Intermatic T101M Owner's Manual

MODEL: T101M
24 HOUR DIAL TIME SWITCH MECHANISM
SINGLE POLE SINGLE THROW (SPST)
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY 120/208/240 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC
CLOCK MOTOR: 110-125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME DIAL
TIME POINTER
OFF TRIPPER
MANUAL LEVER
ON TRIPPER
WIRING INSTRUCTIONS: To wire switch follow diagram above.
Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applica­tions.To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MAX.
MINIMUM
LOAD
COPPER
(AMP)
WIRE SIZE
(AWG)
TEMP(°C)
14
15
12
20
10
30
8
40
MIN.
INSUL-
ATION
SINGLE PHASE
120 V. 240 V. 208 V.
60
1/2
60
1
60
2
75
-
75°C INSULATION MAX. MOTOR
LOAD (HP)
2
2 1/2
3 5
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK- DIAL (the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
•
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER
below CLOCK-DIAL left or right as indicated by arrows. This
will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
158TS10771
SPRING GROVE, ILLINOIS 60081-9698
N/A
WIRING DIAGRAM
SUPPLY
3 PHASE
240 V.
N/A
120V
GRD.
NEUT.
LINE
CLOCK MOTOR
A
2
1
TO
GROUND
LOAD
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE