Keston 50 - GC, 80 - GC, 60 - GC, 50, 80 Installation And Servicing Instructions

...
Page 1
Fan Powered High Efficiency Condensing Gas Boiler
Installation And Servicing Instructions
Keston 50 - GC No 41 930 01 Keston 60 - GC No 41 930 02 Keston 80 - GC No 41 930 03
PI No. : 87AQ306
These instructions must be left either with the user or next to
the household gas meter.
34 West Common Road
Tel. (44)0208 462 0262 Fax. (44)0208 462 4459
WD50/2/1997 The Keston 50, 60 & 80 Condensing Boilers
0087
Page 2
CONTENTS
Section Description 1 GENERAL INSTRUCTION
1.1 Description
1.2 Boiler Schematic
1.3 Related Documents
1.4 Performance Data
1.5 General Data
2 BOILER LOCATION
2.1 Dimensions & Minimum Clearances
2.2 Service Connections
2.3 Position
2.4 Electrical
2.5 Boiler Size Selection
2.6 Gas Supply
2.7 Water Systems
2.8 Flue System
2.9 Air Supply
2.10 Compartment Installation
2.11 Condensate Drainage
2.12 Radiant Floor Heating
2.13 Low Water Volume Boiler vs. Cast Iron Boiler
2.14 Determine Radiation Needed Room-By-Room
3 INSTALLATION OF THE BOILER
3.1 Wall Mounting Bracket
3.2 Mounting The Boiler
3.3 Assembly Practice
3.4 Installing Flue And Air Pipes
3.5 Condensate Drainage
3.6 Water System
3.7 Gas Supply
3.8 Electrical Supply
3.9 Exchanging A Boiler
4 COMMISSIONING OF THE BOILER
4.1 Initial Flushing
4.2 Gas Supply
4.3 Electrical Installation
4.4 LP Gas Conversion
4.5 Initial Firing
4.6 Hot Flushing
4.7 Checking The Gas Pressure
WD50/2/1997 The Keston 50, 60 & 80 Condensing Boilers
Page : i
Page 3
4.8 Timing The Gas Meter
4.9 Handing Over To The User
5 FAULT FINDING
5.1 Electrical Control Sequence
5.2 Fault Finding Flow Chart
5.3 Continuity Checking
5.4 Functional Flow Wiring Diagram
5.5 Electrical Wiring Diagram
5.6 Illustrated Wiring Diagram
5.7 Exploded Assembly Diagrams
6 SERVICING
6.1 Pre Service Checks
6.2 Recommended Routine Service
7 REPLACEMENT OF PARTS
7.1 General
7.2 Precautions
7.3 Access
7.4 Electrical
7.5 Gas Orifice
7.6 Spark Ignition/Flame Detection Electrode
7.7 Burner Head & Burner
7.8 Heat Exchanger
7.9 Air Filter
7.10 Condensate Trap
7.11 Pressure Gauge
7.12 Sight Glass
7.13 HT Ignition Lead
7.14 Air Vent
7.15 Air Orifice
8 SPARE PARTS LISTINGS
WD50/2/1997 The Keston 50, 60 & 80 Condensing Boilers
Page : ii
Page 4
1. GENERAL INSTRUCTION
1.1 DESCRIPTION
The Keston Condensing Boiler is unique in its concept and des ign. While the application for which the boiler was designed is the same as those which other boilers are us ed the Keston boiler has the added advantage of very high efficiency, and small diameter plastic flue which can be extended to 10 metres horizontally or vertically.
The Keston uses a high power combustion blower to deliver a pre-mix of gas and air to a downward firing burner in a high efficiency, single pass heat exchanger.
Normally the combustion temperature of the air gas mixture is around 1800
o
C but the
Keston achieves combustion at an amazing 1000
o
C thereby reducing the NOx emissions
down to an incredible less than 5 p.p.m. The flue system is room sealed and fan powered. The ignition is direct spark and fully
automatic. The boiler housing is not waterproof. The boiler should be installed in a position where it will always be dry. A small air intake point is incorporated within the appliance cabinet to ensure that the interior of the c abinet is maintained under a slight negative pressure. This is a safety feature to ensure no products may leak out of the cabinet into the installation space.
The boiler is suitable f or connection to open vented or sealed system s. The s ystem mus t be pumped central heating or pumped central heating with combined indirect domestic hot water. Gravity circuits must not be used.
The boiler has a primary heat exchanger which, through its combustion chamber and corrugated coil, transfer s the heat produced in the hot gases of combustion pr ocess into the circulating water. Head characteristics of the boiler coil must be taken into consideration when calculating the pump size.
The Keston boiler is not a high water content boiler and does not contain the metal mass, or water volume, of a cast iron or steel boiler. This boiler is of low mass and low water content and therefore responds faster when there is a call for heat. This f eatur e requir es a higher water pumping rate through the boiler otherwise localised boiling will occur within the boiler.
Allow a pressure drop through the boiler of 3.2 ft head and a water flow of 4.2 gallons (19 litres) per minute f or the Keston 50, 4.3 ft head and 5 gallons (23 litres) per m inute for the Keston 60 and 9 ft head and 6.7 gallons (30.5 litres) per minute for the Keston 80.
The boiler selected m ust be sized relative to the total c alculated heat loss of the building. The boiler rated output should not be greater than the total required to make up the calculated heat loss plus the heat required to provide domestic hot water. If there are special conditions such as excessive domestic hot water usage consult the manufacturer.
1.2 BOILER SCHEMATIC
Air is drawn into the boiler through a 40mm ( BS5255) m uPVC pipe. T he air f low is proved by a differential pressure across the air control orifice.
Gas is mixed with com bustion air at the inlet to the fan. T he gas flow is regulated by an orifice located in the housing downstream of the gas valve.
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 1
Page 5
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 2
Figure 1.2 Boiler Schematic
LEGEND
1 Heating Return 2 Water Return Thermostat 3 Downstream Pressture Test Nipple 4 Flame Ignition/Sensing Probe 5 Burner 6 Automatic Air Vent 7 High Limit Thermostat 8 Heating Flow 9 Flue Exhaust 10 Air/Gas Flexible Connector 11 Air Filter 12 Air Inlet Flexible Connector
13 Ignition Control Box 14 Gas Low Pressure Switch 15 Gas Multifunctional Control 16 Gas Inlet Flexible Connector 17 Air Pressure Switch 18 Combustion Bl ower 19 Condensate T rtap 20 Flue Overheat Thermostat 21 Heat Exchanger 22 Flow Overheat Thermostat 23 Water Low Pressure Switch 24 Combustion Test Point
Page 6
The gas and air are thoroughly mixed in the blower and fed into the bur ner located at the top end of the heat exchanger module. The gas and air m ix ture is ignited by a direct spark ignition control system and burns with a blue flame j ust off the surface of the burner. As the hot products of com bustion pass downwards, they are cooled, exchanging heat with the circulating water which enters the heat exchanger coil at the bottom of the heat exchanger.
When the return water temperature is below 54oC, part of the water vapour in the combustion products will condense inside the heat exchanger , thus increasing the boiler efficiency. This condensate f alls to the bottom of the heat exchanger where it is separ ated from the flue gases and exits from the boiler through the condensate drain. Any condensate formed in the flue runs back down the flueway and is drained at the base of the flue connection to the heat exchanger.
The condensate is very slightly acidic (about the same acidity as vinegar) and should be piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed of as normal waste water.
The flue gases are piped in a 40m m m uPVC pipe to the outside. The temperatur e of the flue gases are usually less than
10oC above the temperature of the retur n water. The flue
pipe should be terminated outside the building from where they cannot re-enter the building or any other adjacent building or cause a nuisance by pluming.
The heating level may be controlled by room thermos tats, hot water cylinder thermostats and programmer time clocks.
1.3 RELATED DOCUMENTS
The Keston Condensing Boiler must be ins talled in accordance with the current issue of the Gas Safety (Ins tallation and Use) Regulations, c urrent IEE W iring Regulations, Safety
document no. 635 - The Electricity At Work Regulations 1989, Building Regulations, Building Standards (Scotland) Consolidation, and the Bye Laws of the local Water Undertaking.
In addition, due account must be taken to the following Codes Of Practice:
BS 6891 : Gas Supplies BS 6798 : Installation Central Heating Boilers BS 5449 : Installation Pumped Central Heating BS 5546 : Installation Domestic Hot Water BS 5440.1 : Flues BS 5440.2 : Air Supply BS 5482.1 : Domestic Propane & Butane Burning Installations BS 7074.1 : Expansion Vessels BS 7593 : Treatment of Water in Hot Water Central Heating
Systems
BS 7671 : Requirements for Electrical Installations. IEE Wiring
Regulations 16th Edition.
For Timber Framed Buildings, British Gas Publications DM2. Also British Gas Publications 'Guidance Notes For The Installation Of Domestic Gas Condensing Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 3
Page 7
1.4 PERFORMANCE DATA
Keston 50 Keston 60 Keston 80
10 to 1510 to 1510 to 15
o
CRecommended Temperature
Differential
3.432.712.38mmGas Orifice Size
8.08.08.0in. w g
20.020.020.0mbarInlet Gas Pressure
8.0
8.08.0
Ft
2.5
2.5
2.5MMinimum Head (Open Systems)
2.702.702.70BarMaximum Pressure (Sealed Systems)
100.0100.0100.0Ft
30.5030.5030.50MMaximum Head (Open Systems)
80.0080.0080.00
o
CMaximum Operating Flow
(CV of Gas - 38.7 MJ/m3) (1038 Btu/Ft
3
)
89.1165.854.43Ft
3
/HrRunning
0.70.510.43L/SGas Consumption After 10 mins
3.943.542.36in w.g.
(FACTORY PRESET)
1096mbarBurner Setting Pressure (Hot)
88,80065,00054,000Btu/h60
o
C Flow 40oC Return
2619.215.8KWBoiler Output To Water
80,00060,00050,000Btu/h80
o
C Flow 60oC Return
23.5 17.514.7KWBoiler Output To Water
92,50068,30056,500Btu/h
27.119.916.6KWBoiler Input
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 4
Page 8
1.5 GENERAL DATA
Keston 50 Keston 60 Keston 80
3.30 litres2.35 litres2.35 litresWater Content
Rear panel inside caseRear panel inside caseRear panel inside caseData Badge Posn
50 kg (110 lbs)44 kg (97 lbs)44 kg (97 lbs)Weight - Empty
52 kg (114 lbs)46 kg (101 lbs)46 kg (101 lbs)Weight - Full
5 Amps5 Amps5 AmpsExt. Fuse Rating
175 W140 W140 WPwr Consumption
230V 50Hz230V 50 Hz230V 50 Hz Power Supply
28 mm Copper28 mm Copper
28 mm
Copper
Return Connection
28 mm Copper28 mm Copper
28 mm
CopperFlow Connection
0.5 inch BSPT Male (15mm to gas cock)
0.5 inch BSPT Male (15mm to gas cock)
0.5 inch BSPT Male (15mm to gas cock)
Gas Supply Connection
Keston FilterKeston Filter Keston FilterFilter
Tridelta FS 6717 - 1428Tridelta FS 6717 - 1428Tridelta FS 6717 - 1428Air Pressure Switch
Full Sequence ControlFull Sequence ControlFull Sequence ControlIgnition
RAM ElectronicsRAM Electronics
RAM
Electronics
Direct Spark
0.18 KW 2900 RPM0.18 KW 2900 RPM0.18 KW 2900 RPM
Type LPB 102 220/240Type LPB 102 220/240Type LPB 102 220/240
KestonKestonKestonCombustion Fan
36E Series36E Series36E Series
White RogersWhite RogersWhite Rogers Gas Control
Keston PremixKeston PremixKeston PremixMain Burner
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 5
Page 9
2. BOILER LOCATION
2.1 DIMENSIONS AND MINIMUM CLEARANCES
The boiler must be installed in minimum clearances shown to allow subsequent servicing, and safe operation.
