Make Electrical Connections4........................
START−UP4........................................
SERVICE5.........................................
MAINTENANCE7−9.................................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory−authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
the current editions of the National Electrical Code (NEC)
NFPA70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety−alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
the signal words DANGER, WARNING, and CAUTION. These
words are used with the safety−alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
WARNING
.
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
pollution.
Remove and recycle all components or materials (i.e. oil,
refrigerant, etc.) before unit final disposal.
CAUTION
428 01 9702 01 02/25/15
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split system and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
Check AccuRater Metering Device − Heating Mode
The correct AccuRater (bypass type) refrigerant control is required
for system capacity optimization. An AccuRater device with
field−replaceable piston is supplied with the outdoor unit (see Fig.
2).
Do not interchange components between the AccuRater device
types. Matching of outdoor unit with indoor unit may require field
replacement of piston. Replace piston, if required, before
connecting refrigerant lines. See Fig. 2. Piston replacement
instructions are included in the indoor unit installation instructions.
After system installation is complete, see the Refrigerant Charging
section in this document to check and/or adjust refrigerant charge.
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury
or equipment damage.
R−410A refrigerant systems operate at higher pressures than
standard R−22 systems. Do not use R−22 service equipment
or components on R−410A refrigerant equipment.
PERSONAL INJURY AND EQUIPMENT DAMAGE
HAZARD
Failure to follow this caution may result in personal injury
and / or equipment damage.
DO NOT operate the unit without a filter or with grille
removed.
WARNING
!
CAUTION
COMPLETE PRE−INSTALLATION CHECKS
Unpack Unit
Move the unit to final location. Remove unit from carton, being
careful not to damage service valves and grilles.
Inspect Shipment
File a claim with the shipping company if shipment is damaged or
incomplete. Check the unit nameplates to ensure units match job
requirements.
Consider System Requirements
Consult local building codes and NEC for special installation
requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant
piping, and servicing unit. Locate unit so that condenser airflow is
unrestricted on both sides.
Unit may be mounted on a level pad directly on base legs or
mounted on raised pads at support points.
Matching the Heat Pump to an Indoor Unit
The NH4H4 heat pump units can be matched to corresponding
indoor units. The NH4H4 unit can be matched with under−ceiling
and residential fan coils and evaporator coils. Refer to separate
indoor unit literature for more information.
Expansion Device − Ducted System Cooling Mode
A hard shutoff, thermostatic expansion valve (TXV) is required at
the indoor section of the system for proper operation of these
products. If the indoor section of the system is not equipped with a
hard shutoff TXV, refer to Spec Sheet for the correct TXV kit to be
installed. Follow the instructions in the kit for proper installation.
*
*NOTE: Piston Orientation - Install tapered end
of piston in the direction of the outdoor equipment
for proper heating operation
A07407b
Fig. 2 - AccuRater (bypass type)
Metering Device Components
RIG AND MOUNT UNIT
Mounting on Ground
Mount unit on a solid, level concrete pad. Position unit so water or
ice from roof does not fall directly onto unit. Use field−provided
snow stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.
If conditions or local codes require unit be fastened to a pad, 6
field−supplied tie−down bolts should be used and fastened through
slots provided in unit mounting feet.
Mounting on Roof
Mount unit on a level platform or frame at least 6 in. (152.4 mm)
above roof surface. Isolate unit and tubing from structure.
Clearance Requirements
Single Unit Applications: With coil facing wall: Allow 6” (152.4
mm) minimum clearance on coil side and coil end and 20” (504.0
mm) minimum clearance on fan side. Allow 24” (609.6 mm)
minimum clearance on compressor end for service.
With fan facing wall:
fan side and coil end and 20” (504.0 mm) minimum clearance on
coil side. Allow 24” (609.6 mm) minimum clearance on
compressor end for service when units are stacked or there is less
than 40” (1016 mm) of clearance above the unit. If there is 40”
(1016 mm) clearance above unit and the top panel is accessible for
removal allow 8” (203.2 mm) minimum clearance on compressor
end for service.
Multi−unit Applications:
clearance between fan and coil sides of multiple units. Arrange
units so discharge of one does not enter inlet of another. Allow 24”
(609.6 mm) minimum clearance on compressor end when units are
stacked or there is less than 40” (1016 mm) of clearance above the
unit. If there is 40” (1016 mm) clearance above unit and the top
panel is accessible for removal allow 8” (203.2 mm) minimum
clearance on compressor end for service.
When two units are installed end to end with the coil ends facing
each other allow 12” (304.8 mm) minimum clearance between
units.
IMPORTANT: When installing multiple units, ensure the
discharge air from one unit is not drawn into another unit. When
installing single or multiple units in an alcove, roof well, or
partially enclosed area, ensure there is adequate ventilation to
prevent recirculation of discharge air.
Allow 8” (203.2 mm) minimum clearance on
Allow 24” (609.6 mm) minimum
2428 01 9702 01
Specifications subject to change without notice.
Operating Ambient
Minimum outdoor operating ambient in cooling mode is 55_F
(13_C), maximum 125_F (52_C).
Rigging
!
PERSONAL INJURY AND/OR EQUIPMENT
DAMAGE HAZARD
Failure to follow this caution may result in personal injury
and/or equipment damage.
Be sure unit panels are securely in place prior to rigging.
Keep the unit upright and lift unit using a sling. Use cardboard or
padding under the sling, and spreader bars to prevent sling damage
to the unit. See Fig. 3. Install the unit so that the coil does not face
into prevailing winds. If this is not possible and constant winds
above 25 mph are expected, use accessory wind baffle. See
installation instructions provided with the accessory kit.
NOTE: Accessory wind baffles should be used on all units with
accessory low ambient temperature control.
Field−fabricated snow or ice stands may be used to raise unit when
operation will be required during winter months. Units may also be
wall mounted using the accessory wall mounting kit.
CAUTION
Long Line Application Guide for required accessories. If either
refrigerant tubing or indoor coil is exposed to the atmosphere, the
system must be evacuated following good refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding unnecessary
turns and bends. Suspend refrigerant tubes so they do not damage
insulation on vapor tube and do not transmit vibration to structure.
Also, when passing refrigerant tubes through a wall, seal the
opening so that vibration is not transmitted to structure. Leave
some slack in refrigerant tubes between structure and outdoor unit
to absorb vibration. Refer to separate indoor unit installation
instructions for additional information.
Filter Drier
Refer to Fig. 4 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from
step 1.
4. Connect and braze liquid refrigerant tube to the filter drier.
A07396
Fig. 3 - Lifting Unit with Sling
COMPLETE REFRIGERANT PIPING
CONNECTIONS
Outdoor units may be connected to indoor units using
field−supplied tubing of refrigerant grade and condition. See
Specification Sheet for correct line sizes. Do not use less than 10 ft
(3.05 m) of interconnecting tubing.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4
mm) vertical rise to the valve connections on the outdoor
unit. If more than the recommended length is buried,
refrigerant may migrate to cooler, buried section during
extended periods of system shutdown. This causes refrigerant
slugging and could possibly damage the compressor at
start−up.
When more than 80 ft (24.4 m) of interconnecting tubing and more
than 20 ft (6.1 m) of vertical lift is used, consult the residential
CAUTION
A05227
Fig. 4 - Filter Drier Components
The filter drier must be replaced whenever the refrigeration system
is exposed to the atmosphere.
Only use factory specified liquid−line filter driers with rated
working pressures less than 600 psig.
NOTE: Do not install a suction−line filter drier in liquid line.
Make Piping Sweat Connections
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
Remove plastic caps from liquid and suction service valves. Use
refrigerant grade tubing. Service valves are closed from the factory
and are ready for brazing. After wrapping the service valve with a
wet cloth, the tubing set can be brazed to the service valve using
either silver bearing or non−silver bearing brazing material.
Consult local code requirements. Refrigerant tubing and the indoor
coil are now ready for leak testing.
NOTE: Unit is shipped with R−410A refrigerant factory charge
indicated on nameplate.
Pass nitrogen or other inert gas through piping while brazing to
prevent formation of copper oxide.
428 01 9702 013
Specifications subject to change without notice.
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.