully. Alternatively, discharge into a purpose made condensate soakaway can be considered. Existing or purpose built drains must use suitable corrosion resistant material as condensate is mildly acidic.
A minimum slope downwards towards the drain of 1 in 20 is essential. Freezing of the termination and pipework must be prevented. Any drainage pipes outside the property must be at least 32 mm inside diameter.
2.12 RADIANT FLOOR HEATING
The low operating temperatures of this type of system lead to very good operating efficiencies. In fact, under floor heating can produce in excess of 95% operating efficiency from a Keston condensing boiler.
Water temperatures in radiant floor heating systems must be kept relatively low, generally under 48
o
C, so that surfaces do not become uncomfortably warm to the touch. If radiant heating is only one application for a multi-zone system which also requires higher delivery water temperatures for other zones (i.e. water heating, skirting heaters etc.) then the radiant floor zone temperature will need to be controlled separately from the boiler.
If radiant floor heating is the only application of the boiler, the boilers maximum operating temperature can be lowered accordingly by introducing a supplementary control
thermostat within the control system of the installation. Mixing valves are also available which will mix return water from the system with boiler
output water to dilute the temperature of water transmitted to the distribution system. Mixing valves may create problems with low flow and high temperatures through the boiler, unless care is taken to design a system which will provide proper flows and will fully load the boiler. Keeping the boiler's temperature high will prevent the boiler from operating at peak efficiencies. Systems which maintain boiler temperatures in this way should be avoided.
Installation & Servicing Instructions
Page : 14
Page 18
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
If only a portion of the boiler's available output is to be used for radiant floor heating a thermal storage tank will improve the boiler's operation and give adequate control of temperature for the distribution system. By heating water to be distributed to the radiant floor zone to the proper temperature in an indirect-fired water heater, full load conditions will be available to the boiler because the heat exchanger in the tank can be sized to match the boiler's output. The tank's thermostat can be set at the optimum operating temperature needed by the distribution system and short-cycling of the boiler will be prevented. An insulated thermal storage tank without the heat exchanger may also be used.
2.13 LOW WATER VOLUME BOILER VS. CAST IRON BOILER
Because of their high water content and mass of metal, cast iron and steel boilers are less responsive but somewhat more forgiving of design errors. Short-cycling of the burner on the temperature limit control is less pronounced, though no less detrimental to operation, because the boiler itself will absorb and radiate a significant amount of heat. Low water volume boilers respond more quickly to a call for heat, can be made more compact and lightweight, but must have adequate heat delivery systems to avoid short-cycling of the burner on the temperature limit control. The heat delivery system's output must be equal to or greater than the boiler's output to fully load the boiler or short-cycling will occur.
Likewise, pumping rates of water through low water volume boilers must be maintained so that water is moved through the boiler fast enough so as not to reach boiling temperatures. The slower the water moves through the boiler the more heat it will absorb and the higher the temperatures will rise. Consequently, the pump selected must be adequate to maintain the critical flow of water.
2.14 DETERMINE RADIATION NEEDED ROOM-BY-ROOM
A radiator or convector's ability to deliver heat is related to the water temperature and the rate of delivery to the unit. Most systems in the past have been rated at about 80 Higher efficiencies can be gained from a condensing boiler if ratings published at lower temperatures are used. However, this is not imperative. With normal 80 condensing boiler will still deliver significantly higher efficencies than a non-condensing boiler. Lower water temperatures in the system tend to increase the efficiency of the boiler and will help assure that the boiler is subjected to a sufficient load to avoid short-cycling.
The Keston boilers are capable of temperatures of up to 80 temperature of the return water, the lower the efficiency of the system. This is true of all boilers, though all non-condensing boiler must be kept at higher temperatures to avoid condensation in the boiler which destroys such boilers quickly. Materials used in the Keston are made to withstand the condensates corrosive nature.
o
C ratings used a
o
C but the higher the
o
C.
Installation & Servicing Instructions
Page : 15
Page 19
WD51/2/1997 Chapter 3 : Installation
The Keston 170 Condensing Boiler
3. INSTALLATION OF THE BOILER
Read Chapter 2 - Boiler Location and decide upon the position of the boiler. Installation of the boiler is straightf orward but consideration m ust be given to access to allow f lue
and air pipes to be pushed through walls and ceilings. The order in which the components are installed will depend upon particular site conditions, but in general it will be easiest and most accurate to install the boiler and then build up the flue outlet and air inlet pipes to the terminal - this is the sequence described.
3.1 WALL MOUNTING BRACKET
a Place the bracket on the wall
horizontally with the pre-drilled holes at the bottom.
b Drill through the centre hole of
the bracket, plug the hole and fix in position.
c Using a spirit level make sure
the bracket is completely level and mark the position of the other screw holes.
93
All dimensions in mm.
d Remove the bracket and drill the
holes in the positions marked. Plug these holes.
e Screw the bracket to the wall
using screws of an appropriate size for the wall type (No. 12 x 2 inch wood screws normally suffice).
f Mark the bottom fixing hole and
drill for a No 8 x 1 inch wood screw. Insert plug.
3.2 MOUNTING THE BOILER
a Lift and locate the upper rear lip on the boiler to the boiler wall bracket. b Move the boiler sideways to centralise the boiler on the bracket. c Screw in the lower fixing screw.
3.3 ASSEMBLY PRACTICE
Remove all plastic debris and burrs when installing air intake piping. Plastic filings caused by cutting muPVC pipe must not be allowed to be drawn into the filter or combustion air blower. Prevent dust entering the air intake when cutting on building sites. Blower failure which is determined to be caused by plastic filings or other debris will not be covered by guarantee.
280
250
Figure 3.1 Wall Mounting Fixing Locations
Combustion air filters are fitted to the Keston condensing boilers as standard. This filter must be examined at least once every year, and more often in particularly dusty and dirty areas.
Installation & Servicing Instructions
Page : 16
Page 20
WD51/2/1997 Chapter 3 : Installation The Keston 170 Condensing Boiler
The combustion air filter will prevent plugging of the burner caused by dirt being trapped in the burners outer mesh. The filter element supplied with the boiler is obtainable from Keston Boilers or its distributors.
3.4 INSTALLING FLUE AND AIR PIPES
Remember the flue pipe must achieved using 92.5
o
bends.
slope downwards back towards the boiler and this is best
a From the two connections on the boiler, mark the positions of the two holes for
the flue and air pipes on the wall(s) or ceiling. To allow access to drill the holes it may be necessary to temporarily remove the boiler. If the boiler stays put then it is imperative that the front panel and top access plate are replaced and the two plastic pipes capped off whilst drilling. Under no circumstances must debris from the wall or cut pipes be allowed to enter the appliance or the plastic pipework.
b Drill the two holes in the wall/ceiling, preferably using a core drill.
3.4.1 Diameter of holes.
i) Allowance must be made for socketed lengths if these are to be passed
through the holes : du = unsocketted
diameter
= 56 mm
ds = socketed
diameter
= 65 mm
T
d
D
ii) For 'horizontal' runs of flue
pipe the holes must either be oversized or cut at a 5 (the latter may be difficult on
o
slope
L
long holes).
u
3.4.2 Oversizing
For every 1m length of run, L, the minimum diameter of the horizontal hole, D, must be du + 10 mm or ds + 10 mm respectively, assuming the pipe touches the wall at points T otherwise D will have to be increased by clearance from T. See Section 3.4.3 - Examples.
3.4.3 Examples
a. Wall Depth L = 750 mm
Unsocketted pipe du = 56 mm Diameter hole D = 56+{(
b. Wall depth L = 2.3 m
Socketed Pipe ds = 65 mm Diameter Hole D = 65+{2.3x10}
Installation & Servicing Instructions
Flue Pipe
750
= 56+7.5 = 63.5 mm
= 65+23
/
1000
d
)x10}
s
Page : 17
Page 21
WD51/2/1997 Chapter 3 : Installation
c. Measure, cut and check the air and flue pipes to pass to the exit from the
wall(s) or ceiling.
Always thoroughly deburr all pipes and, most important, remove shavings from within the pipe.
d. Assemble, using adhesive, the pipework from the boiler connections to
the exit from the first wall/ceiling (remount the boiler if removed). When pushing pipe through walls, ensure grit and dust is not allowed to enter the pipe. Ensure pipes are fully engaged into sockets. Connect the condensate drainage system and fill the condensate trap by pouring water down the boiler flue spigot ( See Section 3.5 Condensate Drainage). Make the final connection of flue and air pipe to the boiler using push on, or plastic compression couplings. Ensure that the connectors are set vertically otherwise leakage of condensate may occur which will corrode the casing. Do not use adhesive on the 'push on' end of the connecting couplings.
