Julabo F25-HL, F32-HL, F33-HL, FP35-HL, FP40-HL Operating Manual

...
English
www.julabo.com
Operating Manual
Circulators
air-cooled
F25-HL F32-HL F33-HL
FP35-HL FP40-HL FP50-HL
water-cooled
FPW50-HL
Original Operating Manual
19532809-V5.doc 09.11.17
JULABO USA, Inc. 884 Marcon Boulevard Allentown, PA 18109 Phone: +1(610) 231-0250 Fax: +1(610) 231-0260 info.us@ julabo.com
Temperature control devices for research and industry are developed,
Congratulations!
You have made an excellent choice. JULABO thanks you for the trust you have placed in us. This operating manual has been designed to help you gain an understanding of the operation and possible applications of our circulators. For optimal utilization of all functions, we recommend that you thoroughly study this manual prior to beginning operation.
The JULABO Quality Management System
produced, and distributed according to the requirements of ISO 9001 and ISO 14001. Certificate Registration No. 01 100044846
Unpacking and inspecting
Unpack the circulator and accessories and inspect them for possible transport damage. Damage should be reported to the responsible carrier, railway, or postal authority, and a damage report should be requested. These instructions must be followed fully for us to guarantee our full support of your claim for protecting against loss from concealed damage. The form required for filing such a claim will be provided by the carrier.
Printed in Germany Changes without prior notification reserved
Important: keep operation manual for future use
1.953.2809-V5 11/17
2
TABLE OF CONTENTS
Operating manual ................................................................................................................ 5
1. Intended use ................................................................................................................. 5
1.1. Description ............................................................................................................... 5
2. Operator responsibility – Safety recommendations ....................................................... 6
2.1. Disposal ................................................................................................................... 8
2.2. Technical specifications ........................................................................................... 9
2.3. Cooling water connection ....................................................................................... 13
Operating instructions ....................................................................................................... 14
3. Safety notes for the user ............................................................................................. 14
3.1. Explanation of safety notes .................................................................................... 14
3.2. Explanation of other notes ...................................................................................... 14
3.3. Safety recommendations ........................................................................................ 15
4. Operating controls and functional elements ................................................................ 17
5. Preparations ............................................................................................................... 22
5.1. Installation .............................................................................................................. 22
5.2. Bath fluids .............................................................................................................. 22
5.3. Temperature application to external systems ......................................................... 24
5.3.1. Tubing ............................................................................................................... 25
5.4. Filling / draining ...................................................................................................... 26
6. Operating procedures ................................................................................................. 27
6.1. Power connection ................................................................................................... 27
6.2. Switching on / Selecting the language .................................................................... 27
6.2.1. Switching on the circulator ................................................................................. 27
6.2.2. Switching on the cooling machine ...................................................................... 28
6.3. Start - Stop ............................................................................................................. 28
HL
7. Setting of temperatures ................................................................................. 29
8. Safety installations, warning functions ........................................................... 29
8.0.1. Early warning system, low level protection ......................................................... 33
9. Menu functions .............................................................................................. 34
9.1. Start of a program .................................................................................................. 36
9.1.1. Status at the end of a program .......................................................................... 38
9.1.2. Indication after successful start .......................................................................... 38
9.1.3. Editing after Start ............................................................................................... 39
9.1.4. Interrupting a program ....................................................................................... 39
9.1.5. Interruption after a power failure ........................................................................ 40
9.1.6. Termination of a program................................................................................... 40
9.2. Program administration, creation ............................................................................ 41
9.3. Setting the pump pressure ..................................................................................... 45
9.4. Configuration .......................................................................................................... 46
9.4.1. Remote control via the serial interface ............................................................... 49
9.4.2. Keypad control or setpoint setting via the analog input ...................................... 49
9.4.3. Autostart ............................................................................................................ 50
3
9.4.4.
Off-Mode ............................................................................................................ 50
9.4.5. ActVar - actuating variable .................................................................................. 51
9.4.6. Setting of clock and date .................................................................................... 52
9.4.7. Language ........................................................................................................... 52
9.4.8. Unit ..................................................................................................................... 52
9.4.9. Program type ...................................................................................................... 52
9.4.10. Reset ............................................................................................................. 52
9.5. Control .................................................................................................................... 53
9.5.1. Control internal / external ................................................................................... 55
9.5.2. Selftuning ........................................................................................................... 56
9.5.3. Dynamik intern ................................................................................................... 56
9.5.4. CoSpeed - extern ............................................................................................... 57
9.5.5. Control parameters – internal/external ................................................................ 57
9.6. Serial Interface ........................................................................................................ 59
9.7. ATC Absolute Temperature Calibration, 3-point calibration ..................................... 60
9.7.1. ATC Fühler - intern / extern ................................................................................ 63
9.7.2. ATC Status - yes / no ......................................................................................... 63
9.7.3. Type 1 -/ 2 -/ 3 point .......................................................................................... 63
9.7.4. Example: 3-point calibration for internal control ................................................. 64
9.8. Limits ...................................................................................................................... 66
9.8.1. Limits for internal control and external control..................................................... 67
9.8.2. Limits for external control.................................................................................... 68
9.9. Analog inputs/outputs ............................................................................................. 69
9.9.1. Control connector ............................................................................................... 73
9.9.2. Outputs of the connector - REG+E-PROG .......................................................... 74
9.9.3. Input of the connector - REG+E-PROG .............................................................. 75
9.9.4. External Stand-by input ...................................................................................... 77
9.9.5. Alarm-output ....................................................................................................... 78
10. Troubleshooting guide / Error messages ..................................................................... 79
11. Electrical connections .................................................................................................. 82
12. Remote control ............................................................................................................ 85
12.1. Setup for remote control .......................................................................................... 85
12.2. Communication with a PC or a superordinated data system ................................... 85
12.3. List of commands .................................................................................................... 86
12.4. Status messages .................................................................................................... 90
12.5. Error messages....................................................................................................... 90
13. Installation of electronic module with analog connectors ............................................. 91
14. JULABO Service – Online remote diagnosis ............................................................... 92
15. Cleaning / repairing the unit ......................................................................................... 93
16. WARRANTY PROVISIONS ......................................................................................... 94
4

