Intermatic T104R3 User Manual

MODEL: T104R3
24 HR. DIAL TIME SWITCH (DPST)
IN TYPE 3R RAINPROOF ENCLOSURE SUITABLE FOR POOL EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL
LR3730
40 AMP. RESISTIVE, PER POLE 120-480V. AC; 40 AMP. INDUCTIVE OR TUNGSTEN OR 1000V.A. PILOT DUTY PER POLE 120-277 V. AC; 2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240 V. AC
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME DIAL
TIME POINTER
OFF TRIPPER
MANUAL LEVER
WIRING
ON TRIPPER
DIAGRAM 240 V. 2 WIRE AND GROUND
240V.
SUPPLY
277/480 VOLT- CONNECT MOTOR LEADS TO TERMINALS “A” AND 1 AND SUPPLY NEUTRAL TO TERMINAL “A”.
GR LINE 1 LINE 2
A
1 32 4
CLOCK
MOTOR
TO LOAD
WIRING INSTRUCTIONS: To wire switch follow diagram
above. Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MAX.
MINIMUM
LOAD
COPPER
(AMP)
WIRE SIZE
(AWG)
TEMP(°C)
14
15
12
20
10
30
8
40
PROGRAMMING INSTRUCTIONS
1.
TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF opera-
tions are desired, tighten tripper screws firmly. See caution below. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2.
TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer. DO NOT
MOVE THE POINTER.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation. IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-
of-day. See programming instructions.
158TS13085
75°C INSULATION MAX. MOTOR
MIN.
INSUL-
ATION
60 60 60 75
INTERMATIC INCORPORATED
LOAD (HP)
SINGLE PHASE
120 V. 240 V. 208 V.
1/2
2 1/2
1 2
-
SPRING GROVE, ILLINOIS 60081-9698
3 PHASE
N/A
240 V.
N/A
2
3 5
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE