This document may not be copied in whole or in part, or otherwise reproduced except as specifically
permitted under US copyright law, without the prior written consent from UTC Fire & Security.
Document number/revision: 1054312D.
DisclaimerThe information in this document is subject to change without notice. UTC Fire & Security accepts
Trademarks and patentsTrade names used in this document may be trademarks or registered trademarks of the manufac-
Software license
agreement
Intended useUse this product only for the purpose for which it was designed; refer to the data sheet and user
FCC complianceThis equipment has been tested and found to comply with the limits for a Class A digital device,
no responsibility for inaccuracies or omissions and specifically disclaims any liabilities, losses, or
risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document.
This publication may contain examples of screen captures and reports used in daily operations.
Examples may include fictitious names of individuals and companies. Any similarity to names and
addresses of actual businesses or persons is entirely coincidental.
turers or vendors of the respective products.
UTC Fire & Security software supplied with UTC Fire & Security products is proprietary and
furnished under license and can be used or copied only in accordance with the license terms.
THE ENCLOSED PROGRAM IS FURNISHED SUBJECT TO THE TERMS AND CONDITIONS OF
THIS AGREEMENT. RETENTION OF THE PROGRAM FOR MORE THAN 30 DAYS, OPENING
OF THE SEALED WRAPPER, IF ANY, SURROUNDING THE PROGRAM, OR USE OF THE
PROGRAM IN ANY MANNER WILL BE CONSIDERED ACCEPTANCE OF THE AGREEMENT
TERMS. IF THESE TERMS ARE NOT ACCEPTABLE, RETURN THE UNUSED PROGRAM AND
ANY ACCOMPANYING DOCUMENTATION TO GE FOR A FULL REFUND OF THE LICENSE FEE
PAID. (FOR INFORMATION REGARDING THE RETURN OF PROGRAMS ENCODED OR
INCORPORATED WITHIN EQUIPMENT, CONTACT THE NEAREST UTC FIRE & SECURITY
SALES OFFICE.)
documentation. For the latest product information, contact your UTC Fire & Security sales representative or visit us online at www.UTCFireandSecurity.com.
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications.
You are cautioned that any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
Remote Input Module
WARNING
The Remote Input Module (RIM) provides the interface between the ACU Controller and additional alarm
sensors. The RIM consists of the electronic circuit board and the screw terminal connector board connected
together by a ribbon cable. The RIM can be installed in its own tampered enclosure.
Note: The RIM with backplate only is Product Number RIM16-E00.
The RIM with key locked enclosure is Product Number RIM16-E1L.
•When attaching a RIM to a Summit system, please refer to the ACU3 Family Installation and
Operation Guide for the list of input and output assignments.
•Surface Mount (SMT) refers to a method of construction that allows the various module components to
be mounted directly on the surface of the board rather than using the traditional thru-hole method.
•Each RIM provides 16 supervised inputs, 3 unsupervised inputs and 2 relay outputs (wet or dry contact
relays Single Pole Double Throw).
•The Remote Input Module connects to the expansion port on the ACU in the upper addresses (4-7)
only. Each expansion port can support four readers in addition to remote modules (RIM, RRM).
•Each of the 16 alarm inputs is supervised as 6-states, Alarm, Secure, Open, Shorted, Ground and
Circuit Fault.
1
Auxiliary Power Supply for RIM
In many cases, the ACU can supply the power for the RIM. The exception is when using an ACURS with a
plug-in transformer for its power supply. When the ACU can not supply power an auxiliary power supply must
be used. When using an auxiliary power supply, make sure the 0V terminal on all remote modules and the
ACU share a common ground.
The Remote Input Module requires 24 VDC (±15%).
Do not use the relays on the ACU Controller, Remote Reader Electronics (RRE), Remote Input Module
(RIM) or Remote Relay Module (RRM) to switch any voltage above 30 volts. Failure to heed this
WARNING can cause death, personal injury or damage to unit(s).
RS-485 Information
RS-485 is a differential voltage communication circuit. The Impedance is 120 ohms. End-of-line terminators
are required on both ends of the communications path (See Figure 1). Multi-drop configurations are allowed
with a maximum length of 4,000 feet (1,219 meters).
Stubs can be dropped, off the RS-485 cable, but the length of any stub cannot be longer than 10 feet (3
meters). Stubs can connect to ACU Controllers or remote modules (One-Stage reader, RRE, RIM or RRM).
Stubs must not be terminated. We strongly recommend that star configurations be avoided. All remote
modules have built-in terminators that are switch selectable.
Remote Input Module
+24
0V
TT+
RR+
+24
0V
TT+
RR+
+24
0V
TT+
RR+
+24
0V
TT+
RR+
ACUX
Readers
Port
RRE
or
Reader
RRE
or
Reader
RRM
or
RIM
+24
0V
TT+
RR+
RRE
or
Reader
Figure 1. RS-485 Communication Wiring for RRM and RIM as last device
Figure 3. PIN Locations on the Terminal Board of the SMT RIM
Remote Input Module
4
User Manual
Terminal Block Output Connections
Table 1. Wiring the Output Connections on the SMT Remote Input Module
Pin
TB
Table 2. Wiring the Communication Connections on the SMT Remote Input Module
TB
111+24V+ 24 Volts In
112G N D0 V
113R-To ACU Expansion Port TX -
114R+To ACU Expansion Port TX+
115T-To ACU Expansion Port RX-
No.
91K2 N.O.Aux Relay 2 Normally Open
92K2 N.C.Aux Relay 2 Normally Closed
93K2 C.Aux Relay 2 Common
94K1 N.O.Aux Relay 1 Normally Open
95K1 N.C.Aux Relay 1 Normally Closed
96K1 C.Aux Relay 1 Common
Pin
No.
Term.
Strip
Term.
StripDescription
Description
116T+To ACU Expansion Port RX+
Table 3. RIM Wiring Connections for TB1 - TB3
5
TB
Pin
No.
Ter m.
Strip
Description
11IN1Zone Input 1
12IN1Zone Input 1
13IN2Zone Input 2
14IN2Zone Input 2
21IN3Zone Input 3
22IN3Zone Input 3
23IN4Zone Input 4
24IN4Zone Input 4
31IN5Zone Input 5
32IN5Zone Input 5
33IN6Zone Input 6
34IN6Zone Input 6
Table 4. Connections for TB4, TB7 and TB8 on RIM
TB
Pin
No.
Ter m.
Strip
Description
71IN12Zone Input 12
72IN12Zone Input 12
73IN11Zone Input 11
74IN11Zone Input 11
81IN10Zone Input 10
82IN10Zone Input 10
83IN9Zone Input 9
84IN9Zone Input 9
41IN8Zone Input 8
42IN8Zone Input 8
43IN7Zone Input 7
44IN7Zone Input 7
Remote Input Module
6
User Manual
Table 5. Connections for TB5, TB6, and TB10 on RIM
Pin
TB
101IN17Unsupervised Zone Input 17
102GNDGround
103IN18Unsupervised Zone Input 18
104GNDGround
105IN19Unsupervised Zone Input 19
106GNDGround
No.
61IN13Zone Input 13
62IN13Zone Input 13
63IN14Zone Input 14
64IN14Zone Input 14
51IN15Zone Input 15
52IN15Zone Input 15
53IN16Zone Input 16
54IN16Zone Input 16
Ter m.
Strip
Description
Input State Standard Resistance Ranges for Troubleshooting
When correctly wired, the input terminals should test with the default resistance listed in the table below. The
end-of-line (EOL) resistor for the SECURE state is 1,000 Ohms as selected using the DIP switch settings. The
End-Of-Line resistors must be located within the alarm zone sensor enclosure or the alarm zone circuit will be
considered unsupervised.
When 1000 Ohms terminators are used, the sensors can be wired for either normally closed contacts or
normally open contacts. In either case, the SECURE or inactive state should test at 1,000 ohms. A pair of 1 K
ohm resistors, at the sensor end of each alarm circuit, ensures that the line resistance is typically 1 K ohm when
the alarm is in the secure state.
Table 6. Input Zone Status By Resistance
Zone Input
State
Secure10001000
Active2000500
Open> 50,000> 50,000
Short< 50< 50
Sensor Circuit in Ohms
Normally Closed
Sensor Circuit in Ohms
Normally Open
7
Figure 4. Zone Sensor 1000 Ohms Resistors
Remote Input Module
8
User Manual
Setting the DIP Switches on the SMT RIM
SW1 Switch Settings
Note: The use of SW1-7 to provide the 200/10K termination option is available with firmware version 3.07 or later.
Table 7. RIM DIP Switch Settings
Switch NumberDescription
SW1-1SW1-2Module address:
OffOffAddr 4
OnOffAddr 5
OffOnAddr 6
OnOnAddr 7
SW1-4Alarm Latching:
OnEnables latching – Associated LEDs for
zones 1—16 will latch on alarm. Zone 18
will reset cleared zone LEDs.
OffDisables latching
SW1-3SW1-5SW1-6Zone Termination:
OffOffOff0.5K alarm, 1K safe, 2K alarm
OnOffOff75 ohms alarm, 150 safe, 300 alarm
OffOnOff1K safe, 3K alarm, 5—7K ground
OnOnOff1K safe, 3K alarm
OffOffOn6.8K safe, 24K alarm
OnOffOn1.5K safe, 3K alarm
OffOnOn10K safe, 5K alarm
OnOnOn5K safe, 10K alarm
SW1-3SW1-5SW1-6SW1-7Zone Termination
OffOffOffOn200 ohms safe, 10K alarm
Switch 8 is a spare
SW2 Switch Settings for RS485 Termination
The 2-position DIP switch SW2 located on the RIM is used to terminate the RS485 communication when
required.
Table 8. SMT RIM Switch SW2 for RS485 Termination
Switch SW2Description
SW2-1 ONTermination of Receive Pair
SW2-2 ONTermination of Transmit Pair
SW3 and SW4 Switch Settings for Input Zone Termination
The 8-position DIP switch (SW3 and SW4) located on the RIM are used to terminate the unused RIM Inputs.