Operating manual

JULABO circulators are not suitable for direct temperature control of foods, semi-
medium (bath fluid).
ICC
TCF
ATC
3
RS232 RS485
Pt100
PUMP
SMART
applications.

1. Intended use

JULABO circulators have been designed to control the temperature of specific fluids in a bath tank. The units feature pump connections for temperature control of external systems (loop circuit).
luxury foods and tobacco, or pharmaceutical and medical products. Direct temperature control means unprotected contact of the object with the bath

1.1. Description

The circulators are operated via the splash-proof keypad. The implemented
microprocessor technology allows to set and to store different values that can be indicated on the VFD COMFORT-DISPLAY and LCD DIALOG-DISPLAY. Three menu keys facilitate adjusting setpoints, warning and safety functions and menu functions.
HL
The integrated programmer allows storing and running temperature and time-
dependent processes.
The control electronics including “ICC - Intelligent Cascade Control“ automatically
adapts the heat supplied to the thermal requirements of the bath.
The TCF - Temperature Control Features allow the user to have access to all
important temperature control parameters. This means: Full control on the control mode and the chance to manually adjust or adapt control to the specific application.
Absolute Temperature Calibration (ATC3) provides high temperature stability in the
bath. With the 3-point calibration an offset is adjusted at three temperatures to ensure an accurate temperature pattern at the selected spot in the bath over the full temperature range.
Electrical connections:
The serial interface, switchable from RS232 to RS485, allows modern process technology without additional interface. Connection for Pt100 external sensor for external temperature measurement and control. Alarm output for external alarm message or control of JULABO refrigerating baths or solenoid valve (cooling water). The electronic module (option) provides 3 further analog connections (alarm input, standby input, recorder output, programmer input).
The excess temperature protection conforming to IEC 61010-2-010 is a safety
installation independent from the control circuit. This protection can be indicated and set on the LCD DIALOG-DISPLAY.
The early warning system for low level signals that bath fluid needs to be refilled
before the low level protection conforming to IEC 61010-2-010 causes a complete shut-down of the main functional elements.
Intelligent pump system: The pump capacity (electronically adjustable via the motor
speed) enables to adapt to varying conditions for internal and external temperature
5

Operator responsibility – Safety recommendations

2. Operator responsibility – Safety recommendations
The products of JULABO ensure safe operation when installed, operated, and maintained according to common safety regulations. This section explains the potential dangers that may arise when operating the circulator and also specifies the most important safety precautions to preclude these dangers as far as possible.
The operator is responsible for the qualification of the personnel operating the units. The personnel operating the units should be regularly instructed about the dangers involved with
their job activities as well as measures to avert these dangers.
Make sure all persons tasked with operating, installing, and maintaining the unit have read and
understand the safety information and operating instructions.
When using hazardous materials or materials that could become hazardous, the circulator may be
operated only by persons who are absolutely familiar with these materials and the circulator. These persons must be fully aware of possible risks.
If you have any questions concerning the operation of your unit or the information in this manual, please contact us!
Contact
Safety instructions for the operator:
You have received a product designed for industrial use. Nevertheless, avoid strikes to the
housing, vibrations, damage to the operating-element panel (keypad, display), and contamination.
Make sure the product is checked for proper condition regularly (depending on the conditions of
use). Regularly check (at least every 2 years) the proper condition of the mandatory, warning, prohibition and safety labels.
Make sure that the mains power supply has low impedance to avoid any negative effects on
instruments being operated on the same mains.
This unit is designed for operation in a controlled electromagnetic environment. This means that
transmitting devices (e.g., cellular phones) should not be used in the immediate vicinity. Magnetic radiation may affect other devices with components sensitive to magnetic fields (e.g., monitors). We recommend maintaining a minimum distance of 1 m.
Permissible ambient temperature: max. 40 °C, min. 5 °C. Permissible relative humidity: 50% (40 °C). Do not store the unit in an aggressive atmosphere. Protect the unit from contamination. Do not expose the unit to sunlight.
JULABO USA, Inc. 884 Marcon Boulevard Allentown, PA 18109
Phone: +1(610) 231-0250 Fax: +1(610) 231-0260 info.us@ julabo.com www.julabo.com
Appropriate operation
Only qualified personnel is authorized to perform configuration, installation, maintenance and repairs of the circulator. Routine operation can also be carried out by untrained personnel who should however be instructed by trained personnel.
6
HL
Use:
The bath can be filled with flammable materials. Fire hazard! There might be chemical dangers depending on the bath medium used. Observe all warnings for the used materials (bath fluids) and the respective instructions (safety data sheets). Insufficient ventilation may result in the formation of explosive mixtures. Only use the unit in well ventilated areas.
Only use recommended materials (bath fluids). Only use non-acid and non corroding materials.
When using hazardous materials or materials that could become hazardous, the operator must affix the enclosed safety labels to the front of the unit so they are highly visible:
If this unit is intended for use within the United States of America, all 3 warning labels must be affixed to the housing of the unit prior to use. Directions for the positioning of the individual warning labels are enclosed with the warning labels included in the delivery. Warning labels must be easily visible to users.
1
Warning label W00: Colors: yellow, black Danger area. Attention! Observe instructions. (operating manual, safety data sheet)
2
Mandatory label M018: Colors: blue, white Carefully read the user information prior to beginning operation.
Scope: EU
or
2
Semi S1-0701 Table A1-2 #9 Carefully read the user information prior to beginning operation.
Scope: USA, NAFTA
3
Warning label Proposition 65
Particular care and attention is necessary because of the wide operating range. There are thermal dangers: Burn, scald, hot steam, hot parts and surfaces that can be touched.
Warning label W26: Colors: yellow, black
Hot surface warning. (The label is put on by JULABO)
Observe the instructions in the manuals for instruments of a different make that you connect to the circulator, particularly the respective safety recommendations. Also observe the pin assignment of plugs and technical specifications of the products.
7
Operator responsibility – Safety recommendations
Contact an authorized waste management company in your country.

2.1. Disposal

The circulator contains a back-up battery that supplies voltage to memory chips when the unit is switched off. Do not dispose of the battery with household waste! Depending on battery regulations in your country, you might be obliged to give back used or defect batteries to gathering places. The product may be used with oil as bath fluid. These oils fully or partially consist of mineral oil or synthetic oil. For disposal, observe the instructions in the safety data sheets.
This unit contains refrigerants, which at this time are not considered harmful to the ozone layer. However, over the long operating period of the unit, disposal rules may change. Therefore, only qualified personnel should handle the disposal.
Disposal with household waste (unsorted waste) or similar collections of municipal waste is not permitted!
8
Medium: ethanol
kW
0.26 0.2 0.06
0.45 0.39 0.15 0.06
Medium: ethanol
kW
0.5 0.32 0.12 0.03

2.2. Technical specifications

F25-HL F32-HL
Working temperature range °C
Temperature stability °C
Cooling capacity
°C
-28 ... 200 -35 ... 200
±0,01 ±0,01
+20 0 -20
+20 0 -20 -30
HL
Refrigerant
Overall dimensions (WxDxH) cm
Bath opening (WxL) cm
Bath depth cm
Filling volume liters
Weight kg
Mains power connection V/ Hz 230 / 50 230 / 50
Current draw (at 230 V) A 12 12
Current draw, CH, GB (at 230 V) A <9+2> <9+2>
Mains power connection V/ Hz ----- 230 / 60
Current draw (at 230 V) A ----- 12
Mains power connection V/ Hz 115 / 60 115 / 60
Current draw (at 115 V) A 13 14
Mains power connection V/ Hz 100 / 50/60 100 / 50/60
Current draw (at 100 V) A 13 14
F33-HL
Working temperature range °C
Temperature stability °C
Cooling capacity
°C
R134a R134a
23x42x64 31x42x64
12x14 18x12
14 15
3 ... 4,5 5,5 ... 8
32 38
-30 ... 200
±0.01
+20 0 -20 -30
Refrigerant
Overall dimensions (WxDxH) cm
Bath opening (WxL) cm
Bath depth cm
Filling volume liters
Weight kg
Mains power connection V/Hz 230 / 50/60
Current draw (at 230 V) A 12
Current draw, CH, GB (at 230 V) A <9+2>
Mains power connection V/ Hz 100 / 50/60
Current draw (at 100 V) A 15
Mains power connection V/ Hz 115 / 60
Current draw (at 115 V) A 15
R134a
36x46x71
23x14
20
12 ... 16
45
9
Operator responsibility – Safety recommendations
FP35-HL
FP40-HL
-35 ... 200
-40 ... 200
±0.01
±0.01
Medium: ethanol
kW
+20 0 -20 -30
+20 0 -20 -40 R134a
R134a
31x42x66
36x46x71
18x12
23x14
-----
20
2.5
9 ... 16
38
49
V/Hz
230 / 50
230 / 50
A
12
13
A
<9+2>
<9+3>
V/ Hz
-----
230 / 60
A
-----
13
V/ Hz
115 / 60
-----
A
14
-----
V/ Hz
100 / 50/60
-----
A
14
----­ FP50-HL
Working temperature range
°C
-50 ... 200
Temperature stability
°C
±0.01
Medium: ethanol
kW
0.9 0.8 0.5 0.16
Working temperature range °C
Temperature stability °C
Cooling capacity
°C
Refrigerant
Overall dimensions (WxDxH) cm
Bath opening (WxL) cm
Bath depth cm
Filling volume liters
Weight kg
Mains power connection
Current draw (at 230 V)
Current draw, CH, GB (at 230 V)
Mains power connection
Current draw (at 230 V)
Mains power connection
Current draw (at 115 V)
Mains power connection
Current draw (at 100 V)
0.45 0.39 0.15 0.05
0.68 0.5 0.32 0.04
Cooling capacity
°C
Refrigerant
Overall dimensions (WxDxH) cm
Bath opening (WxL) cm
Bath depth cm
Filling volume liters
Weight kg
Mains power connection 230 V/50 Hz
Current draw (at 230 V)
Current draw, CH, GB (at 230 V)
Mains power connection
Current draw (at 230 V)
V/Hz 230 / 50
A 14
A <9+4>
V/ Hz 230 / 60
A 14
+20 0 -20 -40
R404A / R507
42x49x72
18x12
20
5.5 ... 8
57
10
HL
FPW50-HL
Working temperature range
°C
-50 ... 200
Temperature stability
°C
±0.01
Medium: ethanol
kW
0.9 0.8 0.5 0.16
HL
Temperature selection
digital
via keypad
indication on LCD DIALOG-DISPLAY (°C/°F)
remote control via PC
indication on monitor
Temperature indication
VFD COMFORT-DISPLAY (°C/°F)
Resolution
°C
0.01
ATC3 INT / EXT
°C
±3 / ±9
Temperature control
ICC - Intelligent Cascade Control
Heater wattage (at 230 V)
kW
2.0
Heater wattage (at 115 V)
kW
1.0
Electronically adj. pump capacity
stages
1 ... 4
Flow rate at 0 bar
l/min
22 ... 26
Max. pressure at 0 liters
bar
0.7 Max. suction at 0 liters
bar
0.4
Electrical connections:
see page 12
Ambient temperature
°C
5 ... 40
Mains power connection
V/ Hz
208-230 / 50/60
Current draw (at 208 V / 230 V)
A
8 / 9
Mains power connection
V/ Hz
100-115 / 50/60
Current draw (at 100 V / 115 V)
A
9 / 10
Cooling capacity
°C
Refrigerant
Overall dimensions (WxDxH) cm
Bath opening (WxL) cm
Bath depth cm
Filling volume liters
Weight kg
Mains power connection
Current draw (at 230 V)
Current draw, CH, GB (at 230 V)
Mains power connection
Current draw (at 230 V)
V/Hz 230/ 50
A 14
A <9+4>
V/ Hz 230 / 60
A 14
+20 0 -20 -40
R404A / R507
42x49x72
18x12
20
5.5 ... 8
57
All measurements have been carried out at: rated voltage and frequency ambient temperature: 20 °C Technical changes without prior notification reserved.
11
Operator responsibility – Safety recommendations
Caution:
compatibility may be impacted.
Electrical connections:
External alarm device 24-0 V DC / max. 25 mA Computer interface RS232 or RS485 External Pt100 sensor
Optional for HL, SL (Order No. 8900100 Electronic module with analog connections) Programmer input -100 °C to 400 °C = 0 - 10 V or 0 - 20 mA or 4 - 20 mA Input for the signal of a flow meter or external manipulated variable Temperature recorder outputs 0 - 10 V (0 V = -100 °C, 10 V = 400 °C) 0 - 20 mA (0 mA = -100 °C, 20 mA = 400 °C) 4 - 20 mA (4 mA = -100 °C, 20 mA = 400 °C) Standby input for external emergency switch-off Alarm output for external alarm signal
Safety installations according to IEC 61010-2-010: Excess temperature protection adjustable from 0 °C ... 320 °C Low liquid level protection float switch Classification according to DIN 12876-1 class III Supplementary safety installations Early warning system for low level float switch High temperature warning function optical + audible (in intervals) Low temperature warning function optical + audible (in intervals) Supervision of working sensor plausibility control Reciprocal sensor monitoring between working and safety sensors difference >35 K Alarm message optical + audible (permanent) Warning message optical + audible (in intervals) Environmental conditions according to IEC 61 010-1: Use indoors only. Altitude up to 2000 m - normal zero. Ambient temperature: see Technical specifications Humidity: Max. relative humidity 80% for temperatures up to +31 °C, linear decrease down to 50% relative humidity at a temperature of +40 °C Max. mains voltage fluctuations of ±10% are permissible. Protection class according to IEC 60 529 IP21 The unit corresponds to Class I Overvoltage category II Pollution degree 2
The unit is not suitable for use in explosive environment
EMC requirements
The device is an ISM device of group 1 per CISPR 11 (uses HF for internal purposes) and is classified in class A (industrial and commercial sector).
NOTICE:
Devices of class A are intended for the use in an industrial electromagnetic
When operating in other electromagnetic environments, their electromagnetic
12
environment.

2.3. Cooling water connection

pH – value
7,5 to 9,0
Sulfate [SO4 2- ]
< 100 ppm
Hydrocarbonate [HCO3- ] / Sulphate [SO4 2-]
> 1 ppm
Hardness [Ca2+, Mg2+] / [HCO3-]
> 0,5 dH
Alkalinity
60 ppm < [HCO3-] < 300 ppm
Conductivity
< 500 μs / cm
Chloride (CL-)
< 50 ppm
Phosphate (PO43-)
< 2 ppm
Ammonia (NH3)
< 0,5 ppm
Free Chlorine
< 0,5 ppm
Ferri Ions (Fe3+ )
< 0,5 ppm
Mangano Ions (Mn2+)
< 0,05 ppm
Carbon dioxide (CO2)
< 10 ppm
Hydrosulfide (H2S)
< 50 ppm
Content of oxygen
< 0,1 ppm
Algae growth
impermissible
Suspended solids
impermissible
Avoid putrid water.
Notice: Cooling water circuit
location where the unit is operated.
Cooling water pressure (IN / OUT ) max. 6 bar Difference pressure (IN - OUT ) 3.5 to 6 bar Cooling water temperature <20 °C
Recommended quality of cooling water:
HL
Notice:
Danger of corrosion of heat exchanger due to unsuitable quality of cooling water.
Due to its high content of lime hart water is not suitable for cooling and causes calcination of the heat exchanger.
Ferrous water or water containing ferrous particles will cause formation of rust even in heat exchangers made of stainless steel.
Chlorous water will cause pitting corrosion in heat exchangers made of stainless steel.
Due to its corrosive characteristics distilled and deionized water is unsuitable and will cause corrosion of the bath. .
Due to its corrosive characteristics sea water is not suitable.
Due to its microbiological (bacteria) components which settle in the heat
exchanger untreated and unpurified river water and water from cooling towers is unsuitable.
Avoid particulate matter in cooling water.
Risk of oil leaking from the cooling circuit (compressor) of the recirculating cooler into the cooling water in case of a fault in the circuit! Observe the laws and regulations of the water distribution company valid in the
13

Operating instructions

In addition to the safety warnings listed, warnings are posted throughout the operating
Warning:
Caution:
Notice:
in its surroundings can be damaged.
Note! Draws attention to something special.
Important! Indicates usage tips and other useful information.
This icon is used in the operating instructions to indicate which have to be set or confirmed.
Operating instructions

3. Safety notes for the user

3.1. Explanation of safety notes

manual. These warnings are designated by an exclamation mark inside an equilateral triangle. “Warning of a dangerous situation (Attention! Please follow the documentation).” The danger is classified using a signal word. Read and follow these important instructions for averting dangers.
Describes a possibly highly dangerous situation. If these instructions are not followed, serious injury and danger to life could result.
Describes a possibly dangerous situation. If this is not avoided, slight or minor injuries could result. A warning of possible property damage may also be contained in the text.
Describes a possibly harmful situation. If this is not avoided, the product or anything

3.2. Explanation of other notes

flashing values or parameters
14
these parts.

3.3. Safety recommendations

Follow the safety instructions to avoid personal injury and property damage. Also, the valid safety instructions for workplaces must be followed.
Only connect the unit to a power socket with an earthing contact (PE – protective earth)!
The power supply plug serves as a safe disconnecting device from the line and must always be easily accessible.
Place the unit on an even surface on a base made of nonflammable material.
Do not stay in the area below the unit.
Make sure you read and understand all instructions and safety precautions listed in
this manual before installing or operating your unit.
Adjust excess-temperature safety device below the flash point of the bath fluid.
Observe the limited working temperature range when using plastic bath tanks.
Never operate the unit without bath fluid in the bath.
Pay attention to the thermal expansion of bath oil during heating to avoid
overflowing of the fluid.
Prevent water from entering the hot bath oil.
Do not drain the bath fluid while it is hot!
Check the temperature of the bath fluid prior to draining (e.g., by switching the unit on for a short moment).
Use suitable connecting tubing.
Avoid sharp bends in the tubing, and maintain a sufficient distance from
surrounding walls.
Make sure that the tubing is securely attached.
Regularly check the tubing for material defects (e.g., for cracks).
Never operate damaged or leaking units.
Always turn off the unit and disconnect the mains cable from the power source
before performing any service or maintenance procedures, or before moving the unit.
Always turn off the unit and disconnect the mains cable from the power source before cleaning the unit.
Always empty the bath before moving the unit.
Transport the unit with care.
Sudden jolts or drops may cause damage in the interior of the unit.
Observe all warning labels.
Never remove warning labels.
Never operate units with damaged mains power cables.
Repairs are to be carried out only by qualified service personnel.
HL
Some parts of the bath tank and the pump connections may become extremely hot
during continuous operation. Therefore, exercise particular caution when touching
15
Safety notes for the user
Caution:
determine the method of decontamination.
example.
defects or other reproductive harm.
The temperature controlling i.e. of fluids in a reactor constitutes normal circulator practice.
We do not know which substances are contained within these vessels. Many substances are:
inflammable, easily ignited or explosive
hazardous to health
environmentally unsafe
i.e.: dangerous
The user alone is responsible for the handling of these substances!
The following questions shall help to recognize possible dangers and to reduce the risks to a minimum.
Are all tubes and electrical cables connected and installed? Note: sharp edges, hot surfaces in operation, moving machine parts, etc.
Do dangerous steams or gases arise when heating? Is an exhaust needed when working?
What to do when a dangerous substance was spilled on or in the unit? Before starting to work, obtain information concerning the substance and
Notice: Check the safety installations at least twice a year!
Excess temperature protection according to IEC 61010-2-010. With a screwdriver turn back the adjustable excess temperature protection until the shut-down point (actual temperature).
Low level protection according to IEC 61010-2-010. To check the function of the float, it can be manually lowered with a screwdriver for
WARNING
This product contains chemicals known to the state of California to cause cancer, birth
16

