Keston K170 Installation Manual

WD51/2/1997 The Keston 170 Condensing Boiler
170,000 Btu/h (50 kW) Model
Fan Powered High Efficiency
Condensing Gas Boiler
Installation And Servicing Instructions
Keston 170 - GC No 41 930 04
CE No : 87AR50
These instructions must be left either
with the user or next to the site gas
34 West Common Road
Hayes, Bromley, Kent BR2 7BX
Tel. 0181 462 0262 Fax. 0181 462 4459
WD51/2/1997 The Keston 170 Condensing Boiler
CONTENTS
Section Description 1 GENERAL INSTRUCTION
1.1 Description
1.2 Boiler Schematic
1.3 Related Documents
1.4 Performance Data
1.5 General Data
2 BOILER LOCATION
2.1 Dimensions & Minimum Clearances
2.2 Service Connections
2.3 Position
2.4 Electrical
2.5 Boiler Size Selection
2.6 Gas Supply
2.7 Water Systems
2.8 Flue System
2.9 Air Supply
2.10 Compartment Installation
2.11 Condensate Drainage
2.12 Radiant Floor Heating
2.13 Low Water Volume Boiler vs. Cast Iron Boiler
2.14 Determine Radiation Needed Room-By-Room
3 INSTALLATION OF THE BOILER
3.1 Wall Mounting Bracket
3.2 Mounting The Boiler
3.3 Assembly Practice
3.4 Installing Flue And Air Pipes
3.5 Condensate Drainage
3.6 Water System
3.7 Gas Supply
3.8 Electrical Supply
3.9 Exchanging A Boiler
4 COMMISSIONING OF THE BOILER
4.1 Initial Flushing
4.2 Gas Supply
4.3 Electrical Installation
4.4 LP Gas Conversion
4.5 Initial Firing
4.6 Hot Flushing
4.7 Checking The Gas Pressure
Page : i
WD51/2/1997 The Keston 170 Condensing Boiler
4.8 Timing The Gas Meter
4.9 Handing Over To The User
5 FAULT FINDING
5.1 Electrical Control Sequence
5.2 Fault Finding Flow Chart
5.3 Continuity Checking
5.4 Functional Flow Wiring Diagram
5.5 Electrical Wiring Diagram
5.6 Illustrated Wiring Diagram
5.7 Exploded Assembly Diagrams
6 SERVICING
6.1 Pre Service Checks
6.2 Recommended Routine Service
7 REPLACEMENT OF PARTS
7.1 General
7.2 Precautions
7.3 Access
7.4 Electrical
7.5 Gas Orifice
7.6 Spark Ignition/Flame Detection Electrode
7.7 Burner Head & Burner
7.8 Heat Exchanger
7.9 Air Screen
7.10 Condensate Trap
7.11 Pressure Gauge
7.12 Sight Glass
7.13 HT Ignition Lead
7.14 Air Vent
7.15 Air Orifice
8 SPARE PARTS LISTINGS
BENCHMARK INITIATIVE
As part of the industry wide “Benchmark” Initiative all Kes ton 170 boilers now include a Benchmark Installation, Commiss ioning and Service Rec ord Log Book . Pleas e read this c aref ully and complete all sections relevant to the appliance installation. T he details of the Log Book will be required in the event of and warranty work being required. There is also a section to be completed after each regular service visit. The completed Log Book should be left with the customer.
CORGI CONTACT INFORMATION
The boiler should be installed and serviced only by CORGI registered operatives. All CORGI registered Installers carry a CORGI ID cad, and have a registration number. Both should be recorded in the Benchmark Log Book. You can call CORGI direct on 01256 372300.
Page : ii
WD51/2/1997 Chapter 1 : General Instruction
1. GENERAL INSTRUCTION
1.1 DESCRIPTION
The Keston Condensing Boiler is unique in its concept and design. While the application for which the boiler was designed is the sam e as those which other boilers are us ed, the Keston boiler has the added advantage of very high efficiency, and small diameter plastic flue which can be extended to 15 metres horizontally or vertically.
The Keston uses a high power combustion blower to deliver a pre-mix of gas and air to a downward firing burner in a high efficiency, single pass heat exchanger. Normally the combustion temper ature of the air gas mixtur e is around 1800
combustion at an amazing 1000 The flue system is room sealed and fan powered. The ignition is direct spark and fully
automatic. The boiler housing is not waterproof. The boiler should be installed in a position where it will always be dry. A small air intake point is incorporated within the appliance cabinet to ensure that the interior of the cabinet is maintained under a slight negative pressure. This is a safety feature to ensure no products may leak out of the cabinet into the installation space.
The boiler is suitable for c onnection to open vented or, preferably, sealed systems. The system must be pumped centra l heating or pum ped c entr al heating with combined indirec t sanitary hot water. Gravity circuits must not be used.
The Keston 170 Condensing Boiler
o
C thereby reducing the NO
o
C but the Keston achieves
x emissions.
Forming part of the boiler is the heat exchanger which is made f rom a highly corrosion resistant stainless steel, form ed into tightly wound coil. The hot combustion gases from the central down firing burner pass thr ough this coil im parting heat into the system water. Head characteristics of the boiler coil must be taken into consideration when calculating the pump size. The Keston boiler is not a high water content boiler and does not contain the metal mass , or water volume, of a cast iron or steel boiler . This boiler is of low mass and low water content and therefore responds f aster when there is a call for heat. This feature requires a higher water pum ping rate through the boiler otherwise localised boiling will occur within the boiler. Allow a pressure drop through the boiler of 13.75 ft head and a
water flow of 13.2 gallons (60 litres) per minute. The boiler selected m ust be sized relative to the total c alculated heat loss of the building.
The boiler rated output should not be greater than the total required to make up the calculated heat loss plus the heat required to provide sanitar y hot water, if the system is not hot water priority design. If there are special conditions such as excess ive sanitary hot water usage consult the manufacturer.
1.2 BOILER SCHEMATIC
Air is drawn into the boiler through a 50mm muPVC pipe. The air flow is proved by a differential pressur e across the air control orif ice. Gas is mix ed with combustion air at the inlet to the fan. The gas flow is r egulated by an orifice located in the housing downstr eam of the gas valve.
The gas and air are thoroughly mixed in the blower and f ed into the burner located at the top end of the heat exchanger module. The gas and air mixture is ignited by a direct spark ignition control system and burns with a blue flame j ust off the surface of the burner. As the hot products of combustion pass downwards, they are cooled by exchanging heat with the circulating water which enters the heat exchanger coil at the bottom of the heat exchanger.
Fig. 1.2 - Boiler Schematic
Installation & Servicing Instructions
Page : 1
WD51/2/1997 Chapter 1 : General Instruction
The Keston 170 Condensing Boiler
When the return water temperature is below 54oC, part of the water vapour in the combustion products will condense ins ide the heat exchanger, thus increasing the boiler efficiency by releasing the latent heat of condensation. This condensate falls to the bottom of the heat exchanger where it is separated from the flue gases and exits from the boiler through the condensate drain. Any condensate formed in the flue runs back down the flueway and is drained at the base of the flue connection to the heat exchanger or drain points within the flue..
The condensate is very slightly acidic (about the same acidity as vinegar) and should be piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed of as normal waste water.
The flue gases are piped in a 50m m m uPVC pipe to the outside. The temper ature of the flue gases are usually around 10 pipe should be terminated outside the building from where they cannot re-enter the building or any other adjacent building.
The heating level may be controlled by room therm ostats, hot water cylinder therm ostats, programmer time clocks and energy management systems.
1.3 RELATED DOCUMENTS
The Keston Condensing Boiler must be ins talled in accordance with the current issue of the Gas Safety (Installation and Use) Regulations, current IEE Wiring Regulations,
Building Regulations, Building Standards (Scotland) Consolidation, and the Bye Laws of the local Water Undertaking.
o
C above the temperature of the return water. T he flue
In addition, due account must be taken to the following Codes Of Practice:
BS 6891 : Gas Supplies BS 6798 : Installation Central Heating Boilers BS 5449 : Installation Pumped Central Heating BS 5546 : Installation Domestic Hot Water BS 5440.1 : Flues
Installation & Servicing Instructions
Page : 2
WD51/2/1997 Chapter 1 : General Instruction
BS 5440.2 : Air Supply BS 5482.1 : Domestic Propane & Butane Burning Installations BS 7074.1 : Expansion Vessels BS 7593 : Treatment of Water in Hot Water Central Heating
BS 7671 : Requirments for Electrical Installations.IEE Wiring For Timber Framed Buildings, British Gas Publications DM2. Also British Gas
Publications 'Guidance Notes For The Installation Of Domestic G as Condensing Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
1.4 PERFORMANCE DATA
The Keston 170 Condensing Boiler
Systems Regulations 16th Edition.
Boiler Input (gross) kW 55.0 Btu/h 187,600
Boiler Output To Water kW 49.8
o
C Flow 60oC Return) Btu/h 170,000
(80 Boiler Output To Water kW 52.4
o
C Flow 40oC Return) Btu/h 179,000
(60 Boiler Output To Water kW 54.5
o
C Flow 30oC Return) Btu/h 186,000
(50 Burner Setting Pressure mbar 10.0
(Hot) in wg 3.94 Gas Comsumption After l/s 1.42
10 mins Running Ft (CV of Gas - 38.7 MJ/m (1038 Btu/Ft
3
)
3
)
3
/hr 180.73
1.5 GENERAL DATA
Max. Operating Flow Temp.
o
C 80.00
Max. Head (Open Systems) m 30.50
Ft 100.0 Max. Press. (Sealed Sys.) Bar 2.70 Min. Head (Open Systems) m 2.5
Ft 8.0 Inlet Gas Pressure mbar 20.0
in wg 8.0 Gas Orifice Size mm 4.5 Air Orifice Size mm 23.0
o
Recommended Temperature
C 10 to 15
Differential
Main Burner Keston Premix Gas Control White Rogers 36E Series Combustion Fan Keston
Type LPB 103 220/240
0.6 kW 2900 RPM
Direct Spark RAM ElectronicsIgnition Ignition Full Sequence Control
Air Press. Switch Tridelta FS6717-1428 Filter Keston Filter Gas Supply 0.75 inch BSPT Male
Connection (22mm to gas cock)
Installation & Servicing Instructions
Flow Connection 35mm Copper Return Connection 35mm Copper Power Supply 230V 50Hz Pwr Consumption 610 W Ext Fuse Rating 10 Amps Weight - Full 68 kg (150 lbs)
Weight - Empty 61 kg (134 lbs) Data Badge Posn Right Hand Panel Inside
Case
Water Content 7.0 litres
Page : 3
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
2. BOILER LOCATION
All dimensions in mm.
2.1 DIMENSIONS AND MINIMUM CLEARANCES
The boiler must be installed in m inim um clearances shown to allow subsequent servicing, and safe operation.
2.2 SERVICE CONNECTIONS
254
Gas, water, air and flue pipe, condensation, and electrical connections are as shown. Gas :7 0.5 inch BSP male. Flow/Return 35 mm
copper.
2.3 POSITION
The Keston is not suitable for external installation. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Figure 2.1.2 Dimensions
Air Intake
Return
50
Flow
Flue
1
1
305
Figur e 2.1.1
127
Minimum Clearances
All dimensions in mm.
890
Condense
Gas
Where a room-sealed appliance is installed in a
50
244
190
263
405
Top View
Installation & Servicing Instructions
113
152
65
37
Service Connection Locations
97
500
7
2
3
35
85
50
30
44
Base View
All dimensions are in mm.
Page : 4
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
room containing a bath or shower, any electrical switch or appliance control, utilising mains electricity, should be so situated that it cannot be touched by a person using the bath or shower.
Compartment installation is permitted - such compartments must be constructed in accordance with BS 6798.
The wall on which the boiler is mounted must be of suitable load bearing capacity and must be non-combustible.
Important : It is not recommended to install the boiler on a studded wall or similar - it is possible that the vibration from the fan would be amplified and transmitted to other parts of the property.
[NB: Refer to Section 2.8.3]
The Keston can be located virtually anywhere desired provided that all regulations are complied with. Because of the boiler's compact size and venting flexibility, the installation is not limited to a boiler room setting. Before locating the boiler near a living space
consider whether the sounds generated by the boiler will be objectionable.
2.4 ELECTRICAL
2.4.1 Electrical Connections
The boiler must be connected to a 230V ~ 50Hz supply, fused at 10A. All external controls and wiring must be suitable for mains voltage. Wiring
external to the boiler must be in accordance with current I.E.E wiring regulations and local regulations.
Chimneys not used for venting any other
appliance may be used.
Secure air & flue pipes at chimney outlet.
Figure 2.3
The method of connection to the mains electricity supply must facilitate complete electrical isolation of the boiler, preferably by the use of a fused,
Installation & Servicing Instructions
Page : 5
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
unswitched three pin plug and a shuttered socket-outlet, both complying with the requirements of BS 1363.
The appliance must be connected to the supply via a fused double pole switch having at least 3mm (1/8 inch) contact separation in both poles, serving only the boiler and the system.
The connection point to the mains supply should be readily accessible and adjacent to the boiler, except for rooms containing a bath or a shower. Refer to section 2.3 Position.
2.4.2 External Wiring & Controls
1. The boiler is deisgned so that all control wiring is external to the boiler. Hence, any programmers or room thermostats etc must act by switching the 230V supply to the boiler.
2. System designs which allow the boiler to fire when there is no pumped circulation must NOT be used.
3. A programmer may be used with zone valves to give independent control of central heating and hot water.
2.5 BOILER SIZE SELECTION
The size of the boiler to be used is determined by the total calculated heat loss of the building. Match the calculated heat loss with the boilers rated output. If a boiler is installed
with an output rating greatly exceeding the total capacity of the distribution system the efficiency of the boiler will be reduced.
2.6 GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas region or their contractor. An existing meter should be checked preferably by the gas region to ensure that the meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891.
Minimum/Maximum Natural Gas Pressure:
Natural gas pressure before the gas valve must be maintained at 20 mbar (8 in WG) while the boiler is running.Gas pressures above or below this level will lead to problems associated with the gas valve's internal pressure regulator.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (22 mm). Due consideration must be given to the supply pressure to other gas appliances in the premises. Reduction in dynamic gas supply pressure will result in intermittent ignition failures. Ensure gas supply pipe work is adequately sized for the length of run from the meter to the boiler.
A gas cock is supplied loose with the boiler. This cock should be fitted in the gas line to the boiler as close to the boiler as possible so that it is easily identified as the cock to isolate the boiler.
2.7 WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply Bylaws for forced hot water heating systems. Consideration must be given to pipe capabilities and pressure drop through the piping.
Installation & Servicing Instructions
Page : 6
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
Water treatment must be carried out to BS 7593 : Treatment of Water in Hot Water Central Heating Systems. Pump isolating valves must be positioned as close to the pump as possible.
a The Keston 170 is suitable for use on open vented water systems with combined
feed and vent.
b It is preferable for use on sealed water systems, provided the appropriate
components required (see Section 2.7.2 Sealed Systems) are included in the system.
c Any system must
connection with the boiler. A trap should be installed in the flow line to collect any solder, or other debris, from the installation.
d All water systems must be constructed to comply with requirements of the Local
Water Authority. e Only fully pumped systems can be used - gravity systems are strictly f Always use a system complying with the requirements of BS 5449 and BS 6798. g The system must be so arranged that there shall always be a minimum flow of
13.2 gpm (60 litres/min) when the boiler is firing.
be thoroughly flushed clean of grease, dirt and debris, prior to
not suitable.
This can be via a specially
installed by-pass arrangement.
h Copper tubing to BS 2871 Part 1 is recommended. i Jointing should be either with capillary, threaded or compression fittings. Pipes
should have a gradient to ensure air is passed easily to vent points and water
flows readily to drain points. j Draining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 22 mm in
nominal size and be in accordance with BS 2879.
AIR VENT POINTS k These must be fitted at all high points where air will naturally collect and must be
sited to allow complete draining of the system.
2.7.1 Open Vented Systems
A typical system is shown in Figure 2.7.1 which includes a combined feed and
vent. Note there must be no valve between the boiler flow and the open vent.
Note that the minimum static head required is 9 ft at the boiler flow pipe. If the
cold feed/vent is not brought to the flow pipe as shown, then the pressure loss
across the heat exchanger may have to be taken into account when estimating
the static pressure.
Although suitable for open vented systems with combined feed and vent
arrangements, the Keston is a low water content boiler. As such, any air
entrainement within the system water will produce boiler “kettling”. It is
therefore recommended, if in any doubt, to consider the use of sealed
systems where possible.
Installation & Servicing Instructions
Page : 7
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
Boiler
Expansion Pipe
28mm
Minimum
Keston
Strainer
Rad. 2 Rad. 1
Expansion Tank
Pump
Minimum 9ft Heig ht
By-pass Bal. Valve
Valve
Cylinder
L/S Valve
Valve
2.7.2 Sealed Systems
Sealed systems must be designed in accordance with BS 5449 and BS 7074 Pt1. A typical sealed system is shown in Figure 2.7.2. It must include :
(i) A safety valve fitted on the flow, adjacent to the boiler. It must be non
(ii) An expansion vessel complying with BS 4814 and sized in accordance
(iii) A filling point, in accordance with local water authority requirements. (iv) A method of system make-up (automatic or manual), in accordance with
(v) There must be no permanent connection of mains water to the boiler
(vi) The installation must be designed to work with flow temperatures of up to
Figure2.7.1 : Open Vented System Diagram
adjustable and preset to 3 bar. A drain pipe must be attached, at least as big as the valve connection, and routed to drain in any area not hazardous nor where it may be subject to freezing.
with the requirements of BS 5449 and BS 7074 Pt 1. The vessel must be positioned on the inlet to the pump.
local water authority requirements.
system.
o
C.
110
Installation & Servicing Instructions
Page : 8
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
k
Make -up vessel. Max. capacity of
Air Vent
3 lt. (5pt)
Boiler
Drain Coc
Keston
Safety Valve
Expansion Vessel
Pressure Guage
Strainer
By-pass Bal. Valve
Pump
Doubl e Check Valve
Figure 2.7.2 : Sealed System Diagram
L/S
Test Cock
RETURN
HEATING CIRCUIT
FLOW
BS 1010:2 Stop T ap
Non-Return Valve
Auto Air Vent
Hose Union bib tap
Hosepipe (disconnected after filling)
Hose Connector
All components of the system including the heat exchanger of the indirect cylinder
must be suitable for a working pressure of 3 bar and a temperature of 110
Care should be taken in making all connections that the risk of leakage is
minimised.
2.7.3 Hot Water System (if applicable)
The hot water storage vessel must be of the indirect type (certain direct cylinders
can be used provided
they are suitably adapted by fitting an immersion calorifier).
DIRECT CYLINDERS MUST NOT BE USED. Further guidance is provided in BS
1394. It is advisable to fit a lockshield valve on the cylinder return to enable
balancing of the flow rate through the cylinder.
2.7.4 Boiler By-pass Piping
Boiler water flows are critical to the operation of the boiler. If flow cannot be
maintained through the system piping to meet the minimums required by the
boiler (see paragraph 2.7 (g)). Insufficient water flows through the boiler will cause
the boiler to "kettle" or even produce steam which can damage the heat
exchanger and will invalidate the heat exchanger warranty.
It is normally advisable to incorporate a boiler by-pass in the system, especially if
thermostatic radiator valves are used. The by-pass should be fitted with an
automatic by-pass valve to permit balancing of the by-pass flow rate. The
flow/return differential should be 10
maintain this condition with all thermostatic radiator valves closed.
o
C.
o
C to 15oC. The valve should be adjusted to
Installation & Servicing Instructions
Page : 9
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
2.7.5 Air Elimination
In the initial charge of water to the boiler system and in all subsequent additions of water to the system some air will be dissolved in the water. As the water is heated the air is driven out of the solution and will collect in high spots in the system. These air bubbles can interfere with pumping and heat transfer and
must be eliminated.
Installation of air bleed valves at the high spot(s) in the system will allow for air elimination when filling the system and will allow re-venting in a day or so after all air has been driven out of solution.
2.7.6 Strainers
Debris in the heating system can cause noise if it enters the heat exchanger. Fitting of a Y-strainer ahead of the circulating pump will trap any debris left in the system and will protect the pump from damage. The boiler guarantee does not cover heat exchanger failure due to debris abrasion within the
system.
Y-Strainer will collect an y loose debris in the piping.
Figure 2.7.6 Strainers
2.7.7 Pump Selection
The Keston boilers have low water content heat exchangers with a high resistance to flow, when compared with cast iron heat exchanger boilers. As a result selection of the correct pump is essential localised boiling within the heat exchanger. The selected pump must be capable of maintaining the required flow rate for the boiler against the pressure losses contributed
by the boiler.
The Keston 170 condensing boiler offers a hydraulic resistance of
4.2m (13.75ft) water at the required flow rate of 60 l/m (13.2 gpm).
If a single pump is to be used for the entire installation the boiler resistance must be added to the pressure loss caused by the rest of the
in order to avoid
Static Pressure - m WC
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
20 30 40 50 60
10
Water Flow - L/min
Figure 2.7.7 : Pressure Loss Gra ph
70
Installation & Servicing Instructions
Page : 10
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
g
system and a pump selected that is capable of meeting the flow rate required at
the total pressure loss generated by the boiler and the rest of the system. The
selected pump must comply with BS 1394. It is important to note that the
minimum flow rate must be maintained whenever the boiler is firing. Systems
using zone valves must be specifically designed to only fire the boiler when the
pump is running and the minimum flow rate can be achieved.
2.8 FLUE SYSTEM
2.8.1 Design
Individual air supply and flue outlet pipes are used. The material used for flue
outlet &/or air inlet must be muPVC to BS 5255 an of an internal diameter of 51
mm.
O56
40
87
80
Flue Outlet Terminal
Both flue outlet terminal and air inlet terminal are supplied and are illustrated in
Figure 2.8.1 above.
2.8.2 Maximum Lengths
The maximum lengths of both air inlet pipe and flue outlet pipe, when no bends
are used, are as detailed below.
Maximum Air Inlet Length : 15.0 m
Maximum Flue Outlet Length : 15.0 m
However, each bend used has an equivalent length that must be deducted from
the maximum straight length stated above. Knuckle bends must not be used.
Fi
ure 2.8.1 : Terminals
211
O83
O56
Air Intake Terminal
o
A 92.5
sweep elbow is equivalent to 1.0m straight length. Example: Air inlet uses two one 92.5o sweep elbows. Hence, maximum length permissible
(ie a+b in figure 2.8.2) = 15.0m - 1.0m - 1.0m = 13.0m
o
Flue outlet uses one 92.5
sweep elbow. Hence, maximum length permissible (ie
c+d in figure 2.8.2) = 15.0m - 1.0 m = 14.0m
Installation & Servicing Instructions
Page : 11
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
2.8.3 Slope
FLUE
d
c
AIR
b
a
Keston
Figure 2.8.2 : Flue & Air Maximum Length Example
'Horizontal' flue outlet pipework MUST slope at least 5 degrees (80 mm per metre run) downwards towards the boiler. Pipework can be vertical. Only swept elbows can be used. Air inlet pipework can be truly horizontal or vertical, or sloping in a downward direction towards the boiler but in this case rain, etc, must
be prevented from entering the pipe. There must be no troughs in any of the pipework, whether it be air inlet or flue outlet. If a 80 mm per meter slope is not possible, contact Keston Boilers Technical Department for further guidance.
Due the low temperature of the flue gases further condensate will form within the flue system. Drain points, with suitable traps, must therefore be incorporated within the flue system at the base of vertical flue sections in excess of 2m. These additional condensate drains must be run to discharge as detailed in section 2.11. Such drain points can be formed using standard muPVC fittings. Refer to the example in Figure 2.8.3.
2.8.4 Terminations Air inlet terminals must be
facing upwards and positioned to ensure only fresh air is drawn into the boiler. The air terminal must be located outside of the building. Drawing of combustion air directly from a ventilated boiler room will invalidate the heat exchanger warranty. The air intake terminal must face upwards to prevent entry of rain into the air intake pipework.
The flue outlet terminal is designed to face outwards but can, if desired, be
Figure 2.8.3 :
Flue Condensate Drain Point Example
To Terminal
To Boiler
50mm Tee Fitting
6 in min.
Installation & Servicing Instructions
Page : 12
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
adapted to face in any direction BUT must not be directed in the region of the air inlet.
Dimensions (mm)
Flue
Terminal
Air
Inlet
50300A Below openable window, air brick, etc. 7575B Below gutters, soil pipes, drain pipes. 50300C Below eaves. 50200D Below balconies or car port roof. 5075E From vertical drain or soil pipes.
