Intermatic T104 User Manual

MODEL: T104
24 HOUR DIAL TIME SWITCH
DOUBLE POLE SINGLE THROW (DPST)
40 AMP. RESISTIVE EACH POLE 120-480 VOLT AC; 40 AMP.INDUCTIVE OR TUNGSTEN OR 1000 VA PILOT DUTY EACH POLE 120V-277V AC; 2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applica­tions. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULAT OR BEFORE TURNING ON ELECTRICITY.
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
OPERATING INSTRUCTIONS
•TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER
below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10948
TIME POINTER
TIME DIAL
OFF TRIPPER
MANUAL LEVER
ON TRIPPER
CLOCK
MOTOR
GROUND
A
1
2
3
4
GR
240V
SUPPLY
TO LOAD(S)
LINE 1 LINE 2
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A” AND 1 AND SUPPLY NEUTRAL TO TERMINAL “A”.
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX. LOAD
(AMP)
MIN. INSUL­ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V. 240 V. 208 V.
240 V.
14 12 10
8
15 20 30 40
60
60
60
75
1/2
1 2
-
2
2 1/2
3 5
N/A
N/A
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
WIRING DIAGRAM
240 V 2 WIRE AND GROUND
LR3730