Intermatic T106R User Manual

MODEL: T106R
24 HOUR DIAL TIME SWITCH
IN TYPE 3R RAINPROOF ENCLOSURE SUITABLE FOR POOL EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL
ONE NORMALLYOPEN- ONE NORMALLY CLOSED CONTACTS
MAY BE WIRED AS SINGLE POLE DOUBLE THROW.
40 AMP. RESISTIVE INDUCTIVE, TUNGSTEN OR 1000 VAPILOT DUTY 120-277 VOLT AC; 2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
WIRING INSTRUCTIONS: To wire switch follow diagram above. To wire
as SINGLE POLE NORMALLY CLOSED, move motor lead from terminal 3 to 1, and connect LINE to 1, LOAD to 2. To wire as SINGLE POLE DOUBLE THROW, install jumper (the same gauge as LINE wire) between terminals 2 and 3 and connect LINE to 2, LOADS to 1 and 4. NOTE: Line 2 if present is uninterrupted. Use COPPER wire only. For gauge selection and wire connection, see details below. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK- DIAL (the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
•TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER
below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10916
TIME POINTER
CLOCK DIAL
OFF TRIPPER
MANUAL LEVER
ON TRIPPER
CLOCK
MOTOR
GROUND
A
1
2
3
4
FROM
208V, 240V
OR
277V
SUPPLY
TO LOAD
GRD
LINE
TYPICAL WIRING SINGLE POLE NORMALLY OPEN SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX. LOAD
(AMP)
MIN. INSUL­ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V. 240 V. 208 V.
240 V.
14 12 10
8
15 20 30 40
60
60
60
75
1/2
1 2
-
2
2 1/2
3 5
N/A
N/A
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
WIRING DIAGRAM
LR3730
158TS10916 10/31/03 10:06 AM Page 1