Interlogix SuperBus 2000 2X16 Installation Instructions Manual

Page 1
SuperBus 2000 2X16 LCD Alphanumeric Touchpad Installation Instructions
Product summary
The SuperBus® 2000 2x16 LCD (liquid crystal display) Alphanumeric Touchpad lets you control all programming and operation of a compatible security system (see “Specifications” on page 4). The 2-line, 16-character display provides messag
The touchpad includes police, fire, and auxiliary panic buttons that can be activated anytime.
A built in speaker provides alarm sounds, status sounds, and button-press beeps.
es to indicate the current system status.
Installation guidelines
Mount the touchpad in an environmentally controlled area 32 to 120°F (0 to 49°C).
When mounting the touchpad, allow at least 4¼ inches on the left side for the Quick Guide slide-out card.
• For Concord be connected to the panel. For Concord systems (all software versions) up to 16 bus devices can be connected to the panel.
For Concord systems with software versions 1.0–1.6, each bus device must have a different unit number setting to operate correctly. The touchpad unit number is factory set to 001. For Concord panels with software version 2.0 or later and Concord Express panels, bus unit numbers are assigned automatically.
Table 1 below describes the power used by the touchpad.
Express systems, up to 4 bus devices can
Table 2: Maximum touchpad wire lengths Wire Gauge (Unshielded
or Shielded)
18 750 feet 22 300 feet
Maximum wire length between touchpad and panel
Tools and equipment needed
4-conductor, 22- or 18-gauge wire
• Screwdriver
• Drill/bits
#6 screws and anchors (included)
Panhead screws for a gang box installation
Saw or utility knife for cutting wallboard
Installing the mounting plate
The touchpad can be installed on a wall or electrical gang box, either single- or dual-gang.
1. Separate the mounting plate from the touchpad by pressing the tab at the bottom and sliding the mounting plate down (see Figure 1 below).
Figure 1: Separating touchpad from mounting plate
Lift and Pull
Mounting Plate
Tab
Tab
Table 1: Touchpad power usage Current (mA) Condition
90 Maximum alarm current 57 Typical operation 12 Standby current (no AC power)
Do not exceed the maximum available power when using panel power for bus devices and hardwire detectors (see the specific panel Installation Instructions for maximum available power).
Table 2 below describes the maximum wire lengths allo
wed between the touchpad and panel.
P/N 466-17
12 • REV D • January 2011 1
2. Place the mounting plate on the wall and mark the four mounting holes (see Figure 2 on page 2). Be sure to leave a 4¼-inc Guide slide-out card.
3. Insert anchors at the marked locations where studs are not present.
h clearance on the left side to allow for the Quick
Page 2
T
2: Mounting holes
Figure
Wire Access Area
Wall Mounting Holes (4)
Dual-Gang Mounting Holes (4)
Single-Gang Mounting Holes (4)
Wiring
Wiring consists of connecting the touchpad to the panel terminals.
1. Disconnect the panel transformer and backup battery.
2. Run a 4-conductor, 18- to 22-gauge wire from the panel to the touchpad location.
3. Splice the 4-conductor cable wires to the red, black, green, and white wires located on the back of the touchpad.
4. Connect the touchpad wiring to the panel terminals as shown in Figure 4 below.
4. Looking at the back side of the mounting plate, turn it so the tab is on the left and position the Quick Guide slide­out card into the slots on back of the mounting plate (see A in Figure 3 below). Make sure the card is unfolded and the “Z
ones” section is facing you.
5. Slide the card in the direction of the arrow in Figure 3 below (A) until it snaps into the position shown in (B).
Figure 3: Inserting the Quick Guide Slide-Out card
Swing card over in
Direction of Arrow
Until Card Snaps into Place
A
B
6. Position the mounting plate in its normal mounting position (tab at the bottom) and fold the card toward you at all three scored lines. The “Zones” section should be facing you and the folds should create a tab to slide the card in and out.
7. Align the mounting plate wall-mount holes with the wall anchors and secure the back-plate to the wall using the screws provided.
OR If installing the back-plate on an electrical gang box,
line up the appropriate gang box holes on the mounting plate with the gang box holes and secure the back-plate to the gang box using the screws provided.
Caution: Do not over tighten screws or the back plate may
bend and prevent the touchpad from mounting properly.
8. For wall-mounted installations, cut a hole in the wall in the wire access area of the mounting plate to pull your cable through for wiring.
Figure 4: Wiring touchpad to panel terminals
+12V
A
BUS
B
6
NEERG/A SUB
GND/BLACK
BUS B/WHITE
BACK OF
OUCHPAD
GND
3 4 5
+12V/RED
Attaching the Touchpad to the Mounting Plate
Align the four slots on the touchpad with the four tabs on the mounting plate and slide the keypad down until you hear the latch on the mounting plate click into place.
