MODEL: T106M
24 HR. DIAL TIME SWITCH (DPST)
ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS
40 AMP. RESISTIVE, INDUCTIVE TUNGSTEN
OR 1000V.A. PILOT DUTY PER POLE 120-277V. AC;
2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240V. AC
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
CLOCK
DIAL
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
WIRING INSTRUCTIONS: To wire switch follow diagram above. To wire as SINGLE
POLE NORMALLY CLOSED, move clock motor lead from terminal 3 to 1, and
connect LINE to 1, LOAD to 2. To wire as SINGLE POLE DOUBLE THROW,
install jumper (the same gauge as line wire) between 2 and 3 and connect
LINE to 2, LOADS to 1 and 4. NOTE: Line 2 if present is uninterrupted. Use
COPPER wire only. for gauge selection and wire connection, see details below.
Use 3/16 or larger screwdriver, tighten terminal screws firmly (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14
12
10
8
PROGRAMMING INSTRUCTIONS
•TO SET “ON” AND “OFF” TIMES: Hold trippers
against edge of CLOCK-DIAL, pointing to time (AM or
PM) when ON and OFF operations are desired,
tighten tripper screws firmly. For additional tripper pairs
on CLOCK-DIAL order 156T1978A.
•TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward.
Turn in either direction and align the exact time-of-day
on the CLOCK-DIAL (time now, when switch is put into
operation) to TIME POINTER. DO NOT MOVE
POINTER.
OPERATING INSTRUCTIONS
•TO OPERATE SWITCH MANUALLY: Move MANUAL
LEVER below CLOCK-DIAL left or right as indicated by
arrows. This will not effect next operation.
•INCASEOF POWER FAILURE, reset CLOCK-DIAL to
proper time-of-day. See programming instructions.
158TS13233
CLOCK MOTOR: 208-277V. 60 HZ.
ON
TRIPPER
FIGURE 1
MAX.
MIN.
LOAD
INSUL-
(AMP)
ATION
TEMP (°C)
15
60
20
60
30
60
40
75
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
FROM
208V
240V
OR
277V
SUPPLY
TYPICAL WIRING SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
75° INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120V 240V
1/2
1
2
2 1/2
2
3
5
240V 240V
N/A
GRD
N
LINE
3 PHASE
N/A
CLOCK
MOTOR
A
WIRING DIAGRAM
4321
GROUND
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
TO
LOAD