MODEL: T104R |
LR3730 |
24 HR. DIAL TIME SWITCH (DPST)
IN TYPE 3R RAINPROOF ENCLOSURE, SUITABLE FOR POOL EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL.
40 AMP. RESISTIVE EACH POLE 120-480 VOLT AC;
40 AMP. INDUCTIVE OR TUNGSTEN OR 1000 VA PILOT DUTY EACH POLE 120V-277V AC; 2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
TIME
DIAL
TIME POINTER
OFF TRIPPER
MANUAL
LEVER
ON TRIPPER
WIRING
DIAGRAM
240 V 2 WIRE AND GROUND
|
A |
1 |
2 |
3 |
4 |
|
GR |
|
|
|
|
240V |
LINE 1 |
|
|
|
|
SUPPLY LINE 2 |
|
|
|
GROUND |
|
|
|
|
|
|
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A” AND 1 AND SUPPLY NEUTRAL TO TERMINAL “A”.
CLOCK
MOTOR
TO LOAD(S)
WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM |
MAX. |
MIN. |
75°C INSULATION MAX. MOTOR |
PRESSURE PLATE |
||||
COPPER |
LOAD |
INSUL- |
|
|
LOAD (HP) |
|
||
WIRE SIZE |
(AMP) |
ATION |
|
SINGLE PHASE |
3 PHASE |
TERMINAL SCREW |
||
(AWG) |
|
TEMP (°C) |
|
120 V. |
240 V. |
208 V. |
240 V. |
|
|
|
|
|
|
||||
14 |
15 |
60 |
|
1/2 |
2 |
|
|
MAKE SURE WIRE |
12 |
20 |
60 |
|
1 |
2 1/2 |
N/A |
N/A |
INSULATION CLEARS |
10 |
30 |
60 |
|
2 |
3 |
|
|
PRESSURE PLATE |
8 |
40 |
75 |
|
- |
5 |
|
|
|
PROGRAMMING INSTRUCTIONS
1.TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2.TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCKDIAL (the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
•TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
•IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
158TS10919 SPRING GROVE, ILLINOIS 60081-9698