Jenn-Air JMW9330DAS Installation Instruction

INSTALLATION
INSTRUCTIONS
Built-In 30²²²² Electric
Combination Wall Ovens
403 WEST FOURTH STREET, NORTH
NEWTON, IA 50208
30² WALL OVEN DESCRIPTION
11-1/4² Dia. Conduit Access Hole* 25/8² Plywood Floor(MustSupport250 lbs.)
DIMENSIONS
in cm
A 30 MIN 76.20 MIN B 24 MIN 60.96 MIN C47+ D 24 MIN 60.96 E28-1/2+ F 47-5/8 120.97 G 29-3/4 75.57 H 24-7/16 62.07 I 4 to 20 10.2 to 50.8
* Hole must be cut as close to corner of cabinet as possible.
Z Do not block airintakeslots alongbottom ofoven.
1/16 119.38 + .16
1/16 72.39 + .16
NOTES
INSTALLATION
1. Cut hole in cabinet to mount oven. Cutout in cabinet should be level and straight.
NOTE: There are no provisions to level the unit after it is installed. An oven that is not level could cause poor baking results.
3. Attach unit to the cabinet with 4 No. 8² flat head screws supplied inside of envelope containing these instructions. Pre-drill holes in cabinet for attachment screws using 1/8² drill. Oven mounting holes are provided in side trim.
4. See instructions “Electrical Connections” for electrical hook-up.
5. See figure 1 for lower trim installation.
6. See User’s Manual for operating instructions.
COMBINATION WALLOVEN CUTOUT
FIGURE 1
Remove lower screws from hinge receptacle plates. Align lower trim and reinstall screws.
NOTE: Lower trim overlaps front edge of cabinet by 9/16².
CAUTION
For Europeanstyle cabinets(flush front) the requiredclearancefor operation ofthe ovendoor is minimum spacing of 7/8² between the cutout and the door, hinge or drawer of the cabinet.
Some built-in cabinets may not be wide enough, due to their construction, to allow this installation.
8101P565-60
(07-03-00)
ELECTRICAL CONNECTIONS
Unit to be properly circuit protected and wired accordingto local electrical code and National Electrical Code.
It is advisable that the electrical wiring and hookup be accomplished by a competent electrician.
120/240 VAC or 120/208 VAC 60 Hz. See serial plate on each unit for power requirements.
Improper installation of the grounding circuit can result in a risk of electric shock.
The neutral of the lower unit is grounded to the frame through the green or solid grounding wire. (The green and the white wires are twisted together at the termination of the conduit.) If used on new branch-circuit installations (1996 NEC), mobile homes, recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor, untwist or disconnect the green wire and connect the green wire to ground in accordance with local code. Connect the white neutral to the service neutral. Connect all wires to the branch circuit with approved connectors. Use copper or aluminum wire. If aluminum wire is used, use connectors recognized for joining aluminum to copper.
The chart below recommends the minimum circuit protection and wire size if the appliance is the only unit on the circuit.
RECOMMENDED MINIMUM
K.W.RATING CIRCUIT PROTECTION WIRE SIZE
ON SERIAL PLATE IN AMPRES (AWG)
0-4.8 20 12
4.9 - 6.9 30 10
7.0 - 9.9 40 8
10.0 - 11.9 50 8
12.0 - 14.9 60 6
Consult a qualified electrician or serviceman if the grounding instructions are not completely understood, or if doubt exists as whether the appliance is properly grounded.
SERVICE
Interrupt the source of electricity to the unit when attempting to repair or service the oven. Failure to do this could result in a dangerous or even fatal shock.
IMPORTANT - SAVE FOR LOCAL ELECTRICAL INSPECTOR’S USE
Loading...
+ 4 hidden pages