INSTALLATION
INSTRUCTIONS
Built-In 30²²²² Electric
Combination Wall Ovens
403 WEST FOURTH STREET, NORTH
NEWTON, IA 50208
30² WALL OVEN DESCRIPTION
11-1/4² Dia. Conduit Access Hole*
25/8² Plywood Floor(MustSupport250 lbs.)
DIMENSIONS
in cm
A 30 MIN 76.20 MIN
B 24 MIN 60.96 MIN
C47+
D 24 MIN 60.96
E28-1/2+
F 47-5/8 120.97
G 29-3/4 75.57
H 24-7/16 62.07
I 4 to 20 10.2 to 50.8
* Hole must be cut as close to corner of cabinet as possible.
Z Do not block airintakeslots alongbottom ofoven.
1/16 119.38 + .16
1/16 72.39 + .16
NOTES
INSTALLATION
1. Cut hole in cabinet to mount oven. Cutout in
cabinet should be level and straight.
NOTE: There are no provisions to level the unit
after it is installed. An oven that is not level could
cause poor baking results.
2. Install plywood floor as shown above.
3. Attach unit to the cabinet with 4 No. 8² flat head
screws supplied inside of envelope containing
these instructions. Pre-drill holes in cabinet for
attachment screws using 1/8² drill. Oven
mounting holes are provided in side trim.
4. See instructions “Electrical Connections” for
electrical hook-up.
5. See figure 1 for lower trim installation.
6. See User’s Manual for operating instructions.
COMBINATION WALLOVEN CUTOUT
FIGURE 1
Remove lower screws from hinge receptacle plates. Align
lower trim and reinstall screws.
NOTE: Lower trim overlaps front edge of cabinet by 9/16².
CAUTION
For Europeanstyle cabinets(flush front) the requiredclearancefor operation ofthe ovendoor is minimum
spacing of 7/8² between the cutout and the door, hinge or drawer of the cabinet.
Some built-in cabinets may not be wide enough, due to their construction, to allow this installation.
8101P565-60
(07-03-00)
ELECTRICAL CONNECTIONS
Unit to be properly circuit protected and wired accordingto
local electrical code and National Electrical Code.
It is advisable that the electrical wiring and hookup be
accomplished by a competent electrician.
120/240 VAC or 120/208 VAC 60 Hz. See serial plate on
each unit for power requirements.
Improper installation of the grounding
circuit can result in a risk of electric
shock.
The neutral of the lower unit is grounded to the frame
through the green or solid grounding wire. (The green
and the white wires are twisted together at the
termination of the conduit.) If used on new branch-circuit
installations (1996 NEC), mobile homes, recreational
vehicles, or in an area where local codes prohibit
grounding through the neutral conductor, untwist or
disconnect the green wire and connect the green wire to
ground in accordance with local code. Connect the white
neutral to the service neutral. Connect all wires to the
branch circuit with approved connectors. Use copper or
aluminum wire. If aluminum wire is used, use connectors
recognized for joining aluminum to copper.
The chart below recommends the minimum circuit
protection and wire size if the appliance is the only unit
on the circuit.
RECOMMENDED MINIMUM
K.W.RATING CIRCUIT PROTECTION WIRE SIZE
ON SERIAL PLATE IN AMPRES (AWG)
0-4.8 20 12
4.9 - 6.9 30 10
7.0 - 9.9 40 8
10.0 - 11.9 50 8
12.0 - 14.9 60 6
Consult a qualified electrician or serviceman if the
grounding instructions are not completely understood, or
if doubt exists as whether the appliance is properly
grounded.
SERVICE
Interrupt the source of electricity to the unit when
attempting to repair or service the oven. Failure to do
this could result in a dangerous or even fatal shock.
IMPORTANT - SAVE FOR LOCAL ELECTRICAL INSPECTOR’S USE