= 88 mm
The Keston 170 Condensing Boiler
Fully Engaged
Adhesive
e. Using the same methods drill any
further holes (always covering existing pipework), cut and assemble the pipework.
f. From outside, complete the two terminations - See Section 2.8 Flue
System and make good all holes.
g. Support any pipes whose route could be displaced either of its own
accord or by accident. Any horizontal run over 1m or vertical runs of any length must always be supported. Brackets should be placed at intervals of approximately 1m.
h. Check all connections for security and re-seal any joints using sovent
cement where soundness may be in doubt. Note: It is equally important to seal the air inlet with solvent cement as
the flue outlet pipe joints.
3.5 CONDENSATE DRAINAGE
Connect the condensate drainage system to the boiler. It is advisable to use a detachable fitting at connection to the boiler to enable easy removal for servicing.
Fill the condensate trap by pouring water into the boiler flue spigot until water is seen to flow freely from the condensate drainage system. Make the final connection of flue pipe to the boiler using the push on coupling supplied.
FA
Details are provided in Chapter 2 - Section 2.11 Condensate Drainage Connection : 22 mm plastic pipe.
Installation & Servicing Instructions
Page : 18
Page 22
WD51/2/1997 Chapter 3 : Installation The Keston 170 Condensing Boiler
3.6 WATER SYSTEM
Connect the flow and return pipework to the boiler. Ensure a detachable coupling is used at connection to the boiler (ie compression fitting) to enable heat exchanger removal if required. Details of system requirements are given in Chapter 2 - Section 2.7 Water Systems.
Connections: 35 mm compression X 35 mm compression.
3.7 GAS SUPPLY
Connect the gas supply to the appliance. Details of gas supply requirements are given in Chapter 2 - Section 2.6 Gas Supply. Supply of adequate gas pressure (with the boiler running) is critical to ensure reliable operation of the boiler.
Connections: 0.75 inch BSP male.
3.8 ELECTRICAL SUPPLY
The entry point for the electrical supply cable is in the base of the appliance (see Section
2.2 Service Connections fig. 2.1.2) via a cordgrip bush. Feed the cable through this bush and route inside the cabinet to the connection strip located to the front bottom right of the cabinet.
1. The electrical supply must be as specified in Chapter 2 - Section 2.4 Electrical Supply.
WARNING : THIS APPLIANCE MUST BE EARTHED.
2. All external controls and wiring must be suitable for mains voltage. Wiring should be in 3 core PVC insulated cable not less than 24/0.2 mm (0.75mm) to BS 6500 Table 16.
3. The supply connection may be via a 10 amp fused double pole switch, serving only the boiler and system controls. (Refer to Chapter 2 - Section 2.4 Electrical Supply).
4. Securely tighten the terminal screws and route the cable through the re-openable cable clips. Ensure all cables are secured and that the cord grip bush is tightened to securely grip the main cable at entry to the cabinet.
The mains cable must be connected to the terminals as follows:-
N - Blue wire (Neutral) L - Brown wire (Live)
- Yellow/Green Wire (Earth)
Ensure connection is made such that if the cable slips in its anchorage the current carrying conductors become taut before the earthing conductor.
Installation & Servicing Instructions
Page : 19
Page 23
WD51/2/1997 Chapter 3 : Installation
3.9 EXCHANGING A BOILER
Before removing an existing boiler add Fernox Supafloc , or equivalent cleaning agent, in accordance with the manufacturers instructions. Open all radiator valves and fire the boiler. When the system is fully heated, shut off the gas supply and drain down the central heating system.
Important The Keston condensing boiler contains components which could be damaged or blocked by grease, dirt or solder etc. It is essential that sludge or scale is removed from an existing system. As a safety precaution it is advisable to fit an 'in line' strainer before the boiler. The guarantee provided with the Keston 170 does not cover damage caused by system debris or sludge.
Connect the new boiler as instructed in this manual and fit in accordance with Sections
3.1 to 3.8 For sealed systems, fill to a pressure of about 2.7 bar. Check the complete system for
water soundness. If leaks need to be rectified using flux or solder the system must be flushed cold again before proceeding.
Reduce the pressure to the Initial System Design Pressure for sealed systems, if applicable. Vent the system.
The Keston 170 Condensing Boiler
Gas Supply
The complete gas installation up to the boiler service cock must be checked for soundness. BS 6891.
Electrical Installation
Carry out preliminary electrical safety checks, i.e. Earth continuity, Polarity, Resistance to Earth, Short Circuit using a suitable test meter.
Initial Firing
The gas pressure setting is factory adjusted to within the required range and should not normally need re-adjustment.
GAS VALVE
If the reading is incorrect then check such factors as soundness of the air and flue pipe joints, pressure sensible joints and the gas inlet pressure (20 mbar required). If all joints are sound and the gas inlet pressure is satisfactory set the gas pressure to the required
Burner pressure Adjustment
pressure. Full details of this procedure are given in Section
4.7. This will ensure that
Burner pressure test nipple.
combustion is good enough to allow combustion fine tuning to take place.
Combustion Fine Tuning
It is advisable on all carbon dioxide (CO
installations that the combustion quality is checked by measuring the
), or oxygen (O2), level. This procedure is detailed in Section 4.9
2
Combustion Fine Tuning. Badly tuned combustion will lead to reduce the life of the boiler and invalidate the warranty.
Installation & Servicing Instructions
Page : 20
Page 24
WD51/0/1997 Chapter 4 : Commissioning The Keston 170 Condensing Boiler
4. COMMISSIONING OF THE BOILER
Important: This condensing boiler c ontains components which could be dam aged or block ed by grease, dirt, solder etc., from the water system. The following commissioning procedures must be followed precisely.
4.1 INITIAL FLUSHING
All waterways within the Keston are either copper or high alloy stainless steel. As a result standard water treatment chemicals for conventional central heating boilers are suitable. In any event reference must be made to BS 7593 : Treatment Of Water In Hot Water Central Heating Systems.
a. Disconnect the boiler from the system at the flow and return connections and
temporarily
b. Flush the entire system until clean water is discharged, free from dirt, flux, solder
etc. The use of a flushing chemical is recommended, e.g. Fernox Supafloc. Sludge and scale must be removed from an existing system. Boiler failure due to
system debris or sludge shall invalidate the guarantee.
link the flow and return pipes on the system.
c. Connect the system to the boiler and fill in accordance with Section 2.7 - Water
Systems. At this stage, for sealed systems, fill to a pressure of about 2.7 bar.
d. Check the complete system for water soundness. If leaks need to be rectified
using flux and solder, the system must be flushed cold again before proceeding.
e. Reduce the pressure to the Initial System Design Pressure for sealed systems, if
applicable. Vent the system
4.2 GAS SUPPLY
The complete gas installation up to the boiler service cock must be checked for soundness. BS 6891.
4.3 ELECTRICAL INSTALLATION
Carry out preliminary electrical safety checks, i.e. Earth continuity, Polarity, Resistance to Earth, Short Circuit using a suitable test meter.
4.4 LP GAS CONVERSION
All Keston condensing boilers are built and shipped as natural gas fired units. Field conversion kits are available to convert Keston condensing boilers to use LPG. Suitable instructions are supplied with the LPG field conversion kits.
4.5 INITIAL FIRING
Important Checking the gas pressure to the pre-mix burner requires a special procedure, outlined below, which must be carried out.
a. Purge the gas supply in accordance with BS 6891. b. Turn the gas service cock OFF
Installation & Servicing Instructions Page : 21
.
Page 25
WD51/0/1997 Chapter 4 : Commissioning The Keston 170 Condensing Boiler
c. Loosen the screw in the burner pressure test point (Figure 5.7.3 item 105) on the
gas valve and attach a suitable gauge. d. Turn on the electrical supply, setting any external controls to call for heat. e. ON/OFF switch - select 'ON'. The amber light will illuminate on the ON/OFF
switch, the red 'lockout' light will illuminate, the blower and pump will start and,
after about 15 seconds, a spark will attempt to light gas at the burner for
approximately 10 seconds. With the gas service cock off, the boiler will go to
lockout - red light still illuminated, but the blower and pump will continue to run. At
intervals of approximately 1 minute the boiler will make two further attempts to
fire. After the final attempt the blower will run for a further 20 seconds before
shutting down. f. Vent the water system.
Important:
Keston heat exchanger consists of a single coil which can trap an air pocket.
The
Great care must be taken to ensure that water flow has been established through
the heat exchanger and thus ensuring no air pockets remain in the heat
exchanger and pipe work. Firing the boiler while an air pocket exists in the heat
exchanger could damage it.
g. Note the reading on the pressure gauge caused by the suction of the blower. This
should be approximately minus 30 mbar. If it is not, check the system as follows:
If the negative pressure exceeds 30 mbar, then it suggests that there is a possible restriction in the air inlet pipework.
If the negative pressure is less than 30 mbar, then it suggests that there is a possible restriction in the flue outlet pipework. Note the exact reading.
h. Turn the gas service cock to ON. i. Turn off the electricity supply, wait 10 seconds and turn back on. The boiler will
again go through its ignition sequence but this time the main burner will light,
provided all air has been purged from the gas supply to the boiler. When the
burner is lit and the boiler is operating normally the green (run) lamp, the upper
lamp adjacent to the flame symbol, will also be illuminated indicating successful
ignition (If it does not and the green lamp is extinguished after 10 seconds, air is
indicated - turn off and repeat the procedure).
If ignition does not occur, the green (run) lamp, the upper lamp adjacent to the
flame symbol, will be extinguished and, at approximately 1 minute intervals, the
electronic ignition system will make two further attempts to light the burner.
If the ignition is successful and the boiler is operating normally, the green (run)
lamp, the upper lamp adjacent to the flame symbol, and the red (lockout) lamp will
be illuminated simultaneously.
If after three automatic attempts the boiler still fails to ignite, the green (run) lamp,
the upper lamp adjacent to the flame symbol, will be extinguished and the red
(lockout) lamp will remain illuminated.
If, after five manual attempts (to allow for purging of any air in the gas line), the
boiler still fails to ignite (indicated by the red (lockout) lamp) refer to Section 5.2 -
Fault Finding Flow Chart. j. Check for gas soundness between the gas service cock and connection to the
burner manifold.
Installation & Servicing Instructions Page : 22
Page 26
WD51/0/1997 Chapter 4 : Commissioning The Keston 170 Condensing Boiler
4.6 HOT FLUSHING
a. Allow the system to heat up, checking for water soundness. b. Follow instructions provided with the cleaning agent, ie Fernox Supafloc. Turn off
the boiler and flush the water system while still hot. Thoroughly flush the system with clear water.
c. Refill the system using a quality water treatment such as Fernox CP3. For sealed
systems, fill to the required Initial Design Pressure.
4.7 CHECKING THE GAS PRESSURE
With the boiler running measure the burner pressure at the burner pressure test nipple.
The gas setting is factory adjusted to within the required range and should not normally need re-adjustment unless the unit has also been converted to LPG as part of the installation. If the reading is incorrect then check such factors as soundness of the air and flue pipe joints and the gas inlet pressure (20 mbar required). If all joints are sound and the gas inlet pressure is satisfactory remove the brass dust cap covering the burner pressure adjustment screw on the gas valve (See fig. 4.7). Set the gas pressure to the required value as stated in table 4.7 by turning the exposed burner pressure adjustment screw (clockwise will increase burner pressure, anti-clockwise will decrease burner pressure).. This will ensure that combustion is good enough to allow combustion fine tuning to take place. Replace the brass dust cap to cover the burner pressure adjustment screw.
4.8 TIMING THE GAS METER - NATURAL GAS
After the boiler has been started, and with no other appliances using gas, time the gas meter to be certain that the unit is running at the proper gas input. Determine the cubic feet of gas passing through the meter and determine the input in Btu per hour. Input must be within plus or minus 3% of the rated input.
Fig 4.7 GAS VALVE
Burner pressure Adjustment
Burner pressure test nipple.
Time, in seconds, the time taken to pass 2 cubic feet of gas through the meter (ie one revolution of a 2 cu ft dial) or 0.1 cubic metres if the meter is of the new metric digital type. The Keston 170, when correctly set, should take 39.8 seconds for 2 cubic feet of natural gas and 70.3 seconds for 0.1 cubic metres of natural gas (assuming 1038 btu/h per cubic foot). Adjust the gas valve screw clockwise to increase the input (speed up the meter) or anticlockwise to decrease the input (slow down the meter) accordingly.
4.9 COMBUSTION FINE TUNING
Although the gas pressure is preset at the factory differing flue arrangements may require fine tuning of the gas pressures to produce the best combustion and ensure long burner life. It is advisable to check proper combustion by measuring gas input and the level of carbon dioxide, or oxygen, in the flue outlet from the boiler. Overfiring or underfiring the burner will reduce the longevity of the appliance.
Installation & Servicing Instructions Page : 23
Page 27
WD51/0/1997 Chapter 4 : Commissioning The Keston 170 Condensing Boiler
Carbon dioxide is a colourless, odourless gas produced by all combustion processes. When the Keston condensing boiler is operating properly carbon dioxide (CO
be between 8.2 and 8.9% CO
for natural gas.
2
) levels will
2
To measure CO
levels in the Keston boiler remove the 1/8" plug from the flue outlet pipe
2
inside the boiler (Figure 5.7.2 item 69). Insert the probe of a combustion analysis meter and sample the gases as instructed in the test equipment's instructions.
If the CO
levels need raising increase the gas output by turning the brass screw, under
2
the metal cap in the front of the gas valve, clockwise. Reduce CO screw anti-clockwise.
levels do not respond to adjustments the burner is probably running with too much
If CO
2
gas pressure. If, for instance, a clockwise adjustment to the brass screw in the gas valve produces a decrease in CO
the burner is too fuel-rich and not enough oxygen is present
2
for proper and complete combustion.
4.10 HANDING OVER TO THE USER
It is important to fully explain the following : a. Procedure to light and turn off the boiler, including isolation of the electrical supply
if necessary. b. The function of the lockout feature must be explained :
If the red light only is illuminated for more than four minutes, this means that the
boiler has failed to light. Turn off the electrical supply and wait 20 seconds. Turn
ON again and wait.
i) If lockout recurs immediately then the gas supply should be checked as
ON, otherwise consult a Service Engineer.
ii) If it is not possible to relight, the boiler must be isolated and a Service
Engineer called in to rectify the fault.
c. Advise that a reduction in the water pressure reading on the gauge, for sealed
systems, indicates a leak which should be rectified before further use. d. Advise that the appliance should be serviced by a competent person at least once
a year. e. Advise on frost precautions.
f. Hand over User Instructions.
levels by turning this
2
Installation & Servicing Instructions Page : 24
Page 28
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
5. FAULT FINDING
5.1 ELECTRICAL CONTROL SEQUENCE
When the external controls are calling for heat, power will be fed to the boiler connection strip at terminals L (Live) and N (Neutral). If the ON/OFF switch is also in the ON position the boiler ON lamp (amber) will be illuminated. Provided all temperature thermostats and pressure switches are closed, power will be fed to pins 1 & 2 on the control box, initiating the following sequence.
(1) The boiler lockout lamp (red) will be illuminated (2) The fan will start. (3) When the fan reaches running speed, the Air Pressure switch, normally open, will
close which will start the ignition sequence.
(4) After a pre-purge period of about 15 seconds, the gas valve will open to allow gas
to mix with the air at the suction side of the fan and the ignition spark will occur at the main burner.
(5) When the burner ignites, the flame is detected by the control box through the
combined flame sensor/ignitor and the ignition spark is stopped. Both the lockout lamp (red) and the boiler run lamp (green), the upper lamp adjacent to the flame symbol, will be illuminated. The boiler is now in its normal run condition.
(6) The burner will continue to operate until the gas valve interrupts the gas supply.
The gas valve will be closed by the control box if power is interrupted to the boiler by any external control or the boiler thermostat. If an interruption to the gas supply causes loss of the flame, the control box will pause for approximately 10 seconds and then attempt to re-ignite the unit. If this attempt fails, i.e. due to continued lack of gas supply, the boiler will make two further attempts to ignite at intervals of approximately 1 minute and will then go to a lockout state (red lamp illuminated only). Once the gas supply has been resumed the boiler can be reset by turning the boiler off and then on again on the boiler control panel.
