Intermatic T106M Owner's Manual

MODEL: T106M
24 HR. DIAL TIME SWITCH (DPST)
ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS
40 AMP. RESISTIVE, INDUCTIVE TUNGSTEN OR 1000V.A. PILOT DUTY PER POLE 120-277V. AC; 2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240V. AC
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
CLOCK DIAL
TIME POINTER
OFF
TRIPPER MANUAL LEVER
connect LINE to 1, LOAD to 2. To wire as SINGLE POLE DOUBLE THROW, install jumper (the same gauge as line wire) between 2 and 3 and connect
LINE to 2, LOADS to 1 and 4. NOTE: Line 2 if present is uninterrupted. Use COPPER wire only. for gauge selection and wire connection, see details below.
Use 3/16 or larger screwdriver, tighten terminal screws firmly (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
PROGRAMMING INSTRUCTIONS
•TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
•TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (time now, when switch is put into operation) to TIME POINTER. DO NOT MOVE
POINTER. OPERATING INSTRUCTIONS
•TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
•INCASEOF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
158TS13233
CLOCK MOTOR: 208-277V. 60 HZ.
ON TRIPPER
FIGURE 1
MAX.
MIN.
LOAD
INSUL-
(AMP)
ATION
TEMP (°C)
15
60
20
60
30
60
40
75
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
FROM
208V 240V
OR
277V
SUPPLY
TYPICAL WIRING SINGLE POLE NORMALLY OPEN SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
75° INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120V 240V
1/2
1 2
2 1/2
2
3 5
240V 240V
N/A
GRD
N
LINE
3 PHASE
N/A
CLOCK MOTOR
A
WIRING DIAGRAM
4321
GROUND
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
TO LOAD
Loading...