50600F From internal or external corner. 100300G Above ground or balcony or roof. 100600H From surface facing a terminal
1,2001,200I From terminal facing a terminal.
1001,200J From opening in a car port.
1,5001,500K Vertically from terminal on same wall.
300300L Horizontally from terminal on same wall.
Table 2.8.4 Minimum Flue Terminations & Air Inlet Dimensions
The two terminals are subject to the requirements of BS 5440 Pt 1 for clearances from features of the building although some can be decreased to the values indicated. If either the air inlet or the flue outlet terminate at a height of less than 2m (6ft) above ground level the termination must be protected by a suitable guard. The K4 terminal guard, manufactured by Tower Flue Components Ltd, is suitable for this purpose and can be obtained from Keston Boilers. The Keston condensing boiler, as with any condensing boiler, will generate a condensate “plume” from the flue terminal in all weather conditions. Consideration must therefore be given to the effect of this “plume” when selecting a location for the flue terminal. It is advisable, for horizontal flue terminals, to place a 45
O
elbow at the end of the flue to direct the condensate plume up and away from the property,
2.8.5 Clearances From Wall
Flue outlet and air inlet terminations must be at least 60 mm and 95 mm respectively from the wall face.
2.8.6 Distance Between Flue Outlet & Air Inlet
There is no maximum - the terminations can be on opposite sides of the dwelling if desired. A minimum clearance of at least 500 mm must be left between the terminations.
2.8.7 General Installations
All parts of the system must be constructed in accordance with BS 5440 Part 1, except where specifically mentioned in these instructions. All pipework must be adequately supported.
Installation & Servicing Instructions
Page : 13
WD51/2/1997 Chapter 2 - Boiler Connections The Keston 170 Condensing Boiler
All joints other than push-on or plastic compression connectors must be made and sealed
with solvent cement suitable for muPVC pipes and conforming to BS 6209: 1982. External wall faces and any internal faces of cavity walls must be made good.
2.9 AIR SUPPLY
The Keston is a room sealed appliance and therefore does not require purpose provided ventilation for combustion air.
2.10 COMPARTMENT INSTALLATION
The casing temperature of the Keston 170 is very low. Due to this fact, no compartment ventillation is required for cooling purposes.
2.11 CONDENSATE DRAINAGE
Being a condensing boiler, the Keston is fitted with a condensate trap at the base of the heat exchanger and flue assembly, with facility to connect to a drain point underneath the appliance.
Use only plastic piping and do not reduce below 15mm internal diameter within the dwelling. Condensate should preferably be drained into the sanitary waste system or, alternatively, the rainwater system of the property.
Termination of the pipe must be either at a branch or stack internal to the house, or externally at an open gully. Alternatively, discharge into a purpose made condensate soakaway can be considered. Existing or purpose built drains must use suitable corrosion resistant material as condensate is mildly acidic.
A minimum slope downwards towards the drain of 1 in 20 is essential. Freezing of the termination and pipework must be prevented. Any drainage pipes outside the property must be at least 32 mm inside diameter.
2.12 RADIANT FLOOR HEATING
The low operating temperatures of this type of system lead to very good operating efficiencies. In fact, under floor heating can produce in excess of 95% operating efficiency from a Keston condensing boiler.
Water temperatures in radiant floor heating systems must be kept relatively low, generally under 48
o
C, so that surfaces do not become uncomfortably warm to the touch. If radiant heating is only one application for a multi-zone system which also requires higher delivery water temperatures for other zones (i.e. water heating, skirting heaters etc.) then the radiant floor zone temperature will need to be controlled separately from the boiler.
If radiant floor heating is the only application of the boiler, the boilers maximum operating temperature can be lowered accordingly by introducing a supplementary control
thermostat within the control system of the installation. Mixing valves are also available which will mix return water from the system with boiler
output water to dilute the temperature of water transmitted to the distribution system. Mixing valves may create problems with low flow and high temperatures through the boiler, unless care is taken to design a system which will provide proper flows and will fully load the boiler. Keeping the boiler's temperature high will prevent the boiler from operating at peak efficiencies. Systems which maintain boiler temperatures in this way should be avoided.
Installation & Servicing Instructions
Page : 14
Loading...
+ 37 hidden pages