2.2 SERVICE CONNECTIONS
Gas, water, air and flue pipe, condensation, and electrical connections are as shown. Gas : 0.5 inch BSP male. Flow/Return : 28 mm
copper.
2.3 POSITION
The Keston is not suitable for external installation. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Where a room-sealed appliance is installed in a
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 6
All dimensions in mm.
254
305
127
Figure 2.1.1 Minimum Clearances
1
1
All dimensions in mm.
500
3
0
0
Figure 2.1.2 Dimensions
712 (Kest on 50 & 60)
Air Intake
Flue
Return
Flow
890 (Keston 80)
27
47
Top View
68
30
37
97
Base View
Service Connection Locations
All dimensions are in mm.
60
405
237
181
Page 10
room containing a bath or shower, any electrical switch or appliance control, utilising
mains electricity, should be so situated that it cannot be touched by a person using the bath or shower.
Compartment installation is permitted - such compartments must be constructed in accordance with BS 6798.
The wall on which the boiler is mounted must be of suitable load bearing capacity and must be non-combustible.
Important : It is not recommended to install the boiler on a studded wall or similar - it is possible that the vibration from the fan would be amplified and transmitted to other parts of the house.
Chimneys not used for venting any other
appliance may be used.
Figure 2.3
Secure air & flue pipes at chimney outlet.
[NB: Refer to Section 2.8.3]
The Keston can be located virtually anywhere desired provided that all regulations are met. Because of the boiler's compact size and venting flexibility, the installation is not limited to a boiler room setting. Before locating the boiler near a living space consider whether the sounds generated by the boiler will be objectionable. Sound levels from the boiler are no greater than from any other type of high-efficiency boiler but even minimal levels may be objectionable if located near a bedroom or in a living area.
2.4 ELECTRICAL
2.4.1 Electrical Connections
The boiler must be connected to a 230V ~ 50Hz supply, fused at 5A. All external controls and wiring must be suitable for mains voltage. Wiring
external tothe boiler must be in accordance with current I.E.E wiring regulations and local regulations.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 7
Page 11
The method of connection to the mains electricity supply must facilitate complete electrical isolation of the boiler complying with the requirements of BS
1363. The appliance must be connected to the supply via a fused double-pole switch,
having at least 3mm (1/8 inch) contact separation in both poles, serving only the boiler and the system controls.
The connection point to the mains supply should be readily accessible and adjacent to the boiler, except for rooms containing a bath or a shower. Refer to section 2.3 Position.
2.4.2 External Wiring & Controls
1. The boiler is deisgned so that all control wiring is external to the boiler. Hence, any programmers or room thermostats etc must act by switching the 230V supply to the boiler.
2. System designs which allow the boiler to fire when there is no pumped circulation must NOT be used.
3. A programmer may be used with zone valves to give independent control of central heating and hot water.
2.5 BOILER SIZE SELECTION
The size of the boiler to be used is determined by the total calculated heat loss of the building. Match the calculated heat loss with the boilers rated output. If a boiler is
installed with an output rating greatly exceeding the total capacity of the distribution system the efficiency of the boiler will be reduced. If the boiler is to be used to heat
domestic hot water no additional capacity is normally needed for the average residential installation since there is usually some excess capacity in the boiler as water heating is an intermittent load.
2.6 GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas supplier or their contractor. An existing meter should be checked preferably by the gas region to ensure that the meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891.
Minimum/Maximum Natural Gas Pressure:
Natural gas pressure before the gas valve must be maintained at 20 mbar (8 in w.g) while the boiler is running. Gas pressures above or below this level will lead to problems associated with the gas valve's internal pressure regulator.
Minimum/Maximum L P Gas Pressure:
LPG pressure must be maintained between 31.5 mbar (12.4 in w.g) and 37.6 mbar (14.8 in w.g) while the boiler is running
. Gas pressures above or below these levels will lead to problems associated with the gas valve's internal pressure regulator.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (15 mm) Due consideration must be given to the supply pressure to other gas appliances in the premises.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 8
Page 12
A gas cock is supplied loose with the boiler. This cock should be fitted in the gas line to the boiler as close to the boiler as possible so that it is easily identified as the cock to isolate the boiler.
2.7 WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply Bylaws for forced hot water heating systems. Consideration must be given to pipe capabilities and pressure drop through the piping. Water treatment must be carried out to BS 7593 : Treament of Water in Hot Water Central Heating Systems. Pump isolating valves must be positioned as close to the pump as possible.
a The Keston is suitable for use on open, vented water systems with combined feed
and vent.
b It is preferable for use on sealed water systems, provided the appropriate
components required (see Section 2.7.2 Sealed Systems) are included in the system.
c Any system must
be thoroughly flushed clean of grease, dirt and debris, prior to connection with the boiler. A trap may be installed in the flow line to collect any solder, or other debris, from the installation.
d All water systems must be constructed to comply with requirements of the Local
Water Authority.
e Only fully pumped systems can be used - gravity systems are strictly
not
suitable.
f Always use a system complying with the requirements of BS 5449 and BS 6798. g The system must be so arranged that there shall always be a minimum flow of 4.2
gpm (19 litres/min) [Keston 50], 5 gpm (23 litres/min) [Keston 60] or 6.7 gpm (30.5 litres/min) [Keston 80] when the boiler is firing. This can be via a specially installed by-pass arrangement.
h Copper tubing to BS 2871 Part 1 is recommended. i Jointing should be either with capillary or compression fittings. Pipes should have
a gradient to ensure air is passed easily to vent points and water flows readily to drain points.
j Draining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 15 mm in nominal size and be in accordance with BS 2879. AIR VENT POINTS
k These must be fitted at all high points where air may collect.
2.7.1 Open Vented Systems
A typical system is shown in Figure 2.7.1 which includes a combined feed and vent. Note there must be no valve between the boiler flow and the open vent. Note that the minimum static head required is 8 ft at the boiler flow pipe. If the cold feed/vent is not brought to the flow pipe as shown, then the pressure loss across the heat exchanger may have to be taken into account when estimating the static pressure.
Although suitable for open vented systems with combined feed and vent arrangements, the Keston is a low water content boiler. As such, any air entrainement within the system water will produce boiler "kettling". It is therefore recommended, if in any doubt, to consider the use of sealed
systems where possible.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 9
Page 13
2.7.2 Sealed Systems
Sealed systems must be designed in accordance with BS 5449 and BS 7074 Pt1. A typical sealed system is shown in Figure 2.7.2. It must include :
(i) A safety valve fitted on the flow, adjacent to the boiler. It must be non
adjustable and preset to 3 bar. A drain pipe must be attached, at least as big as the valve connection, and routed to drain in any area not hazardous nor where it may be subject to freezing.
(ii) An expansion vessel complying with BS 4814 and sized in accordance
with the requirements of BS 5449 and BS 7074 Pt 1. The vessel must be
positioned on the inlet to the pump. (iii) A filling point, in accordance with local water authority requirements. (iv) A method of system make-up (automatic or manual), in accordance with
local water authority requirements. (v) There must be no permanent connection of mains water to the boiler
system. (vi) The installation must be designed to work with flow temperatures of up to
110
o
C.
All components of the system including the heat exchanger of the indirect cylinder must be suitable for a working pressure of 3 bar and a temperature of 110
o
C. Care should be taken in making all connections that the risk of leakage is
minimised.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 10
Boiler
Rad. 2 Rad. 1
Pump
Expansion Pipe
Expansion Tank
Minimum 8ft Height
Cylinder
Figure2.7.1 : Open Vented System Diagram
Keston
3 Way Valve
Strainer
By-pass Bal. Valve
L/S
22mm pipe
(minimum)
Page 14
2.7.3 Hot Water System (if applicable)
The hot water storage vessel must be of the indirect type (certain direct cylinders can be used provided
they are suitably adapted by fitting an immersion calorifier). DIRECT CYLINDERS MUST NOT BE USED. Further guidance is provided in BS 1394. It is advisable to fit a lockshield valve on the cylinder return
to enable balancing of flow rate through the cylinder.
2.7.4 Boiler By-pass Piping
Boiler water flows are critical to the operation of the boiler. If flow cannot be maintained through the system piping to meet the minimums required by the boiler (see paragraph 2.7 (g)). Insufficient water flows through the boiler will cause the boiler to "kettle" or even produce steam which can damage the heat exchanger and will invalidate the heat exchanger warranty.
It is normally advisable to incorporate a boiler by-pass in the system, especially if thermostatic radiator valves are used. The by-pass should be fitted with a lockshield valve to permit balancing of the by-pass flow rate. The flow/return differential should be 10
o
C to 15oC. The lockshield valve can be adjusted to
maintain this condition with the radiators fully heated.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 11
Valve
Boiler
Figure 2.7.2 : Sealed System Di agram
Keston
Pressure Gauge
Expansion Vessel
Double Check Valve
Pump
Air Vent
Make -up vessel. Max. capacity of 3 lt. (5pt)
Non-Return Valve
Auto Air Vent
Hose Union bib tap
Hosepipe (disconnected after filling)
Hose Connector
BS 1010:2 Stop Tap
Test Cock
Drain Cock
HEATING CIRCUIT
RETURN
FLOW
Strainer
Safety Relief
By-pass
Bal.
Valve
L/S
Page 15
2.7.5 Air Elimination
In the initial charge of water to the boiler system and in all subsequent additions of water to the system some air will be dissolved in the water. As the water is heated the air is driven out of the solution and will collect in high spots in the system. These air bubbles can interfere with pumping and heat transfer and
must be eliminated.
Installation of air bleed valves at the high spot(s) in the system will allow for air elimination when filling the system and will allow re-venting in a day or so after all air has been driven out of solution. Installation of an automatic air vent will ensure that any air, even minute amounts, which subsequently enters the system will be automatically removed.
2.7.6 Strainers
Debris in the heating system can cause noise if it enters the heat exchanger. Fitting of a Y-strainer ahead of the circulating pump will trap any debris left in the system and will protect the pump from damage.
2.7.7 Pump Selection
The Keston boilers have low water content heat exchangers with a high resistance to flow, when compared with cast iron heat exchanger boilers. As a result selection of the correct pump is essential
in order to avoid localised boiling within the heat exchanger. The selected pump must be capable of maintaining the required flow rate for the boiler against the pressure losses contributed by the boiler and the rest of the system.
Refer to the pressure loss/flow rate Table 2.7.7 to determine the pressure loss from the boilers. Add this to the pressure loss caused by the rest of the system and select a pump capable of meeting the flow rate required at the total pressure loss generated by the boiler and the rest of the system. The selected pump must comply with BS 1394.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 12
Y-Strainer will collect any loose debris in the piping.
Figure 2.7.6 Strainers
Figure 2.7.7 : Pressure Loss Graph
5
10 15 20 25 30
0.5
1.0
1.5
2.0
2.5
3.0
Water Flow - L/min
Pressure Loss - m
3.5
4.0
4.5
35
Keston 50 Keston 60
Keston 80
Page 16
It is important to note that the minimum flow rate must be maintained whenever the boiler is firing. Systems using zone valves must be specifically designed to only fire the boiler when the pump is running and the minimum flow rate can be achieved.
The Wilo Salmson Gold Star pump, or the Grundfoss 15/60 pump is normally suitable for use with the Keston condensing boiler range. However, in all cases due consideration must be given to the resistance to flow offered by the rest of the system when making a final pump selection. This is particularly important when using small bore underfloor
heating pipework.
Table 2.7.7 Pump Selection
2.8 FLUE SYSTEM
2.8.1 Design
Individual air supply and flue outlet pipes are used. The material used for flue outlet &/or air inlet must be muPVC to BS 5255 and of an internal diameter of 38 mm.
Both flue outlet terminal and air inlet terminal are supplied and are illustrated in Figure 2.8.1.
2.8.2 Maximum Lengths
The maximum lengths of both air inlet pipe and flue outlet pipe, when no bends are used, are as detailed below.
Maximum Air Inlet Length : 10.0 m Maximum Flue Outlet Length : 10.0 m
However, each bend used has an equivalent length that must be deducted from the maximum straight length stated above.
