ION F-20 Series User Manual

I
CONTENTS
1-1. UPS Block Diagram ................................................................................................................................................................ 3
1-2. UPS Outlook View .................................................................................................................................................................. 4
2-1. Storage and Installation Environment ................................................................................................................................... 13
2-2. Unpacking, Removing and Fixing UPS ................................................................................................................................. 14
2-3. General Requirement for Ventilation and Maintenance ......................................................................................................... 21
2-4. Power Cables Connections ................................................................................................................................ .................. 22
2-5. Communication Cables Connections .................................................................................................................................... 30
2-6. UPS Parallel Connections ................................................................................................................................ .................... 34
3-1. Operation Modes .................................................................................................................................................................. 39
3-2. Online Operations ................................................................................................................................................................ 40
3-3. Manual Bypass Operation ................................................................................................................................ .................... 40
3-4. Operation Processes ............................................................................................................................................................ 41
4-1. Screen Introduction .............................................................................................................................................................. 42
4-2. Menu .................................................................................................................................................................................... 43
4-3. Mimic Display ....................................................................................................................................................................... 46
5-1. Dry Contact Card .................................................................................................................................................................. 47
5-2. RS-485 MODBUS Card ........................................................................................................................................................ 47
5-3. SNMP Card .......................................................................................................................................................................... 47
5-4. Temperature Sensor............................................................................................................................................................. 48
5-5. DC Cold Start Kit .................................................................................................................................................................. 48
5-6. Parallel Communication Cable.............................................................................................................................................. 48
1
Preface
Thank you for purchasing the ION F20 series 3 Phase UPS solution. Our equipment complies with the European Community directives for professional equipment and is
authorized to use the CE marking.
The purpose of this manual is to introduce the operating principles of the UPS and to provide instructions for its safe operation. The manual also provides troubleshooting assistance should an abnormal message or behavior occur.
Should an abnormal message not covered in this manual appear, please contact your local authorized service agent for troubleshooting and repair.
info@ionups.com.au or call us on 1300 700 805
All of the installation, operation, and maintenance of this device must be performed by authorized and qualified ION technicians who are familiar with this manual.
2
Safety
Important Rules
(1) Please follow these UPS operating instructions to ensure safe and proper operation. (2) When the UPS is being moved or operated, please ensure that the machine is standing vertically. Do
not shake or tip over the machine. Avoid heavy impact.
(3) Poor grounding will lead to unexpected current leakage. Please ensure that the AC power input is
properly grounded (PE Ground) before making any connections.
(4) Please make sure that the UPS is placed in an insulated environment before use and that there are no
electrocution hazards to the operating personnel. (5) Do not connect the neutral wire with the ground and make sure that the input voltage is correct. (6) Once the UPS has been switched on, if the UPS needs to be moved then it must be fully switched off
and fully discharged. If the UPS is not discharged, the UPS will switch to battery power after grid power
is disconnected and pose an electrocution hazard. (7) Do not place any objects, liquid containers, or coverings over the UPS. The liquid spilt into the UPS or
heat prevented from dissipating could lead to internal damage or cause electrocution. (8) Make sure that the battery specifications match the UPS requirements before connecting any external
batteries.
(9) Please follow the rules below before engaging in any activity that involves the battery.
a. Remove all metallic items such as rings, watches and jewelry before working on the battery. b. Please use insulated tools. c. Do not open or damage the battery. The toxic liquid inside will harm the skin and eyes. d. Keep batteries away from fire to prevent explosion.
Symbols
Please follow the instructions and warnings on the UPS.
WARNINGRefer to the operating instructions.
WARNINGHigh voltage inside. Ground
1. Function Description
1-1 UPS Block Diagram
This UPS provides Mains input and Bypass input for dual inputs application. The system block diagram as shown below.
3
1
Input Switch
5
Inverter
2
Bypass Switch
6
Static Switch
3
Manual Bypass Switch
7
Charger/Booster
4
IGBT Rectifier
8
Output Switch
Load
Bypass Input
Mains Input
Battery
4
1-2 UPS Outlook View
ION F20 10-40kW Front View
1
Control panel with colorful LCD touch screen
3
Ventilation grille
2
Handle with lock
4
Wheels for handling
1 ○2 ○3 ○4
5
ION F20 10-40kW Right Side View
1
Through hole for the optional parallel communication cable
1
6
ION F20 10-40kW Interval View
11
Mains Input Switch
14
Output Switch
12
Bypass Input Switch
15
Fuses for Control Power
13
Manual Bypass Switch
16
Battery Tray (Option)
1
Parallel Communication Ports
2
HMI Communication Port
3
Communication Selector for service only
4
USB Port for service only
5
Terminal Resistor Setting Switch for parallel communication
6
Status LED Indictors
7
EPO
8
Backfeed Protection
9
Communication Card Slot2
10
Communication Card Slot1
Please find the detail descriptions of above items on section 2-5.
1 ○2
9
10
11 ○12 ○13 ○14 ○16 ○15 ○7 ○8
3 ○4 ○6 ○5
7
ION F20 10-20kW Rear View
1
X40: Bypass Input Connections Terminal (R, S,T , N)
4
X20: External Battery Connections Terminal (B+,N,B-)
2
X10: Mains Input Connections Terminal (R, S, T, N)
5
Ground Connections
3
X50: Output Connections Terminal (R, S, T, N)
1
2
3
4
5
8
ION F20 30-40kW Rear View
1
X40: Bypass Input Connections Terminal (R, S, T, N)
4
X20: External Battery Connections Terminal (B+,N,B-)
2
X10: Mains Input Connections Terminal (R, S,T , N)
5
Ground Connections
3
X50: Output Connections Terminal (R, S, T, N)
1
2
3
4
5
9
ION F20 60kW Front View
10
ION F20 60kW Left Side View
1
Through hole for parallel communication cable
1 ○1
Wheel Type
Stationary Type
(Without Wheel)
11
ION 60kW Internal View
11
Mains Input Switch
16
X20: External Battery Connections Terminal(B+,N,B-)
12
Output Switch
17
X10: Mains Input Connections Terminal (R, S,T , N)
13
Bypass Input Switch
18
X40: Bypass Input Connections Terminal (R, S, T, N)
14
Manual Bypass Switch
19
X50: Output Connections Terminal (R, S, T, N)
15
Fuses for Control Power
20
Ground Connections
1
Parallel Communication Ports
2
HMI Communication Port
3
Communication Selector for service only
4
USB Port for service only
5
Terminal Resistor Setting Switch for parallel communication
6
Status LED Indictors
7
EPO
8
Backfeed Protection
9
Communication Card Slot2
10
Communication Card Slot1
Please find the detail descriptions of above items on section 2-5.
1 ○2 ○3 ○4 ○5 ○6 ○7 ○8
9
10 ○11 ○12 ○13 ○14 ○16 ○17 ○18 ○19 ○20 ○15
Front Door
12
Rear Side of Front Door View
1
USB Port for Setting Software
4
Output &Input Contacts
2
SD Card Slot
5
RS-232 Port for Setting Software
3
External Battery Temperature Connector
6
Communication Port for Remote Panel
Please find the detail descriptions of above items on section 2-5.
4 ○5 ○1 ○2 ○3 ○6
13
2. Installation and Wiring 2-1 Storage and Installation Environment
Storage Environment
Temperature -20~70 Relative Humidity 95%
Installation Environment
A proper installation environment not only ensures the effective operation of the UPS but also reduces the chance of failure and extends service life. Please take the following recommendations into account to select the most suitable environment and reduce the likelihood of accidents.
Temperature 0~40 (20~25is recommended for extend batteries life time). Relative Humidity 95% (without condensation) Altitude 1000m at normal power. Over 1000m above sea level, the maximum output current
must be derated by 1% every additional 100m.
This product must not be used in an environment with sparks, smoke or gas to prevent
arcing, injury, and fire hazards.
Avoid using dusty materials, volatile gases, or corrosive substances with a high salt-content
in the environment where the UPS is installed.
The installation location of the UPS should be well-ventilated. During charging, the
chemical reaction of the battery generates small amounts of gases. If there is a crack in the battery then this may pose an environmental hazard.
Do not place in a location near a heat source as this will shorten the battery life. Do not place outdoors and avoid direct exposure to sunlight. Please ensure that the environment where the UPS is placed is free from animals that may
damage the wiring, such as: rats and other small animals.
Please ensure that the floor is strong enough to hold the UPS and battery. It must keep the
equipment stable to ensure that it won't suffer damage in a fall.
We recommend placing a fire extinguisher near the UPS in case of an emergency.
