KACO XP500, XP550-HV User Manual

following guideline provided in this application note.
Design Guide of the Medium Voltage Transformers for KACO Central Inverter
This document describes the requirements of medium-voltage transformers that are connected to
KACO central inverter.
12-NPD-01-3dm-170c
Model
Rated Power
Rated AC Voltage
Protection Class
Type
XP100-HV
100kW
3*380V(±10%)
IP21, Indoor
Transformer
XP200-HV
200kW
3*380V(±10%)
IP21, Indoor
Transformer
XP250-HV
250kW
3*380V(±10%)
IP21, Indoor
Transformer
XP200-HV-TL
200 kW
3*290V(±10%)
IP21, Indoor
Transformerless
XP250-HV-TL
250 kW
3*290V(±10%)
IP21, Indoor
Transformerless
XP350-HV-TL
350 kW
3*290V(±10%)
IP21, Indoor
Transformerless
XP500-HV-TL
500 kW
3*370V(±10%)
IP21, Indoor
Transformerless
XP550-HV-TL
550 kW
3*370V(±10%)
IP21, Indoor
Transformerless
XP500-OD-TL
500kW
3*370V(±10%)
IP54, Outdoor
Transformerless
XP550-OD-TL
550kW
3*370V(±10%)
IP54, Outdoor
Transformerless
blueplanet 333 TL3 OD
333kW
3*370V(±10%)
IP54, Outdoor
Transformerless
blueplanet 1000 TL3 OD
1000kW
3*370V(±10%)
IP54, Outdoor
Transformerless
1. LIST OF TH E CENTRAL INVERTERS OF KACO
Table. 1 List of central Inverters of KACO
Table 1 shows the list of central inverter models of KACO, which can be connected to medium voltage
transformer.
KACO’s solar inverters are classified into 2 types : transformer type and transformerless type.
Unlike transformer inverters, the transformerless inverters don’t have transformers inside, so their
medium voltage transformers must be designed according to the guide when they need to be connected
with external medium voltage transformers.
2/14
Conductor voltage regarding ground
V
0
Central Inverter
MV Transformer
2. TECHN ICAL PROPERTIES
Medium voltage transformer that is connected with transformerless solar inverter must comply with
following technical specifications:
1. The transformer must be suitable for PWM (Pulse Width Modulation) Inverter. The transformer
should be designed such that its magnetic flux is not saturated even if 1% of DC current flow on its
low voltage winding. Also the transformer should be designed and tested in accordance with
ANSI/IEEE, NEMA, and Department of Energy standards.
2. The transformer must be designed considering the voltages that arise during pulsed operation of
the inverter. The voltages can reach a magnitude of maximum ±1400 V reference to ground. The
rmsvalue of the voltages reference to ground is maximum 700V. (See Fig.2)
Fig. 1 KACO central inverter with Double-winding Transformer
Fig. 2 Conductor voltage to ground and line-to-line voltage
3/14
3. The transformer must be designed for voltages on its lowvoltage windings that can exhibit a
voltage gradient dV/dt of up to 500V/µs reference to the ground. The linetoline voltages must be
sinusoidal.
4. A shield winding that is grounded to the tank is necessary between the lowvoltage windings and
the high voltage windings. This shield plate must be designed to protect against the heat due to
eddy current by the flux of both the low voltage winding and the high voltage winding. This serves
as an additional dV/dt filter.
5. In ambient temperatures off up to 50 °C the transformer must have a current load capability of
110 %.
Further information can be found in the following documents:
KACO central inverter data sheet
Power derating of KACO central inverter
6. During thermal rating, the load curve and the ambient conditions at the respective installation site
should be taken into account.
7. KACO new energy recommends to use a transformer with a tap changer on the highvoltage side
that enables an alignment to the voltage level of the mediumvoltage grid. Our recommendation
is 5 taps with 2.5% resolution.
8. The country-specific grid frequency should be taken into consideration.
9. The country specific standards valid should be taken into consideration.
4/14
Central Inverter
MV Transformer
3. REQUIREMENTS FOR MEDIUM-VOLTAGE TRANSFORMERS, THAT ARE CONNECTE D
TO 1 CENTRAL INVERTER
The transformer shown in Fig.3 is a double-winding transformer. Its low-voltage side is connected to KACO
central inverter of which rated output voltage is 370V, and its high voltage side is for connection to the
medium-voltage grid in Europe which is 20kV typically. However, other high voltages are also available: 10
kV, 15 kV, 22 kV, 25 kV, 27 kV, 30 kV, 34.5kV or 35 kV etc.
Fig. 3 KACO central inverter with Double-winding Transformer
This transformer must comply with the following technical specifications:
1. Equivalent series impedance between low voltage and high voltage winding:
The equivalent series impedance Z(%) of the transformer must be 6 %. Impedance voltage
tolerance limits of 5.4 % ~ 6.6 % must be maintained. This value can be determined when the high-
voltage winding is short-circuited and the voltage on the other lowvoltage winding is increased
until the nominal current flows. (see Fig.4).
Fig.4 Equivalent circuit with short circuited high voltage winding
5/14
ZH(1%) ZLa(5%)
2. Equivalent series impedance Z(%) of the double-winding transformer:
To summarize of the contents in Article 2, the equivalent series impedance Z(%) of the double-
winding transformer can be shown as followed.
ZL is the equivalent series impedance of low voltage winding, and ZH is the equivalent series
impedance of high voltage winding.
Fig. 5 Equivalent series impedance Z(%) of double-winding transformer
3. No neutral point is required on the low voltage side. Nevertheless, if a neutral point shows up on
the lowvoltage side, this neutral point must not be either connected or grounded.
4. Double-winding transformers with varying windings each on the highvoltage side and the
lowvoltage side can be used. For example YNd11, YNd5, YNd1 or Dy11, Dy5, Dy1 with an
ungrounded neutral point on the lowvoltage side (see Fig.6)
Fig. 6 Diagram of double-winding transformer
6/14
Central Inverter
Central Inverter
MV Transformer
4. REQUIREMENTS FOR MEDI UM-VOLTAGE TRANSFORMERS, THAT ARE CONNECTED
TO 2 CENTRAL INVERTERS
The transformer shown in Fig.7, is a dual stacked (four-winding) transformer. Its low-voltage side is
connected to KACO central inverter of which rated output voltage is 370V, and its high voltage side is for
connection to the medium-voltage grid in Europe which is 20kV typically. However, other high voltages
are also available: 10 kV, 15 kV, 22 kV, 25 kV, 27 kV, 30 kV, 34.5kV or 35 kV etc.
Fig. 7 KACO central inverter with dual stacked (four-winding) transformer
This transformer must comply with the following technical specifications:
1. Equivalent series impedance between low voltage and high voltage winding:
The equivalent series impedance Z(%) of the transformer must, in relation to every inverter, be 6 %
in each case. Impedance voltage tolerance limits of 5.4 % ~ 6.6 % must be maintained. This value
can be determined when the high-voltage winding is short-circuited and the voltage on the other
lowvoltage winding is increased until the nominal current flows. At the same time another low
voltage windings are idle (see Fig.8).
7/14
Y
Y
V
sc
I
sc
Fig.8 Equivalent circuit with short circuited high voltage winding
2. Equivalent series impedance between both low voltage winding:
The equivalent series impedance Z(%) between both lowvoltage windings must be 10 %. The
tolerance limits of this impedance voltage of 9 % ~ 11 % must be maintained. This value can be
determined when one of the lowvoltage winding is short-circuited and the voltage on the other
lowvoltage winding is increased until the nominal current flows. At the same time the
highvoltage windings are idle (see Fig.9).
Fig.9 Equivalent circuit with short circuited low voltage winding
3. Equivalent series impedance Z(%) of the dual stacked (four-winding) transformer:
To summarize of the contents in Article 1 and Article 2, the equivalent series impedance Z(%) of
the dual stacked (four-winding) transformer can be shown as followed.
ZL is the equivalent series impedance of low voltage winding, and ZH is the equivalent series
impedance of high voltage winding.
8/14
ZH(1%)
ZLa(5%)
ZLb(5%)
Fig. 10 Equivalent series impedance Z(%) of dual stacked (four-winding) transformer
4. No neutral point is required on the low voltage side. Nevertheless, if a neutral point shows up on
the lowvoltage side, this neutral point must not be either connected or grounded.
5. dual stacked (four-winding) transformers with varying windings each on the highvoltage side and
the lowvoltage side can be used. For example YNd11d11, YNd5d5, YNd1d1 or Dy11y11, Dy5y5,
Dy1y1 with an ungrounded neutral point on the lowvoltage side (see Fig.11).
Fig. 11 Diagram of dual stacked (four-winding) transformer
9/14
Central Inverter
Central Inverter
MV Transformer
Central Inverter
5. REQUIREMENTS FOR MEDIUM-VOLTAGE TRANSFORMERS, THAT ARE CONNECTED
TO 3 CENTRAL INVERTERS
The transformer shown in Fig.12 is a section-winding transformer.(Refer to the appendix) Its low-voltage
side is connected to KACO central inverter of which rated output voltage is 370V, and its high voltage side
is for connection to the medium-voltage grid in Europe which is 20kV typically. However, other high
voltages are also available: 10 kV, 15 kV, 22 kV, 25 kV, 27 kV, 30 kV, 34.5kV or 35 kV etc.
Fig. 12 KACO central inverter with section-winding transformer
This transformer must comply with the following technical specifications:
1. Equivalent series impedance between low voltage and high voltage winding:
The equivalent series impedance Z(%) of the transformer must, in relation to every inverter, be 6 %
in each case. Impedance voltage tolerance limits of 5.4 % ~ 6.6 % must be maintained. This value
can be determined when the high-voltage winding is short-circuited and the voltage on the other
lowvoltage winding is increased until the nominal current flows. At the same time another low
voltage windings are idle (see Fig.13).
10/14
Y
Y
Y
V
sc
I
sc
Fig.13 Equivalent circuit with short circuited high voltage winding
2. Equivalent series impedance between both low voltage winding:
The equivalent series impedance Z(%) between both lowvoltage windings must be 10 %. The
tolerance limits of this impedance voltage of 9 % ~ 11 % must be maintained. This value can be
determined when one of the lowvoltage winding is short-circuited and the voltage on the other
lowvoltage winding is increased until the nominal current flows. At the same time the
highvoltage windings are idle (see Fig.14).
Fig.14 Equivalent circuit with short circuited low voltage winding
3. Equivalent series impedance Z(%) of the section -winding transformer:
To summarize of the contents in Article 1 and Article 2, the equivalent series impedance Z(%) of
the section -winding transformer can be shown as followed.
ZL is the equivalent series impedance of low voltage winding, and ZH is the equivalent series
impedance of high voltage winding.
11/14
ZH(1%)
ZLa(5%)
ZLb(5%)
ZLc(5%)
Fig. 15 Equivalent series impedance Z(%) of section-winding transformer
4. No neutral point is required on the low voltage side. Nevertheless, if a neutral point shows up on
the lowvoltage side, this neutral point must not be either connected or grounded.
5. Section-winding transformers with varying windings each on the highvoltage side and the
lowvoltage side can be used. For example YNd11d11d11, YNd5d5d5, YNd1d1d1 or Dy11y11y11,
Dy5y5y5, Dy1y1y1 with an ungrounded neutral point on the lowvoltage side (see Fig.16).
Fig. 16 Diagram of section-winding transformer
12/14
Central Inverter
Central Inverter
MV Transformer
Central Inverter
Central Inverter
6. REQUIREMENTS FOR MEDI UM-VOLTAGE TRANSFORMERS, THAT ARE CONNECTED
TO 4 CENTRAL INVERTERS
The transformer shown in Fig.12 is a section-winding transformer.(Refer to the appendix) Its low-voltage
side is connected to KACO central inverter of which rated output voltage is 370V, and its high voltage side
is for connection to the medium-voltage grid in Europe which is 20kV typically. However, other high
voltages are also available: 10 kV, 15 kV, 22 kV, 25 kV, 27 kV, 30 kV, 34.5kV or 35 kV etc.
Fig. 17 KACO central inverter with section-winding transformer
This transformer must comply with the following technical specifications:
1. Equivalent series impedance between low voltage and high voltage winding:
The equivalent series impedance Z(%) of the transformer must, in relation to every inverter, be 6 %
in each case. Impedance voltage tolerance limits of 5.4 % ~ 6.6 % must be maintained. This value
can be determined when the high-voltage winding is short-circuited and the voltage on the other
lowvoltage winding is increased until the nominal current flows. At the same time another low
voltage windings are idle (see Fig.18).
13/14
Y
Y
Y
V
sc
I
sc
Y
Fig.18 Equivalent circuit with short circuited high voltage winding
2. Equivalent series impedance between both low voltage winding:
The equivalent series impedance Z(%) between both lowvoltage windings must be 10 %. The
tolerance limits of this impedance voltage of 9 % ~ 11 % must be maintained. This value can be
determined when one of the lowvoltage winding is short-circuited and the voltage on the other
lowvoltage winding is increased until the nominal current flows. At the same time the
highvoltage windings are idle (see Fig.19).
Fig.19 Equivalent circuit with short circuited low voltage winding
3. Equivalent series impedance Z(%) of the section -winding transformer:
To summarize of the contents in Article 1 and Article 2, the equivalent series impedance Z(%) of
the section -winding transformer can be shown as followed.
ZL is the equivalent series impedance of low voltage winding, and ZH is the equivalent series
impedance of high voltage winding.
14/14
ZH(1%)
ZLa(5%)
ZLb(5%)
ZLc(5%)
ZLd(5%)
2
4
6
5
3
1
2
4
6
5
3
1
2
4
6
5
3
1
2
4
6
5
3
1
2
4
6
5
3
1
2
4
6
5
3
1
1W
1V
1U
3W
3V
3U
1W
1V
1U
1W
1V
1U
3W
3U
3V
1W
1U
1V
2
4
6
5
3
1
2
4
6
5
3
1
2
4
6
5
3
1
2W
2V
2U
2W
2U
2V
2
4
6
5
3
1
2
4
6
5
3
1
2
4
6
5
3
1
4W
4V
4U
4W
4U
4V
Fig. 20 Equivalent series impedance Z(%) of section-winding transformer
4. No neutral point is required on the low voltage side. Nevertheless, if a neutral point shows up on
the lowvoltage side, this neutral point must not be either connected or grounded.
5. Section-winding transformers with varying windings each on the highvoltage side and the
lowvoltage side can be used. For example YNd11d11d11d11, YNd5d5d5d5, YNd1d1d1d1 or
Dy11y11y11y11, Dy5y5y5y5, Dy1y1y1y1 with an ungrounded neutral point on the lowvoltage side
(see Fig.21).
Fig. 21 Diagram of section-winding transformer
15/14
Core
LVW1 LVW2 LVW3
HVW1 HVW2 HVW3
Core
LVW1 LVW2
HVW1 HVW2
LVW: Low Voltage winding HVW: High Voltage winding
Case1. Dual stacked Case2. Triple stacked
Core
Low Voltage winding1
Low Voltage winding2
High Voltage winding
Core
Low Voltage winding1
Low Voltage winding2
High Voltage winding
Case1. LLH Case2. LHL
APPENDIX
Winding technology
Medium voltage transformer that is connected with transformerless solar inverter must be
designed with section winding transformer.
Section winding transformer
Multi-layer winding transformer
16/14
Core
Low Voltage winding1
Low Voltage winding2
Low Voltage winding3
High Voltage winding
Case3. LLLH
17/14
B-1701~1716, 2ND Woolim Lions Valley, 146-8, Sangdaewon-dong, Jungwon-gu, Seongnam-si, Gyeonggi-
do, South Korea
TEL +82-31-8018-2700 FAX +82-31-8018-2738 www.kaco-newenergy.kr
12-NPD-01-3dm-170c
Revision
number
Description
Name
(Date)
0
Initial version
Joon.Kim
(20-Oct-2014)
a
Revision by adding the model (blueplanet 1000 TL3 OD )
Joon.Kim
(12-Jan-2015)
b
Revision by adding the model (blueplanet 333 TL3 OD )
Joon.Kim
(13-Feb-2015)
c
Revision by adding appendix Revision by changing terms(Multi winding Section winding, Four-
winding transformer --> Dual stacked (four-winding) transformer)
Revision by adding chapter 6.
Yeji.Jang
(10-Mar-2015)
Written
Checked
Approved
디지털 서명 자Yeji.jang
DN: cn=Yeji.jang, o=KACO-newenergy, ou=System, email=Yeji.jang@kac o-newenergy.kr, c=KR 날짜: 2015.03.10 21:24:41 +09'00'
Nick .choi
디지털 서명 자Nick.choi
DN: cn=Nick.choi, o=KACO, ou=system, email=nick.choi@ka co-newenergy.kr, c=KR 날짜: 2015.03.11 09:37:09 +09'00'
REVISION HISTO RY
19/14
Loading...