A 92.5
o
sweep elbow is equivalent to 1.0m straight length. Example: Air inlet uses two 92.5o sweep elbows. Hence, maximum length permissible (ie
a+b in figure 2.8.2) = 10.0m - 1.0m - 1.0m = 8.0m Flue outlet uses one 92.5
o
sweep elbow. Hence, maximum length permissible (ie
c+d in figure 7 = 10.0m - 1.0 m = 9.0m
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 13
9.0 ft
2.75m
27.5 kPa
4.3 ft
1.3m
13 kPa
3.2 ft
0.97m
9.7 kPa
Pressure Loss Through Boiler
6.7 GPM
30.5 litres/min
5.0 GPM
22.7 litres/min
4.2 GPM
19.1 litres/min
Min Flow Rate Required
Keston 80Keston 60Keston 50Boiler Model
Page 17
2.8.3 Slope
'Horizontal' flue outlet pipework MUST slope at least 2.5 degrees (45 mm per metre run) downwards towards the boiler. Pipework can be vertical. Only swept elbows can be used. Air inlet pipework can be truly horizontal or vertical, or sloping in a downward direction towards the boiler but in this case rain, etc, must
be prevented from entering the pipe. There must be no
troughs in any of the pipework, whether it be air inlet or flue outlet. If a 45
mm per meter slope is not possible, contact Keston Boilers Technical Department for further guidance.
Due the low temperature of the flue gases further condensate will form within the flue system. Drain points, with suitable traps, must therefore be incorporated within the flue system at the base of vertical flue sections in excess of 2m. These additional condensate drains must be run to discharge as detailed in section 2.11. Such drain points can be formed using standard muPVC fittings. Refer to the example in
Figure 2.8.3.
2.8.4 Terminations
It is not advisable to terminate air
intake or flue within a car port area.
Air inlet terminals must be facing upwards and positioned to ensure only fresh air is drawn into the boiler directly from outside the property. The flue outlet terminal is designed to face outwards but can, if desired, be adapted to face in any direction BUT
must not be directed in the region of the air inlet. The two terminals are subject to the requirements of BS 5440 Pt 1 for clearances from features of the building although some can be decreased to the values indicated. If either the air inlet or the flue outlet terminate at a height of less than 2m (6ft) above ground level the termination must be protected by a suitable guard. The K4 terminal guard, manufactured by Tower Flue Components Ltd, is suitable for this purpose and can be obtained from Keston Boilers. The Keston Condensing Boiler, as with any condensing boiler, will generate a condensate "plume" from the flue terminal in all weather conditions.
Consideration must therefore be given to the effect of this "plume" when selecting a location for the flue terminal.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 14
FLUE
AIR
c
d
a
b
Figure 2.8.2 : Flue & Air Maximum Length Example
Keston
6 in min.
Figure 2.8.3 :
Flue Condensate Drain Point Example
40mm Tee Fitting
To Boiler
To Terminal
Page 18
It is advisable for horizontal flue terminals to place a 45o elbow at the end of the flue to direct the condensate plume up and away from the property.
Table 2.8.4 Minimum Flue Terminations & Air Inlet Dimensions
2.8.5 Clearances From Wall
Flue outlet and air inlet termination must be at least 60 mm and 95 mm respectively from the wall face.
2.8.6 Distance Between Flue Outlet & Air Inlet
There is no maximum - the terminations can be on opposite sides of the dwelling if desired.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 15
300300L Horizontally from terminal on same wall.
1.51.5K Vertically from terminal on same wall.
1001.2J From opening in a car port.
1.21.2I From terminal facing a terminal.
100600H From surface facing a terminal
100300G Above ground or balcony or roof.
50600F From internal or external corner.
5075E From vertical drain or soil pipes.
50200D Below balconies.
50300C Below eaves.
7575B Below gutters, soil pipes, drain pipes.
50300A Below openable window, air brick, etc.
Air
Inlet
Flue
Terminal
Dimensions (mm)
Flue Outlet Terminal
Air Intake Terminal
Fi
g
ure 2.8.1 : Terminals
O43
65
36
70
170
O43
O67
Page 19
A minimum clearance of at least 350 mm must be left between the terminations.
2.8.7 General Installations
All parts of the system must be constructed in accordance with BS 5440 Part 1, except where specifically mentioned in these instructions. All pipework must be adequately supported. All joints other than push-on or plastic compression connectors must be made and sealed
with solvent cement suitable for muPVC pipes and conforming to BS 6209: 1982. External wall faces and any internal faces of cavity walls must be made good.
2.9 AIR SUPPLY
The Keston is a room sealed appliance and therefore does not require purpose provided ventilation for combustion air.
2.10 COMPARTMENT INSTALLATION
Where the appliance is installed in a cupboard or compartment, no air vents are required. The boiler will run sufficiently cool without ventilation.
2.11 CONDENSATE DRAINAGE
Being a condensing boiler, the Keston is fitted with a condensate trap at the base of the heat exchanger and flue assembly, with facility to connect to a drain point underneath the appliance.
Use only plastic piping and do not reduce below 22mm internal diameter within the dwelling. Condensate should preferably be drained into the house sanitary waste system or, alternatively, the rainwater system. Termination of the pipe must be either at a branch or stack internal to the house, or externally at an open gully. Alternatively, discharge into a purpose made condensate soakaway can be considered. Existing or purpose built drains must use suitable corrosion resistant material as condensate is mildly acidic.
A minimum slope downwards towards the drain of 2.5
o
(45mm fall in 1m) is essential. Freezing of the termination and pipework must be prevented. Any drainage pipes outside the house must be at least 32 mm inside diameter.
Further guidance is given in the British Gas Publication 'Guidance Notes for the Installation of Domestic Gas Condensing Boilers'.
2.12 RADIANT FLOOR HEATING
This type of heat distribution creates an exceptionally evenly heated environment and since it is hidden beneath the finished flooring does not interfere with furniture placement. The homeowner has complete freedom to decorate without having to contend with any heating equipment visible in the homes interior. The low operating temperatures of this type of system lead to very good operating efficiencies. In fact, under floor heating can produce in excess of 95% operating efficiency from a Keston condensing boiler. Water temperatures in radiant floor heating systems must be kept relatively low, generally under 48
o
C, so that surfaces do not become uncomfortably warm to the touch. If radiant heating is only one application for a multi-zone system which also requires higher delivery water temperatures for other zones (i.e. water heating, skirting heaters etc.) then the radiant floor zone temperature will need to be controlled separately from the boiler.
If radiant floor heating is the only application of the boiler, the boilers temperature limits can be lowered accordingly by introducing an external thermostat control mounted on the return pipework into the boiler. This thermostat can then be used to interrupt power
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 16
Page 20
supply to the boiler when the required temperature is reached. Mixing valves are also
available which will mix return water from the system with boiler output water to dilute the temperature of water transmitted to the distribution system. Mixing valves may create problems with low flow and high temperatures through the boiler unless care is taken to design a system which will provide proper flows and will fully load the boiler. Keeping the boiler's temperature high will prevent the boiler from operating at peak efficiencies. Systems which maintain boiler temperatures in this way should be avoided.
If only a portion of the boiler's available output is to be used for radiant floor heating a thermal storage tank will improve the boiler's operation and give adequate control of temperature for the distribution system. By heating water to be distributed to the radiant floor zone to the proper temperature in an indirect-fired water heater, full load conditions will be available to the boiler because the heat exchanger in the tank can be sized to match the boiler's output. The tank's thermostat can be set at the optimum operating temperature needed by the distribution system and short-cycling of the boiler will be prevented. In such insulations it is advisable to calibrate the thermal store's operating thermostat to become the controlling thermostat of the boiler, ie the thermal store operating thermostat is always activated to shut off the boiler before the boilers own thermostat is activated. An insulated thermal storage tank without the heat exchanger may also be used.
2.13 LOW WATER VOLUME BOILER VS. CAST IRON BOILER
Because of their high water content and mass of metal, cast iron and steel boilers are less responsive but somewhat more forgiving of design errors. Short-cycling of the burner on the temperature limit control is less pronounced, though no less detrimental to operation, because the boiler itself will absorb and radiate a significant amount of heat. Low water volume boilers respond more quickly to a call for heat, can be made more compact and lightweight, but must have adequate heat delivery systems to avoid short-cycling of the burner on the temperature limit control. The heat delivery system's output must be equal to or greater than the boiler's output to fully load the boiler or short-cycling will occur.
Likewise, pumping rates of water through low water volume boilers must be maintained so that water is moved through the boiler fast enough so as not to reach boiling temperatures. The slower the water moves through the boiler the more heat it will absorb and the higher the temperatures will rise. Consequently, the pump selected must be adequate to maintain that critical flow of water.
2.14 DETERMINE RADIATION NEEDED ROOM-BY-ROOM
A radiator or convector's ability to deliver heat is related to the water temperature and the rate of delivery to the unit. Most systems in the past have been rated at about 80
o
C. Higher efficiencies can be gained from a condensing boiler if ratings published at lower temperatures are used. However, this is not imperative. With normal 80
o
C ratings used a condensing boiler will still deliver significantly higher efficencies than a non-condensing boiler. Lower water temperatures in the system tend to increase the efficiency of the boiler and will help assure that the boiler is subjected to a sufficient load to avoid short-cycling.
The Keston boilers are capable of temperatures of up to 80
o
C but the higher the temperature of the return water, the lower the efficiency of the system. This is true of all boilers, though all non-condensing boiler must be kept at higher temperatures to avoid condensation in the boiler which destroys such boilers quickly. Materials used in the Keston are made to withstand the condensates corrosive nature.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 17
Page 21
3. INSTALLATION OF THE BOILER
Read Chapter 2 - Boiler Location and decide upon the position of the boiler. Installation of the boiler is straightfor ward but consideration m ust be given to access to allow flue
and air pipes to be pushed through walls and ceilings. The order in which the components are installed will depend upon particular site conditions, but in general it will be easiest and most accurate to install the boiler and then build up the flue outlet and air inlet pipes to the terminal ­this is the sequence described.
3.1 WALL MOUNTING BRACKET
a Place the bracket on the wall
horizontally with the pre-drilled holes at the bottom.
b Drill through the centre hole of
the bracket, plug the hole and fix in position.
c Using a spirit level make sure
the bracket is completely level and mark the position of the other screw holes.
d Remove the bracket and drill the
holes in the positions marked. Plug these holes.
e Screw the bracket to the wall
using screws of an appropriate size for the wall type (No. 12 x 2 inch wood screws normally suffice).
f Mark the bottom fixing hole and
drill for a No 8 x 1 inch wood screw. Insert plug.
3.2 MOUNTING THE BOILER
a Lift and locate the upper rear lip on the boiler to the boiler wall bracket. b Move the boiler sideways to centralise the boiler on the bracket. c Screw in the lower fixing screw.
3.3 ASSEMBLY PRACTICE
Remove all plastic debris and burrs when installing air intake piping. Plastic filings caused by cutting muPVC pipe must not be allowed to be drawn into the filter or combustion air blower. Prevent dust entering the air intake when cutting on building sites. Blower failure which is determined to be caused by plastic filings or other debris will not be covered by guarantee.
WD50/2/1997 Chapter 3 : Installation The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 18
All dimensions in mm.
Figure 3.1 Wall Mounting Fixing Locations
110
285
250
Page 22
Combustion air filters are fitted to the Keston condensing boilers as standard. This filter must be examined at least once every year, and more often in particularly dusty and dirty areas.
The combustion air filter will prevent plugging of the burner caused by dirt being trapped in the burner's outer mesh. The filter element supplied with the boiler is obtainable from Keston Boilers or its distributors.