14
2-2 Unpacking, Removing and Fixing UPS
This section describes the unpacking and removing processes for wheel type.
Remove the packing materials and cut straps. Remove the cardboard box.
10-40kW 60kW
Unscrew the fastening rail kits on the front and rear side of 10-40kW, and right and left side of
60kW.
10-40kW 60kW
Putting 2 fastening rail kits on the pallet edge and making them steady by fastening 4 screws in
the pallet.
15
10-40kW
60kW
16
Raising 2 wheel brakes or expansion foots for remove the UPS from the
pallet.
10-40kW
60kW
Expansion Foot
Wheel Brake
17
Block the wheels breaks or adjust the expansion foots to fix the UPS.
10-40kW
60kW
Floor Fixing for 10-40kW
It is possible to reuse the fastening rail kits to fix the UPS to the floor.
Expansion Foot
Wheel Brake
18
19
Floor Fixing for 60kW Stationary Type(Without Wheel)
20
Floor Fixing for 60kW Wheel Type
It is possible to reuse the fastening rail kits to fix the UPS to the floor.
21
2-3 General Requirement for Ventilation and Maintenance
During installation ensure that the following conditions are met.
Keep at least 1000 mm of free space in front of the UPS for air flow and future maintenance
purposes.
Keep at least 300mm of free space in rear of the UPS for air-flow space. Keep at least 500mm of free space in the top of UPS for maintenance operations.
Front Side >1000mm
Rear Side
>300mm
Top Side >500mm
UPS
Other
Equipment
22
2-4 Power Cables Connections
Power Cable Sizing
The drawing below shows the positions of power terminals.
10-20kW Power Terminal Positions
30-40kW Power Terminal Positions
60kW Power Terminal Positions
PE
(Ground)
PE
(Ground)
PE
(Ground)
PE
(Ground)
Output
Bypass
Mains
Battery
Output
Bypass
Mains
Battery
Output
Bypass
Mains
Battery
23
Maximum Current
Input/Output
Voltage
Output Power
Maximum
Input
Current
(1)
Max.
Output/Bypass
Input Current
(2)
Max. Battery
Discharge
Current
(3)
380 V
10kVA/10KW
19 A
15 A
35 A
20kVA/20KW
38 A
30 A
69 A
30kVA/30KW
57 A
46 A
103 A
40kVA/40KW
75 A
61 A
137 A
60kVA/60KW
113 A
91 A
206 A
400 V
10kVA/10KW
18 A
14 A
35 A
20kVA/20KW
36 A
29 A
69 A
30kVA/30KW
54 A
43 A
103 A
40kVA/40KW
72 A
58 A
137 A
60kVA/60KW
108 A
87 A
206 A
415 V
10kVA/10KW
17 A
14 A
35 A
20kVA/20KW
35 A
28 A
69 A
30kVA/30KW
52 A
42 A
103 A
40kVA/40KW
69 A
56 A
137 A
60kVA/60KW
104 A
83 A
206 A
(1)
The UPS is operating at rated voltage, rated power and batteries are charging but regardless
of the overload.
(2)
The UPS is operating at rated voltage and rated power but regardless of the overload.
(3)
12Vbattery blocks × 32pcs. The UPS is operating at rated voltage and rated power but
regardless of the overload.
Recommended Cables Size
Capacity
Mains Input
(1)
Output/Bypass Input
(1)
External Battery
(1)
R/S/T/N
PE
R/S/T/N
(2)
PE
+/-/N
PE
10kVA
5 mm
2
3 mm2
5 mm2
3 mm2
8 mm2
3 mm2
20kVA
8 mm
2
5 mm2
6 mm2
5 mm2
16 mm2
8 mm2
30kVA
16 mm
2
8 mm2
13 mm2
8 mm2
30 mm2
10 mm2
40kVA
25 mm
2
10 mm2
20 mm2
10 mm2
50 mm2
16 mm2
60kVA
40 mm
2
16 mm2
35 mm2
16 mm2
70 mm2
25 mm2
(1)
The recommended maximum length of cabling is less than 10meters.
(2)
Please over size neutral line N by 1.7 times of the phase line for non-linear loads.
24
Recommended Circuit Breaker Size
Input/Output
Voltage
Output Power
Mains Input
(1)
Output/Bypass Input
(1)
380 V
10kVA/10KW
30 A
25 A
20kVA/20KW
65 A
50 A
30kVA/30KW
95 A
80 A
40kVA/40KW
125 A
105 A
60kVA/60KW
185 A
160 A
400 V
10kVA/10KW
30 A
25 A
20kVA/20KW
60 A
50 A
30kVA/30KW
90 A
75 A
40kVA/40KW
120 A
100 A
60kVA/60KW
175 A
150 A
415 V
10kVA/10KW
30 A
25 A
20kVA/20KW
55 A
50 A
30kVA/30KW
85 A
70 A
40kVA/40KW
115 A
95 A
60kVA/60KW
170 A
145 A
(1)
The sizing takes into account 150% overload capacity.
25
Electrical System Connections
UPS with single Input
Load
3P+N
UPS with single input and isolation transformer
Load
3P 3P+N
UPS with dual inputs
Load
3P+N
3P+N
26
UPS with dual inputs and isolation transformer
Load
3P 3P+N
3P 3P+N
Load
3P+N
3P 3P+N
Load
3P 3P+N
3P+N
Note : You have to install an isolation transformer on one of the inputs if
the two power system are different.
27
UPS in parallel, use separate battery
Load
3P+N
UPS in parallel, use common battery
Load
3P+N
28
UPS in parallel with output transformer Please do not use separate output transformer for each UPS. A common output transformer is
recommended.
Load
3P+N
Load
3P+N
29
Converter Mode Please do not connect the bypass input.
Load
3P+N
Load
3P+N
Note : Up to 6 units can be operated in parallel for Converter Mode
operation and common battery function is available.
30
2-5 Communication Cables Connections
10-40kW
60kW
Paral-1& Paral-2--parallel communication port
Parallel communication cables are required to connect UPS each other when UPSs operation in
parallel. Please refer to section 2-6for detail connections.
Switch--the switch for terminal resistor of parallel communication
To ensure good parallel communication quality please set the Switch of the two farthest UPS to the “ON” position. Please refer to section 2-6 for detail.
HMIcommunication port for control panel
This port connects to the LCD display and control panel.
H↔U—communication selector
This switch is to select HIM or USB port. Please ensure this switch on “H” position for ensure HMI port is workable.
USB
This port is for service only.
LED Status Indictors
Normal : The UPS is normal. Alarm : The UPS has some abnormal conditions.
31
EPO-- Emergence Power Off
This EPO contact allows you to turn off the UPS in an emergency. Shorting these contact to turns off the UPS immediately.
Backfeed Trip
The UPS provide a backfeed protection contact to trip the external electromechanical device for isolation from the power circuit. The backfeed protection is for ensuring personnel safety against any risk of accidental energy return to the input circuit. It imposes the automatic opening of an
switching device in case of a malfunction of the static switch.
Communication Slot1
This slot can install Relay card or RS-485 MODBUS card.
Communication Slot2
This slot can install Relay card or SNMP card. Please ensure the SW2 switch to correct position when this slot is used.
USB
Complies with USB V.2.0, 12 Mbps Pin Assignment:
1  VCC (+5V) 2  D- 3  D+ 4  Ground
32
This port is available for change the setting of UPS by setting software.
Batt. Temp.--External battery temperature connector
Connect to external battery temperature sensor. Please refer to section 5-4.
SW2
When Relay card is installed in Slot2, please switch to “Slot” position. When SNMP card is installed in Slot2, please switch to “SNMP” position.
SW3--the switch for terminal resistor of parallel communication
To ensure good parallel communication quality please set the Switch of the two farthest UPS to the “ON” position. Please refer to section 2-6 for detail.
Output & Input Contacts
The UPS provides 3 output dry contacts and1 input contact. Specification of Output dry contact250 VAC/ 2 A; 30 VDC/2 A
There have 3 jumpers (J1~J3) to set NC/NO for each output contact. To short the input contact for send a command to UPS.
The user can change the definition for each contact, please contact the local authorized service agent to change the setting.
OUT_1
OUT_2
OUT_3
IN
33
RS-232
Pin Assignment:
1 2 3 4 5
6 7 8 9
Baud Rate
57600bps
Data Length
8 bits
Stop Bit
1 bit
Parity
None
This port is available for change the setting of UPS by setting software.
2 TX (OUT) 3 RX (IN) 5 Ground
34
2-6 UPS Parallel Connections
The UPS can be operated in parallel for extend the capacity and enhances system reliability.
