Intermatic T102P Owner's Manual

MODEL: T102P
24 HOUR DIAL TIME SWITCH (SPST)
IN TYPE 3R DUSTPROOF RAINPROOF ENCLOSURE, SUITABLE FOR POOL EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL.
LR3730
40 AMP. RESISTIVE, INDUCTIVE TUNGSTEN OR 1000V.A. PILOT DUTY 120-277 VOLT AC; 2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240V. AC
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
CLOCK
DIAL TIME POINTER
OFF
TRIPPER
MANUAL LEVER
WIRING INSTRUCTIONS: To wire switch follow diagram above.
Use solid or strand COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
CLOCK MOTOR: 208-277V. 60 HZ.
WIRING DIAGRAM
208
THRU
277V
SUPPLY
FOR 208 OR 240 V SUPPLY CONNECT LINE 1 TO TERMINAL “A”
75° INSULATION MAX. MOTOR
LOAD (HP)
2 1/2
2
3 5
3 PHASE
240V 240V
N/A
SINGLE PHASE
120V 240V
1/2
1 2
GR.
LINE 1
LINE 2
N/A
MAX. LOAD (AMP)
15 20 30 40
ON TRIPPER
FIGURE 1
MIN. INSUL­ATION
TEMP (°C)
60 60 60 75
CLOCK MOTOR
2
1
A
TO
GROUND
LOADS
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
PROGRAMMING INSTRUCTIONS
•TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
•TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (time now, when switch is put into operation) to TIME POINTER. DO NOT MOVE
POINTER.
OPERATING INSTRUCTIONS
•TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
•INCASEOFPOWERFAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.