(7) The boiler can also be shut down by any of the flow limit, flow overheat and the
flue overheat thermostats, gas low pressure switch and by the low water pressure switch.
In such an event the green (run) lamp, the upper lamp adjacent to the flame symbol, will be extinguished and only the red (lockout) lamp will be illuminated.
Any failure of the boiler to sequence in the above manner should be investigated using the following trouble shooting flow diagram.
Before attempting any electrical fault finding, always carry out preliminary electrical system checks. On completion of any service/fault finding task which has required the breaking and remaking of electrical connections, the checks, earth continuity, polarity, short circuit, resistance to earth must be repeated.
Installation & Servicing Instructions Page : 25
Page 29
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
5.2 FAULT FINDING FLOW CHART
yes
yes
START
Is amber switch light on?
no
Is there 230V between
terminals SL & N?
yes
Is the boiler switched on?
yes
Faulty Switch Neon
-Replace .
Is the fan running?
no
Is the boiler thermostat closed?
yes
Is there 230V between control
box pins 10 & 2 and between
pins 10 and 1?
yes
Is the air pres sure swi tch st uck
in the NO position?
no
Is there 230V between control
box pins 6 & neutral?
no
no
no
no
yes
no
Apply Power To Boiler.
Check External Controls.
Switch On Boi ler.
Boiler return is too hot. Allow
to cool. OR faulty thermostat -
Check continuity (see section
Faulty pipe connections to Air
Press. Switch. OR Faulty Air
Replce.
5.3)
Press. Switch - Replace.
Control box faulty.
yes
Is the motor relay operating?
yes
Is there continuity between live
supply from relay to blower &
Neutral through motor
resistance?
no
Is motor overload tripped?
no
Is there wiring continuity
& in-line connector
to motor?
Continued on sheet 2
Installation & Servicing Instructions
no
yes
yes
no
Relay not sec ure in so cket or
relay faulty - replace
Motor/Fan faulty - Replace.
Wait for motor to cool.
Identify & correct break.
Page : 26
Page 30
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
Continued from sheet 1
Does ignition sequence start?
yes
no
Is lockout light on?
yes
Has the Air Press. Switch
changed over?
no
Are tubes and connections to the Air Press. Switch sound?
yes
no
yes
no
Switch off & if problem persists
replace control box.
Blocked air filter - replace
OR
Faulty control box - r eplace
Correct tube connection
yes
Is the air press. across the Air
Press. Switch more than 4 in
water?
no
Is the air filter dirty or the air
inlet, exhaust or condensate
pipe blocked?
no
Is the B ur ner bl ock ed
no
Fan faulty - change
Is the gas flow rate to the boiler correct
for the gas type in use (ie LPG or Nat.
Gas)?
no
Is gas supply pressure at gas
valve correct?
yes
Is gas burner pressure per
specification (Secti on 4.7)?
yes
yes
yes
no
yes
Faulty pressure switch -
replace
Replace air filter
OR
clear blockage
Clear blockage
Check gas supply or turn on
gas cock.
Replace gas orifice.
no
Is gas valve opening?
no
Faulty gas valve - replace.
yes
Continued on sheet 3
From sheet 3
Installation & Servicing Instructions Page : 27
Page 31
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
Continued from Sheet 2
Is there 230V at valve
Is there 230V at Gas Low
Press. Sw itch
Faulty Control Box - Replace.
Is there a spark present?
yes
Is the HT voltage present at
top of ignition electrode?
Is the spark gap 4 mm?
no
no
no
yes
yes
yes
no
no
Continued on sheet 2
Faulty Gas Valve - Replace.
Faulty Gas Low Pressure
Switch - Replace
Faulty Conrtrol Box - Replace.
Replace/Adjust Spark Plug.
Electrode Faulty - Replace.
Does the burner ignite?
yes
Recheck gas output pressure.
Check HT lead is securely
fixed. Clean or replace burner.
Does flame stop after 5 - 10
seconds?
Is boiler earthed correctly?
Are live and neutral supply
lines crossed at terminals L &
N?
yes
no
yes
yes
no
no
yes
Earth Boiler.
Correct Wiring.
Faulty Control Box - Replace.
Installation & Servicing Instructions
Page : 28
Page 32
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
5.3 CONTINUITY CHECKING
To check continuity connect one probe to a neutral and use the other probe to check for 230V.
START
Is there 230V at terminal L?
yes
Is there 230V at the ON/OFF
switch (both terminals)?
yes
Is there 230V at the boiler
thermostat (both terminals)?
yes
Is there 230V at the flow
overheat thermostat (both
terminals)?
yes
Is there 230V at the thermal
fuse link (both terminals)?
yes
no
no
no
no
no
Check external controls.
Faulty switch - Rep lace.
Boiler is up to temperature.
Allow to cool OR pump not
running OR faulty thermostat -
Thermostat tripped - reset OR
faulty thermostat - Replace.
High cabinet temperature -
chec k all jo ints for pr odu cts
leakage - Replace thermal fuse
Replace
Is there 230V at the flow high
limit th ermo stat (bo th
terminals)?
no
High water temperature OR faulty thermostat - Replace.
yes
Is there 230V at the water
press. switch (both terminals)?
no
Check water level header
tank/system pressure OR faulty
switch - Replace
yes
Is there 230V at the flue
protection thermostat (both
terminals)?
no
Thermostat tripped - reset OR
faulty thermostat - Replace.
yes
Is there 230V at the gas low
press. switch (both terminals)?
no
Check gas supply to boiler OR
faulty switch - Replace.
Installation & Servicing Instructions Page : 29
Page 33
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
5.4 FUNCTIONAL FLOW WIRING DIAGRAM
PL SL
EMC Filter
2
5
10
1 4 6
8
Pump L Pump N
N
EMC Filter
Installation & Servicing Instructions
Page : 30
Page 34
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
5.5 ELECTRICAL WIRING DIAGRAM
LEGEND
B -BLUE BK -BLACK OR -ORANGE R -RED PK -PINK W -WHIT E G -GREEN BR -BROWN V -VIOLET Y/G-GREEN-YELLOW
FLUE OVERHEAT THERMOSTAT
WATER PRESSURE
SWITCH
FLOW HIGH LIMIT THERMOSTAT
THERMAL FUSE
FLOW OVERHEAT THERMOSTAT
54G53W56R
52BK51PK
BOILER
THERMOSTAT
RED
LAMP
90R
5R
HV
13 121110
55BR
GREEN
LAMP
12V
RAM-2EMC22 IGNITION CONTROL
9 8 7 6 5 4 3 2 1
G/Y
91OR
ON/OFF SWITCH
10BK
GAS LOW PRESSURE SWITCH
59PK
92OR
93OR
mp
GAS
VALVE
95G
93R
no
nc
APS
12V
12
11W
11
10BK
10
9G
8W 7W
6B
5BR
4B
3BR
1BR
EMC FILTER
APS-AIR PRESSURE L -INCOMING N -INCOMING
-INCOMING
15BR
14B
SWITCH LIVE NEUTRAL EARTH
PUMP
15 14
L
N
13
6BR
1BR 12
8
3 4
67
12B
RELAY
BLOWER
9 8
W
7
6B
6
5BR
5
N
4 3
SL
2
PL
1
BR
Installation & Servicing Instructions Page : 31
Page 35
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
5.6 ILLUSTRATED WIRING DIAGRAM
ILLUSTRATED WIRING DIAGRAM
Boiler Stat
7W
Low Water Pressure Switch
Ignition Electrode
5R
Flue Overheat Stat
8W
Flow Overheat Stat
51PK
52BK
Flow High
Limit Stat
54G
91OR
Thermal Fuse
56R
53W
Gas Low Pressure Switch
Gas Valve
G/Y
93OR
11W
92OR
RAM Control
1 2 3 4 5 6 7
G/Y
8 9 10
10BK
55BR
Air Pressure Switch
G/Y
8W
95G
93R
PUMP
L
15
N
14 13
59PK
W
room
( )
stat
6BR 5BR
4B
3BR
5R
ON/OFF
SWITCH
12V
9G
N SL
PL
8W
7W 6B
12 11
10
9 8
7 6 5 4 3 2 1
FILTER
Installation & Servicing Instructions
10BK
Lockout
Lamp
Run
Lamp
BR
91OR
90R
Blower
Page : 32
12B
B
6BR
Relay
BR
B
G/Y
Page 36
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
5.7 Exploded Assembly Diagrams
5.7.1 Boiler Controls Asembly
SCREW
154
106
PACTROL RAM
156 122
PACTROL RAM
124
123
04.1.00.78.0
IGNITION CONTROL
04.4.01.00.0
04.4.01.00.1
SCREW
04.1.00.84.0
IGNITION CABLE
04.4.11.00.0
04.4.11.00.1
RELAY SOCKET
17.4.04.00.0
RELAY
17.4.03.00.0
158
1
TR2 THERMOSTAT
17.4.11.00.0 OPTIONAL
SECTION 1
BOILER CONTROLS
K170 - 17.4.00.00.0
FUSE ISOLATOR
145
04.4.20.00.0
FUSE SOCKET
112
04.4.19.00.0
RELAY CLAMP
105
17.4.00.02.0
SCREW
125
17.4.00.01.0
AIR PRESSURE
109
04.4.04.00.1
BLUE/WH.