Up to 6 UPS units can be operating in parallel. The size and length of the input and output cables must be identical for all UPS units. The phase rotation must be the same for each UPS unit. It is recommended to use an external bypass cabinet to facilitate maintenance and system testing
for parallel operation system.
Parallel configuration must be performed by authorized and qualified technicians who are familiar
with this UPS.
Parallel communication cables are requested to connect to UPS each other. Please only use the parallel communication cables which are supplied with UPS manufacturer for
ensure UPS can operate correctly in a parallel configuration.
The parallel communication cables must be connected in a ring topology, and the maximum total
length of the parallel communication cables must be less than 38 meters. To ensure good communication quality you must set the Switch & SW3 of the two farthest UPS to the “ON” position as shown in below.
When installing the parallel communication cables, it recommended the parallel communication
cable through the hole at side of UPS, as shown below.
35
Recommended 1+1 parallel system configuration
36
Mains
Load
Mains Bypass
Load
1+1 parallel, Single Input 1+1 parallel, Dual Input
Recommended N+1 parallel for single input system configuration
Parallel
Communication
Cables
37
Up to 6 UPS Units
Load
Mains
External
Manual
Bypass Switch
Recommended N+1 parallel for dual input system configuration
Parallel
Communication
Cables
38
Up to 6 UPS Units
Load
Mains
External
Manual
Bypass Switch
Bypass
Parallel
Communication
Cables
39
3. Operation Descriptions
3-1 Operating Mode
The UPS provide the following operating modes:
(1) Normal Mode(Online Mode):
In Normal mode, grid power is passed through Rectifier then used to charge the battery and provide power through the Inverter simultaneously. Different output voltages settings can be set in VFI mode. The three options are 380/220V, 400/230V and 415/240V. These can be fine-tuned by ±8V.
(2) Economy Mode (ECO):
Economy Mode effectively improves overall efficiency. In ECO Mode grid power is routed through the Static Switch to the load. At the same time, grid power continues to charge the battery in DC/DC mode through Rectifier following the same setup as VFI Mode. Inverter is also kept ready to switch power supply modes at any time. If VFI mode is set then power can be quickly routed from Bypass to Inverter.
Attention: In ECO Mode the power supply frequency and voltage will be less stable. Please check the load requirements and use ECO Mode with care.
(3) Converter Mode:
Converter Mode allows the user to provide a power supply with constant voltage and constant frequency based on their power requirements. The frequency can be set to 50HZ or 60HZ. The voltage options are 380/220V, 400/230V and 415/240V. These can be fine-tuned by ±8V. When Converter mode is used, in the event of grid power failure then power is provided from the battery in Back-up mode. In the event of the battery running low, UPS overload, Inverter failure or module overheating, the entire system will shut down.
40
3-2 Online Operations
An online UPS provides stable power that is not affected by an unstable main power supply (ex. grid power). Through the online UPS, grid power can provide a clean, noise-free power supply environment. The online architecture offers three types of power supply methods depending on the power environment.
(1) Normal Mode:
When grid power is normal, once Rectifier has been turned on at the main power supply then the battery is charged in DC/DC mode while the required power is supplied via Inverter at the same time.
(2) Bypass Mode:
In the event of UPS overload, INV failure or module overheating, the power supply circuit switches from INV to the bypass output.
(3) Battery Mode:
When the UPS detects a failure in the main power supply then power is provided from the battery instead. The touch screen at the front of the module will also display current battery level to remind the user.
3-3 Manual Bypass Operation
When the manual bypass switch is activated, the load is powered directly from the bypass input. This operation is useful when maintenance needs to be carried out on UPS since service personnel can work on the installation without having to cut off the power to the load.
Attention:
UPS maintenance can only be performed by authorized and qualified technicians who are
familiar with this UPS.
If the UPS is in battery mode, turn on the manual bypass switch may cut off power to the
load.
41
3-4 Operation Processes
3-4-1 Normal Mode Start-up
(1) Close UPS Mains Input and Bypass Input Switches. (2) Select CommandOperationNormal mode on LCD display. The UPS will be
started and supply output voltage.
(3) Close UPS Output Switch to supply the power to the load.
3-4-2 Cold Start
(1) User can start-up UPS by battery when main input power is not available. (2) Select CommandOperationCold start precharge ready on LCD display. (3) And then select Normal mode to start UPS.