3.4 INSTALLING FLUE AND AIR PIPES
Remember the flue pipe must
slope downwards back towards the boiler and this is best
achieved using 92.5
o
bends.
a From the two connections on the boiler, mark the positions of the two holes for
the flue and air pipes on the wall(s) or ceiling. To allow access to drill the holes it may be necessary to temporarily remove the boiler. If the boiler stays put then it is imperative that the front panel and top access plate are replaced and the two plastic pipes capped off whilst drilling. Under no circumstances must debris from the wall or cut pipes be allowed to enter the appliance or the plastic pipework.
b Drill the two holes in the wall/ceiling, preferably using a core drill.
3.4.1 Diameter of holes.
i) Allowance must be made for
socketed lengths if these are to be passed through the holes :
du = unsocketted
diameter
= 43 mm
ds = socketed
diameter
= 50 mm
ii) For 'horizontal' runs of flue
pipe the holes must either be oversized or cut at a 5
o
slope (the latter may be difficult on long holes).
3.4.2 Oversizing
For every 1m length of run, L, the minimum diameter of the horizontal hole, D, must be du + 10 mm or ds + 10 mm respectively, assuming the pipe touches the wall at points T otherwise D will have to be increased by clearance from T. See Section 3.4.3 - Examples.
3.4.3 Examples
a. Wall Depth L = 750 mm
Unsocketted pipe du = 43 mm Diameter hole D = 43+{(
750
/
1000
)X10} = 43+7.5 = 50.5 mm
WD50/2/1997 Chapter 3 : Installation The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 19
D
L
d
u
T
d
s
Flue Pipe
T
Page 23
b. Wall depth L = 2.3 m
Socketed Pipe ds = 50 mm Diameter Hole D = 50+{2.3x10}
= 50+23 = 73 mm
c. Measure, cut and check the air and flue pipes to pass to the exit from the
wall(s) or ceiling.
Always thoroughly deburr all pipes and, most important, remove shavings from within the pipe.
d. Assemble, using adhesive, the pipework from the boiler connections to
the exit from the first wall/ceiling (remount the boiler if removed). When pushing pipe through walls, ensure grit and dust is not allowed to enter the pipe. Ensure pipes are fully engaged into sockets. Connect the condensate drainage system and fill the condensate trap by pouring water down the boiler flue spigot ( See Section 3.5 Condensate Drainage).
Make the final connection of flue and air pipe to the boiler using push on, or plastic compression couplings. Ensure that the connectors
are set vertically otherwise leakage of condensate may occur which will corrode the casing. Do not use adhesive on the 'push on' end of the connecting couplings.
e. Using the same methods drill any further holes (always covering existing
pipework), cut and assemble the pipework.
f. From outside, complete the two terminations - See Section 2.8 Flue
System and make good all holes.
g. Support any pipes whose route could be displaced either of its own
accord or by accident. Any horizontal run over 1m or vertical runs of any length must always be supported.
h. Check all connections for security and re-seal any joints using sovent
cement where soundness may be in doubt. Note: It is equally important to seal the air inlet with solvent cement as
the flue outlet pipe joints.
3.5 CONDENSATE DRAINAGE
Connect the condensate drainage system to the boiler. It is advisable to use a detachable fitting at connection to the boiler to enable easy removal for servicing.
Fill the condensate trap by pouring water into the boiler flue spigot until water is seen to flow freely from the condensate drainage system. Make the final connection of flue pipe to the boiler.
Details are provided in Chapter 2 - Section 2.11 Condensate Drainage Connection : 22 mm plastic pipe.
WD50/2/1997 Chapter 3 : Installation The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 20
FA
Fully Engaged
Adhesive
Page 24
3.6 WATER SYSTEM
Connect the flow and return pipework to the boiler. Ensure a detachable coupling is used at connection to the boiler (ie compression fitting) to enable heat exchanger removal if required. Details of system requirements are given in Chapter 2 - Section 2.7 Water Systems.
Connections : 28mm copper
3.7 GAS SUPPLY
Connect the gas supply to the appliance. Details of gas supply requirements are given in Chapter 2 - Section 2.6 Gas Supply.
Connections : 0.5 inch BSP male. (15mm connection to gas cock).
3.8 ELECTRICAL SUPPLY
The entry point for the electrical supply cable is in the base of the appliance (see Section
2.2 Service Connections fig. 2.1.2) via a cordgrip bush. Feed the cable through this bush and route inside the cabinet to the connection strip located to the front bottom right of the cabinet.
1. The electrical supply must be as specified in Chapter 2 - Section 2.4 Electrical Supply.
WARNING : THIS APPLIANCE MUST BE EARTHED.
2. All external controls and wiring must be suitable for mains voltage. Wiring should be in 3 core PVC insulated cable not less than 24/0.2 mm (0.75mm) to BS 6500 Table 16.
3. The supply connection must be via a 5 amp fused double pole switch, serving only the boiler and system controls. (Refer to Chapter 2 - Section 2.4 Electrical Supply).
4. Securely tighten the terminal screws and route the cable through the re-openable cable clips. Ensure all cables are secured and that the cord grip bush is tightened to securely grip the main cable at entry to the cabinet.
The mains cable must be connected to the terminals as follows:-
N - Blue wire (Neutral) L - Brown wire (Live)
- Yellow/Green Wire (Earth)
Ensure connection is made such that if the cable slips in its anchorage the current carrying conductors become taut before the earthing conductor.
3.9 EXCHANGING A BOILER
Before removing an existing boiler add Fernox Supafloc , or equivalent cleaning agent, in accordance with the manufacturers instructions. Open all radiator valves and fire the boiler. When the system is fully heated, shut off the gas supply and drain down the central heating system.
WD50/2/1997 Chapter 3 : Installation The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 21
Page 25
Important The Keston condensing boiler contains components which could be damaged or blocked by grease, dirt or solder etc. It is essential that sludge or scale is removed from an existing system.
Connect the new boiler as instructed in this manual and fit in accordance with Sections
3.1 to 3.8 For sealed systems, fill to a pressure of about 2.7 bar. Check the complete system for
water soundness. If leaks need to be rectified using flux or solder the system must be flushed cold again before proceeding.
Reduce the pressure to the Initial System Design Pressure for sealed systems, if applicable. Vent the system.
Gas Supply
The complete gas installation up to the boiler service cock must be checked for soundness. BS 6891.
Electrical Installation
Carry out preliminary electrical safety checks, i.e. Earth continuity, Polarity, Resistance to Earth, Short Circuit using a suitable test meter.
Initial Firing Checking The Gas Pressure At The Burner Pressure Test Nipple
The gas burner pressure must be checked at the burner pressure test nipple (Figure 5.7.3 item 54). Full details of this procedure are given in Section 4.7 Checking The Gas Pressure.
The gas pressure setting is factory adjusted to within the required range and should not normally need re-adjustment. If the reading is incorrect
then check such factors as soundness of the air and flue pipe joints, pressure sensible joints and the gas inlet pressure (20 mbar required). If all joints are sound and the gas inlet pressure is satisfactory set the gas pressure to the required
pressure.
WD50/2/1997 Chapter 3 : Installation The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 22
Burner pressure Adjustment
Burner pressure test nipple.
GAS VALVE
Page 26
4. COMMISSIONING OF THE BOILER
Important: This condensing boiler c ontains components which could be dam aged or block ed by grease, dirt, solder etc., from the water system. The following commissioning procedures must be followed precisely.
4.1 INITIAL FLUSHING
All waterways within the Keston are either copper or high alloy stainless steel. As a result standard water treatment chemicals for conventional central heating boilers are suitable. In any event reference must be made to BS 7593 : Treatment Of Water In Hot Water Central Heating Systems.
a. Disconnect the boiler from the system at the flow and return connections and
temporarily
link the flow and return pipes on the system.
b. Flush the entire system until clean water is discharged, free from dirt, flux, solder
etc. The use of a flushing chemical is recommended, e.g. Fernox Supafloc. Sludge and scale must be removed from an existing system.
c. Connect the system to the boiler and fill in accordance with Section 2.7 - Water
Systems. At this stage, for sealed systems, fill to a pressure of about 2.7 bar.
d. Check the complete system for water soundness. If leaks need to be rectified
using flux and solder, the system must be flushed cold again before proceeding.
e. Reduce the pressure to the Initial System Design Pressure for sealed systems, if
applicable. Vent the system
4.2 GAS SUPPLY
The complete gas installation up to the boiler service cock must be checked for soundness. BS 6891.
4.3 ELECTRICAL INSTALLATION
Carry out preliminary electrical safety checks, i.e. Earth continuity, Polarity, Resistance to Earth, Short Circuit using a suitable test meter.
4.4 LP GAS CONVERSION
All Keston condensing boilers are built and shipped as natural gas fired units. Field conversion kits are available to convert Keston condensing boilers to use LPG. Suitable instructions are supplied with the LPG field conversion kits.
4.5 INITIAL FIRING
Important Checking the gas pressure to the pre-mix burner requires a special procedure, outlined below, which must be carried out.
a. Purge the gas supply in accordance with BS 6891. b. Turn the gas service cock OFF. c. Loosen the screw in the burner pressure test point (Figure 5.7.3 item 106A) on
the gas valve and attach a suitable gauge.
WD50/0/1996 Chapter 4 : Commissioning The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 23
Page 27
d. Turn on the electrical supply, setting any external controls to call for heat. e. ON/OFF switch - select 'ON'. The amber 'run' light will illuminate on the ON/OFF
switch, the red 'lockout' light will illuminate, the blower and pump will start and, after about 15 seconds, a spark will attempt to light gas at the burner. With the gas service cock off, the boiler will go to lockout - red light illuminated, but the blower and pump will continue to run. At intervals of approximately 1 minute the boiler will make two further attempts to fire. After the final attempt the blower will run for a further 20 seconds before shutting down.
f. Vent the water system.
Important:
The
Keston heat exchanger consists of a single coil which can trap an air pocket. Great care must be taken to ensure that water flow has been established through the heat exchanger and thus ensuring no air pockets remain in the heat exchanger and pipe work. Firing the boiler while an air pocket exists in the heat exchanger could damage it.
g. Note the reading on the pressure gauge caused by the suction of the blower. This
should be approximately minus 12 mbar for the Keston 80, minus 26 mbar for the Keston 60 and minus 32mbar for the Keston 50. If it is not, check the system as follows:
If the negative pressure exceeds the required figure, then it suggests that there is a possible restriction in the air inlet pipework.
If the negative pressure is less than required figure, then it suggests that there is a possible restriction in the flue outlet pipework. Note the
exact reading. h. Turn the gas service cock to ON. i. Turn off the electricity supply, wait 10 seconds and turn back on. The boiler will
again go through its ignition sequence but this time the main burner will light, provided all air has been purged from the gas supply to the boiler. When the burner is lit and the boiler is operating normally the the green (run) lamp, the upper lamp adjacent to the flame symbol, will also be illuminated indicating successful ignition.(If it does not, air is indicated - turn off and repeat the procedure).
If this does not occur, the green (run) lamp, the upper lamp adjacent to the flame symbol, will be extinguished and, at approximately 1 minute intervals, the
electronic ignition system will make two further attempts to light the burner. If the ignition is successful and the boiler is operating normally, the green (run)
lamp, the upper lamp adjacent to the flame symbol, and the red (lockout) lamp will be illuminated simultaneously.
If, after three automatic attempts, the boiler still fails to ignite, the green (run) lamp, the upper lamp adjacent to the flame symbol, will be extinguished and the
red (lockout) lamp will remain illuminated. If, after five manual attempts (to allow for purging of any air in the gas line), the
boiler still fails to ignite (indicated by the red (lockout) lamp) refer to Section 5.2 ­Fault Finding Flow Chart.
j. Check for gas soundness between the gas service cock and connection to the
burner manifold.
WD50/0/1996 Chapter 4 : Commissioning The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 24
Page 28
4.6 HOT FLUSHING
a. Allow the system to heat up,
checking for water soundness.
b. Follow instructions provided with
the cleaning agent, ie Fernox Supafloc. Turn off the boiler and flush the water system while still hot. Thoroughly flush the system with clear water.
c. Refill the system using a quality water treatment such as Fernox MB1 or Fernox
Super Concentrate. If aluminium radiators are used then Fernox Copal should be used. For sealed systems, fill to the required Initial Design Pressure.
