I.R.I.S. P522 User Manual

FLAME MONITORING SYSTEM
MODEL P522 SIGNAL PROCESSOR
APPLICATION MANUAL
IRIS MODEL P522 APPLICATION MANUAL
Table of Contents
IRIS MODEL P522 ---------------------------------------4 WIRING AND INSTALLATION------------------------4 FIGURE 1 - P522 REAR MOTHERBOARD-------4 WIRING TO THE PLUG-IN TERMINALS ----------5 WIRING OF VIEWING HEAD-------------------------6 FIGURE 2 - WIRING OF VIEWING HEAD --------6 FIGURE 3 - WIRING AND ASSEMBLY -
VIEWING HEAD -------------------------------------- 7 OPTIONAL LTA ADAPTER----------------------------7 POWER SUPPLY ----------------------------------------8 FIGURE 4 - POWER SUPPLY TABLE -------------9 FACTORY STOCKED POWER SUPPLIES------- 9 REDUNDANT POWER SUPPLIES------------------ 9 SELF-CHECKING FUNCTION --------------------- 10 APPROVALS -------------------------------------------- 10 POWERING UP THE P522-------------------------- 10 SET POINTS -------------------------------------------- 11 FIGURE 5 - SET POINTS---------------------------- 11 CHANGING SET POINTS --------------------------- 11 FLAME FAILURE RESPONSE TIME (F.F.R.T.) 12 4-20mA REMOTE OUTPUT------------------------- 12 FIGURE 6 - REMOTE METER ANALOG OUTPUT 12 INSTALLATION OF VIEWING HEAD------------- 13 FIGURE 7 - VEWING HEAD CROSS-
REFERENCE TABLE--------------------------- 13 SIGHTING OF THE VIEWING HEAD------------- 13 MULTIBURNER REQUIREMENTS --------------- 14 FIGURE 8 - CUTOFF FREQUENCIES----------- 14 MULTIPLE VIEWING HEADS ---------------------- 14 DETERMINING SIGHT PIPE SIZE---------------- 15 SELECTING THE PIPE------------------------------- 15 MOUNTING HOLE------------------------------------- 15 MOUNTING OF SIGHT PIPE ----------------------- 15 INSTALLING THE VIEWING HEAD--------------- 15 PURGE AIR---------------------------------------------- 15 SETUP AND ADJUSTMENT PROCEDURES -- 16 SIGHTING ADJUSTMENT--------------------------- 16 INITIAL SETUP ----------------------------------------- 16 ADJUSTING SET POINTS -------------------------- 17 TROUBLESHOOTING GUIDE --------------------- 18 NOISE INTERFERENCE AND GROUNDING-- 18
S506 VIEWING HEAD -------------------------------- 19 S506 SELF-CHECKING VIEWING HEAD------- 20 S509 VIEWING HEAD -------------------------------- 20 S511 VIEWING HEAD -------------------------------- 21 S512 VIEWING HEAD -------------------------------- 21 ORIFICING----------------------------------------------- 23 FIGURE 9 - ORIFICING: SIGNAL-REDUCING
CHARACTERISTICS OF DISCS ---------------- 23 SIGNAL SOURCES ----------------------------------- 23 VIEWING HEAD - ANGLE OF VIEW------------- 24 FIGURE 10 - VIEWING HEAD: ANGLE OF VIEW
- DISTANCE AND DIAMETER ------------------- 25 APPLICATION OF IRIS VIEWING HEADS ----- 25 LOW NOx APPLICATIONS-------------------------- 26 APPLICATION OF P522 ----------------------------- 26 USING A PLC WITH IRIS FLAME MONITOR-- 26 FIGURE 11 - VIEWING HEAD APPLICATION
TABLES ------------------------------------------------ 27
FIGURE 11 - VIEWING HEAD APPLICATION
TABLES Cont’d--------------------------------------- 28 BASIC BURNER START CIRCUIT ---------------- 29 FIGURE 12 - BASIC BURNER START CIRCUIT 30 MODULE COMMUNICATIONS -------------------- 31 MODBUS COMMUNICATION ---------------------- 31 COMMUNICATING WITH MODICON PLC ----- 32 COMMUNICATION WITH HUMAN-INTERFACE
HOST COMPUTER --------------------------------- 32 RS-232 to RS-422 CONVERSION----------------- 32 SETTING ADDRESSES------------------------------ 32 TECHNICAL HELP------------------------------------- 33 FIGURE 13 - SPECIFICATIONS------------------- 34 FIGURE 14 - MODEL P522 FRONT PANEL --- 35 FIGURE 15 - MODEL P522 SIDE VIEW --------- 36 FIGURE 16 - S5XX VIEWING HEAD DIMENSIONS ------------------------------------------- 36 FIGURE 17 - IR VIEWING HEAD LOCATION-- 37 FIGURE 18 - UV VIEWING HEAD LOCATION 37 FIGURE 19 - OPPOSED FIRED VIEWING HEAD SIGHTING -------------------------------------- 38 FIGURE 20 - VIEWING HEAD MOUNTING ---- 38 INDEX ----------------------------------------------------- 39
Page 2
IRIS MODEL P522 APPLICATION MANUAL
Figure Index
FIGURE 1 - P522 REAR MOTHERBOARD--------------------------------------------------------------------4 FIGURE 2 - WIRING OF VIEWING HEAD ---------------------------------------------------------------------6 FIGURE 3 - WIRING AND ASSEMBLY - VIEWING HEAD ------------------------------------------------7 FIGURE 4 - POWER SUPPLY TABLE --------------------------------------------------------------------------9 FIGURE 5 - SET POINTS----------------------------------------------------------------------------------------- 11 FIGURE 6 - REMOTE METER ANALOG OUTPUT-------------------------------------------------------- 12 FIGURE 7 - VEWING HEAD CROSS-REFERENCE TABLE-------------------------------------------- 13 FIGURE 8 - CUTOFF FREQUENCIES------------------------------------------------------------------------ 14 FIGURE 9 - ORIFICING: SIGNAL-REDUCING CHARACTERISTICS OF DISCS ----------------- 23 FIGURE 10 - VIEWING HEAD: ANGLE OF VIEW - DISTANCE AND DIAMETER---------------- 25 FIGURE 11 - VIEWING HEAD APPLICATION TABLES-------------------------------------------------- 27 FIGURE 11 - VIEWING HEAD APPLICATION TABLES Cont’d ---------------------------------------- 28 FIGURE 12 - BASIC BURNER START CIRCUIT----------------------------------------------------------- 30 FIGURE 13 - SPECIFICATIONS-------------------------------------------------------------------------------- 34 FIGURE 14 - MODEL P522 FRONT PANEL ---------------------------------------------------------------- 35 FIGURE 15 - MODEL P522 SIDE VIEW ---------------------------------------------------------------------- 36 FIGURE 16 - S5XX VIEWING HEAD DIMENSIONS ------------------------------------------------------ 36 FIGURE 17 - IR VIEWING HEAD LOCATION--------------------------------------------------------------- 37 FIGURE 18 - UV VIEWING HEAD LOCATION ------------------------------------------------------------- 37 FIGURE 19 - OPPOSED FIRED VIEWING HEAD SIGHTING------------------------------------------ 38 FIGURE 20 - VIEWING HEAD MOUNTING ----------------------------------------------------------------- 38
Page 3
IRIS MODEL P522 APPLICATION MANUAL
IRIS MODEL P522
The P520 and P522 Signal Processors are used with the IRIS Model 500 Viewing Heads. The P522 Signal Processor is a relay panel mount ver­sion of the P520 plug-in module, and replaces the M502 motherboard and its two plug-in daughter boards, the A513 and the D504.
GND +26V BAT
SC C
F1 .75 A
WIRING AND INSTALLATION
Before wiring or installing the P522, we recommend that you read the companion colour brochure describ­ing the functions and attributes of this series of sig­nal processors.
SC OFF
SC ON
RF C
RF OFF
SC RELAY
RF ON
RF ON
RF
RELAY
RF C
RF OFF
RS-422
+TX
-TX
+RX
0-20mA or
4-20mA
ANALOG
CURRENT
DRIVE
-RX
GND
RMT
METER
+26V
SIG
GND SIG
VH SEL
RELAY
CHAN
SELECT
++--+
CHAN
SEL
V.H. SEL
SIG
SHUTTER
DRIVE
+V
SC
SIG
GND
V.H.A. V.H.B.
GND
SIG
GND
F2
.25A
SIG
SC
+V
GND
Page 4
FIGURE 1 - P522 REAR MOTHERBOARD
IRIS MODEL P522 APPLICATION MANUAL
WIRING TO THE PLUG-IN TERMINALS
Figure 1 illustrates the plug-in terminals on the rear mother board and how they are connected internally. The flame relay and self-checking relay contacts are situated together in the upper right portion of the diagram.
