Intermatic FD Series Data Sheet

Project:
Location:
FD Series
Auto-Off Timers
FD Series
The FD Series Decorator Auto-Off Timers are designed to replace any standard wall switch - single or multi-gang. This series of energy-efcient mechanical timers do not require electricity to operate. In addition, they automatically limit the ON times for fans, lighting, motors, heaters, and other energy consuming loads.
Features
• Hold feature enables user to override the automatic shut-off function
• Supplied time dial plates are designed to t either toggle (FF) or decorator style (FD) switch plates
• Single or multi-gang with no eld modications required
• Time saving up front terminal connection with teeter-type terminals
• Press-on knob design ensures quick and easy installation
• CFL Compatible
Not for use with sunlamps, saunas, or loads that could cause personal injury if timed incorrectly.
Ratings
Resistive: 20 Amp, 125 VAC, 50/60 Hz
10 Amp, 250 VAC, 50/60 Hz 10 Amp, 277 VAC, 50/60 Hz
Tungsten: 7 Amp, 125 VAC
Product Type:
Contact/Phone:
Model #:
Motor: 1 HP, 120 VAC, 50/60 Hz
2 HP, 240 VAC, 50/60 Hz
Operating Temperature: -40˚F to 104˚F (-40˚C to 40˚C)
Style: Can be used with decorator and toggle
type switch plates
Dimensions: 2.79" H x 1.6" W x 1.19" D
FD30MWC
Energy Controls
FD Series
White Models Ivory Models Almond Models Time Cycle Switch Hold
FD5MW FD5M - 5 Minutes SPST No
FD15MWC FD15MC FD15MAC 15 Minutes SPST No
FD15MHW FD15MH - 15 Minutes SPST Yes
FD30MWC FD30MC FD30MAC 30 Minutes SPST No
FD30MHW FD30MH - 30 Minutes SPST Yes
FD60MWC FD60MC FD60MAC 60 Minutes SPST No
FD60MHW FD60MH - 60 Minutes SPST Yes
FD2HW FD2H - 2 Hours SPST No
FD4HW FD4H - 4 Hours SPST No
FD6HW FD6H - 6 Hours SPST No
FD6HHW FD6HH - 6 Hours SPST Ye s
FD12HWC FD12HC - 12 Hours SPST No
FD12HHW FD12HH - 12 Hours SPST Yes
FD32HW FD32H - 2 Hours SPDT No
FD34HW FD34H - 4 Hours SPDT No
- FD36H - 6 Hours SPDT No
- FD415M - 15 Minutes DPST No
FD430MW FD430M - 30 Minutes DPST No
FD460MW FD460M - 60 Minutes DPST No
FD46HW FD46H - 6 Hours DPST No
Specification
The time switch shall be of the appropriate dimensions and design to provide direct replacement of a standard wall switch in single or multi-gang 2 ½" deep junction boxes. The timer shall include a molded _________ (Almond)(Ivory) (White) knob and plate with a spiral time scale to provide easy selection of the time setting. The molded plate (time dial) and knob shall be the standard industry accepted______________ (Almond)(Ivory)(White) and shall provide for installation using a standard toggle or standard decorator wall switch plate without modications. The knob shall be a press on type requiring no screws or other hardware to secure. The threaded hole for plate mounting shall be extruded to provide a minimum of .085" thread engagement. Switch Rating (Each Pole for DPST Models). The timer shall have a UL listed rating of:
• 1 HP at 125 VAC, 50/60 Hz
• 2 HP at 250 VAC, 50/60 Hz
• 20 Amp, 120 VAC, 50/60 Hz
• 10 Amp, 250 VAC, 50/60 Hz
• 10 Amp, 277 VAC, 50/60 Hz
• 7 Amp, 125 VAC The timer eld wiring connections shall be secured by means of a teeter-type terminal screw to provide secure connections for appropriate wire sizes. The timer shall be _____________ (SPST)(DPST)(SPDT). The timer __________ (Shall)(Shall Not) have a Hold feature and shall have a time cycle of _____________ (See Time Cycles Listed). The timer shall be Intermatic model _______________ (See Model Numbers Listed).
Energy Controls
Diagrams
STRIP
GAUGE
2.79"
1.60"
[7.09cm]
[4.06cm]
Example for SPST motor load control.
Example for SPST large motor load control using a 3-pole contactor or motor starter.
Example for control of low voltage set-back set-up thermostats using SPDT timer.
LOAD
LOAD
CR1
CR1
24 VAC
Hot
Neutral
Load 1Line 1
Load 1Line 1
Load 1
Jumper From Line 2 To Line 1
Load 2
Line 1
Line 2
Hot
Neutral
Hot
Neutral
Load Supply
55º
72º
Example for controlling two loads simultaneously by using DPST contacts.
Example for breaking both sides of a 240 volt load using DPST contacts.
240 VAC
120 VAC
120 VAC
Line 1
Load 1
Load 2
Line 2
Hot
Neutral
Line 1
Load 1
Load 2
Line 2
LOAD
LOAD
FD Series
Jumper From
Hot
Optional
Line 2 To Line 1
Line 1
Load 2
Load 1
Line 2
Example for timed selection of low or high speed motor with optional timer to limit operation time regardless of speed selected.
Hot
Line 1
Jumper From Line 2 To Line 1
Line 2
Load 2
Load 1
Jumper From Line 2 To Line 1
Line 2
Load 2
Line 1
Example for 3-way load control providing timed override from more than one location.
Hot
Line 2
No Connections Required For Line 1 and Load 1
Load 2
Solder Pot
Example for reverse action control. The load is switched off when timer is operated for a limited time then switches back on.
Low
High
Neutral
LOAD
Neutral
Neutral
Energy Controls
FD Series
Notes
Energy Controls
Loading...