4.7 CHECKING THE GAS PRESSURE
With the boiler running measure the burner pressure at the burner pressure test nipple. The gas setting is factory adjusted to within the required range and should not normally
need re-adjustment unless the unit has also been converted to LPG as part of the installation. If the reading is incorrect then check such factors as soundness of the air and flue pipe joints and the gas inlet pressure (20 mbar required). If all joints are sound and the gas inlet pressure is satisfactory remove the brass dust cap covering the burner pressure adjustment screw on the gas valve (See fig. 4.7). Set the gas pressure to the required value as stated in table 1.4 by turning the exposed burner pressure adjustment screw (clockwise will increase burner pressure, anti-clockwise will decrease burner pressure). Replace the brass dust cap to cover the burner pressure adjustment screw.
4.8 TIMING THE GAS METER - NATURAL GAS
Table 4.8 Meter Timings
After the boiler has been started, and with no other appliances using gas, time the gas meter to be certain that the unit is running at the proper gas input. Determine the cubic feet of gas passing through the meter and determine the input in Btu per hour. Input must be within plus or minus 5% of the rated input.
Time, in seconds, the time taken to pass 2 cubic feet of gas through the meter (ie one revolution of a 2 cu ft dial) or 0.1 cubic metres if the meter is of the new metric digital type. Refer to table 4.8 to determine the input to the boiler and the time required for 2 ft
3
(or
WD50/0/1996 Chapter 4 : Commissioning The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 25
Burner pressure Adjustment
Burner pressure test nipple.
GAS VALVE
Fig 4.7
1011 btu/h per ft
3
NB:
152.3686.384,300Keston 80
203.9115.563,018Keston 60
236.2133.854,400Keston 50
Seconds For 0.1 m
3
Of Natural Gas
Seconds For 2 ft
3
Of Natural Gas
Btu/h Input RequiredModel
Page 29
0.1m3) of natural gas. Adjust the gas valve screw clockwise to increase the input (speed up the meter) or anticlockwise to decrease the input(slow down the meter) accordingly.
4.9 HANDING OVER TO THE USER
It is important to fully explain the following : a. Procedure to light and turn off the boiler, including isolation of the electrical supply
if necessary.
b. The function of the lockout feature must be explained :
If the red light only is illuminated for more than four minutes, this means that the boiler has failed to light. Turn off the electrical supply and wait 20 seconds. Turn ON again and wait. i) If lockout recurs immediately then the gas supply should be checked as
ON, otherwise consult a Service Engineer.
ii) If it is not possible to relight, the boiler must be isolated and a Service
Engineer called in to rectify the fault. c. Advise that a reduction in the water pressure reading on the gauge for sealed
systems indicates a leak which should be rectified before further use.
d. Advise that the appliance should be serviced by a competent person at least once
a year.
e. Advise on frost precautions. f. Hand over User Instructions.
WD50/0/1996 Chapter 4 : Commissioning The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 26
Page 30
5. FAULT FINDING
5.1 ELECTRICAL CONTROL SEQUENCE
When the external controls are calling for heat, power will be fed to the boiler connection strip at terminals L (Live) and N (Neutral). If the ON/OFF switch is also in the ON position the boiler ON lamp (amber) will be illuminated. Provided all temperature thermostats and pressure switches are closed, power will be fed to pin 2 on the control box, initiating the following sequence.
(1) The boiler lockout lamp (red) will be illuminated (2) The fan will start. (3) When the fan reaches running speed, the Air Pressure switch, normally open, will
close which will start the ignition sequence.
(4) After a pre-purge period of about 15 seconds, the gas valve will open to allow gas
to mix with the air at the suction side of the fan and the ignition spark will occur at the main burner.
(5) When the burner ignites, the flame is detected by the control box through the
combined flame sensor/ignitor and the ignition spark is stopped. Both the lockout lamp (red) and the boiler run lamp (green), the upper lamp adjacent to the flame symbol, will be illuminated. The boiler is now in its normal run condition.
(6) The burner will continue to operate until the gas valve interrupts the gas supply.
The gas valve will be closed by the control box if power is interrupted to the boiler by any external control or the boiler thermostat. If an interruption to the gas supply causes loss of the flame the control box with pause for approximately 10 seconds and then attempt to re-ignite the unit. If this attempt fails, ie due to lack of gas supply, the boiler will make two further attempts to ignite at intervals of approximately 1 minute and will then go into a lockout state (red lamp illuminated only). Once gas supply has been resumed the boiler can be reset by turning the boiler off and then on again via the on/off switch on the boiler control panel.
(7) The boiler can also be shut down by any of the flow limit, flow overheat and the
flue overheat thermostats, gas low pressure switch and by the low water pressure switch.
In such an event the green (run) lamp, the upper lamp adjacent to the flame symbol, will be extinguished and only the red (lockout) lamp will be illuminated.
Any failure of the boiler to sequence in the above manner should be investigated using the following trouble shooting flow diagram.
Before attempting any electrical fault finding, always carry out preliminary electrical system checks. On completion of any service/fault finding task which has required the breaking and remaking of electrical connections, the checks, earth continuity, polarity, short circuit, resistance to earth must be repeated.
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 27
Page 31
5.2 FAULT FINDING FLOW CHART
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 28
yes
no
yes
yes
no
no
no
yes
yes
no
yes
no
no
yes
Continued on sheet 2
no
yes
yes
no
yes
no
no
STA RT
Is amber switch light on?
Is ther e 23 0V be twe en
terminals L & N?
Is the boiler switched on?
Faulty Switch Neon
-Repl a ce.
Switch On Boiler.
Check External Controls.
Apply Power To Boiler.
Is the boiler thermostat closed?
Is ther e 23 0V be twe en co ntr ol
box pi ns 10 & 2?
Is the air pressure switch stuck
in the NO position?
Is there 230V between pins 6 &
neutral?
Is there con tin uity bet we en pi n
6 & Neutral through motor
resistance?
Is the fan running?
Is motor overload tripped?
Is ther e wi ri ng co nti nu ity
& in-line connector
to motor?
Boiler return is too hot. Allow
to cool. OR faulty thermostat -
Replce.
Check continuity (see section
5.3)
Faulty pipe connections to Air
Press. Switch. OR Faulty Air
Press. Switch - Replace.
Control box faulty.
Motor/Fan faulty - Replace.
Wait for motor to cool.
Identify & correct break.
Page 32
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 29
From sheet 3
yes
yes
no
Continued on sheet 3
no
yes
no
yes
yes
yes
yes
no
yes
no
no
no
no
yes
no
yes
no
Continued from sheet 1
yes
Does ignition sequence start?
Is lockout light on?
Has the Air Press. Switch
changed over?
Are tubes and connections to the Air Press. Switch sound?
Is the air press. across the Air
Press. Switch more than 4 in
water?
Is the air filter dirty or the air
inlet, exhaust or condensate
pipe blocked?
Is the Burner blocked
Fan faulty - change
Is the gas flow rate to the boiler correct
for the gas type in use (ie LPG or Nat.
Gas)?
Is gas supply pressure at gas
valve correct?
Is gas burner pressure per
specification (Section 4.7)?
Is gas valve openeing?
Check gas supply or turn on
gas cock.
Replace gas orifice.
Faulty gas valve - replace.
Switch off & if problem persists
replace control box.
Blocked air filter - replace
OR
Faulty control box - replace
Correct tube connection
Faulty pressure switc h -
replace
Replace air filter
OR
clear blockage
Clear blockage
Page 33
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 30
Continued on sheet 2
yes
no
no
no
yes
yes
yes
yes
no
yes
yes
no
yes
yes
no
no
no
Continued from She et 2
Is there 230V at valve
Is there 230V at Gas Low
Press. Switch
Faulty Control Box - Replace.
Faulty Ga s Va lve - Repl ace .
Faulty Gas Low Pressure
Switc h - Rep lac e
Is there a spark present?
Is the HT voltage present at
top of ignito electrode?
Is the s par k gap 4 mm ?
Faulty Conrtrol Box - Replace.
Replace/Adjust Spark Plug.
Does the burner ignite?
Electrode Faulty - Replace.
Recheck gas output pressure.
Check HT lead is securely
fixed. Clean or replace burner.
Does flame stop after 5 - 10
seconds?
Is boiler earthed correctly?
Are live and neutral supply
lines crossed at terminals L &
N?
Faulty Control Box - Replace.
Earth Boiler.
Correct Wiring.
Page 34
5.3 CONTINUITY CHECKING
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 31
STAR T
Is there 2 30 V a t term ina l L?
Is there 23 0V a t the ON /OF F
sw itch (b o th t erm in als )?
Is there 230V at the bo iler
thermostat (both term inals)?
Is there 2 30 V a t the fl ow
overheat thermostat (bo th
term inals)?
Is there 230V at the th ermal
fuse link (both terminals)?
Is there 230V at the flow high
limit the r mo sta t ( bo th
term inals)?
Is there 230V at the w ater
press. switch (both terminals)?
Is there 2 30 V at the flu e
protection thermostat (both
term inals)?
Check external c ontrols.
Faulty switch - Re place.
Thermosta t tripped - reset OR
faulty thermostat - Replace.
High cabinet temperature -
check a ll joints for pro ducts
leakage - Repl ace therma l fuse
High water temperature OR
faulty thermostat - Replace.
Check w ater level header
tank/system pressure OR faulty
switch - Re plac e
Thermosta t tripped - reset OR
faulty thermostat - Replace.
yes
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
no
no
Is there 230V at the gas low
press. switch (both terminals)?
Ch ec k g as su pp ly t o b o iler O R
faulty switch - Replace.
no
yes
To check continuity connect one probe to a neutral and use the other probe to check for 230V.
Boiler is up to tem perature.
Allow to cool OR pum p not
running OR fa ulty thermostat -
Replace
Page 35
5.4 FUNCTIONAL FLOW WIRING DIAGRAM
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 32
ON/OFF Switch
Boiler
Flow Overheat
Thermal Fuse
Flow High Limit
Low Water
Flue Overheat
RAM-2EMC22 IGNITION CONTROL
Thermostat
Thermostat
Thermostat
Thermostat
Pressure Switch
5
2
1
4
610
Lockout (Red)
Run(Green) Indicator
Gas Valve
Gas Low Pressure
ON/OF F Switch
Blower
N
L
Air Pressure Switch
EMC Filter
EMC Filter
8
230V 50Hz Fuse 5A
Link
Switch
Indicator
HT
Page 36
5.5 ELECTRICAL WIRING DIAGRAM
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 33
IGNITION CONTROL
RAM-2EMC22
13 121110
9 8 7 6 5 4 3 2 1
1
2
4 3
5
7 6
8
10
9
11
12
N
L
FILTER
ON/OFF SWITCH
GREEN LAMP
FLUE OVERHEAT THERMOSTAT
WATER PRESSURE
SWITCH
FLOW HIGH LIMIT
THERMOSTAT
FLOW OVERHEAT
THERMOSTAT
BLOWER
A.P.S.