RF C refers to the common terminal of the flame relay, with ON being flame on, and OFF being flame off. You will note that there are two sets of contacts used for the flame relay.
SC C refers to the common terminal of the self-check- ing relay. There is only one pair of contacts used
for the self-checking function. Here, the designa­tion ON refers to the self-checking taking place in a normal manner. OFF indicates a failure in the view­ing head or processor resulting from:
- the hardware (i.e. the shutter mechanism in the viewing head, or the output relay itself);
- electronic components anywhere, or internal software in the P522; or
- the power to the unit is OFF – the most likely condition.
The main power feeds in through the terminals situ­ated on the upper left side (see GND, +26V and BAT). Each designated terminal is a double terminal, or pair, so that the wiring from the power supply can be “daisy chained” from one P522 to the next without having to twist wires together into one termination.
The pair designated BAT is for battery backup, if used. Note the rectifier used internally to prevent the 26 VDC main power supply from feeding into the battery. The backup battery, if used, should be 24 volts, to ensure that the 26 VDC power feeding the P522 will not feed back into the battery. In other words, no current will flow from the battery as long as voltage of the main power supply is above that of the battery. The negative side of the battery goes to the GND terminal on the left.
and is rated at .25 Amp. On newer units (those with NO, CAL, and YES in red letters on the front panel) these fuses are self-resetting types, and will recover from an overload automatically after power is re­moved from the P522 for 10 seconds.
The viewing head terminals (bottom right) are iden- tified as V.H. A. and V.H. B. If only one viewing head is used, you must wire to the V.H. A. termi­nals. To the left of the viewing head terminals are two terminals marked V.H. SEL (viewing head se- lector relay). Energizing this connection with 19 to 38 VDC will cause the relay on this PC board to switch to viewing head B. The nominal voltage of this relay is 24V, but the 26 VDC power circuit can be used to switch this relay, if desired.
Only the viewing head signal wire (SIG) and the sig- nal ground wire (SIG GND) are switched with this changeover relay; the 26 VDC and power ground circuit is not disturbed. Make sure that the viewing head signal wire and signal ground (braided shield in the four-conductor cable) are both connected, be­cause this ground connection is the only return path for the signal and self-checking circuit. Also, the 26 VDC used to switch this relay must be connected with the proper polarity, because the relay used is a single-side stable type. (Relays that are polarized magnetically offer increased contact force resulting in higher current-carrying capability). The two ter­minals marked V.H. SEL go directly to the relay coil.
The pair of terminals designated CHAN SEL (to the left of the V.H. SEL terminals) is used for selecting channel A or channel B on the P522. Energizing this pair of terminals causes the B channel to be se­lected. Polarity must be observed when wiring this connection (the positive terminal is on the right). This is an isolated input, so two wires are required. Any DC voltage from 7.5 to 30 may be used. The current required will depend upon the voltage, be­cause this is a photocoupler interface circuit with a 3900 ohm resistor feeding the LED light source.
Figure 1 shows how these terminals are connected inside the P522. Note the two fuses marked F1 and F2. F1 is the main power fuse for the signal proces­sor as well as the viewing head(s), and is rated at .75 Amp. Fuse F2 feeds only to the viewing head(s),
For example: a 26 VDC voltage will result in a current flow of 25/3900 = .0064 Amp.
If flame is being detected and the channels are switched, the flame relay will remain energized for
Page 5
IRIS MODEL P522 APPLICATION MANUAL
one cycle regardless of the new set points, allowing channel changes “on the fly,” so to speak. If the new flame OFF set point is equal to or greater than the current signal count, then the flame relay will de-energize on the subsequent cycle.
The pair of terminals designated RMT METER (to the left of the CHAN SEL terminals) is for the remote meter connection. This output is a current-driven sig­nal that ranges from 0 to 20 mA for remote meters, and can be switched to a range of 4 to 20 mA for DCS (distributed control system) applications (refer to sec- tion 4-20mA REMOTE OUTPUT). Connect the terminal marked “positive” to the positive meter ter­minal. This current signal can be used with a volt meter by feeding the signal to a resistor connected to the ground. The voltage developed across the resis­tor will follow Ohm’s law V = IR.
For example: a 3-volt meter can be used with a resistor of 3/.02 = 150 ohms, which will result in a full-scale reading of 3 volts for a 20mA output.
The four terminals called +TX, -TX, +RX, and -RX (to the left of RMT METER terminals) are used for the serial communication link. The serial commu­nication is achieved by using ASCII character code transmission at 4800 or 9600 baud through the RS­232 com ports on the host computer. The P522 uses RS-422 data transmission which is over two, twisted pairs that are differentially transmitted and received, allowing long wire runs to be used through noisy environments. An RS-232 to RS-422 converter must
be used to communicate with the P522, and the con­nections are made to the terminals marked +TX, ­TX, +RX and -RX. The transmitting, twisted pair goes to the TX terminals, and the receiving, twisted pair goes to the RX terminals.
Note: the terms “transmit” and “receive” used here with respect to the P522 will be reversed with re­spect to the RS-232 connection on the host computer. Refer to later sections in this manual for a detailed description of the software and how it is to be used with the P522.
WIRING OF VIEWING HEAD
Wiring of the viewing head is made to the terminals on the lower right side of the P522. These terminals are described as follows:
TERM DESCRIPTION
+V 24 VDC power to viewing head GND Power Ground SC Self-check/shutter drive signal to
viewing head SIG Flame signal from viewing head SIG GND Signal ground
Figure 2 shows a four-conductor cable to the view­ing head. Note that the flame signal wire going to terminal SIG is shielded, and the shield is terminated at both ends of the cable SIG GND.
WIRING SIDE VIEW - COVER REMOVED
CONNECT SHIELD
TO TER M 3
USE SHRINK TUBING
Page 6
WHITE
SHIELD
FIGURE 2 - WIRING OF VIEWING HEAD
RED
GREEN
BLACK
+V
GND
SC
SIG
GND
SIG
P522
+24VDC
GND
SHUTTER DRIVE
GND
SIGNAL
CABLE ENTRY NUT
CABLE
IRIS MODEL P522 APPLICATION MANUAL
IRIS CABLE 3 CONDUCTORS PLUS 1 COAX 3CONDUCTORS: 16 AW G 19 STRAND INSULATED WITH
CROSSED-LINKED-POLYETHYLENE .017 THK COLORS: BLACK-RED-GREEN
1 COAX: 16 AW G 19 STRAND INSULATED WITH
CROSSED-LINKED-POLYETHYLENE .017 THK
COLOR WH ITE
36 AW G B RAIDED SHIELD 90% COVERAGE WITH .012 THK JACKET COLOR BLACK
CABLED: POLYPROPYLENE FILLERS FOR ROUNDNESS
JACKET: CROSSE D-LINKED-POLYETHYLENE
GROMMET
FLAT WASHE R
CABLE
PREPA RATION
STRIP 3/8“ TYPICAL
(TYP)
1 3/4“
SHIELD *
CABLE CLAMP
FINAL ASSEMBLY
Optional LTA Adapter
INSULATE SHIELD WITH SHRINK TUBING LEAVING 3/8“ STICKING OUT
CONNECTOR WITH
REAR COVER REMOVED
CONNECTOR JACKSCREW
* CABLE IS SHOWN WITH SHIELD
ALREADY REMOVED FROM W HITE WIRE
FIGURE 3 - WIRING AND ASSEMBLY - VIEWING HEAD
Page 7
IRIS MODEL P522 APPLICATION MANUAL
A source impedance resistor is required when using the P522 module with a S550 viewing head. This resistor should be 330 ohm (factory installed) for viewing head cable runs up to 500 feet, and it should be 150 ohm for cable runs 500 feet to 1000 feet. The resistor should be installed across the SC and SIG GND terminals. A 1/4 watt resistor is suitable.
Originally, specifications of the IRIS Model 500 in­structed that a five-conductor cable be used, with one wire shielded. However, the standard is now a four-conductor cable, with one wire shielded. In this case, the shield is used as the signal ground wire that goes to terminal SIG GND on the P522 and to pin 3 on the viewing head plug. The shield should be a braided type for this application –do not use a foil type shield– so that a solid signal ground is main­tained. This signal ground shield is also the self­checking circuit return path. Refer to Figures 2 and 3 for wiring details.
Connections of the IRIS cable to the viewing head plug should be performed as follows:
5. Slide nut (with threads toward the cable end), the washer and the grommet onto the cable approximately six inches.
6. Slip the cable through the bottom open­ing of the connector, making sure that the cable’s outer jacket is secure under the cable clamp, and tighten the two screws on the cable clamp.
7. Reassemble the grommet, flat washer and cable entry nut, and tighten.
8. Before wiring to connector, strip each wire 3/8 inch, as shown in assembly dia­gram, Figure 3.
9. Proceed to wire the connector. Refer to Figure 2 for terminal locations.
Connect the viewing head signal wire
WHT (the shielded wire) to terminal No. 1 by inserting it into the opening, then tightening the retaining screw.
After removing the plug from its packaging, take the cable entry nut out of its housing. Remove rubber grommet and flat sealing washer. With a pair of long­nosed pliers, remove the center ring only of the rub­ber grommet.
1. Strip two inches of the cable’s outer cover from the cable, removing any cellophane wrap or filler material, and strip the in­sulation from the shielded wire (if insu­lated over shield) a full two inches, to expose shield.
2. Slide the shield back until a bulge devel­ops close to where the wire exits the cable’s outer covering.
3. Carefully spread a few strands of the shield at the bulge –making sure not to break any strands– to create an opening, and slip wire out of shield through opening.
4. Carefully return shield to original shape and length by pulling gently, then cover with plastic shrink tubing to prevent shorts.
Connect the shutter drive signal wire
BLK to terminal No. 2.
Connect the signal ground shield from
the WHT wire to terminal No. 3 with shrink tubing.
Connect the 24 VDC power wire RED
to terminal No. 4.
Connect the power ground wire GRN
to terminal No. 5.
Assemble the back of the plug and insert
jackscrew through the plug assembly.
The cable wiring at the other end going to the signal processor is easier. The cable should be prepared in a similar way to the plug end – particularly the shield from the WHT wire. Make sure the shield doesn’t touch the other terminals.
POWER SUPPLY
Careful consideration should be given to the power supply used for the P522. 26 VDC is used to back bias the “steering” rectifier, as shown in Figure 1, to
Page 8
IRIS MODEL P522 APPLICATION MANUAL
prevent the power from feeding into the 24 VDC supply. Each P522 module draws approximately 150 mA, and each viewing head draws about 100 mA of power (26 VDC). Actually, the S506 and S511 view­ing heads use less current, but it is a good idea to figure 100 mA for each viewing head used. Also, the amount of current drawn by the P522 will de­pend upon other factors that can affect the peak cur­rent, such as whether or not there is flame being de­tected, the remote meter output is connected, and se­rial communication is occurring.
The viewing head is powered through the P522 via a
0.25 A self-resetting fuse. In other words, the 26 VDC power feeds into the P522 (through a 0.75 A self-resetting fuse) and feeds back out through a 250 mA fuse to the viewing head, resulting in a current drain of about 0.25 A for each P522 (with one view­ing head). This small amount of current means that one power supply could support a number of P522 modules. The self-resetting fuses change to high re­sistance when their current ratings are exceeded, but recover to their normal low resistance when power is removed.
with one viewing head each. And the 100-watt power supply will support up to fifteen P522 modules with one viewing head per each 100 watt. These “switch­ing type” power supplies are efficient and very com­pact. To obtain the size and weight of the power supplies, contact IRIS Systems Inc.
Each power supply can be either rail mounted or panel mounted, and it is up to each end user to deter­mine their installation preferences and requirements.
We recommend that not more than four P522 signal pro­cessors be supported by one 26 VDC power supply. For instance, four P522 processors with one viewing head each equals a total of 26 watts – a relatively small power supply, particularly if an efficient, switching type is used.
Other possible combinations can be used; for in­stance, the battery backup terminal could be used for redundancy. However, care must be taken with these redundant schemes to make sure that failure of the primary power supply won’t affect the backup power supply, as well.
REDUNDANT POWER SUPPLIES
STTAWNIYTICAPACYLPPUSREWOP225PLEDOMSIRI
YTQW5.7W51W03W05W001
1 2
3 4 5 6 7 8 9
01
XXXX
XXX XXX
XX
X X X X X X
FIGURE 4 - POWER SUPPLY TABLE
FACTORY STOCKED POWER SUPPLIES
Power supplies are readily available from the fac­tory for the P522 modules. The 30-watt power sup­ply will support up to six or seven P522 modules with one viewing head each. The 50-watt power supply will power up to six or seven P522 modules
It may be more economical to use larger-capacity power supplies for applications using 12 or more P522 signal processors.
For example: the 100-watt power supply available from the factory can handle twelve P522 modules, each with one view­ing head. Should the power supply fail, a redundant scheme utilizing two power supplies with “steering” rectifiers to pre­vent current from flowing into a failed power supply output would prevent the 12 flame monitors from being de-energized.
The positive output from each power supply is wired to the anodes of the MBR 1545CT. This dual, Schottky-type rectifier, rated for 15 Amps, will present a low forward voltage drop for this application. Both power supplies can be adjusted for 26V output, and a low-voltage indicator light can be used on the output of each power supply to monitor their outputs.
Larger power supplies can be used with this redun­dant wiring scheme if there are more than twelve P522
Page 9
IRIS MODEL P522 APPLICATION MANUAL
modules in a system. Care should be taken when wir­ing multiple P522s to ensure the selected bus wires will carry the current. The plug-in terminals on the P522 will accommodate a wire size up to 14AWG, allowing for relatively high currents. Note that, if the power wiring (26 VDC) is “daisy chained” by using the terminal pairs provided, the pairs are “jumpered” by copper traces on the mother board; so, if the plug is pulled out, the jumpered connection is broken.
SELF-CHECKING FUNCTION
When energized, the self checking function indicates that both the P522 and the viewing head are func­tioning properly. The software in the P522 activates the self-checking relay only if there are less than 10 pulses coming in from the viewing head during each dark period. To energize this relay, the software must generate pulses –at a particular rate and with a spe­cific duty cycle– to a self-checking circuit. If this regular pattern is not maintained, or if any of the circuitry fails, the relay will drop out. The blinking LED on the front panel labelled SELF-CHECK O.K. is evidence that voltage is applied to the coil of this self-checking relay, because both are energized by the same voltage. The difference is that the voltage to the coil is applied steadily, while the voltage from the relay to the LED is gated on and off by the soft­ware in conjunction with the pulses counted during the dark period.
Note that, with regard to the viewing head, the self checking function still works the same way as with the M502, A513 and D504 signal processors. For instance, a runaway UV tube will cause a “lockout condition” (more than 10 pulses counted during the dark period). (Refer to section EXPLANATION
OF 1-9, > 10 PULSES COUNTED DURING THE DARK PERIOD, in the Model 500 Signal Proces-
sor Application Manual.) A runaway UV tube or any component failure, in-
cluding the shutter, will cause a lockout condition that will de-energize the flame relay. The LOCKOUT light on the P522 will indicate this condition, requiring a reset to return to normal flame monitoring mode. A reset can be achieved only if the lockout condition
has been corrected, and can be performed from the front panel (by pressing the RESET button), or re­motely through the serial communication.
APPROVALS
The P522 and viewing heads have Factory Mutual (FM) Approval for Combustion Safety; Canadian Standards Association (CSA) Certification, and National Recog­nized Testing Laboratories (NRTL) Listing.
POWERING UP THE P522
Once the power is connected (26 VDC) to the plug-in connector, the P522 will be operational. There is no ON/OFF switch on the P522; the moment it is pow­ered on, it will reset and start up. The self-checking light will start blinking, and one of the channel LEDs (A or B) will light (A will be ON if the channel select input at the plug-in connector is de-energized). Make sure the voltage is 24 to 26 VDC. The P522 will be reset when the power is turned on; however, the power must be a step function (i.e., the power must be ap­plied abruptly) for this reset to work properly.
The P522 has been designed to deal with any fore­seeable power failure or anomaly.
For example: if the power goes off while you are in the process of storing a set point (either from the front panel or from the remote, host computer), the internal power monitor circuit will signal the P522 processor to complete the store function before shutting down in an or­derly manner. This prevents bogus num­bers from being stored and protects ex­isting data in the EEPROM (Electrically Erasable Programmable Read Only Memory) from corruption, and is facili­tated by a special internal power supply that holds a charge (like a battery) just long enough to allow the processor to do its job before going dead.
This internal circuit monitors the 26 VDC power feeding the P522, and when the voltage drops to about 19 volts, the processor shuts down, the pro­gram stops running, and the self-checking function ceases (the self-checking relay de-energizes). The
Page 10
IRIS MODEL P522 APPLICATION MANUAL
blinking, SELF-CHECK O.K. light on the front panel will go out, and the flame relay will de-energize. Please note that the S509 and S512 viewing heads will shut down at about 17.0 volts; these heads have their own power-monitoring capability, and will shut down on their own, independent of the signal processor.
When the power feeding the P522 exceeds 19 volts, the processor starts the program again. The SELF­CHECK O.K. light will start blinking, and the self­check relay will energize. If flame is present and a S509 or S512 viewing head is being used, the flame signal will not come back on until the power reaches
21.5 volts. This can cause a lockout condition if the viewing head turns on during the dark period (defined by the periodic self-check signal going to the viewing head each second), requiring a manual reset of the P522. There is a 20 per cent probability that a lock­out will occur because of the duty cycle of the self­check function (200 mSEC on and 800 mSEC off). The other viewing heads (the S506, S511) do not in­corporate the power-monitoring shutdown function, and will not cause a lockout condition.
To see what the current set points are, simply push the desired button. For instance, to determine the current FLAME ON set point, press the FLAME ON button. The set point will be displayed on the readout for about four seconds, then return to normal. The set points displayed will be for the channel that is active, which is indicated by a steady illumination of push-button A or B.
To see the other channel set points, first select the chan­nel (A or B), then press the desired set point button.
For example: if channel A is already ON, indicating it is functional, and B is pressed, A will go out and B will pro­ceed to blink slowly, indicating that fur­ther action is required. If A is already ON and A is pressed, it will stay steady ON and start to blink rapidly after a set point button is pressed.
In all cases, A or B will rapidly blink after the set point is selected. This action alerts the user that the current display is no longer that of the flame signal, and further action is required.
These design precautions ensure that there will never be an unsafe situation created by abnormal line power (115 VAC) conditions. The 26 VDC power is very unlikely to come on gradually, but, if this did occur, the P522 would not get a proper reset. So, there is another function in the 87C52 processor (used in the P522), implemented by circuitry and software, that causes the P522 to appear dead (i.e., the front panel will be dark) and to stay this way until the power is recycled in an abrupt manner, initiating the reset.
SET POINTS
There are 10 set points stored in memory in the P522, divided into two equal sets, A and B.
SET POINT DISPLAY NUMBER
FLAME ON 4 DIGIT NUMBER 0001-2999
FLAME OFF 4 DIGIT NUMBER 0000-2999
GAIN S ET 2 DIGIT NUMBER 00 - 99
F.F.R.T. 1 DIGIT NUMBER 1, 2 OR 3
TIME DELAY ON 1 DIGIT NUMBER 0, 1, 2 or 3
The fact that A or B is already on has nothing to do with the process of viewing the current set points, except that you do not have to select the channel if it is already on. The steady illumination of A or B indi­cates which channel is functionally active, and is se­lected at the plug-in terminals marked CHAN SEL.
At any time, you can press the reset button causing the P522 to go back to its normal operating condi­tion. The reset button is also used for resetting the lockout condition as explained in the section SELF- CHECKING FUNCTION.
CHANGING SET POINTS
Changing any of the five set points is easy. Simply bring up the desired set point and change it using the UP or DOWN arrow buttons. When the desired num­ber is displayed, press the STORE button. When the set point is stored, four dashes are displayed momentarily, indicating that the selected number was stored into the EEPROM. Illogical settings cannot be made; so, if four “E’s” are displayed when push­ing STORE P.B., then an error was made when se-
FIGURE 5 - SET POINTS
Page 11
IRIS MODEL P522 APPLICATION MANUAL
lecting the set points. For instance, selecting a flame out set point that is equal to or greater than the flame on set point will result in this error indication.
As well, the set points can be selected remotely through the serial communication port using a host computer – explained in greater detail later in this manual.
FLAME FAILURE RESPONSE TIME (F.F.R.T.)
The flame failure response time, or F.F.R.T., is de­fined as the time it takes for the flame relay to de­energize after the flame signal (from the viewing head) drops out. This time delay is programmable from both the front panel of the P522 and a remote, host computer. Only three settings are possible: one, two and three seconds.
The maximum time delay is limited to three seconds in compliance with the FM (Factory Mutual) limit of the F.F.R.T. to not more than four seconds.
The P522 decision-making process occurs on a pe­riodic basis, and the decision to start a F.F.R.T. time delay before de-energizing the flame relay is initi­ated every second in step with the sampling rate of the flame signal. This means that the actual flame out condition (i.e., drop-out of the flame signal from the viewing head) will, in all probability, occur dur­ing the sampling period that causes the actual F.F.R.T. to be greater than the set time.
For example: suppose the signal from the viewing head drops out immedi- ately after a sampling from the P522, and the sampling perceives flame to be present. If the F.F.R.T. set point is set for three seconds, there will be an actual time delay of nearly four sec­onds. In other words, the actual F.F.R.T. will be the current set-point time, plus an additional amount of time not exceeding one second, de­pending upon when the flame signal from the viewing head drops out.
4-20mA REMOTE OUTPUT
The standard remote meter output has a 0-20mA range and is designed to drive remote meters, as ex­plained earlier in this manual. You can convert this output to a 4-20mA range, as follows:
Press the front panel push-buttons (indicated in the table below) while holding down both the and buttons. Press all in each row together (i.e., three in the first row, two in the second row, and three in the last row).
EMALF
NO
XXX
XXX
FIGURE 6 - REMOTE METER ANALOG
Doing this toggles the function back and forth be­tween the 0-20mA and 4-20mA ranges.
The change will be verified by four dashes “----” and “4-20” momentarily displayed. If the module is programmed for the 4-20mA range, “4-20” will be displayed; toggling back to the 0-20mA range will again cause four dashes to appear on power-up of the unit. Tha factory default setting are 4-20.
One thing to consider when feeding the 4-20mA sig­nal to a remote computer or DCS, is that there is no isolation between the P522 ground and the remote system ground. If there is a ground potential differ­ence between the two systems, then there could be serious noise and performance problems. You will not encounter this problem when using a remote meter by itself, because it will not be tied into an­other electrical system (will not be sharing grounds).
The bargraph reading on the front panel will not be affected by this change to 4-20mA output. It will re­main the same as before (i.e., go to zero on no signal
EMALF
FFO
OUTPUT
TESNIAGTRFF
XX
NO
LEDEMIT
Page 12
IRIS MODEL P522 APPLICATION MANUAL
detected). The 4-20mA output will still perform the same way on the high end (i.e., on a strong signal, it will saturate at the same level, slightly above 22mA).
Specifications for the analog current output signal are provided in SPECIFICATIONS Figure 13.
INSTALLATION OF VIEWING HEAD
Before beginning the actual installation, determine the best location for mounting the viewing head based upon the following factors:
VIEWING HEAD CROSS-REFERENCE
REBMUNDLOREBMUNWEN
605S605S
S2XRI905S
SGRI115S
SRI215S
The model S5xx series of viewing heads have in place a sensor for sensing the internal temperature of the head. To access the reading of the viewing head temperature, press the “Reset” and the “Down” arrow key at the same time. The temperature read­ing will be displayed in the four-digit readout. The reading (indicated in °C) will disappear and the nor­mal reading will continue after several seconds.
VIBRATION
Do not install the viewing head where it could be subject to vibration. A vibrating viewing head (flicker type) can simulate flame when viewing a glowing background. Provide an antivibration mount if excessive vibrations are present.
CLEARANCE
Make sure there will be sufficient room to remove the housing for servicing (see Figure 16).
SIGHTING OF THE VIEWING HEAD
FIGURE 7 - VEWING HEAD CROSS-
REFERENCE TABLE
PRESSURE
The viewing head lens will withstand 5 psi. If the lens assembly is exposed to greater than 5 psi through sight pipe, then an isolation unit must be used. An IRIS isolation unit with purge air entrance is avail­able as an accessory.
TEMPERATURE
The viewing head will withstand an ambient tem­perature to 80°C (176°F). However, the case tem-
perature of the housing must not exceed 60°C (140°F). Purge air will help reduce conducted heat
through sight pipe to flange (a plastic nipple will also help), but direct radiation can cause housing case temperature to exceed limits. If the ambient heat (direct radiation) is excessive, then a fiber optic ex­tension should be used (please refer to the IRIS Model 500 Fiber Optic System manual). This sys­tem is composed of a viewing head, a fiber optic assembly, and an amplifier module.
In general, the sighting of the viewing head should be parallel to the center line of the burner in the di­rection of the burner flame. This applies to both the UV type as well as the flicker type. Flicker type detectors respond to the high frequency flicker of the flame; so, in order to achieve maximum dis­crimination between burners, the near portion of the primary combustion zone should be favoured – meaning the sight pipe should be mounted as close as possible to the burner center line. The sight pipe should be aimed at the root of the flame, which radi­ates the most intense, high-frequency flicker energy. Sighting along the flame rather than across it per­mits the detector to view a greater depth of the flame root, obtaining better response (see Figure 17).
When sighting for a UV viewing head, you must aim for the UV zone, which is usually at the very first part of the flame root. UV radiation from most flames is restricted to a narrow region: it starts very close to the burner nozzle and does not extend out very far from the burner nozzle. You may have to angle the sighting inward toward the flame root, as shown in Figure 18.
Page 13
Loading...
+ 29 hidden pages