Intermatic T104-50 Owner's Manual

MODEL: T104-50
24 HOUR DIAL TIME SWITCH
DOUBLE POLE SINGLE THROW (DPST)
40 AMP. RESISTIVE EACH POLE 120-480 VOLT AC; 40 AMP.INDUCTIVE OR TUNGSTEN OR 1000 VA PILOT DUTY EACH POLE 120V-277V AC; 2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
CLOCK MOTOR: 208-277 VOLTS - 50 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
TIME DIAL
TIME POINTER
OFF TRIPPER
MANUAL LEVER
ON TRIPPER
WIRING INSTRUCTIONS: To wire switch follow diagram above.
MAX.
MINIMUM
LOAD
COPPER
(AMP)
WIRE SIZE
(AWG)
TEMP(°C)
14
15
12
20
10
30
8
40
MIN.
INSUL-
ATION
SINGLE PHASE
120 V. 240 V. 208 V.
60
1/2
60
1
60
2
75
-
75°C INSULATION MAX. MOTOR
LOAD (HP)
2
2 1/2
3 5
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK- DIAL (the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
• TOOPERATESWITCHMANUALLY:Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This
will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
154--01037
SPRING GROVE, ILLINOIS 60081-9698
WIRING DIAGRAM
240 V 2 WIRE AND GROUND
A 1
GR
LINE 1
240V
LINE 2
SUPPLY
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A” AND 1 AND SUPPLY NEUTRAL TO TERMINAL “A”.
3 PHASE
240 V.
N/A
N/A
2 3 4
GROUND
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
CLOCK
MOTOR
TO LOAD(S)