
PROCEDURE
10
FAN
PROCEDURE
TO
ELECTRICAL
Unplug
>
"Τι
1
Ζ
Remove
Remove
op
Remove
BLY
5.
Remove
NOTE:
erly
6.
Remove
7.
Move
8,
Disconnect
9.
Remove
10.
Remove
10
PREVENT
OUTLET
unit.
cabinet
control
compressor
OR
CAPACITOR).
heat
Before
reinstalled
removing
the
fan
to
wires
GREEN
existing
to
four
access
REPLACING
-
ELECTRICAL
BEFORE
(Refer
panel
exchanger
secure
(4)
from
fan.
to
(Refer
assembly
the
heat
mounting
the
wires
spade
ground
COOLING
SHOCK,
SERVICING,
PROCEDURE
to
PROCEDURE
(Refer
(Refer
wire
to
four
(4)
mounting
exchanger.
screws
connected
connectors
from
CAUTION
ALWAYS
1 -
to
PROCEDURE
PROCEDURE
located
to
fan.
on
back
rear
of
fan
(FIGURE
FAN
DISCONNECT
REMOVING
9 - REMOVING
8 - REPLACING
clips,
note
under
by
sound
side
of
removing
1)
CABINET).
CONTROL
7 - REPLACING
HEAT
their
position.
box and
fan.
self-tapping
remove
CONCENTRATOR
PANEL).
COMPRESSOR
EXCHANGER).
These
screw
clips
mounting
on
fan
FROM
ASSEM-
must
be
prop-
clips.
assembly.
Fan
must
be
flow
arrow
11.
Reverse
12.
Reinstail
13.
Reinstall
on
STEPS
heat
compressor
CAPACITOR).
14.
Reinstall
15.
Plug
NOTE:
nical
Service.
16.
Reinstall
unit
Run
contro!
in
unit
cabinet
positioned
back
of
fan)
6-9
exchanger
panel
and
check
for
at
least
(Refer
properly
or
damage
to
install
(Refer
(Refer
(Refer
for
leaks
1/2
to
PROCEDURE
WARNING
so
air
from
to
the
NEW
fan.
to
PROCEDURE
to
PROCEDURE 7 -
to
PROCEDURE
(Refer
hour.
If
to
PROCEDURE
unit
runs
1 -
the
fan
unit
will
8 - REPLACING
REPLACING
9 - REMOVING
properly,
REMOVING
blows
occur.
19 - LEAK
replace
CABINET).
DOWN
onto
HEAT
COMPRESSOR
CONTROL
TEST).
cover.
the
compressor
EXCHANGER).
ASSEMBLY
PANEL).
If
not,
call
Invacare
(see
Tech-
air
OR
4-9

PROCEDURE
11
P.C.
BOARD
REPLACEMENT
PROCEDURE
TO
P
ELECTRICAL
C
1.
B
2.
0
3.
A
R
D
ONLY
S
These
Before
the
tor
available.
When
solder
slight
Before
4, . Remove
PREVENT
Unplug
Remove
Remove
unit.
cabinet
control
QUALIFIED
are
precautions
handling
components
clip.
Electrical
Care
removing
joint
may
rocking
installing
Sensor
11 - REPLACING
ELECTRICAL
OUTLET
any
of
should
quick
occur.
motion
any
BEFORE
(Refer
panel
to
(Refer
SERVICE
that
P.
C.
boards,
the
board. A Static
conduit
or a water
be
taken
disconnects,
Hold
to
remove
P.
C.
boards,
Wiring
Hamess
PROCEDURE 1 -
TECHNICIANS
should
P.C.
SHOCK,
SERVICING.
to
PROCEDURE
be
you
to
ensure
down
the
the
ensure
Jumper
BOARD(S)
CAUTION
ALWAYS
REMOVING
WARNING
SHOULD
followed
need
to
Cuff
must
pipe
is
normally
that
DO
NOT
pull
P.
C.
board
terminals.
that
(P2)
Кот
(FIGURE
DISCONNECT
9 - REMOVING
MAKE
to
prevent
be
properly
be
worn
sufficient
alligator
all
insulators
Р.С.
clip
on
wire
with
one
board(s)
1)
CABINET).
CONTROL
ANY
CHANGES
damage
grounded
and
contact
itself
hand
are
to
be
to
properly
when a known
as
and
in
place.
replaced,
CONCENTRATOR
PANEL).
TO
THIS
the
P,
C.
to
prevent
grounded
good
with
bare
metal
damage
use
to
an
upward
EQUIPMENT.
boards:
static
damage
using
ground
surface.
the
connector
force
FROM
an
alliga-
is
with
to
not
or
a
5.
Disconnect
DO
NOT
sensor
3LX,
assembly
SLX
Sens02
a)
Sensor
CONTROL
Control
a)
Wiring
b)
Wiring
©)
Transformer connector(P3).
d)
Pressure
Integrated
a)
Wiring
b)
Wiring
©
Transformer
d)
Pressure
e)
Oxygen
CONTROL
f)
Wiring
the
remove
and
5LXO2
(Top)
tubing
PANEL).
(Bottom)
Hamess
Hamess
transducer
Board
Hamess
Hamess
transducer
Sensor
Hamess
following:
sensor
could
before
PC.
Board
from
P.C.
from
from
(5LXO2/5LXO2T/6LXO2/6L.XO2T)
from
from
connector(P3).
PANEL).
occur.
(SLXO2
“T*
Board
9-Pin
8-Pin
tubing
9-Pin
8-Pin
tubing
tubing
from
4-pin
tubing
from
P.C.
S/N97JXXXX
ONLY):
fitting
(3LX,
Wiring
Wiring
from
Wiring
Wiring
from
from
behind
SLX,
5LXO2):
Hamess
Hamess
producttank.
Hamess
Hamess
producttank.
“T°
fitting
wiring
Connector(P5).
behind
hamess
CAUTION
Board.
control
Connector
Remove
panel
(P1).
(Refer
Connector(P5).
After
S/N97JXXXX
Connector
connector
(P1).
control
panel
(P6)
from
to
(Refer
to
[5LXO2T,
tee
fitting
PROCEDURE
PROCEDURE
6LXO2T
Telemetry
ONLY.
Damage
9 - REMOVING
9 - REMOVING
Unit
to
ONLY].
Remote
a)
6.
Pinch
Display
Sensor
end
wiring
hamess
of
each
Board
if
not
stand-off
disconnected
with
needle-nose
in
STEP
pliers
4-11
1.
and
remove
the
P.C.
Board(s).

PROCEDURE
14
FLOWMETER
PROCEDURE
nmamesorm
10.
TO
PREVENT
ELECTRICAL
Unplug
Remove
Remove
Remove
Remove
Remove
Install
Reinstall
Run
PASAR»
new
unit
19 - LEAK
Reinstall
14 - REPLACING
ELECTRICAL
OUTLET
unit.
cabinet
control
tygon
palnuts
flowmeter
control
and
(Refer
panel
tubing
from
flowmeter
panel
check
TEST).
cabinet
(Refer
BEFORE
to
PROCEDURE
(Refer
from
rear
of
from
front
reversing
(Refer
for
leaks
to
FLOWMETER
SHOCK,
SERVICING.
to
PROCEDURE
the top
and
flowmeter.
of
contro!
STEPS
to
PROCEDURE
where
PROCEDURE
tygon
(FIGURE
CAUTION
ALWAYS
1 - REMOVING
9 - REMOVING
bottom
panel.
4-5.
fittings
9 - REMOVING
tubing
1 - REMOVING
engages
1)
DISCONNECT
CABINET).
CONTROL
on
back
of
|
CONTROL
flowmeter
CABINET).
CONCENTRATOR
flowmeter.
fittings
PANEL).
PANEL).
(Refer
to
FROM
PROCEDURE
Flowmeter
Flowmeter
(Back
Fittings
of
Flowmeter)
FIGURE 1 -
REPLACING
FLOWMETER
Control
Panel
4-14

PROCEDURE
16
4-WAY
VALVE
PROCEDURE
TO
ELECTRICAL
Replacing
ES
1.
‘Position
oP oN
ш<гр<
valve
Torque
could
Tighten
6.
7.
The
8.
PREVENT
4-way
Unplug
Remove
Remove
Remove
Pre-torque
unit.
cabinet
control
the
NEW
and
sequence
result.
mounting
mounting
into
16 - REPLACING
ELECTRICAL
OUTLET
Valve
four
4-way
manifold
the
screws
BEFORE
(FIGURE
(Refer
panel
(Refer
(4)
mounting
valve
assembly.
and
specification
screws
mounting
can
to
screws
4-WAY
SHOCK,
SERVICING.
1)
PROCEDURE
to
PROCEDURE
screws
onto
manifold
MUST
in
the
sequence
to
be
now
be
VALVE/MANIFOLD
CAUTION
ALWAYS
1 - REMOVING
that
secure
assembly
CAUTION
BE
adhered
described
10 + 2
in.
torqued
lbs.
to
DISCONNECT
CABINET).
9 - REMOVING
the
4-way
and
loosely
to
or
below
using
the
27 + 3-in.
Ibs.
ASSEMBLY/PILOT
CONCENTRATOR
CONTROL
valve
to
the
manifold
install
mounting
possible
(FIGURE
torque
in
damage
1).
sequence.
the
same
PANEL).
assembly.
screws
to
the
sequence.
VALVES
through
4-way
FROM
4-way
valve
STOP!
Replacing
Unplug
Remove
Remove
Remove
Remove
Remove
POIANA
the
4-way
unit.
control
manifold
THIS
IS A MAINTENANCE
VOID
Valve
cabinet
panel
the
ty-wraps
hoses
and
from
code
assembly.
ANY
Manifold
(Refer
(Refer
from
manifold
the
four
AND
2)
ALL
FIGURE 1 -
to
PROCEDURE
to
the
assembly.
(4)
spade
WARRANTIES
Manifold
Assembly
PROCEDURE
sieve
bed
connectors - two
FREE
Assembly
<<
REPLACING
(FIGURE
1 -
REMOVING
9 - REMOVING
hoses
to
top
VALVE.
APPLICABLE
MOUNTING
.
Pre-torque
4-WAY
2)
of
(2)
VALVE
CABINET).
manifold
each
OPENING
4-way
SCREW
to
10
to
CONTROL
assembly.
from
the
two
THE
TO
Valve
Sá
TORQUE
+ 2-in.
27
+ 3-in.
PANEL).
(2)
valve
VALVE
THE
Face
lbs.,
Ibs.
pilots
WILL
VALVE.
SEQUENCE
then
Torque
on
top
of
8.
9.
10.
Remove
(Refer
Remove
Loosen
Remove
the
to
PROCEDURE
muffler
the
adjustable
hose
mounting
from
muffler
clamp
from
front
screw
2 - PREVENTIVE
of
that
canister.
that
secures
heat
exchanger.
secures
muffler
MAINTENANCE).
valve
manifold
canister
input
assembly
hose
to
front
of
to
rear
heat
exchanger.
of
sound
«box

PROCEDURE
17
PURITY
SWITCH
PROCEDURE
で
ご
TO
コー
PREVENT
DISCONNECT
TRICAL
ゴー
Operation
The
の
an
the
concentrator.
コー
の
〇
indicator
の
NOTE:
warm-up
unit
will
initial
the
if
other
condition
tor
illuminate.
Indicator
GREEN
YELLOW
concentrator
supplier.
that
RED
IMMEDIATELY
Supplier
.
Invacare 5 and 6 with
oxygen
purity
Concentrator
is
initially
illuminate.
startup, a GREEN
Oxygen
the
concentration
indicator
may
BACKUP
LIGHT - Total
17 - SENSO2
CAUTION
ELECTRICAL
CONCENTRATOR
OUTLET
purity
level
lights
time
that
be
Lights
LIGHT - Normal
LIGHT - You
Cal!
IMMEDIATELY.
BEFORE
indicator.
of
the
If
purity
falls
on
the
(approx.
turned
Within 5 to
Purity
used
unless
Section
level
light
requires
while
(FIGURE
instructed
Supplier
OXYGEN
to
BACKUP
contro!
can
ON,
illuminating
IMMEDIATELY.
ALARM
SHOCK,
SERVICING.
SensO2
This
feature
oxygen
30
service.
Operation.
may
is
unit
generated
below
no
is
alarm
panel!
be
used
minutes).
oxygen
30
light
will
of
the
in
specification.
waiting
.
1)
continue
otherwise
nearby.
shutdown.
OXYGEN
INDICATORS
ALWAYS
FROM
is
equipped
will
during
minutes
illuminate
Control
will
The
for a light
ELEC- | Auto
monitors
by
thresholds,
illuminate.
When
purity
signal
concentra-
to
use
by
Be
certain
Switch
supply.
with
the
initial
the
lights
after
in
Panel
Any
a
to
the
your
Call
AND
SWITCH
Oxygen
Shut-
Down
Use
Backup
Below
Purity
1.
Unplug
2.
Remove
REMOVING
3.
Locate
Board.
4.
Settheindicator
is
olds
manual).
5.
‘Plug
6.
Run
in
PROCEDURE.
7.
If
8.
Refer
TION
of
9.
(Refer
Normal
Normal
FIGURE
Indicator
unit.
cabinet.
purity
factory
in
the
in
power
unit
and
accordance
problems
fo
Operating
AND
this
manual.
operation
to
PROCEDURE
=
Purity
y,
cal
@
©
1 -
INDICATOR
Switch - If
(Refer
CABINET).
switch
preset
cord.
check
exist,
SEQUENCE
is
on
switch
to
at
73%).
SPECIFICATION
the
with
specifications
call
Invacare
Sequence
within
specification,
Suppli
PP
LIGHTS
Installed
to
PROCEDURE
upper
left
either
73%
(Refer
indicator
to
section
lights
Technical
in
OF
OPERATION
1 -
REMOVING
_
RED
YELLOW
~*~
GREEN
(FIGURE
comer
or
85%.
Alarm
for
set
the
reinstall
2)
of
Sensor
(Switch
Thresh-
of
operation
forth
in
Support.
INSTALLA-
portion
cabinet.
CABINET).
1
-
this
this
GREEN
-
Oxygen
to
use
ATELY.
NOTE:
board
switch
purity
located
unit.
(FIGURE
Refer
TION
NOTE:
If
(See
to - Alarm
section
LIGHT - with
sensor
the
your
is
then
indicators
on
PURITY
2).
Indicator
malfunctioning;
concentrator.
Invacare
equipped
you
can
the
sensor
INDICATOR
Thresholds
of
this
lights
YELLOW
Call
Concentrator
with
an
set
the
will
activate.
board
manual.
are
visible
LIGHT
Supplier
alarm
level
near
you
The
FLASHING
may
SensO,
at
the top
SWITCH
in
the
SPECIFICA-
only
continue
IMMEDI-
Р.С.
threshold
which
switch
of
the
is
the
graphic)
when
lit.
4-20
TOP-LEFT
LI
FIGURE 2 -
73%
85%
~
PURITY
Purity
Switch
+.
INDICATOR
Settings
SWITCH