GAS
SWITCH
GAS
VALVE
M
P
5R
BR
B
B
BR
6W
5BR 4B
91/OR
10/BK 9G
HV
92/OR
59PK
51/OR
52BK
53W
54G
55BR
90 R
Y/G
W
12V
11W
93 OR
7W
LEGEND
B -BLUE BK -BLACK OR -ORA NGE R -RED PK -PINK W -WHITE G -GREEN BR -BROWN V -VIOLET Y/G-YELLOW-GREEN
APS-AIR PRESSURE
SWITCH
L -INCOMING
LIVE
N -INCOMING
NEUTRAL
-INCOMING EARTH
12B
6BR
95G
93R
RED LAMP
BOILER
THERMOSTAT
THERMAL FUSE
56R
Page 37
5.6 ILLUSTRATED WIRING DIAGRAM
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 34
ILLUSTR A TED WIRING DIAGRAM
RAM Control
Overheat Stat
Flow High Limit S tat
Boiler Stat
Air Pressure Switch
Gas Valve
Flue Overheat Stat
Ignition Electrode
Low Water Pressure Switch
Gas Low Pressure Switch
Blower
5R
51OR
52BK
93OR
92OR
11W
55BR
10BK
Y-G
7W
6W
W 5BR 4B
N L
E
53W
54G
91OR
95G
93R
5R
12V
90OR
ON/OFF
SWITCH
9G
Lockout
Lamp
Run
Lamp
FILTER
1 2 3 4 5 6 7
9
10
8
59PK
B
BR
90R
c
1
2
3
4
5
6
7
8
9
10
11
12
Thermal Fuse
56R
d
Page 38
5.7 Exploded Assembly Diagrams
5.7.1 Boiler Controls Assembly
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 35
K50 - 05.4.00.00.0 K60 - 06.4.00.00.0 K80 - 08.4.00.00.0
BOILER CONTROLS
b
a
r
O
I
111
04.4.00.04.0
SEALING GASKET
13
SECTION 1
115
04.4.06.00.0
ON/OFF SWITCH
04.1.00.84.0
SCREW
RED LAMP
04.4.08.00.0
117
GREEN LAMP
04.4.07.00.0
116
GAUGE
04.4.09.00.0
118
NEON BULB
04.4.12.00.0
121
SCREW
04.4.00.10.0
TERMINAL BLOCK
04.4.05.00.0
113
04.4.04.00.1-K80
04.4.04.00.0-K50/60
110
SWITCH
AIR PRESSURE
MAUVE
BLUE/WH.
04.4.10.00.2
04.4. 10.00.0-K50/60
119
HARNESS
PACTRO L RAM
109
SUPRESSOR FILTER
MAINS
04.4.02.00.0
SECTION 1
4
114
BASE LABEL
TERMINAL BLOCK
04.4.00.03.0
63
SECTION 1
123
04.4.18.00.0
THERMAL FUSE
124
04.4.00.06.0
SCREW
125
04.4.19.00.0
FUSE SOCKET
SECTION 1
1
ASSEMBLY
04.4.20.00.0
FUSE ISOLATOR
143
04.1.00.40.0
SCREW
4
154
4
158
04.4.11.00.0
04.4.11.00.1
120
PACTRO L RAM
04.4.01.00.0
04.4.01.00.1
108
PACTRO L RAM
IGNITION CONTROL
IGNITION C AB LE
PACTRO L
08.4.10.00.0-K80
Page 39
5.7.2 Waterway, Condensate & Flue Assembly
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 36
K50 - 05.2.00.00.0 K60 - 06.2.00.00.0 K80 - 08.2.00.00.0
75
THERMOSTAT
WATER FLOW OU T
04.2.21.00.0
WATER WAY, CONDENSATE & FLUE ASSEMBLY
04.1.00.80.1
SCREW
52
51
04.2.13.00.1
IGNITER
50
04.2.00.28.2
IGNITER GA S KET
54
04.2.28.00.0
PRESS. TEST FITT .
53
04.2.00.29.1
SCREW
48
04.2.00.25.0
MANIFOLD
49
04.2.12.00.1
SIGHT GLASS
04.2.00.43.1
WATER INLET
62
47
04.2.00.24.1
GASKET
SEEGER RING
04.2.00.53.0
126
04.2.16.00.0
04.1.00.41.0
7
SCREW
DRAIN VALVE
04.2.00.54.0
GASKET
61
122
46
08.2.11.00.0-K80
06.2.11.00.0-K60
05.2.11.00.0-K50
BURNER
LABEL
04.2.00.58.0
HIGH VOLTAGE
45
04.2.10.00.0-K50/60
44
08.2.10.00.0-K80
HEAT EXCHANGER INSULATION
08.2.01.00.1-K80
04.2.01.00.1-K50/60
HEAT EXCH ANGER
43
04.2.17.00.0
THERMOSTAT
WATER RETURN
64
TRAP HOSE
CONDENSATE
04.2.00.34.1
58
04.2.00.57.0
HOSE CLAMP
67
CONDENSATE HOSE
04.2.00.48.1
71
CONDENSATE TRAP
04.2.14.00.1
59
28 BE ND
04.2.00.76.0
156
PIPE
04.2.00.60.0
28 WATER RETURN
76
04.2.00.65.0-K50/60
28 WATER RETURN
60
PIPE
08.2.00.65.0-K80
149
04.1.00.78.0
SCREW
55
04.2.00.32.2
WATER OUT
7
THERMOSTAT
04.2.22.00.0
FLOW HIGH LIMIT
78
MANIFOLD
79
SWITCH
WATER PRESSURE
04.2.23.00.0
04.2.20.00.1
AUTO AIR VEN T
72
04.2.00.66.0
28 WATER FLOW
74
PIPE
04.2.00.67.0
28 WATER FLOW
83
PIPE
04.2.00.61.0
77
28 ELBOW
04.2.00.33.2
56
GASKET
04.1.00.79.1
150
SCREW
EXHA UST PI PE
68
73
TEST PLUG
COMBUSTION
04.2.00.49.1
70
THERMOSTAT
FLUE OVERHEAT
04.2.19.00.0
04.1.00.41.3
69
SCREW
SECTION 3
97
04.2 .18.00.0-K50/ 60
08.2.18.00.0-K80
Page 40
5.7.3 Air - Gas Assembly
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 37
K50 - 05.3.00.00.0 K60 - 06.3.00.00.0 K80 - 08.3.00.00.0
AIR-GAS ASSEMBLY
PRESS. TEST FITT.
04.2.28.00.0
54
SCREW
04.3.00.28.0
104
GAS TEE
04.3.00.34.1
PRESSURE SWITCH
LOW GAS
04.3.09.00.0
04.3.07.00.0
REGULATOR GAS VALVE
95
92
RUBBER PLUG
04.3.00.18.0
04.3.00.39.0
AIR ORIF FICE SCREW
88
GASKET
94
04.3.00.20.0
54
04.3.00.19.0
AIR/GAS
MANIFOLD PLUG
93
05.3.00.17.0-K50NG
91
GA S O RIF IC E
05.3.00.17.1-K50LPG
06.3.00.17.0-K 60N G
06.3.00.17.1-K60LPG
08.3.00.17.0-K 80N G
08.3.00.17.1-K80LPG
84
FLEXIBLE TUBE
AIR/GAS
04.3.05. 00.1-K50/K60
103
AIR ADJ. SCREW
04.3.10.00.0
08.3.05.00.1-K80
SCREW
04.1.00.81.0
04.1.00.38.0
SEALING GASKET
GASKET
107
04.2.00.33.0
04.3.03.00.0
81
CAPACITOR
BLOWER
80
04.3.01.00.0
82
04.3.04.00.0
BLOWER
RUBBER ISOLATOR
17
SECTION 1
AIR HOSE CLAMP
04.3.00.21.0
96
08.3.00.15.0-K80
04.3.00.15.0-K50/K60
AIR INLET FLEX. CONNECTOR
89
97
04.3.08.00.3
GAS INLET
FLEXIBLE TUBE
08.3.00.13.1-K80LPG
08.3.00.13.0-K 80NG
06.3.00.13.1-K60LPG
06.3.00.13.0-K 60NG
05.3.00.13.1-K50LPG
AIR ORIFICE
87
05.3.00.13.0-K 50NG
GAS IN LE T GASKE T
04.3.00.29.0
99
NUT
04.3.00.30.0
100
102
04.3.00.32.0
HIGH PRESS. TUBE
LOW PRESS. TUBE
04.3.00.31.0
101
86
MANIFOLD
AIR/GAS
04.3.06.00.0
90
04.3.00.16.0
GAS VALVE SCREW
107
94
98
105
MAIN SOLE NOID
04.3.07.01.0
144
CONNECTOR BLOCK
04.3.07.02.0
145
151
04.3.07.03.0
SECONDARY SOLENOID
155
04.1.00.82.0
SCREW
152
21
04.1.00.76.0
SCREW
15
Page 41
5.7.4 Casing Assembly
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 38
W
A
R
N
I
N
G
L
A
B
E
L
W
A
T
E
R
I
N
L
E
T
E
X
H
A U
S
T
W
A
T
E
R
O
U
T
L
E
T
A
I
R
I
N
L
E
T
K
E
S
T
O
N
CASING ASSEMBLY
K50 - 05.1.00.00.0 K60 - 06.1.00.00.0 K80 - 08.1.00.00.0
SCREW
04.1.00.41.0
7
BURN ER ACCE SS COVER
04.1.00.32.0
6
28mm GROMMET
04.1.00.49.1
2
42mm GROMMET
04.1.00.47.0
26
FLOW LABEL
04.1.00.53.0
25
24
04.1.00.52.0
EXH AUST FLUE LA BE L
TOP COVER
04.1.09.00.1
5
HINDER CLAM P
17.1.00.03.2
65
SCREW
04.1.00.40.0
4
AIR INLET LABEL
04.1.00.51.0
23
NEG. PR. ADAPT.
04.`1.00.62.0
157
04.1.14.00.1
AIR FILTER COVER
3
AIR FILTER
17.1.12.00.0
22
37
04.1.00.61.0
CABLE HOLD ERS
NAME PLATE
05.1.00.50.0-K50
20
06.1.00.50.0-K60
08.1.00.50.0-K80
CONTROLS PLATE
04.1.19.00.1
63
11
04.1.00.43.0
WASHER
EARTHI NG LOCKWASHER
04.1.00.45.0
42
NUT
04.1.00.42.0
10
1
04.1.03.00.0-K50/60
OUTER SHELL
08.1.03.00.0-K80
34
04.1.00.58.0
TEST POINT LABEL
WIRE RETAI NER
04.1.16.00.0
ELECTRIC MAIN
33
GAS INLET LAB EL
04.1.00.59.0
35
57
04.1.00.75.0
PLASTIC PLUG
16
04.1.00.39.0
NUT
15
04.1.00.38.0
WASHER
22mmGROMMET
04.1.00.49.0
27
08.1.13.00.0-K80
FRONT DOOR
04.1.13.00.0-K50/60
12
148
04.1.00.77.0
SCREW
13
04.1.12.00.0
FRONT PANEL
36
04.1.00.60.0
FLAME LABEL
FOAM GASKET
04.1.00.48.0
31
WASHER
04.1.00.43.0
11
10
04.1.00.42.0
NUT
8
FIXING RO D
HE AT EXC HANGER
04.1.00.33.0
04.1.00.56.1
ILLUSTRATED WIRING DIAGRAM
30
32
05.1.00.57.0-K50
KESTON LABEL
SILENCER
04.1.20.00.1
14
19
04.1.00.35.0
BRACKET
40
04.1.30.00.0
EXHAUST TERMINAL
41
04.1.18.00.0
GAS VALVE
21
04.1.00.76.0
SCREW
18
17.1.09.00.0
SHUTTING CLAMP
WARNING LAB EL
04.1.00.55.0
29
FRONT DOOR SCREW
04.1.00.37.0
9
RETURN LABEL
04.1.00.54.0
28
BLOWER PLATE
04.1.00.36.0
17
06.1.00.57.0-K60
08.1.00.57.0-K80
Page 42
5.7.5 Exploded Diagrams Parts Reference List
Boiler Controls Assembly (Fig. 5.7.1) GC Number Code Description
E01 074 108 Ignition Control Box 170084 110A Air Pressure Switch (Keston 80) 379 744 110B Air Pressure Switch (Keston 50 & 60) 114 076 113 Electrical Terminal Block 114 077 115 On/Off Switch 114 078 116 Green (Run) Lamp 114 079 117 Red (Lockout) Lamp 114 080 119 Pressure Gauge
Waterway, Condensate & Flue Assembly (Fig. 5.7.2) GC Number Code Description
114 022 43A Heat Exchanger (Keston 50 & 60) 114 023 43B Heat Exchanger (Keston 80) 375 523 46A Burner (Keston 50) 375 524 46B Burner (Keston 60) 375 525 46C Burner (Keston 80) 375 526 47 Burner Head Gasket 114 028 49 Sight Glass 375 527 50 Ignitor Gasket 114 120 51 Spark Ignition Electrode 114 029 54 Pressure Test Nipple 114 032 59 Condensate Trap 114 035 61 Return Drain Valve 375 530 64 Boiler Thermostat 375 532 70 Flue Overheat Thermostat 114 043 73 Combustion Test Plug 114 042 72 Automatic Air Vent 375 533 75 Flow Overheat Thermostat 375 534 78 Flow High Limit Thermostat 114 045 79 Water Pressure Switch
Air - Gas Assembly (Fig. 5.7.3) GC Number Code Description
114 046 80 Combustion Blower 114 051/052/053 87A/B/C Air Orifice (Keston 50/60/80 Nat Gas) 114 089/090/091 87D/E/F Air Orifice (Keston 50/60/80 LPG) 375 536 95 Gas Valve 114 029 54 Pressure Test Nipple 114 073 105 Low Gas Pressure Switch 114 056/057/058 91A/B/C Gas Injector (Keston 50/60/80 Nat Gas) 114 061/062/063 91D/E/F Gas Injector (Keston 50/60/80 LPG)
Casing Assembly (Fig. 5.7.4) GC Number Code Description
375 541 1A Cabinet Outer Shell (Keston 50 & 60) 375 542 1B Cabinet Outer Shell (Keston 80) 114 002 20A/B/C Data Badge (Keston 50/60/80) 375 543 3 Air Filter Cover 114 105 22 Air Filter 375 545 5 Cabinet Top Cover 375 546 6 Burner Access Cover Plate 114 010 30 Illustrated Wiring Diagram 375 548 12A Front Door (Keston 50 & 60) 375 549 12B Front Door (Keston 80)
WD50/2/1997 Chapter 5 : Fault Finding The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 39
Page 43
6. ROUTINE (ANNUAL) SERVICING
To ensure the continued safe and efficient operation of the boiler it is necessary to carry out routine servicing at regular intervals. The frequency of the servicing will depend upon the particular operating conditions, but it is recommended that an annual service should be carried out by a
competent engineer. The appliance has an integral air filter, mounted at the top right hand side of the boiler, to which
the air intake pipe is connected. This filter should be ex amined every time the boiler is serviced. It may need more frequent inspection ac cording to the condition of the atm osphere in which the air intake terminates.
