Intermatic T103M Owner's Manual

MODEL: T103M
24 HOUR DIAL TIME SWITCH MECHANISM
DOUBLE POLE SINGLE THROW (DPST)
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY EACH POLE 120/208.240 VOLT AC; 2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
CLOCK MOTOR: 110-125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME DIAL
TIME POINTER
OFF TRIPPER
MANUAL LEVER
WIRING INSTRUCTIONS: To wire switch follow diagram above.
Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applica­tions. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
MAX. LOAD
(AMP)
15 20 30 40
MIN.
INSUL-
ATION
SINGLE PHASE 3 PHASE
TEMP (°C)
120 V. 240 V. 208 V.
60
1/2 60 60 75
1 2
-
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK- DIAL (the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This
will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions
INTERMATIC INCORPORATED
154--01005
SPRING GROVE, ILLINOIS 60081-9698
TYPICAL WIRING DIAGRAM
120/240 ON TRIPPER
75°C INSULATION MAX. MOTOR
LOAD (HP)
2
2 1/2
3 5
VOLT
3 WIRE
SUPPLY
N/A
NEUT.
LINE 1
LINE 2
GR.
240 V.
N/A
CLOCK MOTOR
1
A
2
3
4
TO LOADS
GROUND
PRESSURE PLATE
TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE