Keston 50 - GC, 80 - GC, 60 - GC, 50, 80 Installation And Servicing Instructions

...
Fan Powered High Efficiency Condensing Gas Boiler
Installation And Servicing Instructions
Keston 50 - GC No 41 930 01 Keston 60 - GC No 41 930 02 Keston 80 - GC No 41 930 03
PI No. : 87AQ306
These instructions must be left either with the user or next to
the household gas meter.
34 West Common Road
Tel. (44)0208 462 0262 Fax. (44)0208 462 4459
WD50/2/1997 The Keston 50, 60 & 80 Condensing Boilers
0087
CONTENTS
Section Description 1 GENERAL INSTRUCTION
1.1 Description
1.2 Boiler Schematic
1.3 Related Documents
1.4 Performance Data
1.5 General Data
2 BOILER LOCATION
2.1 Dimensions & Minimum Clearances
2.2 Service Connections
2.3 Position
2.4 Electrical
2.5 Boiler Size Selection
2.6 Gas Supply
2.7 Water Systems
2.8 Flue System
2.9 Air Supply
2.10 Compartment Installation
2.11 Condensate Drainage
2.12 Radiant Floor Heating
2.13 Low Water Volume Boiler vs. Cast Iron Boiler
2.14 Determine Radiation Needed Room-By-Room
3 INSTALLATION OF THE BOILER
3.1 Wall Mounting Bracket
3.2 Mounting The Boiler
3.3 Assembly Practice
3.4 Installing Flue And Air Pipes
3.5 Condensate Drainage
3.6 Water System
3.7 Gas Supply
3.8 Electrical Supply
3.9 Exchanging A Boiler
4 COMMISSIONING OF THE BOILER
4.1 Initial Flushing
4.2 Gas Supply
4.3 Electrical Installation
4.4 LP Gas Conversion
4.5 Initial Firing
4.6 Hot Flushing
4.7 Checking The Gas Pressure
WD50/2/1997 The Keston 50, 60 & 80 Condensing Boilers
Page : i
4.8 Timing The Gas Meter
4.9 Handing Over To The User
5 FAULT FINDING
5.1 Electrical Control Sequence
5.2 Fault Finding Flow Chart
5.3 Continuity Checking
5.4 Functional Flow Wiring Diagram
5.5 Electrical Wiring Diagram
5.6 Illustrated Wiring Diagram
5.7 Exploded Assembly Diagrams
6 SERVICING
6.1 Pre Service Checks
6.2 Recommended Routine Service
7 REPLACEMENT OF PARTS
7.1 General
7.2 Precautions
7.3 Access
7.4 Electrical
7.5 Gas Orifice
7.6 Spark Ignition/Flame Detection Electrode
7.7 Burner Head & Burner
7.8 Heat Exchanger
7.9 Air Filter
7.10 Condensate Trap
7.11 Pressure Gauge
7.12 Sight Glass
7.13 HT Ignition Lead
7.14 Air Vent
7.15 Air Orifice
8 SPARE PARTS LISTINGS
WD50/2/1997 The Keston 50, 60 & 80 Condensing Boilers
Page : ii
1. GENERAL INSTRUCTION
1.1 DESCRIPTION
The Keston Condensing Boiler is unique in its concept and des ign. While the application for which the boiler was designed is the same as those which other boilers are us ed the Keston boiler has the added advantage of very high efficiency, and small diameter plastic flue which can be extended to 10 metres horizontally or vertically.
The Keston uses a high power combustion blower to deliver a pre-mix of gas and air to a downward firing burner in a high efficiency, single pass heat exchanger.
Normally the combustion temperature of the air gas mixture is around 1800
o
C but the
Keston achieves combustion at an amazing 1000
o
C thereby reducing the NOx emissions
down to an incredible less than 5 p.p.m. The flue system is room sealed and fan powered. The ignition is direct spark and fully
automatic. The boiler housing is not waterproof. The boiler should be installed in a position where it will always be dry. A small air intake point is incorporated within the appliance cabinet to ensure that the interior of the c abinet is maintained under a slight negative pressure. This is a safety feature to ensure no products may leak out of the cabinet into the installation space.
The boiler is suitable f or connection to open vented or sealed system s. The s ystem mus t be pumped central heating or pumped central heating with combined indirect domestic hot water. Gravity circuits must not be used.
The boiler has a primary heat exchanger which, through its combustion chamber and corrugated coil, transfer s the heat produced in the hot gases of combustion pr ocess into the circulating water. Head characteristics of the boiler coil must be taken into consideration when calculating the pump size.
The Keston boiler is not a high water content boiler and does not contain the metal mass, or water volume, of a cast iron or steel boiler. This boiler is of low mass and low water content and therefore responds faster when there is a call for heat. This f eatur e requir es a higher water pumping rate through the boiler otherwise localised boiling will occur within the boiler.
Allow a pressure drop through the boiler of 3.2 ft head and a water flow of 4.2 gallons (19 litres) per minute f or the Keston 50, 4.3 ft head and 5 gallons (23 litres) per m inute for the Keston 60 and 9 ft head and 6.7 gallons (30.5 litres) per minute for the Keston 80.
The boiler selected m ust be sized relative to the total c alculated heat loss of the building. The boiler rated output should not be greater than the total required to make up the calculated heat loss plus the heat required to provide domestic hot water. If there are special conditions such as excessive domestic hot water usage consult the manufacturer.
1.2 BOILER SCHEMATIC
Air is drawn into the boiler through a 40mm ( BS5255) m uPVC pipe. T he air f low is proved by a differential pressure across the air control orifice.
Gas is mixed with com bustion air at the inlet to the fan. T he gas flow is regulated by an orifice located in the housing downstream of the gas valve.
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 1
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 2
Figure 1.2 Boiler Schematic
LEGEND
1 Heating Return 2 Water Return Thermostat 3 Downstream Pressture Test Nipple 4 Flame Ignition/Sensing Probe 5 Burner 6 Automatic Air Vent 7 High Limit Thermostat 8 Heating Flow 9 Flue Exhaust 10 Air/Gas Flexible Connector 11 Air Filter 12 Air Inlet Flexible Connector
13 Ignition Control Box 14 Gas Low Pressure Switch 15 Gas Multifunctional Control 16 Gas Inlet Flexible Connector 17 Air Pressure Switch 18 Combustion Bl ower 19 Condensate T rtap 20 Flue Overheat Thermostat 21 Heat Exchanger 22 Flow Overheat Thermostat 23 Water Low Pressure Switch 24 Combustion Test Point
The gas and air are thoroughly mixed in the blower and fed into the bur ner located at the top end of the heat exchanger module. The gas and air m ix ture is ignited by a direct spark ignition control system and burns with a blue flame j ust off the surface of the burner. As the hot products of com bustion pass downwards, they are cooled, exchanging heat with the circulating water which enters the heat exchanger coil at the bottom of the heat exchanger.
When the return water temperature is below 54oC, part of the water vapour in the combustion products will condense inside the heat exchanger , thus increasing the boiler efficiency. This condensate f alls to the bottom of the heat exchanger where it is separ ated from the flue gases and exits from the boiler through the condensate drain. Any condensate formed in the flue runs back down the flueway and is drained at the base of the flue connection to the heat exchanger.
The condensate is very slightly acidic (about the same acidity as vinegar) and should be piped in a plastic pipe. It is not harmful to the waste disposal system and may be disposed of as normal waste water.
The flue gases are piped in a 40m m m uPVC pipe to the outside. The temperatur e of the flue gases are usually less than
10oC above the temperature of the retur n water. The flue
pipe should be terminated outside the building from where they cannot re-enter the building or any other adjacent building or cause a nuisance by pluming.
The heating level may be controlled by room thermos tats, hot water cylinder thermostats and programmer time clocks.
1.3 RELATED DOCUMENTS
The Keston Condensing Boiler must be ins talled in accordance with the current issue of the Gas Safety (Ins tallation and Use) Regulations, c urrent IEE W iring Regulations, Safety
document no. 635 - The Electricity At Work Regulations 1989, Building Regulations, Building Standards (Scotland) Consolidation, and the Bye Laws of the local Water Undertaking.
In addition, due account must be taken to the following Codes Of Practice:
BS 6891 : Gas Supplies BS 6798 : Installation Central Heating Boilers BS 5449 : Installation Pumped Central Heating BS 5546 : Installation Domestic Hot Water BS 5440.1 : Flues BS 5440.2 : Air Supply BS 5482.1 : Domestic Propane & Butane Burning Installations BS 7074.1 : Expansion Vessels BS 7593 : Treatment of Water in Hot Water Central Heating
Systems
BS 7671 : Requirements for Electrical Installations. IEE Wiring
Regulations 16th Edition.
For Timber Framed Buildings, British Gas Publications DM2. Also British Gas Publications 'Guidance Notes For The Installation Of Domestic Gas Condensing Boilers' and 'Specification For Domestic Wet Central Heating Systems'.
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 3
1.4 PERFORMANCE DATA
Keston 50 Keston 60 Keston 80
10 to 1510 to 1510 to 15
o
CRecommended Temperature
Differential
3.432.712.38mmGas Orifice Size
8.08.08.0in. w g
20.020.020.0mbarInlet Gas Pressure
8.0
8.08.0
Ft
2.5
2.5
2.5MMinimum Head (Open Systems)
2.702.702.70BarMaximum Pressure (Sealed Systems)
100.0100.0100.0Ft
30.5030.5030.50MMaximum Head (Open Systems)
80.0080.0080.00
o
CMaximum Operating Flow
(CV of Gas - 38.7 MJ/m3) (1038 Btu/Ft
3
)
89.1165.854.43Ft
3
/HrRunning
0.70.510.43L/SGas Consumption After 10 mins
3.943.542.36in w.g.
(FACTORY PRESET)
1096mbarBurner Setting Pressure (Hot)
88,80065,00054,000Btu/h60
o
C Flow 40oC Return
2619.215.8KWBoiler Output To Water
80,00060,00050,000Btu/h80
o
C Flow 60oC Return
23.5 17.514.7KWBoiler Output To Water
92,50068,30056,500Btu/h
27.119.916.6KWBoiler Input
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 4
1.5 GENERAL DATA
Keston 50 Keston 60 Keston 80
3.30 litres2.35 litres2.35 litresWater Content
Rear panel inside caseRear panel inside caseRear panel inside caseData Badge Posn
50 kg (110 lbs)44 kg (97 lbs)44 kg (97 lbs)Weight - Empty
52 kg (114 lbs)46 kg (101 lbs)46 kg (101 lbs)Weight - Full
5 Amps5 Amps5 AmpsExt. Fuse Rating
175 W140 W140 WPwr Consumption
230V 50Hz230V 50 Hz230V 50 Hz Power Supply
28 mm Copper28 mm Copper
28 mm
Copper
Return Connection
28 mm Copper28 mm Copper
28 mm
CopperFlow Connection
0.5 inch BSPT Male (15mm to gas cock)
0.5 inch BSPT Male (15mm to gas cock)
0.5 inch BSPT Male (15mm to gas cock)
Gas Supply Connection
Keston FilterKeston Filter Keston FilterFilter
Tridelta FS 6717 - 1428Tridelta FS 6717 - 1428Tridelta FS 6717 - 1428Air Pressure Switch
Full Sequence ControlFull Sequence ControlFull Sequence ControlIgnition
RAM ElectronicsRAM Electronics
RAM
Electronics
Direct Spark
0.18 KW 2900 RPM0.18 KW 2900 RPM0.18 KW 2900 RPM
Type LPB 102 220/240Type LPB 102 220/240Type LPB 102 220/240
KestonKestonKestonCombustion Fan
36E Series36E Series36E Series
White RogersWhite RogersWhite Rogers Gas Control
Keston PremixKeston PremixKeston PremixMain Burner
WD50/2/1997 Chapter 1 : General Instruction The Keston 50, 60 & 80 Condensing Boiler
s
Installation & Servicing Instructions
Page : 5
2. BOILER LOCATION
2.1 DIMENSIONS AND MINIMUM CLEARANCES
The boiler must be installed in minimum clearances shown to allow subsequent servicing, and safe operation.
2.2 SERVICE CONNECTIONS
Gas, water, air and flue pipe, condensation, and electrical connections are as shown. Gas : 0.5 inch BSP male. Flow/Return : 28 mm
copper.
2.3 POSITION
The Keston is not suitable for external installation. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Where a room-sealed appliance is installed in a
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 6
All dimensions in mm.
254
305
127
Figure 2.1.1 Minimum Clearances
1
1
All dimensions in mm.
500
3
0
0
Figure 2.1.2 Dimensions
712 (Kest on 50 & 60)
Air Intake
Flue
Return
Flow
890 (Keston 80)
27
47
Top View
68
30
37
97
Base View
Service Connection Locations
All dimensions are in mm.
60
405
237
181
room containing a bath or shower, any electrical switch or appliance control, utilising
mains electricity, should be so situated that it cannot be touched by a person using the bath or shower.
Compartment installation is permitted - such compartments must be constructed in accordance with BS 6798.
The wall on which the boiler is mounted must be of suitable load bearing capacity and must be non-combustible.
Important : It is not recommended to install the boiler on a studded wall or similar - it is possible that the vibration from the fan would be amplified and transmitted to other parts of the house.
Chimneys not used for venting any other
appliance may be used.
Figure 2.3
Secure air & flue pipes at chimney outlet.
[NB: Refer to Section 2.8.3]
The Keston can be located virtually anywhere desired provided that all regulations are met. Because of the boiler's compact size and venting flexibility, the installation is not limited to a boiler room setting. Before locating the boiler near a living space consider whether the sounds generated by the boiler will be objectionable. Sound levels from the boiler are no greater than from any other type of high-efficiency boiler but even minimal levels may be objectionable if located near a bedroom or in a living area.
2.4 ELECTRICAL
2.4.1 Electrical Connections
The boiler must be connected to a 230V ~ 50Hz supply, fused at 5A. All external controls and wiring must be suitable for mains voltage. Wiring
external tothe boiler must be in accordance with current I.E.E wiring regulations and local regulations.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 7
The method of connection to the mains electricity supply must facilitate complete electrical isolation of the boiler complying with the requirements of BS
1363. The appliance must be connected to the supply via a fused double-pole switch,
having at least 3mm (1/8 inch) contact separation in both poles, serving only the boiler and the system controls.
The connection point to the mains supply should be readily accessible and adjacent to the boiler, except for rooms containing a bath or a shower. Refer to section 2.3 Position.
2.4.2 External Wiring & Controls
1. The boiler is deisgned so that all control wiring is external to the boiler. Hence, any programmers or room thermostats etc must act by switching the 230V supply to the boiler.
2. System designs which allow the boiler to fire when there is no pumped circulation must NOT be used.
3. A programmer may be used with zone valves to give independent control of central heating and hot water.
2.5 BOILER SIZE SELECTION
The size of the boiler to be used is determined by the total calculated heat loss of the building. Match the calculated heat loss with the boilers rated output. If a boiler is
installed with an output rating greatly exceeding the total capacity of the distribution system the efficiency of the boiler will be reduced. If the boiler is to be used to heat
domestic hot water no additional capacity is normally needed for the average residential installation since there is usually some excess capacity in the boiler as water heating is an intermittent load.
2.6 GAS SUPPLY
A gas meter should be connected to the service pipe by the local gas supplier or their contractor. An existing meter should be checked preferably by the gas region to ensure that the meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891.
Minimum/Maximum Natural Gas Pressure:
Natural gas pressure before the gas valve must be maintained at 20 mbar (8 in w.g) while the boiler is running. Gas pressures above or below this level will lead to problems associated with the gas valve's internal pressure regulator.
Minimum/Maximum L P Gas Pressure:
LPG pressure must be maintained between 31.5 mbar (12.4 in w.g) and 37.6 mbar (14.8 in w.g) while the boiler is running
. Gas pressures above or below these levels will lead to problems associated with the gas valve's internal pressure regulator.
Supply pipes to the boiler must not be sized less than the boiler inlet connection (15 mm) Due consideration must be given to the supply pressure to other gas appliances in the premises.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 8
A gas cock is supplied loose with the boiler. This cock should be fitted in the gas line to the boiler as close to the boiler as possible so that it is easily identified as the cock to isolate the boiler.
2.7 WATER SYSTEMS
All piping must be installed in accordance with all applicable local and Water Supply Bylaws for forced hot water heating systems. Consideration must be given to pipe capabilities and pressure drop through the piping. Water treatment must be carried out to BS 7593 : Treament of Water in Hot Water Central Heating Systems. Pump isolating valves must be positioned as close to the pump as possible.
a The Keston is suitable for use on open, vented water systems with combined feed
and vent.
b It is preferable for use on sealed water systems, provided the appropriate
components required (see Section 2.7.2 Sealed Systems) are included in the system.
c Any system must
be thoroughly flushed clean of grease, dirt and debris, prior to connection with the boiler. A trap may be installed in the flow line to collect any solder, or other debris, from the installation.
d All water systems must be constructed to comply with requirements of the Local
Water Authority.
e Only fully pumped systems can be used - gravity systems are strictly
not
suitable.
f Always use a system complying with the requirements of BS 5449 and BS 6798. g The system must be so arranged that there shall always be a minimum flow of 4.2
gpm (19 litres/min) [Keston 50], 5 gpm (23 litres/min) [Keston 60] or 6.7 gpm (30.5 litres/min) [Keston 80] when the boiler is firing. This can be via a specially installed by-pass arrangement.
h Copper tubing to BS 2871 Part 1 is recommended. i Jointing should be either with capillary or compression fittings. Pipes should have
a gradient to ensure air is passed easily to vent points and water flows readily to drain points.
j Draining taps must be located in accessible positions which permit the draining of
the boiler and hot water storage vessel. Draining taps should be at least 15 mm in nominal size and be in accordance with BS 2879. AIR VENT POINTS
k These must be fitted at all high points where air may collect.
2.7.1 Open Vented Systems
A typical system is shown in Figure 2.7.1 which includes a combined feed and vent. Note there must be no valve between the boiler flow and the open vent. Note that the minimum static head required is 8 ft at the boiler flow pipe. If the cold feed/vent is not brought to the flow pipe as shown, then the pressure loss across the heat exchanger may have to be taken into account when estimating the static pressure.
Although suitable for open vented systems with combined feed and vent arrangements, the Keston is a low water content boiler. As such, any air entrainement within the system water will produce boiler "kettling". It is therefore recommended, if in any doubt, to consider the use of sealed
systems where possible.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 9
2.7.2 Sealed Systems
Sealed systems must be designed in accordance with BS 5449 and BS 7074 Pt1. A typical sealed system is shown in Figure 2.7.2. It must include :
(i) A safety valve fitted on the flow, adjacent to the boiler. It must be non
adjustable and preset to 3 bar. A drain pipe must be attached, at least as big as the valve connection, and routed to drain in any area not hazardous nor where it may be subject to freezing.
(ii) An expansion vessel complying with BS 4814 and sized in accordance
with the requirements of BS 5449 and BS 7074 Pt 1. The vessel must be
positioned on the inlet to the pump. (iii) A filling point, in accordance with local water authority requirements. (iv) A method of system make-up (automatic or manual), in accordance with
local water authority requirements. (v) There must be no permanent connection of mains water to the boiler
system. (vi) The installation must be designed to work with flow temperatures of up to
110
o
C.