Note: The air filter can be easily blocked if the boiler is running on or near a building site having
an excess of airborne dust. It is essential, with a premix gas burner, that the air is clean and free of dust.
It is the law that any service work must be carried out by competent qualified persons.
6.1 Pre-Service Checks
It is recommended that an inspection should be carried out prior to shutting down the unit for servicing. Remove the front cover by releasing the 2 slotted screws on the top and lifting the cover from the base (Front cover located by two pegs). The following items should be observed:
a. Smooth starting and running of the blower. b. Smooth lighting of the burner. c. Check for leakage of gas, gas/air or combustion products. d. Check for condensate leaks. e. Check the colour and appearance of the flame. A sky blue flame slightly off the
burner gauze is normal. The burner itself should appear dark. Any glow on the burner indicates gauze blockage requiring cleaning, an incorrect gas flow or an air intake blockage.
f. Check that the temperature differential between the flow and return pipes is less
than 15
o
C. The temperature difference should be between 10oC and 15oC. g. Check for water soundness. h. Inspect the flue vent and air intake pipework. Joints must be sound and all
pipework well bracketed.
i. Check that there is a steady fall back to the boiler from the flue pipe to allow
condensate to run back into the boiler (See Section 2.8.3 Slope).
j. With the boiler operating at a low return temperature (i.e. less than 50
o
C) check
that the condensate flows freely from the condensate line.
6.1.1 Burner & Heat Exchanger Blockage Checks
i) Turn off the boiler & shut off the gas supply to the boiler. ii) Remove the pressure point screws from points A & B. Attach a differential
gauge.
iii) Turn on the boiler and wait for the fan to reach full speed. Obviously the
burner will not light.
iv) The pressure difference should be lower than : 8 mbar on the Keston 50,
8.4 mbar on the Keston 60 and 11.2 mbar on the Keston 80. If not, clean the burner.
WD50/2/1997 Chapter 6 : Servicing The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 40
Page 44
v) Turn off the electrical supply to the boiler. vi) Remove the pressure point screw from point C and transfer the tube from
point A to C, replacing the screw on point A.
vii) Turn on the electrical supply to the boiler (gas still off), wait for the fan to
reach full speed.
viii) The pressure difference should be below 11 mbar. If not, clean heat
exchanger. ix) Disconnect the gauge from point B. Refit the screw. x) Read pressure of point C. xi) The maximum pressure should be 3 mbar. If the pressure is greater than
this, check the flue for blockage. xii) Turn off the electrical supply to the boiler. xiii) Remove the pressure gauge tube and refit the screw. xiv) Open the gas service cock.
6.2 Recommended Routine Service
a. Inspect the air filter located at the top right hand side of the boiler. Release the
projecting leaf on the filter box and slide out the filter. If the filter looks dirty remove the dirt with a vacuum cleaner or by other means. If
in any doubt renew the filter element.
b. Remove the burner head (Section 7.7) and inspect the burner appearance. Black
markings or other discolourations on the gauze indicate too much gas or a lack of air possibly due to a blocked air filter. Any breakages or damage to the burner mesh indicate the burner must be replaced.
WD50/2/1997 Chapter 6 : Servicing The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 41
Pressure Test Point B
Pressure Test Point A
Burner Heat (From Above)
Pressure Test
Point C
Combustion Test Point
Flue Overheat Thermostat
Heat Exchanger Shell
Flue
Fig 6.1.1 Pressure Test Point Locati ons
&
Page 45
c. If necessary, either due to discolouration or a high pressure differential between
points A & B in the pre-service checks, clean the burner with a mild
household
detergent and rinse under a hot running tap.
d. If necessary, either from visual inspection or a high pressure differential between
points B & C in the pre-service checks, clean the heat exchanger using a suitable stiff plastic bristle brush, vacuum out any large particles and flush the heat exchanger with fresh water until the water flowing from the condensate drain is clear. When brushing the heat exchanger take care not to damage the condensing plug in the lower half of the heat exchanger.
e. Remove the condensate trap (Section 7.10) and unscrew the cap. Clean by
flushing through with clean running water. Reassemble in reverse order.
f. Check the electrodes mounted on the burner head. If the points are damaged or
burnt replace them. Check that the spark gap measures 4 mm.
g. Replace the burner head, renewing any gasket as necessary, and reconnect the
gas/air supply and the ignition lead. Ensure the flanged gas/air supply joint is air tight.
h. Turn on the electrical supply to the boiler and allow the boiler to reach operating
temperature levels.
i. Check for gas leakage around the burner head, air/gas flexible hose to the burner
head and ignitor plug if they have been removed.
j. Visually inspect the burner through the glass spy hole at the burner head (a small
mirror will prove useful).
k. Recheck the burner pressure by following the procedure detailed in Section 4.7
WD50/2/1997 Chapter 6 : Servicing The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 42
Page 46
7. REPLACEMENT OF PARTS
INDEX
7.0 GENERAL
7.1 PRECAUTIONS
7.2 ACCESS
7.3 PROCEDURES - GENERAL
7.4 ELECTRICAL
7.4.1 ON/OFF SWITCH
7.4.2 BOILER THERMOSTAT
7.4.3 NEONS
7.4.4 FLOW OVERHEAT, FLOW HIGH LIMIT & FLUE PROTECTION
THERMOMSTATS
7.4.5 WATER PRESSURE SWITCH
7.4.6 IGNITION CONTROL BOX
7.4.7 AIR PRESSURE SWITCH
7.4.8 COMBUSTION BLOWER
7.4.9 GAS CONTROL VALVE
7.4.10 GAS LOW PRESSURE SWITCH
7.5 GAS ORIFICE
7.6 SPARK IGNITION/FLAME DETECTION ELECTRODE
7.7 BURNER HEAD & BURNER
7.8 HEAT EXCHANGER
7.9 AIR FILTER
7.10 CONDENSATE TRAP
7.11 PRESSURE GAUGE
7.12 SIGHT GLASS
7.13 HT IGNITION LEAD
7.14 AIR VENT
7.15 AIR ORIFICE
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 43
Page 47
7.0 GENERAL
The following must always be carried out by a competent/qualified person.
7.1 PRECAUTIONS
i) Always switch off the mains electricity supply and disconnect the plug at the
isolating switch and socket. (If a switch only is used then remove the fuse.)
ii) Gain access to the appliance (Section 7.2) and turn off the gas supply at the
appliance service cock.
7.2 ACCESS
i) Remove the front door by releasing the two slotted screws to the front of the top
panel. The front panel may then be removed by tilting forward and lifting vertically to disengage the two locating studs in the base of the front panel.
ii) Access to the burner head can be gained by removing the access plate in the top
panel of the appliance.
7.3 REPLACEMENT PROCEDURES
i) Always replace in the reverse order unless otherwise stated. ii) Electrical connections must be remade in accordance with the Wiring Diagram
(Section 5.5).
iii) Test the soundness of any gas carrying or water carrying joint broken during the
service procedures.
7.4 ELECTRICAL COMPONENTS
7.4.1 On/Off Switch (Fig. 5.7.1 item 115)
i) Isolate the appliance (Section 7.1) ii) Gain access (Section 7.2) iii) Remove the push on connectors from the switch taking note of the
correct positions.
iv) Press in the catches and push the switch forwards through the control
panel. v) Reassemble (Section 7.3) vi) Check for correct operation of the switch.
7.4.2 Boiler Thermostat (Fig. 5.7.2 item 64) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors from the thermostat taking note of the
correct positions. iv) Unscrew the two retaining screws and remove the thermostat. v) Reassemble (Section 7.3)
NB: When fitting the new thermostat it is a requirement to smear a
thin film of heat sink compound between the thermostat and plate. This, combined with fitting the new thermostat tightly to the plate, ensures a good contact.
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 44
Page 48
7.4.3 Neons (Fig. 5.7.1 items 116 & 117) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors from the neon taking note of the correct
positions.
iv) Press in the catches and push the neon forward through the control
panel.
v) Pull the centre core of the neon from its housing to expose the bayonet
fitting bulb. vi) Reassemble (Section 7.3) vii) Check for correct operation of the neons.
7.4.4 Flow Overheat (Fig. 5.7.2 item 75) , Flow High Limit (Fig. 5.7.2 item 78) & Flue Protection Thermostats (Fig. 5.7.2 item 70)
i) Isolate the appliance (Section 7.1) ii) Gain access (Section 7.2) iii) Remove the push on connectors from the thermostat taking note of the
correct positions. iv) Unscrew the two retaining screws and remove the thermostat. v) Flue protection thermostat only
The thermostat seal is maintained via a small 'O' ring between thermostat
and flue pipe. If this is damaged on removal it must be replaced. vi) Reassemble (Section 7.3)
NB: When fitting the new thermostat it is a requirement to smear a
thin film of heat sink compound between the thermostat and plate. This, combined with fitting the new thermostat tightly to the plate, ensures a good contact.
7.4.5 Water Pressure Switch (Fig. 5.7.2 item 79) i) Isolate the appliance (Section 7.1)
ii) Shut off the water supply to the appliance. iii) Gain access (Section 7.2) iv) Drain the system to below the level of the appliance using the drain off
tap at the base of the heat exchanger.
v) Remove the push on connectors from the water pressure switch taking
note of the correct positions. vi) Unscrew the pressure switch. vii) Reassemble (Section 7.3).
NB: Use a little jointing compound or PTFE tape on the thread. viii) Refill the system (See Section 4 - Commissioning).
