As part of the industry wide “Benchmark” Initiative all Kes ton 170 boilers now include a Benchmark
Installation, Commiss ioning and Service Rec ord Log Book . Pleas e read this c aref ully and complete all
sections relevant to the appliance installation. T he details of the Log Book will be required in the event
of and warranty work being required. There is also a section to be completed after each regular
service visit. The completed Log Book should be left with the customer.
CORGI CONTACT INFORMATION
The boiler should be installed and serviced only by CORGI registered operatives. All CORGI
registered Installers carry a CORGI ID cad, and have a registration number. Both should berecorded in the Benchmark Log Book. You can call CORGI direct on 01256 372300.
Page : ii
WD51/2/1997 Chapter 1 : General Instruction
1. GENERAL INSTRUCTION
1.1DESCRIPTION
The Keston Condensing Boiler is unique in its concept and design. While the application
for which the boiler was designed is the sam e as those which other boilers are us ed, the
Keston boiler has the added advantage of very high efficiency, and small diameter plastic
flue which can be extended to 15 metres horizontally or vertically.
The Keston uses a high power combustion blower to deliver a pre-mix of gas and air to a
downward firing burner in a high efficiency, single pass heat exchanger. Normally the
combustion temper ature of the air gas mixtur e is around 1800
combustion at an amazing 1000
The flue system is room sealed and fan powered. The ignition is direct spark and fully
automatic. The boiler housing is not waterproof. The boiler should be installed in a
position where it will always be dry. A small air intake point is incorporated within the
appliance cabinet to ensure that the interior of the cabinet is maintained under a slight
negative pressure. This is a safety feature to ensure no products may leak out of the
cabinet into the installation space.
The boiler is suitable for c onnection to open vented or, preferably, sealed systems. The
system must be pumped centra l heating or pum ped c entr al heating with combined indirec t
sanitary hot water. Gravity circuits must not be used.
The Keston 170 Condensing Boiler
o
C thereby reducing the NO
o
C but the Keston achieves
x emissions.
Forming part of the boiler is the heat exchanger which is made f rom a highly corrosion
resistant stainless steel, form ed into tightly wound coil. The hot combustion gases from
the central down firing burner pass thr ough this coil im parting heat into the system water.
Head characteristics of the boiler coil must be taken into consideration when calculating
the pump size. The Keston boiler is not a high water content boiler and does not contain
the metal mass , or water volume, of a cast iron or steel boiler . This boiler is of low mass
and low water content and therefore responds f aster when there is a call for heat. This
feature requires a higher water pum ping rate through the boiler otherwise localised boiling
will occur within the boiler. Allow a pressure drop through the boiler of 13.75 ft head and a
water flow of 13.2 gallons (60 litres) per minute.
The boiler selected m ust be sized relative to the total c alculated heat loss of the building.
The boiler rated output should not be greater than the total required to make up the
calculated heat loss plus the heat required to provide sanitar y hot water, if the system is
not hot water priority design. If there are special conditions such as excess ive sanitary hot
water usage consult the manufacturer.
1.2BOILER SCHEMATIC
Air is drawn into the boiler through a 50mm muPVC pipe. The air flow is proved by a
differential pressur e across the air control orif ice. Gas is mix ed with combustion air at the
inlet to the fan. The gas flow is r egulated by an orifice located in the housing downstr eam
of the gas valve.
The gas and air are thoroughly mixed in the blower and f ed into the burner located at the
top end of the heat exchanger module. The gas and air mixture is ignited by a direct spark
ignition control system and burns with a blue flame j ust off the surface of the burner. As
the hot products of combustion pass downwards, they are cooled by exchanging heat with
the circulating water which enters the heat exchanger coil at the bottom of the heat
exchanger.
Fig. 1.2 - Boiler Schematic
Installation & Servicing Instructions
Page : 1
WD51/2/1997 Chapter 1 : General Instruction
The Keston 170 Condensing Boiler
When the return water temperature is below 54oC, part of the water vapour in the
combustion products will condense ins ide the heat exchanger, thus increasing the boiler
efficiency by releasing the latent heat of condensation. This condensate falls to the bottom
of the heat exchanger where it is separated from the flue gases and exits from the boiler
through the condensate drain. Any condensate formed in the flue runs back down the
flueway and is drained at the base of the flue connection to the heat exchanger or drain
points within the flue..
The condensate is very slightly acidic (about the same acidity as vinegar) and should be
piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed
of as normal waste water.
The flue gases are piped in a 50m m m uPVC pipe to the outside. The temper ature of the
flue gases are usually around 10
pipe should be terminated outside the building from where they cannot re-enter the
building or any other adjacent building.
The heating level may be controlled by room therm ostats, hot water cylinder therm ostats,
programmer time clocks and energy management systems.
1.3RELATED DOCUMENTS
The Keston Condensing Boiler must be ins talled in accordance with the current issue of
the Gas Safety (Installation and Use) Regulations, current IEE Wiring Regulations,
Building Regulations, Building Standards (Scotland) Consolidation, and the Bye Laws of
the local Water Undertaking.
o
C above the temperature of the return water. T he flue
In addition, due account must be taken to the following Codes Of Practice:
BS 6891:Gas Supplies
BS 6798:Installation Central Heating Boilers
BS 5449:Installation Pumped Central Heating
BS 5546:Installation Domestic Hot Water
BS 5440.1:Flues
Installation & Servicing Instructions
Page : 2
WD51/2/1997 Chapter 1 : General Instruction
BS 5440.2:Air Supply
BS 5482.1:Domestic Propane & Butane Burning Installations
BS 7074.1:Expansion Vessels
BS 7593:Treatment of Water in Hot Water Central Heating
BS 7671:Requirments for Electrical Installations.IEE Wiring
For Timber Framed Buildings, British Gas Publications DM2. Also British Gas
Publications 'Guidance Notes For The Installation Of Domestic G as Condensing
Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
1.4PERFORMANCE DATA
The Keston 170 Condensing Boiler
Systems
Regulations 16th Edition.
Boiler Input (gross)kW55.0
Btu/h 187,600
Boiler Output To WaterkW49.8
o
C Flow 60oC Return)Btu/h170,000
(80
Boiler Output To WaterkW52.4
o
C Flow 40oC Return)Btu/h179,000
(60
Boiler Output To WaterkW54.5
o
C Flow 30oC Return)Btu/h186,000
(50
Burner Setting Pressure mbar10.0
(Hot)in wg3.94
Gas Comsumption Afterl/s1.42
10 mins RunningFt
(CV of Gas - 38.7 MJ/m
(1038 Btu/Ft
3
)
3
)
3
/hr180.73
1.5GENERAL DATA
Max. Operating Flow Temp.
o
C80.00
Max. Head (Open Systems)m30.50
Ft100.0
Max. Press. (Sealed Sys.)Bar2.70
Min. Head (Open Systems)m2.5
Ft8.0
Inlet Gas Pressurembar20.0
in wg8.0
Gas Orifice Sizemm4.5
Air Orifice Sizemm23.0
o
Recommended Temperature
C10 to 15
Differential
Main BurnerKeston Premix
Gas ControlWhite Rogers 36E Series
Combustion FanKeston
Type LPB 103 220/240
0.6 kW 2900 RPM
Direct SparkRAM ElectronicsIgnition
IgnitionFull Sequence Control
Air Press. SwitchTridelta FS6717-1428
FilterKeston Filter
Gas Supply0.75 inch BSPT Male
Connection(22mm to gas cock)
Installation & Servicing Instructions
Flow Connection35mm Copper
Return Connection 35mm Copper
Power Supply230V 50Hz
Pwr Consumption610 W
Ext Fuse Rating10 Amps
Weight - Full68 kg (150 lbs)
Weight - Empty61 kg (134 lbs)
Data Badge PosnRight Hand Panel Inside
The boiler must be installed in m inim um
clearances shown to allow subsequent
servicing, and safe operation.
2.2SERVICE CONNECTIONS
254
Gas, water, air and flue pipe,
condensation, and electrical
connections are as shown. Gas :7 0.5
inch BSP male. Flow/Return 35 mm
copper.
2.3POSITION
The Keston is not
suitable for external
installation. The boiler
may be installed in any
room or internal space,
although particular
attention is drawn to the
requirements of the
current IEE Wiring
Regulations and, in
Scotland, the electrical
provisions of the Building
Regulations applicable in
Scotland, with respect to
the installation of the
boiler in a room or
internal space containing
a bath or shower.
room containing a bath or shower, any electrical switch or appliance control, utilising
mains electricity, should be so situated that it cannot be touched by a person using the
bath or shower.
Compartment installation is permitted - such compartments must be constructed in
accordance with BS 6798.
The wall on which the boiler is mounted must be of suitable load bearing capacity and
must be non-combustible.
Important : It is not recommended to install the boiler on a studded wall or similar - it is
possible that the vibration from the fan would be amplified and transmitted to other parts
of the property.
[NB: Refer to
Section 2.8.3]
The Keston can be located virtually anywhere desired provided that all regulations are
complied with. Because of the boiler's compact size and venting flexibility, the installation
is not limited to a boiler room setting. Before locating the boiler near a living space
consider whether the sounds generated by the boiler will be objectionable.
2.4ELECTRICAL
2.4.1Electrical Connections
The boiler must be connected to a 230V ~ 50Hz supply, fused at 10A. All
external controls and wiring must be suitable for mains voltage. Wiring
external to the boiler must be in accordance with current I.E.E wiring regulations
and local regulations.
Chimneys not used for
venting any other
appliance may be used.
Secure air & flue pipes at
chimney outlet.
Figure 2.3
The method of connection to the mains electricity supply must facilitate complete
electrical isolation of the boiler, preferably by the use of a fused,
unswitched three pin plug and a shuttered socket-outlet, both complying with the
requirements of BS 1363.
The appliance must be connected to the supply via a fused double pole switch
having at least 3mm (1/8 inch) contact separation in both poles, serving only the
boiler and the system.
The connection point to the mains supply should be readily accessible and
adjacent to the boiler, except for rooms containing a bath or a shower. Refer to
section 2.3 Position.
2.4.2External Wiring & Controls
1.The boiler is deisgned so that all control wiring is external to the boiler.
Hence, any programmers or room thermostats etc must act by switching
the 230V supply to the boiler.
2.System designs which allow the boiler to fire when there is no pumped
circulation must NOT be used.
3.A programmer may be used with zone valves to give independent control
of central heating and hot water.
2.5BOILER SIZE SELECTION
The size of the boiler to be used is determined by the total calculated heat loss of the
building. Match the calculated heat loss with the boilers rated output. If a boiler is installed
with an output rating greatly exceeding the total capacity of the distribution system the
efficiency of the boiler will be reduced.
2.6GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas region or their
contractor. An existing meter should be checked preferably by the gas region to ensure
that the meter is adequate to deal with the rate of gas supply required. Installation pipes
should be fitted in accordance with BS 6891.
Minimum/Maximum Natural Gas Pressure:
Natural gas pressure before the gas valve must be maintained at 20 mbar (8 in WG) while
the boiler is running.Gas pressures above or below this level will lead to problems
associated with the gas valve's internal pressure regulator.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (22 mm).
Due consideration must be given to the supply pressure to other gas appliances in the
premises. Reduction in dynamic gas supply pressure will result in intermittent ignition
failures. Ensure gas supply pipe work is adequately sized for the length of run from the
meter to the boiler.
A gas cock is supplied loose with the boiler. This cock should be fitted in the gas line to
the boiler as close to the boiler as possible so that it is easily identified as the cock to
isolate the boiler.
2.7WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply
Bylaws for forced hot water heating systems.
Consideration must be given to pipe capabilities and pressure drop through the piping.
Water treatment must be carried out to BS 7593 : Treatment of Water in Hot Water
Central Heating Systems.
Pump isolating valves must be positioned as close to the pump as possible.
aThe Keston 170 is suitable for use on open vented water systems with combined
feed and vent.
bIt is preferable for use on sealed water systems, provided the appropriate
components required (see Section 2.7.2 Sealed Systems) are included in the
system.
cAny system must
connection with the boiler. A trap should be installed in the flow line to collect any
solder, or other debris, from the installation.
dAll water systems must be constructed to comply with requirements of the Local
Water Authority.
eOnly fully pumped systems can be used - gravity systems are strictly
fAlways use a system complying with the requirements of BS 5449 and BS 6798.
gThe system must be so arranged that there shall always be a minimum flow of
13.2 gpm (60 litres/min) when the boiler is firing.
be thoroughly flushed clean of grease, dirt and debris, prior to
not suitable.
This can be via a specially
installed by-pass arrangement.
hCopper tubing to BS 2871 Part 1 is recommended.
iJointing should be either with capillary, threaded or compression fittings. Pipes
should have a gradient to ensure air is passed easily to vent points and water
flows readily to drain points.
jDraining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 22 mm in
nominal size and be in accordance with BS 2879.