TIMING
PROCEDURE
18
PROCEDURE
(FIGURE
TO
PREVENT
ELECTRICAL
To
accommodate
control
involves
1.
2.
A:
1.
Unplug
Remove
Plug
の
Run
Take
If
oxygen
の の か
ざさ
Unplug
UNITS
If
retiming
the
increasing
concentrator
unit
O2
WITH
18 - TIMING
1)
ELECTRICAL
OUTLET
for
varying
shifting
unit.
cabinet.
for
reading.
unit
of
the
or
decreasing
(Refer
in,
20
minutes.
conceniration
and
reinstall
CONTROL
is
needed, perform
THE
INVACARE
IRCSLX/5LXO2
CAUTION
BEFORE
tolerances
SHOCK,
SERVICING.
when
ALWAYS
replacing
INVACARE 5 and 6 Pressure
the
to
and
is
cabinet.
BOARD
PROCEDURE
tum
power
within
specification,
OR
the
switch
located
1 - REMOVING
on,
set
flow
retiming
LX
SMT
BOARD
following:
on
at 5 L/min.
CONCENTRATORS
DISCONNECT
components,
Equalization
the
lower
right
CABINET).
for
the
is
not
necessary.
CONCENTRATOR
an
adjustable
(P.E.)
side.of
Valve.
the
IRC5LX/IRC5LXO2.
Retiming
bottom
timer
P.C.
FROM
is
used
of a unit
Board.
to
OZ-E8-+
a)
Unplug
b)
Remove
c)
Locate
Use
extreme
your
before
hands
adjusting
unit.
or
loosen
the
timing
care
to
contact
switch
when
timing
contro!
Panel.
on
making
the
P.C.
switch.
Control
(Refer
the
lower
adjustments
Board
when
Electrical
Panel
to
PROCEDURE 9 -
right
side
of
WARNING
to
the
unit
is
plugged
shock
is
Timing
possible.
Switch
the
bottom
timing
REMOVING
P.C.
switch.
in
and ON.
Board.
DO
NOT
Turn
Control
CONTROL
allow
unit
Panel
screwdriver
OFF
PANEL).
and
unplug
or
FIGURE 1 -
TIMING
THE
INVACARE 5 CONCENTRATOR
-
IRC
5LX/5LX02/6LX02

PROCEDURE
18
TIMING
PROCEDURE
IRC5LX/5LXO2
e)
Insert a small
f)
コ
ミー
テー
の 〇
Set
2.
Turn
3.
If
after
one
4.
Let
positions
NOTE:
The
normal
5.
Continue
value
Once
Reinstall
Reinstall
SENE
Reinstall
unit
You
18
(continued) - TIMING
(FIGURE
common
the
timing
unit
on.
10
(1)
position
run
higher.
will
adjustment
to
achievable.
concentration
inlet
control
cabinet.
switch
minutes
lower
another
find
change
filter.
panel.
initially
of
run
than
10
minutes.
that
the
range
setting
(Refer
has
(Refer
(Refer
1)
or
flathead
at
the
time
the
concentration
the
previous
If
concentration
concentrator
is
between 3 and
one
(1)
step
to
CONCENTRATION
reached
to
specification,
to
PROCEDURE
PROCEDURE
THE
INVACARE 5 AND 6 CONCENTRATOR
screwdriver
number 7 position.
setting.
will
at a time
1 - REMOVING
into
the
is
below
is
lower
perform
A.
(up
or
LEVELS
retiming
9 - REMOVING
better
down)
Chart
is
adjustment
specification,
still,
change
at
in
complete.
CABINET).
screw
the
either
until
the
this
PROCEDURE
CONTROL
the
of
the
timing
change
switch
concentration
setting
to a number
higher
PANEL).
or
lower
of
switch.
to a number
two
setting.
is
the
highest
the
Manual
(2)
.)
PROCEDURE
18 - TIMING
5LXO2T/GLXO2/6LXO2T
B.
UNITS
To
accomodate
time
matic
If
manual
Automatic
Unattended
1.
2.
3.
4.
NOTE:
5.
WITH
INTEGRATED
the
of
the
pressure
(microprocessor
adjustments
adjustment
operation
Tum
power
Remove
a.
If
b.
ff
Replace
and 6 L/min.
The
After
the
tune
mode.
maximum
OFF
cabinet.
the
intergrated
the
intergrated
the
cabinet.
for
flow
MUST
FIRST
The
value
varying
the
valve
microprocessor
tolerances
egulization
controlled)
is
preferred,
is
performed
is
possible
and
unplug
(Refer
or
telemetry
or
telemetry
Plug
IRC6LXO2ARC6LXO2T.
be
shift,
of
oxygen
THE
INVACARE 5 AND 6 CONCENTRATORS
(FIGURE
OR
TELEMETRY
when
(PE.)
valve.
adjustments
please
by
the
without
the
unit.
to
PROCEDURE
board
board
concentrator
at
rated
output
the
front
pane!
automatically
concentration
1)
replacing
The
of
refer
to
onboard
the
use
1 -
has
beeen
has
NOT
in,
and tum
for
optimum
Red
for
the
BOARDS
components,
integrated
the
SECTION A of
microprocessor
of
any
REMOVING
LED
adjusts
unit
and
P.E.
shift
additional
replaced,
beeen
power
replaced,
on,
adjustment
will
slowly
the
at
rated
times.
CABINET).
set
length
an
adjustable
telemetry
this
manual
set
flow
blink.
flow.
boards
procedure.
to
optimize
adjustments.
the
timing
set
the
at5
of
oxygen
This indicates
of
the PE.
timer
allow
the
switch
timing
L/min.
forthe
output
valve
IRC5LXO2/
is
used
to
control
for
either
manual
oxygen
switch
timing
output
to
position
to
IRCSLXO2/IRC5LXO2T
for
that
the
up
concentration.
"0".
position
all
flow
unit
is
or
down
the
shift
or
auto-
“F”.
ranges.
in
the
auto-
to
provide
a.
If
the
b.
ff
the
If
the
front
When
the
LED
will
pauses.
switch
switch
change
This indicates
is
set
is
set
pane!
Red
auto-tune
procedure
from
to
to
LED
slowly
the
position
position
"0",
*F",
does
NOT
is
completed,
blinking
P.E.
timing
the
auto-tune
the
auto-tune
blink
or
to
rapid
value
will
take a minimum
will
take a minimum
the
unit
alarms
the
alarm
will
flashing.
the
microprocessor
Count
4-22
of
of
immediately,
sound
every
the
number
has
determined
three
45
check
3-4
seconds
of
(3)
hours
minutes
the
timimg
Red
LED
as
optimum
to
complete.
to
complete.
switch
and
the
flashes
for
position.
front
panel
between
maximum
Red
the

TIMING
PROCEDURE
18
oxygen
the
If
the
now
production.
manual
timing
function
-everytime
10.
If
the
timing
The
alarm
normally.
unit
is
turned
11.
The
timing
microprocessor
control
ing
by
to
SECTION A of
This
Red
mode.
switch
the
switch
should
The
switch
selecting
Record
was
normally.
unit
timimg
back
is
turned
was
stop
value
ON.
The
in
MUST
for
maximum
position
this
in
position
position
sounding
be
procedure.
CONCENTRATION
4
L/min.
LED
this
number.
timimg
back
is
stored
in
position
oxygen
"1"
to
LEVELS
count
"O"
corresponds
at
the
value
is
stored
ON.
"F"
at
the
start,
and
the
Red
in
the
microprocessor's
"0"
for
concentration.
"E".
Verification
CHART - (IRC5LX/SLXO2/6LXO2)
start,
tum
remove
LED
the
automatic
of
to
the
the
in
the
will
The
oxygen
same
numbers
unit
OFF
and
then
microprocessor's
the
cabinet
stop
memory
contro!
timing
production
and
flashing.
and
of
the
switch
can
MUST
02
95.6%
change
The
is
P.E.
Level
95.6%
95.6%
95.6%
on
the
BACK
memory
the
unit
will
recalled
valve
time
be
changed
be
performed
to
93%
to
93%
to
93%
to
91%
timing
on.
and
switch
The
is
recalled
position
now
function
everytime
by
the
to
in
unit
will
to
"0".
the
unit's
manual
accord-
|
O
5
L/min.
6
L/min.
95.6%
95.6%
to
to
87%
87%

PROCEDURE
19
LEAK
TEST
L
E
A
K
7
E
EN
UN
PROCEDURE
(FIGURES
PREVENT
İTO
DISCONNECT
ELECTRICAL
Test
Leak
Unplug
1.
Remove
2.
REMOVING
3.
Turn
the
4.
Let
concentrator
Apply
tings
leak
for
4-way
to
small
only.
test
pressure
Valve.
enter
19
1-3)
ELECTRİCAL
OUTLET
.
'
unit.
cabinet.
CABINET).
concentrator
amount
Avoid
4-way
into
all
Valve
leaks
DO
4-way
NOT
LEAK
-
CAUTION
TEST
SHOCK,
CONCENTRATOR
BEFORE
(Refer
run
CAUTION
of
other
around
Valve
to
on.
for
20
minutes.
leak
test
components.
body.
Sieve
allow
and
Carefully
leak
ALWAYS
SERVICING.
PROCEDURE
solution
leak
Bed
Hoses
test
system.
FROM
1
to
fit-
DO
NOT
test
at
solution
Sieve
4-way
to
65Τερς-),
-
Bed
Hoses
Valve
FIGURE 1 -
PE.
[BLX/5LX02/6LX02
4-WAY
Valve
Fittings
Hose
Bottom
of
(STEPS-a).
VALVE
Hose
Top
Beds
Fitting
Center
Valve
4-way
HOSES
Connections
Fittings
(STEP
of
5b).
on
Port
to
Sie
5.
With
“leak-test*
test
the
following:
a)
The
two
4-way
on
4-way
NOTE:
MAINTENANCE
exchanger
6.
7.
Refer
and
b)
Hose
connections
sieve
beds.
c)
P.E.
Valve
beds - IRC
d)
Hose
fittings
valves
e)
The
front
(FIGURE
Replace
etc.
Re-install
REMOVING
or
(2)
sieve
Valve
(FIGURE
any
and
Valve
to
PROCEDURE
for
filters.
hose
5LXARC5LXO2
at
and
rear
3).
tubing
cabinet.
CABINET).
equivalent
bed
hoses
hose
to
bottom
(FIGURE
maintenance
to
connections
product
2).
fittings
that
(Refer
1).
2 - PREVENTIVE
top
and
tank
on
appears
to
PROCEDURE
soapy
(FIGURE
water,
at
center
bottom
on
top
cap
and
heat
exchanger
cracked,
leak
the
top
port
of
heat
fittings
of
sieve
2).
check
worn,
of
of
NOTE:
1 -
All
Hoses
FIGURE 2 -
Heat
Exchanger
Hose
(STEP
NEW
FIGURE 3 -
SIEVE
Connections
5-d).
Heat
Product
(STEP
BED
HOSES
(Typical)
Exchanger
HEAT
to
Tank
Cap
5-d).
Hose
Connections
Bottom
Beds
AND
Fittings
(STEP
PRODUCT
does
NOT
have
EXCHANGER
to
of
Sieve
5-b).
TANK
fins.
HOSES
8.
See
SPECIFICATION
for
Concentration
are
observed,
ING
GUIDE
refer
in
this
section
Levels.
to
the
manual.
of
this
manual
!f
low
concentrations
TROUBLESHOOT-

ALARM
TEST
PROCEDURE
20
PROCEDURE
TO
PREVENT
ELECTRICAL
To
check
1.
POWER
mode
NOTE:
will
the
2.
LOW
a.
b.
Test
each
should
With
be
drained.
Battery
PRESSURE
Low
Failure
each
20 - ALARM
ELECTRICAL
OUTLET
alarm,
LOSS - With
sound
the
unit
If
power
Free™
product
in
the
tank
to
reach
following
circuit
BEFORE
CHECK
perform
the
the
audible
unplugged
failure
is
TEST-
pressure
the
set
AND
SHOCK,
SERVICING.
ALARMS
the
unit
running,
alarm
and
alarm
drained.
There
(pressure
point
pressure
manner:
SENSOR
CAUTION
ALWAYS
CAUTION
PERIODICALLY
following:
remove
immediately
inoperable
does
not
It
will
recharge
are
two
(2)
in
tank
within a prescribed
TEST
DISCONNECT
FOR
PROPER
the
line
cord
from
or
within
for a short
sound
when
seperate
failure
drops below a preset
period
with
unit
30
unit
modes
time
CONCENTRATOR
FUNCTION.
power
seconds.
is
Source,
of
time,
unplugged
plugged
for
Low
value,
limit,
or
The
power
the
Battery
and
in
and
Pressure.
typically 7 p.s.i).
Timeout
Free™
power
switched
Failure.
switch
FROM
loss
circuit
on.
alarm
on,
A
L
A
Β
M
T
同
S
T
Low
Pressure
cí.
With
unit
compressor
seconds.
c2.
With
unit
of
the
Shutdown
Time-Out
d.
NOTE:
Test
With
unit
unit
in
to
FIGURE 5 for
If
any
Test
(FIGURE
running,
relief
(Refer
product
to
running,
tank
Mode.)
(FIGURE
OFF,
and
turn
alarm
fails
1).
set
flow
valve
out
as
FIGURE 5 for
set
fiow
The
low
Replace
1)
disconnect
power
ON. The
Shutdown
to
perform
at
maximum
far
as
it
Shutdown
at
maximum
pressure
tubing
and
the
compressor
Time-Out
Mode.)
to
specification,
rating.
will
go
rating.
alarm
tywrap.
When
and
hold
Mode.)
Remove
should
activate
connector
Failure
the
main
it.
The
low
the
within
alarm
should
contact
valve
pressure
P.C.
board
30
seconds.
from
the
activate
Invacare
Compressor
[Disconnect
Harness(STEP
switches,
alarm
should
tubing
:
main
Technical
(tywrap)
(Refer
wiring
within
Molex
pull
the
activate
to
FIGURE 5 for
harness.
40
seconds.
Service.
Connector
from
2-b)].
stem
within
from
on
the
30
the top
Plug
(Refer
Relief
Valve
[Pull
Leak
FIGURE
Out
to
(STEP
1 -
Stem
Simulate
2-a)].
Compressor
LOW
PRESSURE
TEST

PROCEDURE
5-a.
A
Test
上
A
P.E.
R
5-b.
M
om
二
P.E.
Coil,
in
the
Valve
With
P.E.
20
Valve
following
Coil
Coil
Coil
connection
Test
the
unit
running
Alarm
(IRCSLXO2
or
P.C.
manner:
(FIGURE
and
should
after
Board
4)
activate
flow
Circuitry
set
within
S/N
97JXXXxX) - Alarm
has
failed.
at 5 L/min:,
10
remove
seconds.
one
(Refer
RE.
sequence
(1)
yellow
to
FIGURE 5 for
Valve
wire
Coil
occurs
from
ALARM
when
the
the
P.E.
Shutdown
TEST
P.E.
Valve
Valve.
Mode.)
The
ALARM
il
High
Pressure
Low
Pressure
Time-Out
(30
Secs.)
Low
02
All
alarms
ON
and
IRC5LXO2
3LX, 5LX,
(BEFORE
INTERNAL
have
Compressor
FIGURE 4 -
5LXO2
S/N
97JXXXX)
LED
RED
On
On On
On
on
.
Shutdown,
ONLY - RED
Panel
ALARM
GREEN
Off
On
off
LED
P.E.
Horn
Yellow
VALVE
COIL
MODES
8LX,
5LX,
ALARM
Three
(3)
Startup
Short
Long
Continuous
Continuous
Beeps
Beep,
Pause
|
.
Continuous
Wires
TEST
5LXO2/5LXO2T,
(AFTER
INTERNAL
at
S/N
LED
RED
0 0
0
1 1
1
1
6LXO2/6LXO2T
97JXXXX)
FLASHES
GREEN
No
Problems - System
ok
O
Main
Power
Low
Pressure:
Major
2
High
Pressure:
No
Switching
3
commer
Loss
Leak
.
ON.
FIGURE 5 -
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
*No
Shutdown,
All
alarms
5LX02/5LXO2T,
LED
ON.
ALARM
4-28
MODES
Unit
have
Compressor
6LX02/6LXO2T
1
1
2
2
2 4
2
3
continues
4
5
1
3
5
1
Pilot
Valve 1 Coil
Pilot
Valve 2 Coil
73%
Shutdown:
PE Valve
Eprom
Ram
Failure
Oxygen
to
run.
Shutdown,
ONLY - RED
Coil
Failure
Sensor
Hom
Panel
Low
02
Failure
ON
and

SIEVE
BED
PRESSURE
CHECK
PROCEDURE
21
PROCEDURE
PRESSURE
TO
PREVENT
ELECTRICAL
21 - SIEVE
CHECK
ELECTRICAL
OUTLET
BED
(FIGURES
BEFORE
PRESSURE
1, 2 &
SHOCK,
SERVICING.
3)
TAP-IN
CAUTION
ALWAYS
DISASSEMBLY
WARNING
Turn
power
1.
Remove
secure
cabinet
2.
Turn
3.
Loosen
product
4.
Pull
check
3LX
and
are
equipped
on the
from
restrictor.
the
the
the
from
unit
so
and
tank.
product
valve
5LX
left
top
rear.
Install
OFF
and
unplug
eight
cabinet
the
the
lower
tank
PVC
standard
with a restrictor
of
to
base
back
the
up
tubing.
CAUTION
the
DO
NOT
tap-in
(8)
5/8-inch
the
base
of
the
faces
adjustable
and
back
units
product
remove
kit
on the
unit.
screws
and
remove
concentrator.
you.
clamp
to
(without
assembly
tank
opposite
on
access
SensO2)
located
as
viewed
tubing
that
the
the
the
or
side.
KIT
INSTALLATION
DISCONNECT
INSTALLATION
1.
insert
the
"T"
fitting
Secure
2.
ing
3.
Attach
NEW
Insert
silicone
Secure
1/4-inch
“T”
fitting
the
1/4 x 2-inch
“T*
fitting
plug
into
tubing.
with a 1/4-inch
Pvc
Tubing
connection.
CONCENTRATOR
(FIGURE
into
clamps
and
secure
the
open
1/4"
*T*
AND
BED
2)
the
ends
of
to
each
end
silicone
with a 1/4-inch
end
of
the
」
clamp.
Clamp
Fitting
1/4 x 2-inch
Tubing
FROM
the
PVC
of
the
PVC
tubing
clamp.
1/4 x 2-inch
Silicone
tubing.
tub-
to
the
S
I
同
Vv
E
B
E
D
P
R
E
S
S
U
R
回
5.
Locate
right.
6.
Cut
in
half
Restrictor
SHOWN
Clarity
Adjus:
for
table
the
check
the PVC
valve
tubing
Clamp
FIGURE 1 -
:
i
and
PVC
tubing
below
the
Check
Cut
below
Valve
Tap-in
roduct
P
DISASSEMBLY
check
valve.
Valve
PVC
Tubing
Check
to
instail
Kit
to
your
Tank
PRESSURE
1.
Remove
1/4 x 2-inch
inch
clamp.
1/4"
Clamp
FIGURE 2 -
TESTING
plug
and
Connect
silicone
Plug
INSTALLATION
(FIGURE
tubing
and
pressure
3)
secure
gauge
to
with a 1/4-
the
Check
tight.
Turn
each
connection
the
concentrator
to
ON.
make
sure
they
are

RESPIRATORY
3
a
MM
2.5
ALLEN
MM
TOOLS
ALLEN
“T”
FT”
HANDLE
HANDLE
WRENCH
WRENCH
9”
9”
RW
AIR
#1
#2
GAUGE
PHILLIPS
PHILLIPS
STANDARD
LONG
NEEDLE
SLIP-JOINT
PUSH
SONDA
ROD
ASSORTED
TUBE
O2
LITER
OF
ANALYZER
METER
ACCETONE
NUMATICS
“LINT-FREE”
0-30
HEAD
HEAD
P.S.I.
SCREWDRIVER
SCREWDRIVER
SCREWDRIVER
NOSE
PLIERS
(WOOD
DOWEL,
WRENCHES
FLOURMATICS
OR
100%
CLEANER
SHOP
RAGS
PLIERS
1/2” X 6”)
“LOX
ALCOHOL
8”
JOINT
SEALANT
17.
18.
LEAK
DIGITAL
OPTIONAL
1.
2.
3.
4.
INVACARE
3/8”
NYLON
COMPRESSED
CAMEL
DETECTOR
VOLT
TOOLS
DRIVE
MALLET
HAIR
TECHNICAL
METER
SOCKET
AIR
BRUSH
TRAINING
SET
SOURCE
1-800-333-6900
X6697
ELYRIA,
OHIO

FIFTEEN-PIN
MOLEX
CONNECTOR
я
:0
e
FLOWMETER
IRC
501
PE
POWER
EXHAUST
SWITCH
FAN
LAMP
VALVE
(BLACK)
(BLACK)
-@
-©
(BLACK)
(BLACK)
>
ze
e
"0
-@
NEN
“6
POWER
FOUR
FOUR
IRC
POWER
HOUR
—
SOBNONAVN=
.
HOUR
=
POWER
=
EXHAUST
-=
.
COMPRESSOR
—
BROS
NOTE:
INVACARE,
SWITCH
WAY
WAY
501
VALVE
VALVE
PE
VALVE
SWITCH
METER
METER
CORD
FAN
COMPRESSOR
TECHNICAL
(WHITE)
(WHITE)
(WHITE)
(WHITE)
(WHITE)
(BLACK)
(WHITE)
(WHITE)
(WHITE)
(WHITE)
BACK
TO
TRAINING
OFF
ON
RELAY
N.O.
(ZETTLER
1-800-333-6900
RELAY
X6697
ON
P.C.
ELYRIA,
BOARD)
OHIO

8.
Remove
compressor
9.
Remove
10.
Remove
11.
Remove
(FIGURE
12.
Disconnect
hamess
13.
Cut
harness
14.
Remove
panel
15.
Remove
to
caster
16.
Pull
17.
Cut
18.
Disconnect
19.
Disconnect
tapping
(301/501).
NOTE:
Before
20.
Remove
fan
21.
Replace
ting
wires
control
intake
hose
3).
molex
(FIGURE
and
remove
to
sound
compressor
side
of
four
base
compressor
four
(4)
tywraps
wires
fan
screw
removing
must
be
changer
and
screws
(FIGURE
fan
by
discard
cooling
(FIGURES. 2 and
from
the
relay
and
ON/OFF
panel.
hose
from
from
exhaust
connectors
3).
tywrap
that
box
support
green
sound
box
(4)
screws
(FIGURE
assembly
from
from
spade
green
grounding
on
fan
clips
positioned
3).
removing
screws
fan
using
hour
meter,
switch.
resonator
side
from
secures
rod
grounding
(301/501)
securing
3).
out.
heat
exchanger
lugs
wire
assembly.
note
the
position.
properly
four
(4)
screws
and
clips
new
clips
3).
flowmeter
(FIGURE
of
compressor
compressor
compressor
(FIGURE
wire
from
(FIGURE
compressor
(FIGURE
on
fan.
by
removing
Discard
These
to
secure
(FIGURE
and
heat
.
located
3).
four
(4)
light,
3).
wiring
wiring
3).
contro!
3).
bracket
3).
self-
screw
clips
ex-
under
moun-
WARNING
Fan
must
be
properly
blows
down
on
located
will
22.
©
tapping
23.
Secure
tywrap
24,
Replace
25.
Reverse
ponents
26.
Plug
points.
NOTE:
27.
If
28.
If
properly
occur.
FIGURE 2 —-
Reconnect
Run
unit
not,
fan
screw
heat
mounts
compressor
the
of
the
in
unit
unit
runs
call
service.
green
provided
exchanger
preceeding
and
for
properly,
located
the
compressor.
(Figure
POSITIONING
grounding
(301/501).
using
(FİGURE
(FIGURE
steps
concentrator.
test
for
correct
at
least % hour.
replace
so
2)
or
damage
THE
wire
four
3).
3).
and
pressure/leaks
cover.
air
from
The
fan
must
to
the
NEW
by
using
(4)
tywraps
reassemble
the
FAN
#6
to
the
all
.
fan
be
unit
Self-
fan
com-
at
test
Form
No.
92-149
(2001352)
Rew.
11/92