7.4.6 Ignition Control Box (Fig. 5.7.1 item 108) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the HT ignition lead. iv) Pull off the multi-pin connector away from the box. v) Unscrew the two screws securing the control box to the casing and
remove the box.
vi) Reassemble (Section 7.3)
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 45
Page 49
7.4.7 Air Pressure Switch (Fig. 5.7.1 item 110) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors from the air pressure switch taking note
of the correct positions.
iv) Disconnect the union to one plastic tube connection and pull off the
second plastic tube from the air pressure switch.
v) Unscrew the two screws mounting the air pressure switch body to the
boiler casing.
vi) Reassemble (Section 7.3)
NB: Ensure the yellow/green earth connection tag is securely fixed
behind the lower mounting screw.
7.4.8 Combustion Blower (Fig. 5.7.3 item 80) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the cover plate to the electrical connections on the blower motor
by removing the four retaining screws.
iv) Disconnect the wires to the combustion blower taking note of the correct
positions.
v) Remove the allen screws fixing the air intake pipe flange and the gas/air
mixture pipe flange to the blower.
vi) Undo the two nuts securing the combustion blower base plate to the
cabinet base and lift out the combustion blower.
vii) Unscrew the three bolts fixing the base plate and anti-vibration mounts to
the combustion blower.
viii) Reassemble (Section 7.3)
NB: When reassembling inspect any gaskets for damage and replace
if necessary.
ix) Reset the gas rate (See Section 4 - Commissioning)
7.4.9 Gas Control Valve (Fig. 5.7.3 item 95) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the cover concealing the electrical connections on the front of
the gas valve.
iv) Remove the push on connectors exposed taking note of the correct
positions.
v) Remove the push on connectors to the gas low pressure switch taking
note of the correct positions. vi) Remove the earth connection to the side of the gas valve. vii) Remove the four allen bolts securing the gas inlet flanged connections to
the gas control valve. viii) Undo the four bolts fixing the base of the gas control valve to the gas
outlet block. ix) Remove the gas valve. x) Unscrew the gas low pressure switch at its connection to the gas control
valve body. xi) Reassemble (Section 7.3) xii) Reset the gas rate (See Section 4 - Commissioning)
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 46
Page 50
7.4.10 Gas Low Pressure Switch (Fig. 5.7.3 item 105) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the push on connectors to the gas low pressure switch taking
note of the correct positions. iv) Unscrew the gas low pressure switch from the brass holder. v) Reassemble (Section 7.3)
7.5 GAS ORIFICE (Fig 5.7.3 item 91) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Unscrew and remove the brass plug from the gas outlet block. iv) Remove the rubber seal from the injector housing. v) Insert a flat blade screwdriver into the exposed hole and unscrew the gas injector. vi) Check the injector is the correct size for the boiler size and fuel type. vii) Reassemble (Section 7.3)
NB : When fitting the new gas injector ensure that the injector is screwed fully home past the gas port into the chamber from the gas valve.
viii) Reset the gas pressure (See Section 4 - Commissioning)
7.6 SPARK IGNITION/FLAME DETECTION ELECTRODE (Fig. 5.7.2 item 51) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the pull off HT lead to the spark ignition electrode. iv) Remove the burner head (Section 7.7 steps iv) to vii). v) Undo the screws to the spark ignition electrode flange located on the burner
head and withdraw the spark ignition electrode.
vi) Reassemble (Section 7.3)
NB: When reassembling inspect the gasket for damage and replace if
necessary. With the new spark ignition electrode in place it is essential to ensure the gap between the tip of the electrode and the burner surface is 4 mm. Distance above or below 4 mm will affect the ignition performance. If necessary gently bend the electrode taking care not to damage the ceramic insulator.
7.7 BURNER HEAD & BURNER (Fig. 5.7.2 items 46 & 48) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the pull off HT lead to the spark ignition/flame detection electrode head. iv) Remove the four screws retaining the access panel (Fig. 5.7.4 item 6) and
remove the access panel from the top of the cabinet.
v) Remove the two allen screws fixing the flange gas/air mixture pipe connection to
the burner head.
vi) Remove the four allen screws fixing the burner head to the top of the heat
exchanger.
vii) Withdraw the burner & burner head from the top of the heat exchanger through
the access panel opening in the top of the cabinet.
viii) Unscrew the burner from the burner head taking care not to damage the burner
mesh.
ix) Reassemble (Section 7.3)
NB: When reassembling inspect any gaskets for damage and replace if
necessary. Set the spark gas as detailed in Section 7.6.
x) Reset the gas rate (see Section 4 - Commissioning)
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 47
Page 51
7.8 HEAT EXCHANGER (Fig. 5.7.2 item 43) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Shut of the water supply to the appliance. iv) Remove the burner head (Section 7.7) v) Drain the system to below the level of the appliance using the drain off tap at the
base of the heat exchanger. vi) Remove the boiler thermostat (Section 7.4.2) vii) Remove the push on connectors to the water pressure switch, flow overheat
thermostat, flow high limit thermostat and flue protection thermostat taking note of
the correct positions. viii) Remove the condensate trap (Section 7.10) ix) Remove the pressure gauge phial located next to the drain off tap. x) Disconnect the flow and return compression couplings to the flow and return
pipes exiting the top of the boiler. xi) Remove the push on flue connection to the flue pipe exiting the top of the boiler. xii) Remove the complete air filter assembly and flexible air pipe. xiii) Remove the nut fixing the strap retaining the base of the heat exchanger and pull
out the strap by unhooking it from its fixing behind the heat exchanger. xiv) Remove the allen screw securing the top of the heat exchanger to its mounting
bracket. xv) Remove the five screws fixing the top of the cabinet. xvi) Remove the heat exchanger, with pipework attached, & the top of the cabinet. xvii) Separate the top of the cabinet from the combined assembly. xviii) Remove the flow and flue pipework from the heat exchanger (Replacement heat
exchangers are supplied with return pipework attached). xix) Reassemble (Section 7.3) xx) Recommission (Section 4 - Commissioning)
7.9 AIR FILTER (Fig. 5.7.4 item 22) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Drop the lower section of the air filter housing by pulling forward the securing flap. iv) Open the lower section as far as possible and pull out the combined paper filter
element with rubber seal.
v) Reassemble (Section 7.3)
NB: When fitting the new air filter take care to ensure that the new filter is placed to cover completely the air intake entry into the boiler cabinet.
7.10 CONDENSATE TRAP (Fig. 5.7.2 item 59) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Disconnect the condensate line from the base of the heat exchanger. iv) Disconnect the condensate line from the base of the flue assembly. v) Disconnect the condense lines from the projection of the condensate trap from
the base of the cabinet. vi) Withdraw the condensate trap. vii) Mop up any spilled condensate. viii) Reassemble (Section 7.3)
NB: When re-fitting condensate trap pour water into the condensate hose
from the base of the heat exchanger until nearly full. Then reconnect the condensate hose to the base of the heat exchanger.
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 48
Page 52
7.11 PRESSURE GAUGE (Fig. 5.7.1 item 119) i) Isolate the appliance (Section 7.1) and shut off the boiler from the water circuit.
ii) Gain access (Section 7.2) iii) Shut off the pressure measurement point at the return drain valve located at the
base of the heat exchanger.
iv) Remove the phial from its mounting at the return pipe entry to the base of the heat
exchanger.
v) Press in the catches and push the pressure gauge forward through the control
panel. vi) Reassemble (Section 7.3) vii) Refill the system (See Section 4 - Commissioning)
7.12 SIGHT GLASS (Fig. 5.7.2 item 49) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Unscrew the sight glass fitting from the burner head. iv) Reassemble (Section 7.3)
7.13 HT IGNITION LEAD (Fig 5.7.1 item 120) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Remove the lead from the electrode and the ignition control box. iv) Reassemble (Section 7.3)
7.14 AIR VENT (Fig. 5.7.2 item 72) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Shut off the water supply to the appliance. iv) Gain access (Section 7.2) v) Drain the system to below the level of the appliance using the drain off tap at the
base of the heat exchanger. vi) Unscrew the air vent. vii) Reassemble (Section 7.3) viii) Refill the system (See Section 4 - Commissioning)
7.15 Air Orifice (Fig. 5.7.3 item 87) i) Isolate the appliance (Section 7.1)
ii) Gain access (Section 7.2) iii) Disconnect the flexible air intake hose from the air inlet manifold (Fig 5.7.3 item
102) iv) Unscrew the air orifice grub screw (Fig 5.7.3 item 83) to release the air orifice. v) Lift the air orifice from its seat in the air inlet manifold. vi) Reassemble (Section 7.3) NB: When replacing the air orifice ensure that the new orifice is seated with the
chamfer facing upwards.
WD50/2/1997 Chapter 7 : Replacement Of Parts The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 49
Page 53
8. SHORT SPARE PARTS LIST
Item GC No Part Denomination Item GC No Part Denomination
22 114 105Air Filter 46 375 523Burner
375 524 375 525
47 375 526Burner Manifold Gasket 50 375 527Ignitor Gasket
51 114 120Ignitor/Sensor Probe 56 114 030Flexible Hose Gasket
64 375 530Boiler Thermostat 70 375 532Flue Thermostat
75 375 533Flow Overheat Thermostat 78 375 534Flow High Limit Stat
WD50/2/1997 Chapter 8 : Spare Parts Listings The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 50
Page 54
Item GC No Part Denomination Item GC No Part Denomination
94 375 535Gas Valve Outlet Gasket 107 375 529Flexible Hose Gasket 95 375 536Gas Valve 99 375 537Gas Inlet Gasket
108 E01 074 Ignition Control Box 110 170 084Air Pressure Switch
379 744
120 E01 075 HT Ignition Cable
WD50/2/1997 Chapter 8 : Spare Parts Listings The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 51
Page 55
SHORT SPARE PARTS LIST FOR THE KESTON
CONDENSING BOILER RANGE
Item GC No Part Denomination
22 114 105 Air Filter 46 375 523 Burner (Keston 50)
375 524 Burner (Keston 60)
375 525 Burner (Keston 80) 47 375 526 Burner Manifold Gasket 50 375 527 Ignitor Gasket 51 114 120 Ignitor/Sensor Probe 56 114 030 Flexible Hose Gasket 64 375 530 Boiler Thermostat 70 375 532 Flue Thermostat 75 375 533 Flow Overheat Thermostat 78 375 534 Flow High Limit Thermostat 94 375 535 Gas Valve Outlet Gasket 95 375 536 Gas Multifunctional Control Valve 99 375 537 Gas Valve Inlet Gasket 107 375 529 Flexible Hose Gasket 108 E01 074 Ignition Control Box 110 170 084 Air Pressure Switch (Keston 80)
379 744 Air Pressure Switch (Keston 50 & 60) 120 E01 075 HT Ignition Cable
WD50/2/1997 Chapter 8 : Spare Parts Listings The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 52
Page 56
Read Installation Manual Carefully
For open systems ensure that there is at least 8 feet head of water pressure at the top of the boiler.
DO NOT remove the dust caps from the air and exhaust pipes until ready to connect.
Ensure that ALL dust particles, filings , plastic chips etc. are removed from the inlet pipe.
If the installation is a replacement the system must be flushed clean. System should be drained hot, then refilled, then drained
again until the water is clean.
Ensure that there is a proper electrical supply ie 230V fused at 5A.
Take great care with pipe connections to ensure that no damage is done to the internal pipework.
Ensure that the 22mm condensate pipe is not exposed to freezing conditions.
Make sure that the exhaust pipe terminates away from windows or vents and is out of reach.
Make sure that the air inlet and exhaust pipe outlets are at least 350mm apart.
Check tightness of all connections in the boiler before firing.
Ensure that the terminals supplied are fitted to both the exhaust and air inlet pipes.
Ensure that the air inlet terminal is facing upwards to prevent entry of rain.
The system must be free from air before firing.
The pump must always run when the boiler is firing.
Gravity circuits are not allowed.
If TRV's are installed on radiators ensure that a bypass is installed to maintain required flow.
WD 92/0/1997
KESTON CONDENSING BOILERS
IMPORTANT
KESTON 50, 60 & 80
INSTALLATION KEY POINTS
Loading...