4. Operating controls and functional elements

Front view Rear view
HL
17
Operating controls and functional elements
1a
Mains power switch, illuminated for circulator
2
2.1
2.2
3
LCD DIALOG-DISPLAY
1b
Mains power switch, illuminated for cooling machine
VFD COMFORT-DISPLAY
Header: Control indicators Line 1: Actual value internal or external
The display is depending on the selected control mode in the menu > Control < (internal or external).
Line 2: Working temp. setpoint, constantly S xxx.xx
Line 3: Actual value (E = external or I = internal)
Alternating with the display in line 1
Use the keys PI Capacity in % - with manipulated variable set to >control<* PS Capacity in % - with manipulated variable set to >serial<* or >eprog<* H Heater capacity in Watts U Mains voltage Volts F Flow rate in liters/minute (providing EPROG input set to >Flow rate<)
to indicate further values in line 3
2.3
*refer to >MENU / CONFIGIGURATIO> page 36
Control indicators in the header: Heating / Cooling / Alarm /
Remote control
Control indicators in the header: Temperature indication Internal or External actual value Temperature indication in °C or °F
Display for the adjusted pump pressure stage in the -OFF- mode. Display for the effective pump pressure stage (rotation speed) after start. Four stages, adjustable via the
Line 1: Setpoint and origin of setpoint programming
(Key / RS232 or RS485 / ext. Pt100 / EProg)
Line 2: Actual value - internal or external,
identical to line 1 of the VFD-COMFORT-DISPLAY
Line 3: Heating capacity in %.
Line 4: Control type: internal / external
button, in the menu >PUMP<.
18
Navigation aid in MENU - Window
Actual value / parameter
A beep signals the end of setting
The above graph “front side” shows an example for standard display.
4
Keys / : Selection of menu items / parameters
Orientation aid in MENU - Window
Line 1 - name with allocation to key
2 Submenu Level 2 Example: CONFIGURATION
3 Submenu Level 3
Keypad 1 Navigation keys
HL
- Setting in line 3:
Safety values
T – Setpoint
1 Main menu Level 1
4.1
4.2
4.3
1. Key: >OK< Start / Stop (pump / heater )
2. >OK< in the menu Menu item / select submenu for setting Save set value Save selected parameter
After the actions Start, Stop and change from VFD Display to standard display the key
is locked for a short time.
1. Key: >Return< Stop (pump / heater) Special display on VFD Display leave line 3.
2. >Return< in the menu one menu level down Correction function for parameters or values (prior to OK)
immediately back to standard display
- icon for „keep key pressed down“.
1. Key: >Up / Down <temperature – increase/decrease setpoint Push key quickly for single steps, Keep key pressed for fast change.
2. >Up/Down< in the menu selection of menu items / parameters
4.4
4.5
4.6
Menu keys
Key: start the menu > warning and safety values<
Key: start the menu >temperature setpoints<
Key: display of MENU structure
19
Operating controls and functional elements
Numeric keypad: numerals 0 to 9 Rear view
7
Socket for external measurement and control sensor 8
Interface RS232 / RS485: remote control via personal computer
9
Control cable of JULABO refrigerated circulator The circulator automatically recognizes the connected electronic module.
10
ALARM
Alarm output (for external alarm signal)
11
STAND-BY
Standby input (for external emergency switch-off)
12
REG+E-PROG
Programmer input and temperature recorder output
13
Connector for supplementary pump or solenoid valve
No control voltage in the -OFF- condition
14 Connector solenoid valve
2. Configurable (Refer to page 69)
15
Fuses (for connectors 13, 14), T1.25A
16
5
6
Keypad 2
..
ext Pt100
SERIAL
minus / decimal point
Backspace key on LCD DIALOG-DISPLAY.
Adjustable excess temperature protection according to IEC 61010-2-010
or external setpoint programming
9a
9b
Socket: output for alarm messages
Socket:
Option: Electronic module Order No. 8 900 100
230 V / max. 1.25 A
1. No control voltage in the -OFF- condition
Mains fuses, T16A
20
HL
17a
Mains power cable with plug for circulator 18
Built-in mains outlet for connection of circulator (230 V / 16 A)
19
Drain screw with drain connection
20
Venting grid, removable
21
23
24
17b
22
Mains power cable with plug cooling machine
Pump connections suction pump pressure pump
Selector dial for cooling machine (only F25) Position "1" for operation with HL circulator.
Cooling water OUTLET and INLET.
¾"
21

Preparations

with HL circulator.
(only F25, factory setting)
Caution:
control because it leads to calcification in the bath.
5. Preparations

5.1. Installation

material.
Cooling machine, pump motor and electronics produce intrinsic heat that is dissipated via the venting openings! Never cover these openings!
Keep at least 20 cm of open space on the front and rear venting grids.
The place of installation should be large enough and provide sufficient
air ventilation to ensure the room does not warm up excessively because of the heat the instrument rejects to the environment. (Max. permissible ambient temperature: 40 °C). For a fault (leakage) in the refrigeration system, the standard EN 378 prescribes a certain room space to be available for each kg of refrigerant. The refrigerant quantity is specified on the type plate.
Place the unit on an even surface on a pad made of non-flammable
3
> > For 0.25 kg of refrigerant R134a, a room space of 1 m > For 0.52 kg of refrigerant R404A, a room space of 1 m > For 0.49 kg of refrigerant R507, a room space of 1 m
is required.
3
is required.
3
is required.
Do not set up the unit in the immediate vicinity of heat sources and do not expose to sun light
Before operating the unit after transport, wait about one hour after setting it up. This will allow any oil that has accumulated laterally during transport to flow back down thus ensuring maximum cooling performance of the compressor.
Set selector dial for cooling machine (23) in position "1" for operation
5.2. Bath fluids
Carefully read the safety data sheet of the bath fluid used, particularly with regard to the fire point! If a bath fluid with a fire point of 65 °C is used, only supervised operation is possible.
Water: The quality of water depends on local conditions.
Due to the high concentration of lime, hard water is not suitable for temperature
Only water cooled models:
Ensure circulation of cooling water by connecting the tubing to cooling water inlet and outlet on the rear of the refrigerated circulator.
Cooling water connecter ¾"
Cooling water see page 12
22
Ferrous water can cause corrosion - even on stainless steel.
corrosion in the bath, even in stainless steel.
Bath fluid
Temperature range
soft/decalcified water
5 °C to 80 °C
mixture water/glycol, mixture 1:1
-20°C to 50°C
Description
G
HY
H5
Order Number
10 liters
8 940 124
8 940 104
8 940 106
5 liters
8 940 125
8 940 105
8 940 107
Temperature range
°C
-30 ... 80
-80 ... 55
-50 ...105
Flash point
°C
--
78
124
Fire point
°C
--
80
142
Color
light yellow
clear
clear
Description
H10
H20S
Order Number
10 liters
8 940 114
8 940 108
5 liters
8 940 115
8 940 109
Temperature range
°C
-20 ... 180
0 ... 220
Flash point
°C
190
230
Fire point
°C
216
274
Color
clear
light brown
No liability for use of other bath fluids!
Chloric water can cause pitting corrosion.
Distilled and deionized water is unsuitable. Their special properties cause
Recommended bath fluids:
JULABO bath fluids
HL
JULABO
JULABO
Thermal
Thermal
See website for list of recommended bath fluids.
Thermal
Thermal
Thermal
ATTENTION: The maximum permissible viscosity is 70 mm
Caution:
Fire or other dangers when using bath fluids that are not recommended:
Use only non-acidic and non-corroding bath fluids.
JULABO assumes no liability for damage caused by the selection of an unsuitable bath liquid. Unsuitable bath fluids are fluids which, e.g.,
are highly viscous (much higher than recommended at the respective working temperature)
have a low viscosity and have creep characteristics
have corrosive characteristics or
tend to crack.
2
/s.
23
Preparations
with the cap nut.
T16A
T16A
T1.25A
ext
Pt100
SERIAL
ALARM
REG+ E-PROG
STAND-BY
21
22
H = Height adjustment

5.3. Temperature application to external systems

Caution: Securely attach all tubing to prevent slipping.
If the circulator is operated without external system, close the pump connector (22)
Temperature application to external, closed systems
closed systems (loop circuit) with simultaneous temperature application in the circulator bath.
Unscrew the M16x1 collar nuts on the pump connectors with a 19 mm (3/4“) wrench and remove the sealing disks. Using the collar nuts, screw on the tubing connection fittings (for tubing 8 mm or 12 mm in diameter) delivered with the unit and tighten firmly. (Pressure pump: 22, suction pump: 21)
Push on the tubing, and secure with tube clamps.
Attach the tubing to the connectors of the external closed
system, e.g., an instrument with a pressure-resistant temperature jacket or a temperature coil, and fasten with tube
The circulator is used for temperature application to external,
clamps to prevent slipping.
Temperature application to external, open systems
The circulator is equipped with both a pressure and suction pump for external temperature application in open systems.
Differing flow rates of the pressure and suction pumps should be compensated. To maintain a constant liquid level, the JULABO „D+S“ Level Adapter is recommended for the external bath tank. The flow rate of the pressure pump will be then regulated by a built-in float device. The liquid level may be changed by a height adjustment on the „D+S“ Level Adapter.
Accessory: „D+S“ Level Adapter Order No. 8 970 410
Important:
The liquid level should be equal in the internal and external
baths (absolute height).
If you take out samples (for example Erlenmeyer flasks) from
the external bath, turn the circulator off with the Start/Stop key.
S = Suction pump connection D = Pressure pump connection K = Float
24
T16A
T16A
T1.25A
ext
Pt100
SERIAL
ALARM
REG+ E-PROG
STAND-BY
13
14
Order No. Length
Temperature range
8930008 1 m
CR® tubing 8 mm inner dia.
-20 °C to 120 °C
8930012 1 m
CR® tubing 12 mm inner dia.
-20 °C to 120 °C
8930108 1 m
Viton tubing 8 mm inner dia.
-50 °C to 200 °C
8930112 1 m
Viton tubing 12 mm inner dia.
-50 °C to 200 °C
8930410 1 m
Insulation for tubing 8 mm inner dia.
-50 °C to 100 °C
8930412 1 m
Insulation for tubing 12 mm inner dia.
-50 °C to 100 °C
8 930 209 0.5 m
8 930 214 3.0 m
Metal tubing, triple insulated, M16x1
-100 °C to +350 °C
8 930 220 0.5 m
8 930 223 3.0 m
Metal tubing, insulated, M16x1
-50 °C to +200 °C
Warning: Tubing:
Backflow safety device
If the liquid levels in the circulator bath and the external system are at different heights, overflowing must be prevented after the power has been turned off.
Flood hazard!
For this reason, solenoid valves for loop circuit or shut-off valves can be integrated in the loop circuit.
Connect the valve to the connector (13). If socket (14) is used:
In menu >Inputs/Outputs< set the menu item >SV-Out< to >Backflow<.
Order No. Description 8 980 701 Set of solenoid valves for loop circuit up to +100 °C
HL
(see page 69)

5.3.1. Tubing

Recommended tubing:
8 930 210 1.0 m 8 930 211 1.5 m
8 970 456 Shut-off valve (suitable up to +90 °C) 8 970 457 Shut-off valve (suitable up to +200 °C)
8 930 221 1.0 m 8 930 222 1.5 m
At high working temperatures the tubing used for temperature application and cooling water supply represents a danger source. A damaged tubing line may cause hot bath fluid to be pumped out within a short time. This may result in:
Burning of skin
Difficulties in breathing due to hot atmosphere
25
Preparations
Safety recommendations
Preventive maintenance: Replace the tubing from time to time.
protection.
Employ suitable connecting tubing.
Make sure that the tubing is securely attached.
Avoid sharp bends in the tubing, and maintain a sufficient distance from
surrounding walls.
Regularly check the tubing for material defects (e.g. for cracks).

5.4. Filling / draining

Notice:
Pay attention to the thermal expansion of bath oil during heating to avoid overflowing of the liquid.
Do not drain the bath fluid while it is hot! Recommendation: Temperature range 5 °C to 40 °C Check the temperature of the bath fluid prior to draining (by switching the unit on for a short moment, for example).
Store and dispose the used bath fluid according to the laws for environmental
Filling
Take care that no liquid enters the interior of the circulator.
Recommended maximum filling level with water as bath fluid: 30 mm below the tank rim
Recommended maximum filling level with bath oils: 40 mm below the tank rim
After filling, immerse the samples in the bath or place the lid on
the bath, in case the opening is not to be used.
The circulator provides an early warning system for low level
(description – please refer to page 33) that may be triggered when changing samples in the bath.
Draining:
Turn off the unit and disconnect the mains cable from the power source.
Hold the venting grid, pull out and remove.
Slide a short piece of tube onto the drain
26
connection and hold it into a container.
Loosen the drain screw a few turns and drain the unit completely.
Tighten the drain tap.

6. Operating procedures

Caution:
We disclaim all liability for damage caused by incorrect line voltages!
the mains socket.
deutsch / english

6.1. Power connection

Only connect the unit to a power socket with earthing contact (PE – protective earth)!
The power supply plug serves as safe disconnecting device from the line and must be always easily accessible.
Never operate equipment with damaged mains power cables.
Regularly check the mains power cables for material defects (e.g. for cracks).
Check to make sure that the line voltage matches the supply voltage specified on the identification plate.
Connect the circulator with mains power cable (17a) to the mains outlet (18).
Connect the control cable (9) to the sockets (9a, 9b).
Connect the refrigerated circulator with mains power cable (17b) to
HL

6.2. Switching on / Selecting the language

6.2.1. Switching on the circulator

Switching on:
Turn on the mains power switch (1a).
The unit performs a self-test.
Then the software version (example: V 1.xx-xxxx) appears. The display „OFF“ or „R OFF“ indicates the unit is ready to operate.
The circulator enters the operating mode activated before switching
the circulator off:
keypad control mode (manual operation) or remote control mode (operation via personal computer).
Selecting the language:
There are two options for the language of the LCD DIALOG-DISPLAY: German or English. Select the desired language in the menu >Configuration< under the submenu >Language/Sprache<.
Press the respective keys in the following order:
3x up to menu Configuration
6x up to submenu >Language/Sprache<
27
Operating procedures
Switching on:
The VFD COMFORT-DISPLAY indicates the message "OFF".

6.2.2. Switching on the cooling machine

Switch on the cooling machine using the switch (1b) .
Control of the cooling machine:
With the mains switch (1b) turned on, the circulator automatically switches the cooling machine off and on.
It is switched off if:
- the current working temperature is increased by > 30 °C (cooling is not required).
- the heater operates at full power (> 800 W) for longer than 5 minutes.
It is switched on if:
- cooling is necessary to maintain the bath temperature. After switch-off, the cooling machine automatically switches on only after a delay of 5 minutes to protect the cooling compressor.
To save energy, turn off the cooling machine with the mains switch
(1b) whenever cooling is not required.

6.3. Start - Stop

Start:
Press The actual bath temperature is displayed on the VFD COMFORT­DISPLAY. The circulating pump starts with a slight delay.
Stop:
Press key. or Keep
key.
key pressed.
28

7. Setting of temperatures

HL
Factory settings:
Press the
3 different working temperatures can be adjusted. Their values are freely selectable within the operating temperature range.
key to call up the menu for temperature selection.
The temperatures can be set in start or stop mode.
Setting of working temperature in the
1. Press the key
2. Select SETPOINT 1 or 2 or 3 using the key
3. Confirm by pressing the
The circulator uses the new working temperature value for
temperature control.
Example: Adjustment/modification of the pre-setting of "SETPOINT 3"
If the active Setpoint is changed, the new value is immediately used for the control of the working temperature. The heater control indicator flashes.
. The value flashes
key.
menu
or .
Setpoint3: Change the value from 70.00°C to 80.00°C. See standard display line 1
Use the numeric keypad to enter
Then press enter
Notice: Refer to SETPOINT MAX / MIN in chapter „LIMITS“
to store the value.
and .

8. Safety installations, warning functions

Check the safety installations at least twice a year! Refer to page 16.
Settings for the excess temperature protection > SafeTemp< and for the
warning functions > OverTemp< and > SubTemp< are made in a menu which is called up by pressing the key
.
Menu item > Type< allows choosing between a warning and an alarm cut-off for the menu items > OverTemp< and > SubTemp<.
29
Loading...
+ 66 hidden pages