Intermatic T102 Owner's Manual

MODEL: T102
LR3730
24 HOUR DIAL TIME SWITCH
SINGLE POLE SINGLE THROW (SPST)
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY 120-277 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
(TO ORDER CLOCK MOTOR REPLACEMENT, SPECIFY PART No. WG--ON MOTOR COVER)
TIME DIAL
TIME POINTER
OFF TRIPPER
MANUAL LEVER
ON TRIPPER
Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applica­tions. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MAX.
MINIMUM
LOAD
COPPER
(AMP)
WIRE SIZE
(AWG)
TEMP(°C)
14
15
12
20
10
30
8
40
MIN.
INSUL-
ATION
SINGLE PHASE
120 V. 240 V. 208 V.
60
1/2
60
1
60
2
75
-
75°C INSULATION MAX. MOTOR
LOAD (HP)
2
2 1/2
3 5
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
• INCASEOFPOWERFAILURE, reset CLOCK-DIAL to prop- er time-of-day. See programming instructions.
INTERMATIC INCORPORATED
158TS10944
SPRING GROVE, ILLINOIS 60081-9698
WIRING DIAGRAM
GRD.
208
THRU
LINE 1
277V
SUPPLY
LINE 2
FOR 208 OR 277 V SUPPLY. CONNECT LINE 1 TO TERMINAL “A”.
3 PHASE
240 V.
N/A
N/A
1
A
CLOCK MOTOR
2
TO
GROUND
LOAD
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE