Kaco Powador 2500xi, Powador 3600xi, Powador 4000xi, Powador 4500xi, Powador 5000xi Operating Instructions Manual

Powador 2500xi 3600xi | 4000xi 4500xi | 5000xi
The next generation of transformerless inverters with an integrated DC disconnector.
Operating instructions
OperatorSkilled and authorised electrician
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 3
Intended for use by the operator
Operating Instructions
Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi
General Notes ..........................................................4
1 About This Documentation ........................................4
1.1 Retention of documents .............................................4
1.2 Symbols used in this document ..................................4
1.3 CE marking................................................................4
1.4 Name plate ...............................................................4
2 Safety Instructions and Regulations ..........................5
3 Notes on Installation and Operation ...........................5
3.1 Intended use .............................................................5
3.2 Factory warranty and liability .....................................5
3.3 Service ......................................................................6
4 Operation ..................................................................6
4.1 Overview of controls and displays .............................6
4.2 LED displays ..............................................................6
4.3 Keys “1” and “2” ......................................................7
4.4 Level 1 menu - Display menu .....................................8
4.5 Level 2 menu - Confi guration mode ...........................9
4.6 DC disconnector ......................................................10
4.7 Night start-up key....................................................10
4.8 The serial RS232 interface .......................................10
4.9 The RS485 interface ............................................ 11
4.10 Display ................................................................ 11
5 Troubleshooting .................................................. 15
6 Recycling and Disposal ........................................ 17
The installation instructions for authorised electri­cians begin after the operating instructions
Page 4 Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
General Notes
By purchasing an inverter from KACO new energy GmbH, you have opted for a reliable, high-performance technology and will profi t from KACO new energy GmbH’s many years of experience in the fi eld of current inverter technology and power electronics. The Powador 2500xi, 3600xi, 4000xi, 4500xi and 5000xi inverters are transformerless, fanless, robust, high-effi ciency inverters. Using the illuminated display and intuitive menu navigation, you can display the most important information pertaining to the inverter’s grid feed. The mounting plate that is included provides for optimal and simple installation on a wall. The inverter’s data can be transmitted over the serial interface to a PC, where it can then be visualised. With protection class IP54, the units are ready for operation in all ambient conditions. The inverters can also be used without hesitation in agriculture and industry.
1 About This Documentation
The following notes guide you through all of the documenta­tion. Additional documents are applicable in conjunction with these operating and installation instructions. We assume no liability for any damage caused by failure to observe these instructions.
Other applicable documents
When installing the inverters, be sure to observe all assembly and installation instructions for components and other parts of the system. These instructions are delivered together with the respective components and additional parts of the system.
1.1 Retention of documents
Please pass these operating and installation instructions on to the plant operator. These documents must be stored next to the system and must be available at all times.
1.2 Symbols used in this document
When installing the inverter, observe the safety instructions provided in these installation instructions.
Danger due to lethal voltages.
1.3 CE marking
The CE marking is used to document that the Powador inverter shown on the name plate fulfi lls the fundamental require­ments of the following relevant directives: Directive concerning electromagnetic compatibility (Council Directive 2004/108/EC) Low Voltage Directive (Council Directive 2006/95/EC).
1.4 Name plate
The name plate showing the exact designation of the unit is located on the support plate on the underside of the housing.
Section 1 · About This Documentation
DANGER
Failure to observe a warning indicated in this manner will directly lead to serious bodily injury or death.
Failure to observe a warning indicated in this manner may directly lead to serious bodily injury or death.
WARNING
CAUTION
Failure to observe a warning indicated in this manner may lead to minor or moderate bodily injury or to serious damage to property.
AT TE NT I ON
Failure to observe a warning indicated in this manner may lead to damage to property.
NOTE
Useful information and notes.
AC TI ON
This symbol indicates that a certain action is required.
IMPORTANT
Failure to observe this information may result in reduced convenience or impaired functionality.
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 5
2 Safety Instructions
and Regulations
Accident prevention regulations
The inverter must be installed by an authorised electrician, who is responsible for observing existing standards and regu­lations.
The proper and safe operation of this unit requires proper transportation, storage, assembly and installation, as well as careful operation and maintenance.
The inverter may only be operated by persons who have read and understood the operating instructions.
Modifi cations
Modifi cations to the inverter are generally prohibited. Always consult an authorised electrician for modifi cations to the sur­roundings of the inverter, as they are qualifi ed to undertake such work.
Transportation
The inverter is subjected to extensive testing and inspections in our test fi eld. This is how we ensure the high quality of our products. Our inverters leave our factory in proper electrical and mechanical condition. Special packaging provides for a safe and careful transportation. However, transport damage may still occur. The shipping company is responsible in such cases.
Thoroughly inspect the inverter upon delivery. If you dis­cover any damage to the packaging which indicates that the inverter may have been damaged, or if you discover any visible damage to the inverter, notify the responsible shipping com­pany immediately.
If necessary, your solar installer or KACO new energy GmbH will assist you. Damage reports must be received by the ship­ping company in writing within six days of receipt of the goods.
When transporting the inverter, the original or equivalent packaging is to be used, as this ensures safe transport.
3 Notes on Installation
and Operation
3.1 Intended use
The unit converts the DC voltage generated by the photo­voltaic (PV) modules into AC voltage and feeds this into the power grid. Powador inverters are built according to the state of the art and recognised safety rules. However, improper use may cause lethal hazards for the operator or third parties, or may result in damage to the units and other property. The inverter may only be operated with a permanent connec­tion to the public power grid. The inverter is not intended for mobile use.
Any other or additional use is not considered the intended use. The manufacturer/supplier is not liable for damage caused by such unintended use. Damage caused by such unintended use is at the sole risk of the operator.
Intended use also includes adherence to the operating and installation instructions. Your authorised electrician under­takes the registration with your power supply company and obtains approval for your photovoltaic installation from the supply grid operator on your behalf. Some of the documents that you require in order to register your photovoltaic instal­lation and have it approved are included in the installation instructions.
3.2 Factory warranty and liability
KACO new energy GmbH issues a warranty of seven years on the Powador inverter starting from the date of installation, but at most 90 months after shipment by KACO new energy GmbH.
During this time, KACO new energy GmbH guarantees the proper operation of the units and to undertake repairs at the factory free of charge in the event of a defect for which we are responsible.
Section 2 · Safety Instructions and Regulations Section 3 · Notes on Installation and Operation
DANGER
Danger due to lethal voltages.
Lethal voltages are present within the unit and on the power supply lines. Therefore, only skilled and authorised electricians may install and open the unit.
Even when the unit is switched off, high contact voltages may still be present inside the unit.
CAUTION
Risk of damage due to improper modifi cations. Never modify or manipulate the inverter or other components of the system.
Page 6 Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
Contact your specialty dealer or installer if your unit exhibits a defect or fault during the warranty period.
Warranty claims are excluded in the following cases:
Use of the units in ways not intendedImproper installation and installation that does not comply
with standards
Improper operationOperation of units with defective protective equipmentUnauthorised modifi cations to the units or repair attemptsInfl uence of foreign objects and force majeure (lightning,
overvoltage, severe weather, fi re)
Insuffi cient ventilation of the unitFailure to observe the relevant safety regulationsTransport damage.
All warranty claims must be handled at the premises of KACO new energy GmbH. The unit must, where possible, be returned in its original or equivalent packaging. The costs for these services cannot be borne by KACO new energy GmbH.
KACO new energy GmbH will only perform warranty services if the defective unit is returned to KACO new energy GmbH together with a copy of the invoice which was issued to the user by the dealer. The name plate on the unit must be fully legible. If these requirements are not fulfi lled, KACO new energy GmbH reserves the right to deny warranty services.
The warranty period for repairs or replacement deliveries is six months after delivery. However, it continues at least until the end of the original warranty period for the delivery item.
3.3 Service
We place special emphasis on the quality and longevity of our inverters, starting with the product development phase. More than 60 years of experience in the fi eld of current inverters support us in this philosophy.
However, despite all quality assurance measures, faults may occur in exceptional cases. In such cases, KACO new energy GmbH will provide you with the maximum possible support. KACO new energy GmbH will make every effort to remedy such faults in an expeditious manner and without a great deal of bureaucracy. In such cases, contact our service department directly by telephone at
+49 (0)7132-3818-660
4 Operation
The grid feed process begins in the morning when suffi cient light is available, and, therefore, when a certain minimum voltage is present at the inverter. The inverter enables grid feed after a country-specifi c start-up time (see Installation Manual, section 4, “Technical Data”). If, as nightfall approaches, the voltage drops below the minimum voltage, the grid feed mode ends and the inverter switches off.
4.1 Overview of controls and displays
Figure 4.1: Overview of the Powador
Legend 1 Display
Displays measured values and confi guration parameters 2 LED displays Display the operating status 3 Control keys Switch between the display and confi guration of parameters
4 Cable fi tting for AC connection 5 Night start-up button
For activating the display after nightfall
6 DC disconnector 7 RS232 interface 8 Cable feedthrough for RS485 interface cable 9 Cable feedthrough for DC connection
4.2 LED displays
During normal operation, the photovoltaic modules generate voltage as soon as the insolation is suffi cient. If this voltage is present in the inverter at a certain level for a certain time, the inverter begins to feed into the grid. The inverter is equipped with three LEDs, which give informa­tion about the various operating statuses as follows.
Section 3 · Notes on Installation and Operation Section 4 · Operation
3
2
1
6
7
9
8
5
4
CAUTION
Incorrect use is prohibited.
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 7
1
2
3
!
ok
Figure 4.2: LED displays
LED (1) (green):
The LED begins to light up beginning with a photovoltaic module voltage of approx. 300 V and goes out again if the module voltage is lower than 250 V. The “OK” LED indicates that the inverter and the inverter con­trol are active. If this LED is not lit, the inverter cannot feed into the grid. In normal mode, the LED begins to light up in the morn­ing (if there is enough sunlight) and goes out as nightfall approaches.
LED (2) (green):
The LED lights up every time the inverter feeds into the grid. For this to happen, the photovoltaic module voltage must exceed 400 V (factory setting) and suffi cient power must be provided by the PV generator. If the grid feed is interrupted because the power is too low, the inverter waits for a country-specifi c length of time before it begins feeding into the grid once again. LED (2) can, therefore, light up only when LED (1) is already lit. In a normal state, the inverter begins feeding into the grid in the morning and stops feeding into the grid as it becomes increasingly darker. On cloudy days and in the winter months, the grid feed can - depending on the PV generator and the current grid feed power - be temporarily interrupted and sub­sequently re-started. This process can repeat itself several times, especially in the morning and evening. This is in no way an indication of defective operation, but instead constitutes normal operating behaviour.
LED (3) (red):
The LED indicates that the grid feed was stopped due to a fault. The following faults activate the LED (3):
Grid overvoltage or undervoltage on one of the three
phases
Failure of one of the phases L2 or L3Generator power is too highShutdown due to the temperature being too highFault in the unit Leakage current is too high (RCD type B) Overfrequency or underfrequencyInsulation faultCommunication errorFault in the DC grid feedFault in the voltage transformerSelftest faultFault in the RCD type B module.
Wait approx. 10 minutes to see if the fault is only temporary in nature. If this is not the case, notify your authorised electri­cian. If the fault is cleared, the grid feed begins once again after a country-specifi c waiting period (see Installation Instructions, Section 4, “Technical Data”).
Check whether the fault in question relates to a general power failure or whether the fuse between the meter and the inverter has failed. If the fuse has failed, notify your authorised techni­cian. If there was a power failure, simply wait until the fault has been cleared. The system automatically re-starts.
4.3 Keys “1” and “2”
Figure 4.3: Powador control keys
Key “1” is used to switch between the various displays for measured values and data. With key “2”, settings such as those relating to the shutdown value can be confi gured. Here, menu navigation is divided into two levels. In level 1 (display mode), measured values such as the solar generator voltage and yields can be read. Here, only key “1” is activated. In con­fi guration mode, key “1” is also used to navigate through the individual displays, and settings are confi gured with key “2”.
Section 4 · Operation
IMPORTANT
If the grid feed phase fails (power failure on the public grid), LED (3) does not light up. If this happens, all LEDs and the display go out. The inverter is shut down com­pletely. The inverter can only resume its normal operation when the grid feed phase is available once again.
AC TI ON
By pressing key “1” for approx. 1 second, you can choose which measured value is to be displayed. The menus are continuous, which means that when you arrive at the last entry in a menu, the fi rst entry is displayed once again the next time key “1” is pressed (see Figure
4.4).
Page 8 Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
4.4 Level 1 menu - Display menu
The display menu is displayed once the Powador inverter has started up. Measured values and all of the meters are dis­played here. Key “1” is used to navigate through the individual menu items.
Inverter type display
Start at 410V
Generator voltage (V) and current (A)
Line voltage (V), current (A) and power (W)
Daily peak capacity
Tem perature inside
Counter yield (clear using key “2”)
Yield today
Tot al yield
(Total) economy of CO
2
Counter oper. hours (clear with key “2”)
Operating hours today
Total operating hours
Figure 4.4: Display mode menu
Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi
The inverter waits until the voltage exceeds 410 V. One minute later, the grid feed begins.
The current voltage and current of the solar generator connected to the inverter.
The current line voltage, line current and the power that is currently being fed into the grid.
The current day’s peak power (in watts) that was fed into the grid over a short time.
A display of the current temperature inside the unit, in °C. The inverter limits the grid feed power depending on the temperature of the semiconductors.
This meter totals all yields until it is reset again. The customer can confi gure the time periods for this meter, e.g. as a monthly meter.
The power that has been fed into the grid on the current day in watt­hours (Wh).
The power that has been fed into the grid since start-up of the inverter.
Shows the CO
2
savings of this PV installation compared to the
German electricity mix. The CO
2
savings are calculated from the total
yield meter and can also be cleared with this meter.
The customer can confi gure the time periods for this meter, e.g. as a monthly meter. The procedure for resetting meters is explained at the bottom of the page. Today’s hours of operation. As soon as the inverter is in standby mode (i.e. when LED (1) lights up), the running time is added up.
Hours of operation since start-up of the inverter. As soon as the inverter is in standby mode (i.e. when LED (1) lights up), the running time is added up.
Explanation of the menu items in display mode
Section 4 · Operation
“Counter yield” and “Counter oper. hours” can be cleared separately from the other meters. When “Counter yield” or “Counter
oper. hours” is displayed, you can reach the “Clear counter?” display by pressing key “2”. Key “2” must now be used to select “yes”. Press key “1” to confi rm the clearing. The display jumps back to the meter that was cleared. “Counter yield” and the “Counter oper. hours” are always cleared together. Therefore, clearing one meter suffi ces to clear both.
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 9
4.5 Level 2 menu - Confi guration mode
Software version
Clear the grid feed meter
Select the interface and confi guration of the RS485 address
S0 interface pulse rate
Immediate start
Figure 4.5: Confi guration mode menu
Clearing the grid feed meter
When the grid feed meter is cleared, all meters (“Counter yield”, “Yield today”, “Total yield”, “Economy of CO
2
”, “Dail y peak capacity”, “Counter oper. hours”, “Operating hours today”, “Total operating hours”) are reset to zero. To clear the meters, select “Yes” with key “2”, and confi rm your selection by pressing key “1”. The required code is “2” and is entered using key “2”. By means of an additional con­fi rmation with key “1”, all meters are cleared. A display indi­cating that the grid feed counters have been cleared confi rms this action.
Choice of interface and address setting
Using the menu item “Interface”, you can use key “2” to switch between the RS232 and RS485 interfaces. If the RS485 interface is activated, you can reach the address setting by pressing key “1”. By pressing key “2”, the address can be set in a consecutive manner from 1 to 32. The address then jumps back to 1. The RS485 interface is used to communicate with the Powador-proLOG. When several inverters are connected to a Powador-proLOG, each address may only be used once. It is, therefore, possible to monitor 32 Powador inverters with one Powador-proLOG.
S0 interface pulse rate
The S0 interface is designed as a galvanically isolated transis­tor output. This interface is designed according to “DIN 43864
- Current interface for transmitting pulses from a pulsing meter to a tariff metering device”. The S0 interface pulse rate can be chosen in three unit inter­vals: 500, 1000 and 2000 pulses/kWh. Due to these toler­ances, the emitted pulse yield may deviate from the values on your supply grid operator’s grid feed meter by up to 15 %.
Immediate start
The inverter can also be started up without any waiting period for the purpose of testing or for the purpose of acceptance by your power supply company. If the inverter is already feeding into the grid, this menu item is not available.
Section 4 · Operation
AC TI ON
To switch to confi guration mode, keep key “1” pressed down while at the same time pressing key “2”, until the software version is displayed in the confi guration mode. Pressing key “1” now switches to the next menu item, and changes can be made in the respective menu item by pressing key “2”. The set value increases each time key “2” is pressed. If the maximum value has been reached, the value jumps to the minimum setting choice. The vari­ous settings are highlighted in fi gure 4.5.