MOBILAIRE”
し
ーー
キイ
ンー
=
COMPRESSOR
KIT
KIT
1.
2.
3.
4.
5.
6.
REPLACING
FROM
The
Mobilaire V (RC501,
1.
NOTE:
hoses,
2,
3.
4.
5.
6.
7.
NO.
INCLUDES
P/N
2001375 - One
P/N
2001370 - Two © Braided
P/N2000765-
tion
with
P/N
2001366 - One
P/N
1021149 - One
P/N
2001377 - One
HEAT
following
Turn
OFF
Oxygen
Removethe8x5/B-inch
housing
When
use
Remove
hose
exchanger
Remove
$07
assembly
Clean
was
removed
When
leave
compressor
piled
that
the
compressor
Apply
into
the
tighten.
insert
and
attach
Slide
and
position
assembly
2001378
THE
FOLLOWING:
One
(1)
Item
7.
THE
HOSE/90
EXCHANGER
instructions
501A
powerand
Concentrator.
assembly
elther a screwdriver
the
and
90
the
the
threads
applying
the
first
on
the
teflon
tefton
threaded
the
Spring
the
3-inch
fitting.
to
removing
two
(2)
degree
to
the
compressor
90
degree
and
discard.
in
with
isopropyl
teflon
two
(2)
housing
remainder
tape
assembly.
tape
and
holes
(Item
to
the
rear
braided
iton
the
OUTLET
(1)
Silicone
Stainless
(1)
Compressor
(1)
Plastic
Bag.
(1)
instruction
DEGREE
TO
COMPRESSOR
apply
to
and
IRC5010).
WARNING
UNPLUG
clamps
elbow
the
hose
the
truss
head
the
base
the
stainless
that
that
compressor
compressor
alcohol.
CAUTION
tape
to
threads
exposed.
of
the
doesn’t
install
the
of
the
compressor
3)
into
of
the
heat
sleeve
end
that
assembly.
or a 1/4-inch
assembly.
that
threads.
break
8.5-inch
(Item
Hose
8.5-inches
Sleeves
Steel
cord
secure
runs
the
Tefion tape
NEW
3-inches
Spring
Fitting
Sheet.
ELBOW
Mobifaire
fromthe
screws
that
steel
the
from
the
fitting
housing
new
straight
are
inserted
This
off
straight
assembly.
silicone
exchanger.
2)
onto
attaches
HOSE
long.
long.
used
in
(Straight).
THAT
ASSEMBLY
til
(IRC301)
Mobilaire
secure
clamps
socket
two
(2)
sections
rear
of
from
the
where
fitting,
into
will
be
is
to
ensure
and
enter
fitting
hose
the
silicone
to
the
compressor
conjunc-
RUNS
and
cabinet
from
the
wrench.
of
the
heat
compres-
the
fitting
the
ap-
the
(item
4)
Securely
(item
1)
hose
8.
Securely
9.
Loosen
remove
exchanger
10.
Slide
and
NOTE:
11.
Securely
12.
Attach
tighten
the
the
hose
to
the
3-inch
position
it on
This
wiil
tighten
cabinet
Installation
Assembly
the
stainless
stainless
the
protect
steel
end.
(This
in-line
braided
the
hose
the
the
stainless
assembly
clamp
hose
filter.)
sleeve
end
that
hoses
to
the
Instructions
steel
clarnps.
(at
the
in-line
runs
from
the
(item
2)
onto
attaches
during
steel
base
tothe
shipment.
camp.
assembly.
frontof
the
silicone
in-line
And
filter)
and
the
heat
hose
filter.
BEFORE
INSTALLATION
INSTALLATION
FIGURE
FROM
1 -
HEAT
REPLACING
EXCHANGER
THE
HOSE/90
TO
COMPRESSOR
DEGREE
ASSEMBLY
ELBOW
Form
No.
93-12
1301
Silver
(2001377)
Lake
Drive * Sanford,
innovation
Florida
in
Health
Care
=
32773 « Phone
(407)
321-5630
Printed
in
U.S.A.

IRC3LX
PILOT
KIT
VALVE
PART
/IRC5LX
POPPET
NO.
2003083
/IRC5LXO2
REPLACEMENT
Assembly,
Installation
and
Operating
Instructions
OZ
=
INVACARE
ue
.
SAFETY
The
following
safe
installation
ment
Kit:
DO
NOT
READING
INSTRUCTIONS.
UNDERSTAND
INSTRUCTIONS,
DEALER
(800-
832-4707)
INSTALLATION.
PERSONAL
DAMAGE.
TECHNICIANS.
INSTALLATION.
Check
damage
Canier/Invacare
Unplug
recommendations
INSTALL
AND
OR
INVACARE
INJURY
ONLY
all
parts
is
found,
concentrator
SUMMARY
are
of
the
Pilot
Valve
Poppet
WARNING
THIS
KIT
WITHOUT
UNDERSTANDING
IF
YOU
THE
WARNINGS,
CONTACT
BEFORE
IMPROPER
AUTHORIZED
SHOULD
for
for
further
ARE
YOUR
TECHNICAL
PERFORMING
USE
AND/OR
PERFORM
shipping
DO
NOT
instructions.
before
beginning.
UNABLE
CAUTIONS,
MAY
EQUIPMENT
AND
damage.
use.
made
for
Replace-
FIRST]
THESE
TO
AND
INVACARE
SERVICES
THIS
CAUSE
QUALIFIED
THIS
Contact
the
If
REMOVING
(FIGURE
1.
Unplug
2.
Remove
cabinet
cabinet
NOTE:
exposed
3.
Cabinet
When
foam
‘To
re-install
Assembly
THE
1)
WARNING
unit.
the
eight
assembly
straight
up.
required,
insulation.
cabinet,
CABINET
(8)
mounting
to
the
vacuum
reverse
Base
screws
base
assembly
inside
STEP
Assembly
Mounting
of
the
2.
Screws
that
secure
and
lift
the
cabinetand
(8
each)
Ensure
Tools
1.
2.
3.
This
that
installed.
Refer
to
Part
No.
Required:
One
(1)
One
Flat
One
Phillips
kit
includes
Slotted
Poppet
N
"O"
Ring
PILOT
all
items
the
IRC3LX
2002728
9/16-inch
Blade
Screwdriver
Head
the
VALVE
POPPET
are
properly
and
5LX
Rev.
Level
Boxed
End
Screwdriver
following:
DESCRIPTION
Slotted
"O"
Labels
Rings
Poppets
2X897A
KIT
and
securely
Service
2/97
Wrench
Manual
for
assistance.
L-96,
COMPONENTS
REMOVING
-
(FIGURE
NOTE:
Service
necessary.
1.
2.
3.
-
forward
Move
Panel
rest
FIGURE 2 -
FIGURE 1 -
2)
Refer
Remove
secure
Loosen
secure
Grasp
concentrator.
out
out
Sound
to
Manual
Control
and
front
Sound
for
the
two
the control
the
two
the
control
the
control
allowing
Control
let
it
of
Box
Bo:
REMOVING
REMOVING
THE
the
CONTROL
IRC
3LXARC5LX/IRC5LXO2
assistance
(2)
upper
panel.
.
(2)
lower
panel.
panel
control
Panel
panel
and
THE
THE
CABINET
in
this
mounting
mounting
gently
to
rest
Upper
Mounting
CONTROL
Form
PANEL
procedure
screws
screws
lift
in
front
Screws
(Remove)
Lower
(Loosen)
and
of
Mounting
Screws
PANEL
No.
97-108
that
that
the
if
-
」
pull
5-9

REMOVING/INSTALLING
VALVE
(FIGURES
Removing
Unplug
NOTE:
4-way
concentrator.
NOTE:
valve
while
1.
Hold
and
(1)
2.
Unscrewihe
fold
on
‘3.
Remove
‚
‘ет.
STOP!
FROM
bottom
not
reassembly
cause
4.
Set
assembly
DO
plastic
plastic
passage
5.
6.
POPPETS
concentrator
Both
pilot
valve
and
DO
NOT
coils.
Simply
performing
pilot
valve
tum
the
complete
while
leaving
stem.
pilot
DO
_THE
of
the
designed
damage
aside
NOT
use
manifold
manifold
could
Remove
3).
Discard
"O"
old
3
AND
WARNING
valves
siève
remove
lay
coils
this
installation.
stem
9/16-inch
tum.
pilotvalve
the
valve
poppet
CAUTION
NOT
REMOVE
COIL.
the
with
sharp
The
yoke
to
be
will
be
to
coil
the
CAUTION
tools
and/or
occur
ring
from
poppet
with
wires
opening.
and
AND
4)
can
bed
spade
with
locknut
stem
coil
and
removed
encountered
components.
FIGURE
"O"
before
be
accessed
hoses
with
the
with
from
washer
the
yoke
still
fo
plastic
manifold
"O"
are
connectors
spade
connectors
flat
blade
counterclockwise
assembly
yoke
and
inside
THE
between
bottom
and
and
intact.
remove
Damage
manifold
3).
opening
ring
(FIGURE
PILOT
RINGS
beginning.
while
intact
on
from
aside
screwdriver
trom
the
mani-
locknutintact
the
pilot
valve
COIL
pilot
"O"
YOKE
the
of
coil
difficulty
that
could
valve
ring
from
to
the
airflow
(FIGURE
3).
the
the
pilot
one
is
in
stem
*0*
Ring
FIGURE 3 -
Installing
1.
Install
NEW
housing
DO
NOT
installing
the
rubber
occur.
p
Install
NEW
valve
stem
(FIGURE
‚3.
Install pilot
coil
with
ing.
4.
Use
the
stem
clockwise
25-inch
5.
Install
NEW
6.
Position
60°
angle
valve)
to
tensioned
7.
Use
the
stem
in
8.
Tighten
until
snug
NOT
OVERTIGHTEN.
inch
lbs. + 3-inch
REMOVING/INSTALLING
"O"
ring into
{FIGURE
overtighten
it
into
plastic
"O"
ring
slotted
with
tapered
4).
valve
stem
yoke
and
flat
blade
until
Ibs. + 5-inch
label
pilot
vaive
to
the
left
ensure
flatblade
place.
locknut
spade
after
reinstallation.
clockwise
to
secure
the
opening
3).
CAUTION
pilot
valve
manifold.
and/or
poppet
locknut
screwdriver and
onto
coil
screwdriver
into
end
and
NEW
intact
snug.
Ibs.).
pilot
with
(as
viewed
connectors
with
the
stem
the
facing
(Reference:
valve
yoke
and
the
and
(Reference:
lbs.).
CAUTION
Manifold
Opening
Air
Flow
Passage
"O"
in
the
stem
Damage
manifold
bottom
slotted
into
tighten
coil
at
from
hold
9/16-inch
coil
of
to
the
poppet
manifold
pilot
Torque
yoke.
an
approximate
the
are not
the
with
Torque
RING
manifold
when
to
may
the
pilot
bottom
with
open-
valve
to
front
of
pulled
or
pilot
valve
wrench
yoke.
DO
to
20-
-
Form
No.
97-108
DO
it
onto
plastic
9.
Repeat
valve.
NOT
overlighten
pilot
manifold
the
valve
may
FIGURE
locknut
stem.
occur.
3.
PROCEDURE
when
Damage
installing
to
the
for
other
pilot

HomEFiLL“
The
Invacare’
system
to
The
safely
six-liter
DandE.
The
greater
also
costly
components
equipment
QUICK
FEATURES/BENEHTS:
will
fill
their
own
Venture
compresses
concentrator
ability
independence
will
benefit
service
REFERENCE
revolutionize
to
flexibility
COMPLETE
Venture™
high
HomeFill
fill
from
calls.
of a concentrator
HomeFill™
ambulatory
pressure
is a multi-stage
oxygen
their
from a specially-adapted
into
high
own
cylinders
and
freedom.
the
elimination
The
HomeFill
inventory
and
«
Fillshigh
concentrator
+
Fill
receive
+
Eliminates
«
Ambulatory
cylinders
+
Patients can
lifestyle
+
Fills
*
Typical
cylinders
pressure
and a compressor
cylinders
M6,
HOME
complete
oxygen
pump
gives
Home
of
system
management.
pressure
while
oxygen
expensive
patients can
at
home
maintain
C,
Dand E size
M6
cylinder
OXYGEN SYSTEM
home
oxygen
by
allowing
from a concentrator.
which
cylinders
in
ambulatory
care
oxygen
time-consuming
consists
for
oxygen
cylinders
patient
from
continues
the
concentrator
service
fill
their
cylinders
fill
time
patients
simply
and
Invacare
sizes
M6,
patients
providers
and
of
the
separate
maximum.
froma
to
calls
their
own
independent
to
2,000
of
one
(1)
hour
M9,
-
PSI
size
cylinders
are
controls
s
that
havea
for
designed
CGA870
of
ease
can
HomeFill
«
style
post
valve.
ambulatory
by
operation
fill
È
M9(C),
M6,
patients.
pe
DandE
Connectionsand
MODEL
10H100
ΙΒΟΘΙΧΟΖΗ
HOMEFILL
ELECTRICAL
POWER
RATED
OXYGEN
INLET
OXYGEN
OUTLET
SELECTION
OXYGEN
REQUIREMENTS
CONSUMPTION
CURRENT
INPUT
PRESSURE
OUTPUT
PRESSURE
WIDTH
HEIGHT
DEPTH
WEIGHT
HOMEFILL
year
components
G
warranty,
full
OXYGEN
and
INVACARE
Venture
Invacare.
Sp
Fi
specifications
COMPRESSOR
INPUT
RATING
RATING
COMPRESSOR
year
3
control
panel
。
一
GUIDE
HomeFill
IRCÉLXO:
6
liter
equipped
and
parts
components
Compressor
tor
con:
Invacare 6 Pier
information
(I0H100)
120
VAC+10%
(32
VAC/102VAO),
Ce
SPECIHCATIONS
350W
304
0-3LPM
6-13.5
PSI
0-3LPM
2,000
PSI
(+
50
PSI)
27"
16"
23.5"
1209.
WARRANTY:
Corporation
ia,
Ohio
oninternal
Way
warranty
labor
Invacare
USA
Qnelnecare
44036-4028
(800)
333-6900
-Foruse
amam
15%
with
en
60
Hz
wear
www.
Canada
ορ
LR53T9
(800)
to
invacare.com
пой,
Hay
Canada
668-5324
*
Unique
the
HomeFill
connection
attaches
compressor
、
specially
The
*
IRC6LXO2H
high
the
patient
Invacare,
Corporation
Patent
Pending.
Specifications
equipped
concentrator
concentrations
and
Venture
ο
are
for
filling
and
HomeFill
subject
of
to
the
concentrator
Invacare
oxygen
change
model
consistently
both
portable
are
trademarks
without
provides
directly
to
cylinders.
of
notification.
to
Invacare