SCREW
13
04.1.00.40.0
117
PACTROL
17.4.10.00.0
13.4.10.00.2
RAM
SUPRESSOR FILTER
144
04.4.02.00.0
SECTION 1
13
SEALING GASKET
121
04.4.00.04.0
SECTION 1
3
ON/OFF SWITCH
113
04.4.06.00.0
SWITCH
HARNESS
MAINS
13
107
THERMAL FUSE
04.4.18.00.0
108
8
148
162
111
110
162
119
116
SCREW
04.4.00.06.0
SECTION 1
TERMINAL BLOCK
13.4.00.10.0
TERMINAL BLOCK
04.4.05.00.0
TERMINAL BLOCK
BASE LABEL
13.4.00.03.1
SCREW
04.4.00.10.0
NEON BULB
04.4.12.00.0
GAUGE
04.4.09.00.0
r
a
115
RED LAMP
04.4.08.00.0
O
I
b
114
GREEN LAMP
04.4.07.00.0
Installation & Servicing Instructions Page : 33
Page 37
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
5.7.2 Waterway, Condensate & Flue Assembly
SCREW
51
50
49
53
52
47
48
46
45
HIGH VOLTAGE
44
HEAT EXCHANGER INSULATION
43
17.2.03.00.1
04.1.00.80.1
IGNITER
04.2.13.00.1
IGNITER GA SKET
04.2.00.28.2
PRESS. TEST FITT.
04.2.28.00.0
SCREW
04.2.00.29.1
MANIFOLD
17.2.00.27.2
SIGHT GLASS
04.2.12.00.1
GASKET
17.2.00.01.2
BURNER
17.2.04.00.0
LABEL
04.2.00.58.0
55
GASKET
17.2.00.05.2
82
SECTION 3
56
SCREW
04.1.00.79.1
65
69
67
81
WATER WAY, CONDENSATE & FLUE ASSEMBLY
K170 - 17.2.00.00.0
EXHAUST PIPE
17.2.06.00.0
COMBUSTION TEST PLUG
04.2.00.49.1
FLUE OVERHEAT THERMOSTAT
04.2.19.00.0
SCREW
04.1.00.41.3
160
70
54
72
35 WATER FLOW
FLOW HIGH LIMIT
PIPE
17.2.00.22.0
IMIT SHEATH
17.2.00.57.0
WATER OUT
MANIFOLD
17.2.00.24.1
THERMOSTAT
04.2.22.00.0
HEAT EXCHANGER
42
17.2.01.00.2
61
75
60
WATER RETU RN
MANIFOLD
17.2.00.23.0
GASKET
04.2.00.54.0
DRAIN VALVE
04.2.16.00.0
WATER RETURN THERMOSTAT
63
04.2.17.00.0
SCREW
14
04.1.00.41.0
35 WATER RE T URN
59
17.2.00.06.0
PIPE
CONDENSATE
57
TRAP HOSE
04.2.00.58.0
SEEGER RING
74
04.2.00.53.0
CONDENSATE TRAP
58
04.2.14.00.1
CONDENSATE HOSE
68
04.2.00.59.0
HOSE CLAMP
64
04.2.00.57.0
14
71
154
73
WATER FLOW OUT
THERMOSTAT
04.2.21.00.0
SCREW
04.1.00.78.0
WATER PRESS URE
SWITCH
04.2.23.00.0
Installation & Servicing Instructions
Page : 34
Page 38
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
5.7.3 Air - Gas Assembly
GAS TEE
100
04.3.00.34.1
PRESSURE SWITCH
101
04.3.09.00.0
REGULATOR GAS VALVE
91
04.3.07.00.0
MAIN SOLENOID
149
04.3.07.01.0
CONNECTOR BLOCK
150
04.3.07.02.0
AIR ADJ. SCREW
103
17.3.10.00.0
AIR ORIFFICE SCREW
84
04.3.00.40.0
SECONDARY SOLENOID
157
04.3.07.03.0
GASKET
90
17.3.00.06.0
AIR/GAS
FLEXIBLE TUBE
82
17.3.05.00.1
LOW GAS
53
88
AIR/GAS
89
17.3.00.05.1
17.3.00.03.0-NG
87
17.3.00.03.1-LPG
PRESS. TEST FITT.
04.2.28.00.0
53
GASKET
17.3.00.04.1
MANIFOLD PLUG
GAS ORIFICE
90
94
SCREW
04.3.00.28.0
104
AIR-GAS ASSEMBLY
K170 - 17.3.00.00.0
AIR HOSE CLAMP
92
17.3.00.07.0
AIR INLET FLEX. CONNECTOR
85
17.3.00.02.0
GAS INLET
FLEXIBLE TUBE
93
17.3.07.00.5
AIR ORIFICE
17.3.00.01.0-NG
131
17.3.00.01.1-LPG
GAS INLET GASKET
95
17.3.00.08.0
NUT
96
17.3.00.09.0
HIGH PRESS. TUBE
98
04.3.00.32.0
LOW PRESS. TUBE
97
04.3.00.31.0
155
102
104
79
78
80
SCREW
04.1.00.81.0
SEALING GASKET
04.1.00.38.0
GASKET
17.2.00.05.0
CAPACITOR
17.3.02.00.0
BLOWER
17.3.01.00.0
BLOWER
RUBBER ISOLATOR
04.3.04.00.0
17
SCREW
04.1.00.76.0
1
SECTION 1
SCREW
52
04.2.00.29.0
AIR/GAS
MANIFOLD
83
17.3.06.00.0
GAS VALVE SCREW
86
04.3.00.16.0
Installation & Servicing Instructions Page : 35
Page 39
WD51/2/1997 Chapter 5 : Fault FindingThe Keston 170 Condensing Boiler
5.7.4 Casing Assembly
GAS VALVE
38
17.1.13.00.0
EXHAUST TERMINAL
39
17.1.16.00.0
BRACKET
9
04.1.00.35.0
SILENCER
37
17.1.11.00.1
FRONT DOOR
4
17.1.06.00.0
ILLUSTRATED WIRING DIAGRAM
29
13.1.00.07.1
13
21
26
28
17
SCREW
04.1.00.40.0
35mm GROMMET
17.1.00.05.0
FLOW LABEL
04.1.00.53.1
WARNING LABEL
04.1.00.55.0
SCREW
04.1.00.76.0
14
SCREW
04.1.00.41.0
BURNER ACCESS COVER
6
17.1.00.01.0
20
56mm GROMMET
17.1.00.04.0 EXHAUST FLUE LABEL
25
04.1.00.52.0
CASING ASSEMBLY
K170 - 17.1.00.00.0
TOP COVER
17.1.04.00.0
242
36
40
19
5
41
34
23
16
AIR INLET LABEL
04.1.00.51.0
NEG. PR. ADAPT.