AIR VENT POINTS
kThese must be fitted at all high points where air will naturally collect and must be
sited to allow complete draining of the system.
2.7.1Open Vented Systems
A typical system is shown in Figure 2.7.1 which includes a combined feed and
vent. Note there must be no valve between the boiler flow and the open vent.
Note that the minimum static head required is 9 ft at the boiler flow pipe. If the
cold feed/vent is not brought to the flow pipe as shown, then the pressure loss
across the heat exchanger may have to be taken into account when estimating
the static pressure.
Although suitable for open vented systems with combined feed and vent
arrangements, the Keston is a low water content boiler. As such, any air
entrainement within the system water will produce boiler “kettling”. It is
therefore recommended, if in any doubt, to consider the use of sealed
Sealed systems must be designed in accordance with BS 5449 and BS 7074 Pt1.
A typical sealed system is shown in Figure 2.7.2. It must include :
(i)A safety valve fitted on the flow, adjacent to the boiler. It must be non
(ii)An expansion vessel complying with BS 4814 and sized in accordance
(iii)A filling point, in accordance with local water authority requirements.
(iv)A method of system make-up (automatic or manual), in accordance with
(v)There must be no permanent connection of mains water to the boiler
(vi)The installation must be designed to work with flow temperatures of up to
Figure2.7.1 : Open Vented System Diagram
adjustable and preset to 3 bar. A drain pipe must be attached, at least as
big as the valve connection, and routed to drain in any area not
hazardous nor where it may be subject to freezing.
with the requirements of BS 5449 and BS 7074 Pt 1. The vessel must be
positioned on the inlet to the pump.
In the initial charge of water to the boiler system and in all subsequent additions
of water to the system some air will be dissolved in the water. As the water is
heated the air is driven out of the solution and will collect in high spots in the
system. These air bubbles can interfere with pumping and heat transfer and
must be eliminated.
Installation of air bleed valves at the high spot(s) in the system will allow for air
elimination when filling the system and will allow re-venting in a day or so after all
air has been driven out of solution.
2.7.6Strainers
Debris in the heating
system can cause noise if
it enters the heat
exchanger. Fitting of a
Y-strainer ahead of the
circulating pump will trap
any debris left in the
system and will protect
the pump from damage.
The boiler guarantee
does not cover heat
exchanger failure due to
debris abrasion within the
system.
Y-Strainer will
collect an y loose
debris in the piping.
Figure 2.7.6 Strainers
2.7.7Pump Selection
The Keston boilers have low
water content heat
exchangers with a high
resistance to flow, when
compared with cast iron heat
exchanger boilers. As a result
selection of the correct pump
is essential
localised boiling within the
heat exchanger. The selected
pump must be capable of
maintaining the required flow
rate for the boiler against the
pressure losses contributed
by the boiler.
The Keston 170
condensing boiler offers a
hydraulic resistance of
4.2m (13.75ft) water at the
required flow rate of 60 l/m
(13.2 gpm).
If a single pump is to be used
for the entire installation the
boiler resistance must be
added to the pressure loss
caused by the rest of the
'Horizontal' flue outlet pipework MUST slope at least 5 degrees (80 mm per metre
run) downwards towards the boiler. Pipework can be vertical. Only swept elbows
can be used.
Air inlet pipework can be truly horizontal or vertical, or sloping in a downward
direction towards the boiler but in this case rain, etc, must
be prevented from
entering the pipe. There must be no troughs in any of the pipework, whetherit be air inlet or flue outlet. If a 80 mm per meter slope is not possible, contact
Keston Boilers Technical Department for further guidance.
Due the low temperature of the
flue gases further condensate
will form within the flue system.
Drain points, with suitable
traps, must therefore be
incorporated within the flue
system at the base of vertical
flue sections in excess of 2m.
These additional condensate
drains must be run to
discharge as detailed in
section 2.11. Such drain points
can be formed using standard
muPVC fittings. Refer to the
example in Figure 2.8.3.
2.8.4Terminations
Air inlet terminals must be
facing upwards and positioned
to ensure only fresh air is drawn into the boiler. The air terminal must be located
outside of the building. Drawing of combustion air directly from a ventilated boiler
room will invalidate the heat exchanger warranty. The air intake terminal must
face upwards to prevent entry of rain into the air intake pipework.
The flue outlet terminal is designed to face outwards but can, if desired, be
adapted to face in any direction BUT must not be directed in the region of the air
inlet.
Dimensions (mm)
Flue
Terminal
Air
Inlet
50300A Below openable window, air brick, etc.
7575B Below gutters, soil pipes, drain pipes.
50300C Below eaves.
50200D Below balconies or car port roof.
5075E From vertical drain or soil pipes.
50600F From internal or external corner.
100300G Above ground or balcony or roof.
100600H From surface facing a terminal
1,2001,200IFrom terminal facing a terminal.
1001,200J From opening in a car port.
1,5001,500K Vertically from terminal on same wall.
300300L Horizontally from terminal on same wall.
Table 2.8.4Minimum Flue Terminations & Air Inlet Dimensions
The two terminals are subject to the requirements of BS 5440 Pt 1 for clearances
from features of the building although some can be decreased to the values
indicated.
If either the air inlet or the flue outlet terminate at a height of less than 2m (6ft)
above ground level the termination must be protected by a suitable guard. The K4
terminal guard, manufactured by Tower Flue Components Ltd, is suitable for this
purpose and can be obtained from Keston Boilers.
The Keston condensing boiler, as with any condensing boiler, will generate a
condensate “plume” from the flue terminal in all weather conditions. Consideration
must therefore be given to the effect of this “plume” when selecting a location for
the flue terminal. It is advisable, for horizontal flue terminals, to place a 45
O
elbow
at the end of the flue to direct the condensate plume up and away from the
property,
2.8.5Clearances From Wall
Flue outlet and air inlet terminations must be at least 60 mm and 95 mm
respectively from the wall face.
2.8.6Distance Between Flue Outlet & Air Inlet
There is no maximum - the terminations can be on opposite sides of the dwelling
if desired.
A minimum clearance of at least 500 mm must be left between the terminations.
2.8.7General Installations
All parts of the system must be constructed in accordance with BS 5440 Part 1,
except where specifically mentioned in these instructions.
All pipework must be adequately supported.
All joints other than push-on or plastic compression connectors must be made
and sealed
with solvent cement suitable for muPVC pipes and conforming to BS
6209: 1982.
External wall faces and any internal faces of cavity walls must be made good.
2.9AIR SUPPLY
The Keston is a room sealed appliance and therefore does not require purpose provided
ventilation for combustion air.
2.10COMPARTMENT INSTALLATION
The casing temperature of the Keston 170 is very low. Due to this fact, no compartment
ventillation is required for cooling purposes.
2.11CONDENSATE DRAINAGE
Being a condensing boiler, the Keston is fitted with a condensate trap at the base of the
heat exchanger and flue assembly, with facility to connect to a drain point underneath the
appliance.
Use only plastic piping and do not reduce below 15mm internal diameter within the
dwelling. Condensate should preferably be drained into the sanitary waste system or,
alternatively, the rainwater system of the property.
Termination of the pipe must be either at a branch or stack internal to the house, or
externally at an open gully. Alternatively, discharge into a purpose made condensate
soakaway can be considered. Existing or purpose built drains must use suitable corrosion
resistant material as condensate is mildly acidic.
A minimum slope downwards towards the drain of 1 in 20 is essential. Freezing of the
termination and pipework must be prevented. Any drainage pipes outside the property
must be at least 32 mm inside diameter.
2.12RADIANT FLOOR HEATING
The low operating temperatures of this type of system lead to very good operating
efficiencies. In fact, under floor heating can produce in excess of 95% operating efficiency
from a Keston condensing boiler.
Water temperatures in radiant floor heating systems must be kept relatively low, generally
under 48
o
C, so that surfaces do not become uncomfortably warm to the touch. If radiant
heating is only one application for a multi-zone system which also requires higher delivery
water temperatures for other zones (i.e. water heating, skirting heaters etc.) then the
radiant floor zone temperature will need to be controlled separately from the boiler.
If radiant floor heating is the only application of the boiler, the boilers maximum operating
temperature can be lowered accordingly by introducing a supplementary control
thermostat within the control system of the installation.
Mixing valves are also available which will mix return water from the system with boiler
output water to dilute the temperature of water transmitted to the distribution system.
Mixing valves may create problems with low flow and high temperatures through the
boiler, unless care is taken to design a system which will provide proper flows and will fully
load the boiler. Keeping the boiler's temperature high will prevent the boiler from operating
at peak efficiencies. Systems which maintain boiler temperatures in this way should be
avoided.
Installation & Servicing Instructions
Page : 14
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.