The switch in ON position will terminate the zone with 1K resister.
Table 9. SMT RIM Switch SW3 and SW4 for Input Termination
SwitchDescription
9
SW3-1Zone 0 Termination
SW3-2Zone 1 Termination
SW3-3Zone 2 Termination
SW3-4Zone 3 Termination
SW3-5Zone 4 Termination
SW3-6Zone 5 Termination
SW3-7Zone 6 Termination
SW3-8Zone 7 Termination
SwitchDescription
SW4-1Zone 8 Termination
SW4-2Zone 9 Termination
SW4-3Zone 10 Termination
SW4-4Zone 11 Termination
SW4-5Zone 12 Termination
SW4-6Zone 13 Termination
SW4-7Zone 14 Termination
SW4-8Zone 15 Termination
Remote Input Module
10
User Manual
Setting the Jumpers on the SMT RIM
Jumper W1 and W2 Settings
Jumpers W1 and W2 located on the RIM () are used to select if 24 VDC will be supplied by relays K1 and K2
on the RIM.
Table 10. SMT RIM Jumpers W1 and W2
JumperDescription
W1Jump pins 2 & 3 Relay K1 Dry
W1Jump pins 1 & 2 Relay K1 energized with +24 V
W2Jump pins 2 & 3 Relay K2 Dry
W2Jump pins 1 & 2 Relay K2 energized with +24 V
Normal LED status on the SMT RIM
The LEDs on the Remote Input Module will light as follows:
Table 11. SMT RIM Normal LED Status
LEDDescription
AOn when board is Communicating to ACU
BHeart 1 Hz Flash - CPU is functioning correctly
CFlashing when offline
TxFlashing when transmitting data to ACU
RxFlashing when receiving data from ACU
ONON when Power is applied to board
D57ON when relay 2 is energized
D52ON when relay 1 is energized
Status of 16 Alarm pointsGreen - Secure
LEDs 1 - 16
Red - Active
Yellow - Trouble
Alarm Numbers on RIM
RIM Alarm Numbers for the Host PC
Table 12. RIM Alarm Numbers for the Host PC
11
Zone
Input
IN1128144160176192208224240
IN2129145161177193209225241
IN3130146162178194210226242
IN4131147163179195211227243
IN5132148164180196212228244
IN6133149165181197213229245
IN7134150166182198214230246
IN8135151167183199215231247
IN9136152168184200216232248
IN10137153169185201217233249
IN11138154170186202218234250
IN12139155171187203219235251
IN13140156172188204220236252
IN14141157173189205221237253
Expansion Port 1 Address:Expansion port 2 Address:
45674567
IN15142158174190206222238254
IN16143159175191207223239255
IN1796100104108112116120124
IN1897101105109113117121125
IN1998102106110114118122126
Offline99103107111115119123127
Remote Input Module
12
User Manual
Relay Numbers on RIM
Table 13. RIM Relay Numbers for the Host PC
Relay
Number
K13234363840424446
K23335373941434547
Expansion port 1 Address:Expansion port 2 Address:
45674567
RIM Field Wiring Test
After making all connections and prior to connecting the ribbon cable to the RIM, the following tests should be
made. Connections should already be completed at the ACU and external power supply if used.
Table 14. RIM Test Points and Voltages
FromToVol tag eTolerance
GND+24V+ 24 VDC3.5 VDC
T+T-+ 4.0 VDC*0.5 VDC
R+ R-+ 2.5 VDC *0.5 VDC
+24VBldg. Gnd.24 VDC3.5 VDC
GNDBldg. Gnd.0 VDC0.5 VDC
T+Bldg. Gnd.Less than 6.0 VDCN/A
T-Bldg. Gnd.Less than 6.0 VDCN/A
R+ Bldg. Gnd.Less than 6.0 VDCN/A
R-Bldg. Gnd.Less than 6.0 VDCN/A
* After the first expansion module is connected, these voltages will modulate due to data on the line.
Most Digital Volt Meters should indicate about 2.0 VDC.
Power-Up Self Test on the RIM
The Remote Input Module should always be tested after installation. The indicators for the RIM are the red
LEDs located on the component board. See Figure 2 for the locations of these LEDs.
Note: The test will complete in less than 10 seconds after power-up.
Table 15. Power-up LED Indicators on the RIM
LEDDescription
AON at power-up
BON RAM test successful
CON PROM tested and initialized
ONON when Power is applied
LEDs 1 - 16All Green, then All Yellow, then All Red
13
Remote Input Module
14
User Manual
Contacting technical support
For assistance with this product, refer to this document and any other documentation provided. If you still have
questions, you may contact technical support during normal business hours (Monday through Friday,
excluding holidays, between 8 a.m. and 7 p.m. Eastern Time).
Web site: www.utcfireandsecurity.com
Phone: 1 888 437 3287
Fax: 561 998 6224
Email: rs-bctsupport@fs.utc.com
Note: Be ready at the equipment before calling for technical support.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.