04.1.00.62.0
HINDER CLAMP
17.1.00.03.2
AIR FILTER
17.1.12.00.0
AIR FILTER COVER
17.1.07.00.0
SHUTTING CLAMP
17.1.09.00.0
CABLE HOLDERS
04.1.00.61.0
NAME PLATE
17.1.00.06.1
WASHER
04.1.00.43.0
7
27
11
153
33
3
HEAT EXCHANGER FIXING ROD
17.1.00.02.1
RETURN LABEL
04.1.00.54.1
SPRING CLAMP
17.1.00.30.0
SCREW
04.1.00.77.0
FLAME LABEL
04.1.00.60.0
DEVICE BOX
17.1.00.19.0
62
10
SWITCH
17.1.00.29.1
15
16
KESTON LABEL
30
K
E
S
T
O
N
17.1.00.72.0
14
62
FIXING NUT
17.1.00.32.0
35
ELECTRIC MA IN WIRE RETAINER
04.1.16.00.0
PLASTIC PLUG
66
04.1.00.75.0
18
15
8
31
1
32
22
EARTHING LOCKWASHER
04.1.00.45.0
NUT
04.1.00.42.0
CONTROLS PLATE
17.1.00.18.3
TEST POINT LABEL
04.1.00.58.0
OUTER SHELL
17.1.03.00.0
GAS INLET LABEL
04.1.00.59.0
22mm GROMMET
04.1.00.49.0
Installation & Servicing Instructions
Page : 36
Page 40
WD51/2/1997 Chapter 5 : Fault Finding The Keston 170 Condensing Boiler
5.7.5 Exploded Diagrams Parts Reference List Boiler Controls Assembly (Fig. 5.7.1)
GC Number Code Description
E01 074 106 Ignition Control Box 170 084 109 Air Pressure Switch
114 076 111 Electrical Terminal Block 114 077 113 On/Off Switch 114 078 114 Green (Run) Lamp 114 079 115 Red (Lockout) Lamp 114 080 116 Pressure Gauge
Waterway, Condensate & Flue Assembly (Fig. 5.7.2) GC Number Code Description
114 115 42 Heat Exchanger 114 117 45 Burner
114 118 46 Burner Head Gasket 114 028 48 Sight Glass 375 527 49 Ignitor Gasket 114 120 50 Spark Ignition Electrode 114 029 53 Pressure Test Nipple 114 032 58 Condensate Trap 375 530 63 Boiler Thermostat 375 532 67 Flue Overheat Thermostat 114 043 69 Combustion Test Plug 375 533 71 Flow Overheat Thermostat 375 534 72 Flow High Limit Thermostat 114 045 73 Water Pressure Switch
Air - Gas Assembly (Fig. 5.7.3) GC Number Code Description
114 131 78 Combustion Blower 114 146 131 Air Orifice
375 536 91 Gas Valve 114 029 53 Pressure Test Nipple 114 073 101 Low Gas Pressure Switch
114 136 87 Gas Injector
Casing Assembly (Fig. 5.7.4) GC Number Code Description
114 095 1 Cabinet 114 108 23 Data Badge 114 099 5 Air Filter Cover 114 105 19 Air Filter 114 096 2 Cabinet Top Cover 114 100 6 Burner Access Cover Plate 114 109 29 Illustrated Wiring Diagram
114 098 4 Front Door
Installation & Servicing Instructions Page : 37
Page 41
WD51/2/1997 Chapter 6 : Servicing The Keston 170 Condensing Boiler
6. ROUTINE (ANNUAL) SERVICING
To ensure the continued safe and efficient operation of the boiler it is necessary to carry out routine servicing at regular intervals. The frequency of the servicing will depend upon the particular operating conditions, but it is recommended that an annual service should be carried out by a qualified engineer.
The appliance has an integral air filter, mounted at the top right hand side of the boiler, to which the air intake pipe is connected. This filter should be ex amined every time the boiler is servic ed. It may need more frequent inspection ac cording to the condition of the atm osphere in which the air intake terminates.
Note: The air filter can be easily blocked if the boiler is running on or near a building site having
an excess of airborne dust. It is essential, with a premix gas burner, that the air is clean and free of dust.
It is the law that any service work must be carried out by competent qualified persons.
6.1 Pre-Service Checks
It is recommended that an inspection should be carried out prior to shutting down the unit for servicing. Remove the front cover by removing the screws retaining the top of the door and lifting the cover from the base (Front cover located by two pegs). The following items should be observed:
a. Smooth starting and running of the blower. b. Smooth lighting of the burner. c. Check for leakage of gas, gas/air or combustion products. d. Check for condensate leaks. e. Check the colour and appearance of the flame. A sky blue flame slightly off the
burner gauze is normal. The burner itself should appear dark. Any glow on the burner indicates gauze blockage requiring cleaning, an incorrect gas flow or an air intake blockage.
f. Check that the temperature differential between the flow and return pipes is less
than 15
o
C. The temperature difference should be between 10oC and 15oC. g. Check for water soundness. h. Inspect the flue vent and air intake pipework. Joints must be sound and all
pipework well bracketed.
i. Check that there is a steady fall back to the boiler from the flue pipe to allow
condensate to run back into the boiler (See Section 2.8.3 Slope).
j. With the boiler operating at a low return temperature (i.e. less than 50
o
C) check
that the condensate flows freely from the condensate line.
6.1.1 Burner & Heat Exchanger Blockage Checks
i) Turn off the boiler & shut off the gas supply to the boiler. ii) Remove the pressure point screws from points A & B. Attach a differential
gauge.
iii) Turn on the boiler and wait for the fan to reach full speed. Obviously the
burner will not light.
iv) The pressure difference should be below 14 mbar. If not, clean the
burner.
v) Turn off the electrical supply to the boiler. vi) Remove the pressure point screw from point C and transfer the tube from
point A to C, replacing the screw on point A.
Installation & Servicing Instructions
Page : 38
Page 42
WD51/2/1997 Chapter 6 : Servicing The Keston 170 Condensing Boilers
Pressure Test Point B
Burner Heat (From Above)
Pressure Test Point A
Heat Exchanger Shell
Fig 6.1.1 Pressure Test Point Loc ations
vii) Turn on the electrical supply to the boiler (gas still off), wait for the fan to
reach full speed.
viii) The pressure difference should be below 17 mbar. If not, clean heat
exchanger.
Flue
Flue Overheat Thermostat
Combustion Test Point
&
Pressure Test
Point C
ix) Disconnect the gauge from point B. Refit the screw. x) Read pressure of point C. xi) The maximum pressure should be 3.5 mbar. If the pressure is greater
than this, check the flue for blockage. xii) Turn off the electrical supply to the boiler. xiii) Remove the pressure gauge tube and refit the screw. xiv) Open the gas service cock.
6.2 Recommended Routine Service
a. Inspect the air filter located at the top right hand side of the boiler. Release the
toggle catch on the filter tray and remove the filter. If the filter looks dirty remove the dirt with a vacuum cleaner or by other means. If
in any doubt renew the filter element.
b. Remove the burner head (Section 7.7) and inspect the burner appearance. Black
markings or other discolourations on the gauze indicate too much gas or a lack of air possibly due to a blocked air filter. Any breakages or damage to the burner mesh indicate the burner must be replaced.
c. If necessary, either due to discolouration or a high pressure differential between
points A & B in the pre-service checks, clean the burner with a mild detergent and rinse under a hot running tap.
Installation & Servicing Instructions Page : 39
household
Page 43
WD51/2/1997 Chapter 6 : Servicing The Keston 170 Condensing Boiler
d. If necessary, either from visual inspection or a high pressure differential between
points B & C in the pre-service checks, clean the heat exchanger using a suitable stiff plastic bristle brush, vacuum out any large particles and flush the heat exchanger with fresh water until the water flowing from the condensate drain is clear. When brushing the heat exchanger take care not to damage the condensing plug in the lower half of the heat exchanger.
e. Remove the condensate trap (Section 7.10) and clean by flushing through with
clean running water.
f. Check the electrode mounted on the burner head. If the point is damaged or
burnt replace it. Check that the spark gap measures 4 mm.
g. Replace the burner head, renewing the gasket if necessary, and reconnect the
gas/air supply and the ignition lead. Ensure the flanged gas/air supply joint is air tight.
h. Turn on the electrical supply to the boiler and allow the boiler to reach operating
temperature levels.
i. Visually inspect the burner through the glass spy hole at the burner head (a small
mirror will prove useful). j. Recheck the burner pressure by following the procedure detailed in Section 4.7 k. Remove the combustion test point plug from the flue pipe. This is situated around
150mm (6ins) from the bottom of the flue elbow at its connection to the heat
exchanger. l. Using an approved combustion tester sample the flue products via the
combustion test point. CO
levels of between 8.2% and 8.9%, for natural gas,
2
should be observed. If such levels are not observed tune the combustion as
described in Chapter 4 - Commissioning. Also check the gas flow as detailed in
Sections 4.8 and 4.9
m. Replace the combustion test point plug.
n. Check all joints for soundness up to the gas burner.