3-4-3 Shutdown
(1) Select CommandOperationShutdown on LCD display.
3-4-4 Switch to bypass
(1) Select CommandOperationShutdown converter except bypass on LCD
display.
(2) The Inverter will be shutdown and bypass will supply the power to the load. If the battery
is disconnected, Rectifier and Charger will be shutdown as well.
42
4. Control Panel Operation and Function Description
Each UPS is equipped with a LCD touch panel to provide the user with a simple and intuitive user interface that is easy to learn. The touch panel offers a combination of graphics and numbers that make it easy to determine the input/output voltage, frequency, load and battery level at a glance. The current status of the UPS is displayed at the main screen. User also can have the real time input/output voltage, frequency, current and battery information from the touch panel.
Please refer to below section for learn more detail information and functions of the LCD touch panel.
4-1 Screen Introduction
ADisplay current time, status and information of UPS.
BIndicate Single or Parallel system, and select the desire UPS unit that want to check the information.
: Single Unit : Parallel System
CClick here to see the alarm message.
: The green pattern indicates that UPS is normal. : The red pattern indicates that UPS occurred abnormal conditions.
DClick here to see the status. EEnter to Sub-Menu, please refer to section 4-2 for more detail. FEnter to Menu, please refer to section 4-2 for more detail.
43
4-2 Menu
Click to enter to Menu screen as shown in above picture. Slide the screen to switch to other menu page and click the menu icon to enter to the desire function.
Click to hide/show the sub-menu.
The button below will appear on some function pages.
Button
Function
Click it to save the new setting
Click it to reload the data
Click it to go to Mimic Display
44
All menus ‘functions are showing in below table.
Menu
Sub-Menu
Functions
Mimic Display
Display the UPS statusalarmoperating mode and
measurements. Please refer to section 4-3 for more detail.
Command
#1
Operation
Normal mode
ECO mode
Converter mode
Shutdown
Shut down converter expect bypass
Cold start precharge ready
Buzzer & Alarm
Enable/Disable Buzzer
Clear latch alarm and buzzer.
Other
Recover backfeed protection signal
Battery Test
Monitor
Identification
Display UPS information
Real Time
Information
Display real time measurements of input, output, bypass and
battery.
Maintenance
Code
Display the maintenance code for technician check the status of the UPS.
Version
Disply the control MCU software and firmware version.
Configuration
Alarm
Set alarm latch function.
General Alarm
Mains Alarm
Bypass Alarm
Over Temperature
Battery Low
Inverter Overload
Bypass Overload
Emergency Stop
Main
Select the measurements that want to display on Mimic Display.
Bypass
Output
Menu
Sub-Menu
Functions
Management
Schedule
Display the schedule.
45
Schedule Setting
#1
To define the schedule for ECO mode.
Battery Test
Schedule
#1
To define the schedule for battery test.
Setting
Language
Select the display language
Update Prog.
Upgrade the software of LCD touch display.
General
Set the backlight of LCD turn off time.
Date and Time
Set current date and time.
Peripherals
#1
Set communication card.
Event Log
Display the event log list of UPS.
Log on Load
Display the history curve of loading. (Up to 7 days data).
Permission
Setting
Login/Logout
Login with the password
#2
Password
Modification
#1
Chang user password.
Maintenance
#1
Screen Calibration
Calibrate the touch screen.
#1
This function menu only appear after login, please refer to “Permission Setting”.
#2
Default password is “3366”.
46
4-3 Mimic Display
Ais Rectifier、【Bis Static Switch and Cis Inverter.
The fade pattern indicates this part isn’t activated. The blue pattern indicates this part is activated. The red pattern indicates this part is occurred abnormal condition.
Ddisplay the bypass input measurements. Edisplay the mains input measurements. Fdisplay the output measurements.
The abnormal measurements will have red background . ClickD】【E】【F to change the measure parameter and press for 3 second to enter to Real
Time Information .
Gdisplay the status of battery.
Press it for 3 second to enter to Real Time Information .
The battery isn’t connected.
The green pattern indicates the battery is charging. The yellow pattern indicates the battery is discharging.
HAlarm silence button. Click it to silence the alarm and press for 3 seconds to enable/disable the buzzer.
Buzzer is enabled.
Buzzer is disabled.
IDisplay UPS internal temperature.
Press for 3 seconds to enter to Real Time Information .
JOverload counter
47
5. Options
5-1 Dry Contact Card
This card provides six output dry contacts and six input contact. These contacts are programmable and user can change the definition for each contact. Please refer to Dry Contact Card manual for more detail.
5-2 RS-485 MODBUS Card
RS-485 ports with JBUS/MODBUS protocol. Please refer to RS-485 Card manual for more detail.
5-3 SNMP Card
This is Ethernet network card with TCP/IP, HTTP and SNMP protocols.
48
5-4 Temperature Sensor
Measure the battery temperature.
5-5 DC Cold Start Kit
This kit allows UPS start-up by the battery without mains input.
5-6 Parallel Communication Cable
The parallel communication cables are required when UPS in parallel. Each UPS provides a 1.5 meter parallel communication cable as standard and it can use for 2 UPS in parallel. A longer parallel communication cable is available for more UPS in parallel.
3000.0mm
4.3mm
7.2mm
49
6. Troubleshooting
In the event of failure, the display area on the control panel will highlight the problem area in red. The
"Alarm" symbol will also blink to warn that there is a problem with the UPS. Click to have a alarm list as below picture.
We recommend checking the error code using the following method when troubleshooting
Click InformationMaintenance Code to bring up the screen shown below. If you can provide the maintenance code to the authorized distributor, this will speed up troubleshooting. You also can click “Export” to save the maintenance code in SD card.
50
7. Technical Specification
Model
F20-10KW
F20-20KW
F20-30KW
F20-40KW
F20-60KW
Capacity
10 kW
20 kW
30 kW
40 kW
60 kW
Input
Voltage
400V 3 Phase + N
Voltage Tolerance
±20% @100% load
-40% ~-20% @50% load
Frequency
45 ~ 65Hz
Power Factor
0.99
THDi
< 3%
Output
Voltage
380/400/415V 3 Phase + N
Voltage Tolerance
±1% (Static Load)
Frequency
50/60Hz
Frequency Tolerance
±0.01% (free running)
Power Factor
1.0
Crest Factor
3:1
Voltage Harmonic
Distortion
1% with linear load;
3% with distorting load
Overload
110% for 60 minutes, 125% for 10 minutes, 150% for 1minutes
Parallel
Up to 6 units
Bypass
Voltage
380/400/415V 3 Phase + N
Voltage Tolerance
±5% ~±25% (Programmable)
Frequency
50/60Hz
Frequency Tolerance
±1Hz / ±3Hz (Selectable)
Battery
Number of batteries
12V 32/34/36/38/40pcs configurable
Max. Charging
Current
3.5 A
7 A
10 A
13 A
20A
Common Battery for
Parallel Configuration
Yes
Internal Battery
Available for housing 12V 7/9Ah 40pcs x 2 strings
N.A.
Maximum Efficiency
VFI Mode
>94%
>94%
>95%
>95%
>95%
ECO Mode
>98%
Backup Mode
>93%
>93%
>94%
>94%
>94%
51
Model
F20-10KW
F20-20KW
F20-30KW
F20-40KW
F20-60KW
HMI & Communication
Display and MMI
4.3" Colorful LCD Touch Screen
Built-in Communication
Port
RS-232, USB, EPO, Dry Contacts
Optional Communication
2 Communication Slots for
SNMP Card, RS-485 MODBUS Card, Dry Contact Card
Mechanical Characteristics
Dimensions
(W x D x H) mm
440 x 810 x 1390 (Wheel type)
600 x 827 x 1253
(w/o wheel)
600 x 827 x 1300
(Wheel type)
Weight
113 kg
115 kg
130kg
132kg
194kg (w/o wheel) 200kg (Wheel type)
Protection Grade
IP20
Color
RAL 7016 , Anthracite Grey
Environment
Storage Temperature
-20 ~ 70
Storage Humidity
95%
Operation Temperature
0~40
Operation Humidity
0~95% (w/o condensation)
Operating Altitude
<1000 m without derating
#1
Tested to standards
LVD: EN62040-1
EMC requirements: EN62040-2
Mark
CE
Noise (at 1 meter)
<52dBA
<52dBA
<56dBA
<56dBA
<60dBA
#1 Over 1000m above sea level, the maximum output capacity must be derated by 1% every
additional 100m.