NOTE
Meters can only be cleared.It is not possible to set the meters.
AC TI ON
Settings are saved only upon exiting confi guration mode. If 2 minutes elapse without a key being pressed, the con­fi guration mode is automatically exited. The confi gura­tion mode can also be immediately exited by pressing both keys. As a confi rmation, “Settings saved” appears on the display for 4 seconds. The settings are now per­manently saved in the Powador inverter.
AC TI ON
Keep key “2” pressed down for a short time until the inverter switches on (relays switch audibly) and the green grid feed LED (2) lights up. If there is insuffi cient solar generator power, the inverter stops feeding into the grid after a short period of time.
Page 10 Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
4.6 DC disconnector
Figure 4.6: Underside of the Powador
The inverters include an internal DC disconnector, which allows for the inverter to be disconnected from the photo­voltaic generator in case of repair or fault.
To disconnect the inverter from the photovoltaic generator, turn the internal DC disconnector on the underside of the inverter from the ON (1) position to the OFF (0) position (see fi gure 4.6).
When delivered, the inverter’s internal DC disconnector is in the OFF (0) position.
4.7 Night start-up key
The unit switches off in the evening as nightfall approaches. The display is no longer shown. In order to retrieve the values from the current day, (daily yield, daily hours of operation and max. grid feed power) after the display switches off, the unit can also be activated during the night by pressing the night start-up key on the underside of the inverter.
You can now scroll through the menu and retrieve the saved values. If over one minute elapses without a key being pressed, the unit switches off automatically once again. The “Counter oper. hours ”, “Total operating hours”, “Coun­ter yield”, and “Total yield” data are permanently saved and totaled. This data remains in memory even if the inverter is switched off for a long time. The daily yield, daily hours of operation and the max. daily grid feed power are available until the following morning and are cleared when PV generator voltage is present again.
4.8 The serial RS232 interface
Operating data can be transmitted to a computer (e.g. notebook) over a galvanically isolated serial interface (see fi gure 4.6 - (7)) from where it can then be individually processed further using standard spreadsheet software.
A standard serial 1:1 interface cable is all that is required for connecting the inverter to the computer. The cable length should not exceed 20 metres.
The data from the inverter is sent unidirectionally as pure ASCII text over the serial interface. The data is not checked for errors.
Tab le 4.1: RS232 interface pin assignment
The RS232 interface has the following parameters:
Baud rate Data bits Parity Stop bits Protocol
9600 baud 8 none 1 none
Figure 4.7 shows, as an example, a few of lines of transmis­sion via the RS232 interface. Data can be received with any terminal emulator, which comes with every operating system, or with the KACO-viso visualisa­tion tool.
Together with the Powador inverter, KACO-viso takes over the role of a data logger. It saves the data from the inverter and displays it in various diagram types as a daily or monthly rep­resentation. The PC, however, must also run continuously. Because of the amount of energy used, this type of monitoring only makes sense over limited periods, such as during a fault analysis. For permanent monitoring, we recommend the optional accesso­ries (see section 5).
Section 4 · Operation
6
5
7
Powador Sub-D male 9-polig
Bedeutung PC Sub-D
female 9-polig 2TXD 2 3RXD3 4RTS 4 5GND5
Signifi cation
male 9-pole female 9-pole
AC TI ON
To do this, press the “night start-up” key (see fi gure 4.6
- (6)) on the underside of the unit for approx. 5 seconds until a display appears.
NOTE
The KACO-viso visualisation software can be down­loaded from http://www.kaco-newenergy.de
NOTE
With the optional accessories (see section 5), you can also implement wireless data transmission over long dis­tances between the inverter and your PC.
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 11
Section 4 · Operation
Tab le 4. 2: Explanation of the individual columns
Figure 4.7: Excerpt from the protocol of a transmission via the RS232 interface
The interface of the PC or laptop that is connected must comply with the standard for RS232 interfaces. Some compu­ter manufacturers do not fully adhere to the standard. In such cases, problems may occur during data transmissions.
4.9 The RS485 interface
Powador inverters are also equipped with an RS485 interface (see Installation Instructions, fi gure 6.7) in order to enable remote monitoring of your photovoltaic installation. Several inverters can be monitored over this interface at the same time. Using the Powador-proLOG series, you can receive yield and operating data as well as error messages by SMS (text message) or e-mail. This monitoring option is especially rec­ommended for situations where you are unable to check the functionality of the installation on-site at regular intervals, e.g. if you live far away from the installation site.
In addition, you can use the Powador link within your instal­lation to bridge long distances between several inverters or between an inverter and the Powador-proLOG by means of a wireless radio transmission. Contact your installer if you wish to integrate remote monitoring into your system.
4.10 Display
Inverters in the Powador xi series are equipped with a back­lit LCD (see fi gure 4.1 - (1)) which displays measured values and data. In normal mode, the backlighting is switched off. As soon as you press one of the keys, the backlighting is activated. If approx. 1 minute elapses without a key being pressed, it switches off once again.
Spalte 1 2 3 4 5 6 7 8 9 10
00.00.0000 00:05:30 4 363.8 0.37 134 226.1 0.53 103 23
00.00.0000 00:05:40 4 366.0 0.39 142 226.1 0.53 112 23
00.00.0000 00:05:50 4 359.5 0.41 147 226.1 0.53 116 23
00.00.0000 00:06:00 4 369.8 0.42 155 226.1 0.58 118 23
00.00.0000 00:06:10 4 377.0 0.43 162 226.1 0.63 131 23
00.00.0000 00:06:20 4 373.6 0.45 168 226.1 0.63 133 23
00.00.0000 00:06:30 4 364.0 0.48 174 226.1 0.68 146 23
00.00.0000 00:06:40 4 364.3 0.49 178 226.1 0.68 146 23
Column
NOTE
The measured data for current and voltage istainted with the specifi ed tolerances (see Installation Instructions).This data is not suitable for measuring effi ciency or compiling yield data.Its sole purpose is to monitor the basic opera­tion of the system.
IMPORTANT
Due to measuring tolerances, the measured values may not always correspond to the actual values. The inverter’s measuring elements have been selected to ensure maxi­mum solar yields.
Due to these tolerances, the daily yields displayed on the inverter may deviate from the values on your supply grid operator’s grid feed meter by up to 15 %.
Column Explanation Column Explanation
1 Not in use 6 Generator power in W
2 Daily operating time 7 Grid voltage in V
3 Operating mode (see table 4.3) 8 Grid current, delivered current in A
4 Generator voltage in V 9 Grid-feeding power in W
5 Generator current in A 10 Device temperature in °C
Page 12 Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
Operating statuses
Status Explanation Comment
0 Inverter has just switched on Only for a brief time after the inverter fi rst switches on in the
morning.
1 Waiting to start Selftest is complete, the Powador will switch to grid feed mode in a
few seconds.
2 Waiting to switch off Generator voltage and power is too low. The status before it changes
over to night shutdown mode.
3 Constant voltage regulator When the grid feed begins, a constant generator voltage is fed in
(80 % of the measured no-load voltage) for a short period.
4 MPP regulator, constant search
movement
In cases of low insolation, the grid is fed into while the MPP regula­tor is searching.
5 MPP regulator, without search
movement
In cases of high insolation, the grid is fed into while the MPP regula­tor is stationary so as to maximise yields.
6 Wait mode before grid feed, test-
ing the grid and solar voltage
The inverter has stopped the grid feed because the power of the PV modules is too low (e.g. twilight). If the generator voltage is higher than the switch-on threshold (410 V), the inverter begins the grid feed once again after a country-specifi c waiting period (see Installation Instructions, section 4, Technical Data).
7 Wait mode before selftest, testing
the line and solar voltage
The inverter waits until the generator voltage exceeds the switch-on threshold and begins the selftest of the relays after a country-spe­cifi cwaiting period (see Installation Instructions, section 4, Technical Data).
8 Selftest of the relays Testing line relays prior to beginning grid feed.
10 Overtemperature shutdown If the inverter overheats (heat sink temperature >85 °C) due to the
ambient temperature being too high and inadequate air circulation, the inverter switches off.
11 Power limitation Protective function of the inverter when too much generator power
is supplied or the heat sink of the unit exceeds 75 °C.
12 Overload shutdown Protective function of the inverter when too much generator power
is supplied.
13 Overvoltage shutdown Protective function of the inverter when the line voltage L1 is too
high.
14 Line failure (3-phase monitoring) Protective function of the inverter when the measured values of one
of the three grid phases are beyond the permitted tolerance. Reasons for line failures are: undervoltage, overvoltage, underfre­quency, overfrequency, a fault in the phase conductor.
15 Changing over to night shutdown
mode
Inverter switches from stand-by to night shutdown mode.
18 RCD type B shutdown Residual current is too high, the integrated AC/DC-sensitive residual
current circuit breaker has registered an unduly high leakage current to the PE.
19 Insulation resistance too low Insulation resistance from PV-/PV+ to PE <1.2 MOhm.
30 Fault in the voltage transformer The current and voltage measurements in the inverter are not plau-
sible.
31 Fault in the RCD type B module A fault has occurred in the AC/DC-sensitive residual current circuit
breaker.
32 Selftest error An error has occurred during the line relay test, a line relay is not
functioning correctly.
33 Fault in the DC grid feed The DC feed into the grid was too large.
34 Communication error An error has occurred in the internal data transmission.
Tab le 4. 3: Explanation of the operating states
Section 4 · Operation
Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 13
Section 4 · Operation
Display Explanation
Line failure Undervoltage Lx
The voltage of a grid phase is too low, the grid cannot be fed into. The phase in which the fault occurs (undervoltage) is displayed in each case.
Line failure Overvoltage Lx
The voltage of a grid phase is too high, the grid cannot be fed into. The phase in which the fault occurs (overvoltage) is displayed in each case.
Line failure Phase conductor
The phase shifts of the phase voltages are incorrect. A proper three-phase supply network is not present.
Line error overvoltage L1
Overvoltage shutdown due to a voltage boost caused by increased line impedance of the grid connection L1.
Line failure Underfrequency
The line frequency is too low.
Line failure Overfrequency
The line frequency is too high.
Error DC grid feeding
The DC feed into the grid has exceeded the permitted limit value. This grid feed can be impressed from the grid on the Powador inverter so that no inverter fault exists.
Error current switch-off
The current and voltage measurements in the inverter are not plausible. This can be caused by very dynamic weather conditions, if there are quick changes between low grid feed power (e.g. 200 W) and high grid feed power (e.g. the inverter’s maximum grid feed power).
Error RCD module
An operational fault has occurred in the AC/DC-sensitive residual current circuit breaker.
Error Selftest
The internal grid separation relay test has failed.
Error Measurement
The current and voltage measurements in the inverter are not plausible. This can be caused by very dynamic weather conditions if there are quick changes between low grid feed power (e.g. 200 W) and high grid feed power (e.g. the maximum grid feed power).
Error isolation generator
The insulation resistance on the DC side is <1.2 MOhm. The grid cannot be fed into. The insulation resistance of the PV modules must be tested.
Temperature to o high inside
The temperature in the unit has become too high (>85 °C). Starting from an internal temperature of 75 °C, the inverter limits the power and levels off between 75 °C and 80 °C.An internal temperature of 85 °C is only achieved if convection cooling is impeded by external factors, e.g. by covering the cooling fi ns.
Failure PV overvoltage
The power of the modules was too high for a short time. This can occur during times of very dynamic weather conditions. The power limiter usually prevents too much power at the input of the inverter so that the inverter does not shut down.
Line failure Average voltage
The average line voltage measurement over a 10 minute period according to EN 50160 has exceeded the maximum permitted limit value.
Tab le 4. 4:
Fault signals
Fault signals
Page 14 Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN
Fault signals
When these error messages are displayed, the grid feed is interrupted, the red LED (3) lights up, and the fault signal relay has switched. This error correction takes a country-specifi c length of time (see Installation Instructions, section 4, Tech­nical Data). Afterwards the red fault LED (3) goes out, the fault signal relay drops out again, and the display signals that it is ready to feed into the grid once again. If the fault is no longer present, the Powador inverter begins feeding into the grid once again after a preset waiting period (see Installation Instructions, section 4, Technical Data). Many of these fault signals point to a fault in the grid, and are, therefore, not an operational fault on the part of the Powa­dor inverter. The minimum triggering levels are determined by applicable standards (e.g. VDE0126-1-1), and the inverter must switch off if the permitted values are exceeded.
Automatic display during operation
Tab le 4.5: Display
Display Explanation
Selftest in progress
The grid separation relays are tested for proper operation.
Section 4 · Operation
Loading...
+ 29 hidden pages