Installation & Servicing Instructions
Page : 40
Page 44
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
7. REPLACEMENT OF PARTS
INDEX
7.0 GENERAL
7.1 PRECAUTIONS
7.2 ACCESS
7.3 PROCEDURES - GENERAL
7.4 ELECTRICAL
7.4.1 ON/OFF SWITCH
7.4.2 BOILER THERMOSTAT
7.4.3 NEONS
7.4.4 FLOW OVERHEAT, FLOW HIGH LIMIT & FLUE PROTECTION THERMOMSTATS
7.4.5 WATER PRESSURE SWITCH
7.4.6 IGNITION CONTROL BOX
7.4.7 AIR PRESSURE SWITCH
7.4.8 COMBUSTION BLOWER
7.4.9 GAS CONTROL VALVE
7.4.10 GAS LOW PRESSURE SWITCH
7.5 GAS ORIFICE
7.6 SPARK IGNITION/FLAME DETECTION ELECTRODE
7.7 BURNER HEAD & BURNER
7.8 HEAT EXCHANGER
7.9 AIR FILTER
7.10 CONDENSATE TRAP
7.11 PRESSURE GAUGE
7.12 SIGHT GLASS
7.13 HT IGNITION LEAD
7.14 AIR ORIFICE
Installation & Servicing Instructions
Page : 41
Page 45
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
7.0 GENERAL
The following must always be carried out by a competent/qualified person.
7.1 PRECAUTIONS
i) Always switch off the mains electricity supply and disconnect the plug at the
isolating switch and socket. (If a switch only is used then remove the fuse.)
ii) Gain access to the appliance (Section 7.2) and turn off the gas supply at the
appliance service cock.
7.2 ACCESS
i) Remove the front door by removing the three screws to the front of the top panel.
The front panel may then be removed by tilting forward and lifting vertically to disengage the two locating studs in the base of the front panel.
ii) Access to the burner head can be gained by removing the access plate in the top
panel of the appliance.
iii) Access to the rear of the control panel and base of the unit can be gained by
removing the control panel at the bottom of the boiler. Remove the two screws to the control panel then gently pull the control panel free of the boiler casing. This is secured by three press studs on either side and a central press stud at the bottom of the control panel.
7.3 REPLACEMENT PROCEDURES
i) Always replace in the reverse order unless otherwise stated. ii) Electrical connections must be remade in accordance with the Wiring Diagram
(Section 5.5).
iii) Test the soundness of any gas carrying or water carrying joint broken during the
service procedures.
7.4 ELECTRICAL COMPONENTS
7.4.1 On/Off Switch (Fig. 5.7.1 item 113)
i) Isolate the appliance (Section 7.1) i) Gain access (Section 7.2) iii) Remove the push on connectors from the switch taking note of the
correct positions.
iv) Press in the catches and push the switch forwards through the control
panel. v) Reassemble (Section 7.3) v) Check for correct operation of the switch.
7.4.2 Boiler Thermostat (Fig. 5.7.2 item 63) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors from the thermostat taking note of the
correct positions.
iv) Unscrew the two retaining screws and remove the thermostat.
Installation & Servicing Instructions
Page : 42
Page 46
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
v) Reassemble (Section 7.3)
NB: When fitting the new thermostat it is an advantage to smear a
thin film of heat sink compound between the thermostat and plate. This, combined with fitting the new thermostat tightly to the plate, ensures a good contact.
7.4.3 Neons (Fig. 5.7.1 items 114 & 115) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors from the neon taking note of the correct
positions.
iv) Press in the catches and push the neon forward through the control
panel.
v) Pull the centre core of the neon from its housing to expose the bayonet
fitting bulb. vi) Reassemble (Section 7.3) vii) Check for correct operation of the neons.
7.4.4 Flow Overheat (Fig. 5.7.2 item 71) , Flow High Limit (Fig. 5.7.2 item 72) & Flue Protection Thermostats (Fig. 5.7.2 item 67)
i) Isolate the appliance (Section 7.1) ii) Gain access (Section 7.2) iii) Remove the push on connectors from the thermostat taking note of the
correct positions. iv) Unscrew the two retaining screws and remove the thermostat. v) Flue protection thermostat only
The thermostat seal is maintained via a small 'O' ring between thermostat
and flue pipe. If this is damaged on removal it must be replaced. vi) Reassemble (Section 7.3)
NB: When fitting the new thermostat it is an advantage to smear a
thin film of heat sink compound between the thermostat and plate. This, combined with fitting the new thermostat tightly to the plate, ensures a good contact.
7.4.5 Water Pressure Switch (Fig. 5.7.2 item 73) i) Isolate the appliance (Section 7.1)
ii) Shut off the water supply to the appliance. iii) Gain access (Section 7.2) iv) Drain the system to below the level of the appliance using the drain off
tap at the base of the heat exchanger.
v) Remove the push on connectors from the water pressure switch taking
note of the correct positions. vi) Unscrew the pressure switch. vii) Reassemble (Section 7.3).
NB: Use a little jointing compound or PTFE tape on the thread. viii) Refill the system (See Section 4 - Commissioning).
7.4.6 Ignition Control Box (Fig. 5.7.1 item 106) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the HT ignition lead. iv) Pull off the multi-pin connector away from the box.
v) Unscrew the two screws securing the control box to the casing and
remove the box.
Installation & Servicing Instructions
Page : 43
Page 47
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
vi) Reassemble (Section 7.3)
7.4.7 Air Pressure Switch (Fig. 5.7.1 item 109) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors from the air pressure switch taking note
of the correct positions.
iv) Disconnect the union to one plastic tube connection and pull off the
second plastic tube from the air pressure switch.
v) Unscrew the two screws mounting the air pressure switch body to the
boiler casing.
vi) Reassemble (Section 7.3)
NB: Ensure the yellow/green earth connection tag is securely fixed
behind the lower mounting screw.
7.4.8 Combustion Blower (Fig. 5.7.3 item 78) NB: This unit is heavy and must therefore be handled carefully when
replacing. i) Isolate the appliance (Section 7.1) ii) Gain access (Section 7.2) iii) Disconnect the wires connecting the blower to the relay (relay terminals
number 6 and 3) vi) Remove the allen screws fixing the air intake pipe flange and the gas/air
mixture pipe flange to the blower. v) Unscrew the three bolts fixing anti-vibration mounts to the combustion
blower through the base of the cabinet. vi) Reassemble (Section 7.3)
NB: When reassembling inspect any gaskets for damage and replace
if necessary.
vii) Reset the gas rate (See Section 4 - Commissioning)
7.4.9 Gas Control Valve (Fig. 5.7.3 item 91) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the cover concealing the electrical connections on the front of
the gas valve.
iv) Remove the push on connectors exposed taking note of the correct
positions.
v) Remove the push on connectors to the gas low pressure switch taking
note of the correct positions. vi) Remove the earth connection to the side of the gas valve. vii) Remove the plastic air tube to the base of the gas valve. viii) Remove the four allen screws securing the gas inlet flanged connections
to the gas control valve. ix) Undo the four bolts fixing the base of the gas control valve to the gas
outlet block. x) Remove the gas valve. xi) Unscrew the gas low pressure switch at its connection to the gas control
valve body. xii) Reassemble (Section 7.3) xiii) Reset the gas rate (See Section 4 - Commissioning)
7.4.10 Gas Low Pressure Switch (Fig. 5.7.3 item 101) i) Isolate the appliance (Section 7.1)
Installation & Servicing Instructions
Page : 44
Page 48
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
ii) Gain access (Section 7.2) iii) Remove the push on connectors to the gas low pressure switch taking
note of the correct positions. iv) Unscrew the gas low pressure switch from the brass holder. v) Reassemble (Section 7.3)
7.5 GAS ORIFICE (Fig 5.7.3 item 87) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Unscrew and remove the brass plug from the gas outlet block. iv) Remove the rubber seal from the injector housing. v) Insert a flat blade screwdriver into the exposed hole and unscrew the gas injector. vi) Check the injector is the correct size for the boiler size and fuel type.
vii) Reassemble (Section 7.3)
NB: Ensure that the injector is screwed fully home
viii) Reset the gas pressure (See Section 4 - Commissioning)
7.6 SPARK IGNITION/FLAME DETECTION ELECTRODE (Fig. 5.7.2 item 50) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the pull off HT lead to the spark ignition electrode. iv) Remove the burner head (Section 7.7 steps iv to vi). v) Undo the screws to the spark ignition electrode flange located on the burner
head and withdraw the spark ignition electrode.
vi) Reassemble (Section 7.3)
NB: When reassembling inspect the gasket for damage and replace if
necessary. With the new spark ignition electrode in place it is essential to ensure the gap between the tip of the electrode and the burner surface is 4 mm. Distance above or below 4 mm will affect the ignition performance. If necessary gently bend the electrode, taking care not to damage the ceramic insulator.
7.7 BURNER HEAD & BURNER (Fig. 5.7.2 items 47 & 45) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the pull off HT lead to the spark ignition/flame detection electrode head. iv) Remove the four screws retaining the access panel (Fig. 5.7.4 item 1) and
remove the access panel from the top of the cabinet.
iv) Remove the two allen screws fixing the flange gas/air mixture pipe connection to
the burner head.
v) Remove the five allen screws fixing the burner head to the top of the heat
exchanger.
vi) Withdraw the burner & burner head from the top of the heat exchanger through
the access panel opening in the top of the cabinet.
vii) Unscrew the burner from the burner head taking care not to damage the burner
mesh.
vi) Reassemble (Section 7.3)
NB: When reassembling inspect any gaskets for damage and replace if
necessary. Set the spark gas as detailed in Section 7.6
vii) Reset the gas rate (see Section 4 - Commissioning)
Installation & Servicing Instructions
Page : 45
Page 49
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
7.8 HEAT EXCHANGER (Fig. 5.7.2 item 42) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Shut of the water supply to the appliance. iv) Remove the burner head (Section 7.7) v) Drain the system to below the level of the appliance using the drain off tap at the
base of the heat exchanger. vi) Remove the front control panel (Section 7.2 (iii)) vii) Remove the boiler thermostat (Section 7.4.2) viii) Remove the push on connectors to the water pressure switch, flow overheat
thermostat, flow high limit thermostat and flue protection thermostat taking note of
the correct positions. ix) Remove the condensate trap (Section 7.10) x) Remove the pressure gauge phial located next to the drain off tap. xi) Remove the air filter (Section 7.9) xii) Remove the two springs connecting the bottom tray of the air filter with the
cabinet top cover. xiii) Disconnect the flow and return connections to the boiler. xiv) Remove the push on flue and air connections to the flue and air pipes exiting the
top of the boiler. xv) Remove the four screws fixing the cabinet top cover to the cabinet body and
remove the top cover. xvi) Remove the nut fixing the strap retaining the base of the heat exchanger and pull
out the strap by unhooking it from its fixing behind the heat exchanger. xvii) Remove the allen screw securing the top of the heat exchanger to its mounting
bracket. xviii) Remove the heat exchanger, with pipework attached. xix) Remove the flow, return and flue pipework from the heat exchanger
(Replacement heat exchangers are supplied with return pipework attached). xx) Reassemble (Section 7.3) xxi) Recommission (Section 4 - Commissioning)
7.9 AIR FILTER (Fig. 5.7.4 item 19) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Drop the lower section of the air filter housing by releasing the toggle clip.
iv) Open the lower section as far as possible and pull out the combined paper filter
element with rubber seal.
v) Reassemble (Section 7.3)
NB: When fitting the new air filter take care to ensure that the new filter is
placed to cover completely the air intake into the boiler cabinet.
7.10 CONDENSATE TRAP (Fig. 5.7.2 item 58) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Disconnect the condensate line from the base of the heat exchanger. iv) Disconnect the condensate line from the base of the flue assembly. v) Disconnect the condense lines from the projection of the condensate trap from
the base of the cabinet. vi) Withdraw the condensate trap. vii) Mop up any spilled condensate. viii) Reassemble (Section 7.3)
NB: When re-fitting the condensate trap pour water onto the condensate hose
from the base of the heat exchanger until nearly full. Then reconnect the condensate hose to the base of the heat exchanger.
Installation & Servicing Instructions
Page : 46
Page 50
WD51/2/1997 Chapter 7 : Replacement Of Parts The Keston 170 Condensing Boilers
7.11 PRESSURE GAUGE (Fig. 5.7.1 item 116) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Shut off the pressure measurement point at the return drain valve located at the
base of the heat exchanger.
iv) Remove the phial from its mounting at the return pipe entry to the base of the heat
exchanger.
v) Press in the catches and push the pressure gauge forward through the control
panel. vi) Reassemble (Section 7.3) vii) Refill the system (See Section 4 - Commissioning)
7.12 SIGHT GLASS (Fig. 5.7.2 item 48) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Unscrew the sight glass fitting from the burner head. iv) Reassemble (Section 7.3)
7.13 HT IGNITION LEAD (Fig 5.7.1 item 122) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the lead from the electrode and the ignition control box. iv) Reassemble (Section 7.3)
7.14 Air Orifice (Fig. 5.7.3 item 131) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Disconnect the flexible air intake hose from the air inlet manifold (Fig 5.7.3 item
83) iv) Unscrew the air orifice grub screw (Fig 5.7.3 item 84) to release the air orifice. v) Lift the air orifice from its seat in the air inlet manifold. vi) Reassemble (Section 7.3) NB: When replacing the air orifice ensure that the new orifice is seated with the
chamfer facing upwards.
Installation & Servicing Instructions
Page : 47
Page 51
WD51/2/1997 Chapter 8 : Spare Parts Listings The Keston 170 Condensing Boiler
8. SHORT SPARE PARTS LIST
Item GC No Part Denomination Item GC No Part Denomination
19 114 105Air Filter 45 114 117Burner
46 114 118Burner Manifold Gasket 49 375 527Ignitor Gasket
50 114 120Ignitor/Sensor Probe 55 114 122Flexible Hose Gasket
63 375 530Boiler Thermostat 67 375 532Flue Thermostat
71 375 533Flow Overheat Thermostat 72 375 534Flow High Limit Stat
Installation & Servicing Instructions
Page : 48
Page 52
WD51/2/1997 Chapter 8 : Spare Parts Listings The Keston 170 Condensing Boiler
Item GC No Part Denomination Item GC No Part Denomination
90 375 535Gas Valve Outlet Gasket 104 114 122Flexible Hose Gasket 91 375 536Gas Valve
106 E01 074 Ignition Control Box 109 170 084Air Pressure Switch
122 E01 075 HT Ignition Cable
Installation & Servicing Instructions
Page : 49
Page 53
WD51/2/1997 Chapter 8 : Spare Parts Listings The Keston 170 Condensing Boiler
SHORT SPARE PARTS LIST FOR THE KESTON
CONDENSING BOILER RANGE
Item GC No Part Denomination
19 114 105 Air Filter 45 114 117 Burner 46 114 118 Burner Manifold Gasket 49 375 527 Ignitor Gasket 50 114 120 Ignitor/Sensor Probe 55/104 114 122 Flexible Hose Gasket 63 375 530 Boiler Thermostat 67 375 532 Flue Thermostat 71 375 533 Flow Overheat Thermostat 72 375 534 Flow High Limit Thermostat 90 114 139 Gas Valve Gasket 91 375 536 Gas Multifunctional Control Valve 106 E01 074 Ignition Control Box 109 173 084 Air Pressure Switch 122 E01 075 HT Ignition Cable
Installation & Servicing Instructions
Page : 50
Page 54
WD 93/0/1997
KESTON CONDENSING BOILERS
IMPORTANT
KESTON 170
INSTALLATION KEY POINTS
† †
Read Installation Manual Carefully
Ensure that there is at least 9 feet head of water pressure at the top of the boiler.
DO NOT remove the dust caps from the air and exhaust pipes until ready to connect.
Ensure that ALL dust particles, filings , plastic chips etc. are removed from the inlet pipe.
If the installation is a replacement the system must be flushed clean. System should be drained hot, then refilled, then drained
again until the water is clean. Ensure that there is a proper electrical supply ie 230V fused at
10A. Take great care with pipe connections to ensure that no
damage is done to the internal pipework. Ensure that the 22mm condensate pipe is not exposed to
freezing conditions.
† †
† † † †
Make sure that the exhaust pipe terminates away from windows or vents and is out of reach.
Make sure that the air inlet and exhaust pipe outlets are at least 500mm apart.
Check tightness of all connections in the boiler before firing. Ensure that the terminals supplied are fitted to both the exhaust
and air inlet pipes. The system must be free from air before firing.
The pump must always run when the boiler is firing. Gravity circuits are not allowed. If TRV's are installed on radiators ensure that a bypass is
installed to maintain required flow.
Loading...