All components of the system including the heat exchanger of the indirect cylinder must be suitable for a working pressure of 3 bar and a temperature of 110
o
C. Care should be taken in making all connections that the risk of leakage is
minimised.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 10
Boiler
Rad. 2 Rad. 1
Pump
Expansion Pipe
Expansion Tank
Minimum 8ft Height
Cylinder
Figure2.7.1 : Open Vented System Diagram
Keston
3 Way Valve
Strainer
By-pass Bal. Valve
L/S
22mm pipe
(minimum)
2.7.3 Hot Water System (if applicable)
The hot water storage vessel must be of the indirect type (certain direct cylinders can be used provided
they are suitably adapted by fitting an immersion calorifier). DIRECT CYLINDERS MUST NOT BE USED. Further guidance is provided in BS 1394. It is advisable to fit a lockshield valve on the cylinder return
to enable balancing of flow rate through the cylinder.
2.7.4 Boiler By-pass Piping
Boiler water flows are critical to the operation of the boiler. If flow cannot be maintained through the system piping to meet the minimums required by the boiler (see paragraph 2.7 (g)). Insufficient water flows through the boiler will cause the boiler to "kettle" or even produce steam which can damage the heat exchanger and will invalidate the heat exchanger warranty.
It is normally advisable to incorporate a boiler by-pass in the system, especially if thermostatic radiator valves are used. The by-pass should be fitted with a lockshield valve to permit balancing of the by-pass flow rate. The flow/return differential should be 10
o
C to 15oC. The lockshield valve can be adjusted to
maintain this condition with the radiators fully heated.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 11
Valve
Boiler
Figure 2.7.2 : Sealed System Di agram
Keston
Pressure Gauge
Expansion Vessel
Double Check Valve
Pump
Air Vent
Make -up vessel. Max. capacity of 3 lt. (5pt)
Non-Return Valve
Auto Air Vent
Hose Union bib tap
Hosepipe (disconnected after filling)
Hose Connector
BS 1010:2 Stop Tap
Test Cock
Drain Cock
HEATING CIRCUIT
RETURN
FLOW
Strainer
Safety Relief
By-pass
Bal.
Valve
L/S
2.7.5 Air Elimination
In the initial charge of water to the boiler system and in all subsequent additions of water to the system some air will be dissolved in the water. As the water is heated the air is driven out of the solution and will collect in high spots in the system. These air bubbles can interfere with pumping and heat transfer and
must be eliminated.
Installation of air bleed valves at the high spot(s) in the system will allow for air elimination when filling the system and will allow re-venting in a day or so after all air has been driven out of solution. Installation of an automatic air vent will ensure that any air, even minute amounts, which subsequently enters the system will be automatically removed.
2.7.6 Strainers
Debris in the heating system can cause noise if it enters the heat exchanger. Fitting of a Y-strainer ahead of the circulating pump will trap any debris left in the system and will protect the pump from damage.
2.7.7 Pump Selection
The Keston boilers have low water content heat exchangers with a high resistance to flow, when compared with cast iron heat exchanger boilers. As a result selection of the correct pump is essential
in order to avoid localised boiling within the heat exchanger. The selected pump must be capable of maintaining the required flow rate for the boiler against the pressure losses contributed by the boiler and the rest of the system.
Refer to the pressure loss/flow rate Table 2.7.7 to determine the pressure loss from the boilers. Add this to the pressure loss caused by the rest of the system and select a pump capable of meeting the flow rate required at the total pressure loss generated by the boiler and the rest of the system. The selected pump must comply with BS 1394.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 12
Y-Strainer will collect any loose debris in the piping.
Figure 2.7.6 Strainers
Figure 2.7.7 : Pressure Loss Graph
5
10 15 20 25 30
0.5
1.0
1.5
2.0
2.5
3.0
Water Flow - L/min
Pressure Loss - m
3.5
4.0
4.5
35
Keston 50 Keston 60
Keston 80
It is important to note that the minimum flow rate must be maintained whenever the boiler is firing. Systems using zone valves must be specifically designed to only fire the boiler when the pump is running and the minimum flow rate can be achieved.
The Wilo Salmson Gold Star pump, or the Grundfoss 15/60 pump is normally suitable for use with the Keston condensing boiler range. However, in all cases due consideration must be given to the resistance to flow offered by the rest of the system when making a final pump selection. This is particularly important when using small bore underfloor
heating pipework.
Table 2.7.7 Pump Selection
2.8 FLUE SYSTEM
2.8.1 Design
Individual air supply and flue outlet pipes are used. The material used for flue outlet &/or air inlet must be muPVC to BS 5255 and of an internal diameter of 38 mm.
Both flue outlet terminal and air inlet terminal are supplied and are illustrated in Figure 2.8.1.
2.8.2 Maximum Lengths
The maximum lengths of both air inlet pipe and flue outlet pipe, when no bends are used, are as detailed below.
Maximum Air Inlet Length : 10.0 m Maximum Flue Outlet Length : 10.0 m
However, each bend used has an equivalent length that must be deducted from the maximum straight length stated above.
A 92.5
o
sweep elbow is equivalent to 1.0m straight length. Example: Air inlet uses two 92.5o sweep elbows. Hence, maximum length permissible (ie
a+b in figure 2.8.2) = 10.0m - 1.0m - 1.0m = 8.0m Flue outlet uses one 92.5
o
sweep elbow. Hence, maximum length permissible (ie
c+d in figure 7 = 10.0m - 1.0 m = 9.0m
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 13
9.0 ft
2.75m
27.5 kPa
4.3 ft
1.3m
13 kPa
3.2 ft
0.97m
9.7 kPa
Pressure Loss Through Boiler
6.7 GPM
30.5 litres/min
5.0 GPM
22.7 litres/min
4.2 GPM
19.1 litres/min
Min Flow Rate Required
Keston 80Keston 60Keston 50Boiler Model
2.8.3 Slope
'Horizontal' flue outlet pipework MUST slope at least 2.5 degrees (45 mm per metre run) downwards towards the boiler. Pipework can be vertical. Only swept elbows can be used. Air inlet pipework can be truly horizontal or vertical, or sloping in a downward direction towards the boiler but in this case rain, etc, must
be prevented from entering the pipe. There must be no
troughs in any of the pipework, whether it be air inlet or flue outlet. If a 45
mm per meter slope is not possible, contact Keston Boilers Technical Department for further guidance.
Due the low temperature of the flue gases further condensate will form within the flue system. Drain points, with suitable traps, must therefore be incorporated within the flue system at the base of vertical flue sections in excess of 2m. These additional condensate drains must be run to discharge as detailed in section 2.11. Such drain points can be formed using standard muPVC fittings. Refer to the example in
Figure 2.8.3.
2.8.4 Terminations
It is not advisable to terminate air
intake or flue within a car port area.
Air inlet terminals must be facing upwards and positioned to ensure only fresh air is drawn into the boiler directly from outside the property. The flue outlet terminal is designed to face outwards but can, if desired, be adapted to face in any direction BUT
must not be directed in the region of the air inlet. The two terminals are subject to the requirements of BS 5440 Pt 1 for clearances from features of the building although some can be decreased to the values indicated. If either the air inlet or the flue outlet terminate at a height of less than 2m (6ft) above ground level the termination must be protected by a suitable guard. The K4 terminal guard, manufactured by Tower Flue Components Ltd, is suitable for this purpose and can be obtained from Keston Boilers. The Keston Condensing Boiler, as with any condensing boiler, will generate a condensate "plume" from the flue terminal in all weather conditions.
Consideration must therefore be given to the effect of this "plume" when selecting a location for the flue terminal.
WD50/2/1997 Chapter 2 - Boiler Connections The Keston 50, 60 & 80 Condensing Boilers
Installation & Servicing Instructions
Page : 14
FLUE
AIR
c
d
a
b
Figure 2.8.2 : Flue & Air Maximum Length Example
Keston
6 in min.
Figure 2.8.3 :
Flue Condensate Drain Point Example
40mm Tee Fitting
To Boiler
To Terminal
Loading...
+ 39 hidden pages