Power Up
After making all wiring connections from the touchpad to the panel, you are ready to power up the panel. Upon power up, the panel scans the bus for connected devices and automatically learns the unit number of each bus device.
Note: If you plan on installing systems with no alphanumeric touchpads, it is recommended that you keep an alphanumeric touchpad with you, specifically for programming. This touchpad can be quickly connected and disconnected from the header pins on the lower portion of the panel circuit board, as described later in this document.
To power up the panel and verify bus communication:
1. Verify that all wiring between the panel and touchpad is correct.
Note: If the touchpad does not display the date and time, see “Troubleshooting” on page 4.
Connect the panel battery and plug in the panel
2. transformer. Alphanumeric touchpads should show a date and time display.
Connecting the touchpad for system programming only
or installations that don’t include an alphanumeric touchpad
F as a permanent part of the system, you can connect one for
2
SuperBus 2000 2X16 LCD Alphanumeric Touchpad Installation Instructions
Page 3
system programming to the Programming Touchpad Header on the panel.
To do this you must first connect a Programming Touchpad Cable (60-791) to the touchpad wires (see Programming Touchpad Cable Installation Instructions—466-1604, included with the cable). Then, use the appropriate procedure for connecting the touchpad.
To connect a programming touchpad to a Concord
press or Concord panel with software version 2.0 or
Ex later:
1. With the panel powered up, connect the cable to the Programming Touchpad Header (see Figure 5 below).
Figure 5: Connecting a programming touchpad
Programming Touchpad Cable (60-791)
2. Activate the service touchpad by pressing 8 + CODE + 0 +
2.
3. Enter program mode by pressing 8 + installer/dealer CODE + 0 + 0 and program the panel using the panel documentation.
4. When programming is completed, simply disconnect the programming touchpad.
To connect a programming touchpad to a Concord panel
ith software versions 1.0–1.6:
w
1. Disconnect AC and backup battery power.
2. Connect the cable plug to the panel Programming Touchpad Header pins (see Figure 5 above).
3.
Reconnect the AC and backup battery power. The touchpad briefly displays ***********, SCANNING BUS DEVICES, then shows a time and date display.
Note: If the touchpad does not respond as described in step 3, there may be a bus conflict. To correct this, change the touchpad unit number as described in the section “Changing the Touchpad Unit Number.”
Removing the programming touchpad from Concord p
anels with software versions 1.0–1.6:
To prevent a trouble condition, you must delete the programming touchpad unit number from Concord panel memory before disconnecting it.
1. After programming is completed, return to the ACCESSORY MODULES menu, then press É. The display should read BUS DEVICES.
2. Press É. The display shows the lowest unit number and its device name.
3. Press A or B until the display shows the programming touchpad unit number.
4. Press D to delete the device and its unit number from panel memory. The display shows:
UNIT - TYPE 14-NONE
5. Exit program mode and disconnect the programming cable from the panel header.
Testing
Caution: Contact the Central Monitoring Station before
activating any alarms, to avoid dispatching local police and fire departments.
Test the touchpad by arming/disarming the system, activating the touchpad panics, bypassing sensors, and by turning chime and lights on/off to verify correct operation. Refer to the panel documentation for system operating instructions.
Adjusting Display
The touchpad display can be adjusted for easier viewing to help compensate for lighting conditions in the touchpad location. The brightness adjustment lightens or darkens the background. The contrast adjustment lightens or darkens the text.
To adjust display brightness:
Enter user programming mode by pressing 9 + user,
1. partition, or system master CODE. The display shows SYSTEM MENU, then TIME AND DATE (Concord panels with software versions 1.0–1.6 display USER CODES.)
2. Press B until the display shows OPTIONS, then press É. The display shows DOWNLOADING ON/OFF (current setting).
3. Press B until the display shows TOUCHPAD BRIGHTNESS 2 (default setting).
4. Enter a setting from 0 (darkest background) to 3 (brightest background), then press É.
5. The display flashes the entered selection, then stops after pressing É and displays the new setting and brightness level.
6. Exit user programming mode by entering: Ç + 0 + 0 + É for Concord panels with software
versions 2.0 or later or Ç + 7 + É for Concord panels with software versions 1.0–
1.6.
To adjust display contrast:
Enter configuration mode by pressing the D and 6 buttons
1. together for at least two seconds. The display shows DA nnn.
SuperBus 2000
2X16 LCD Alphanumeric Touchpad Installation Instructions 3
Page 4
2. Press and release the 1 and 2 buttons together repeatedly, until the desired contrast level is displayed.
3. Press Ç and the display briefly shows DONE, then shows the time and date.
Troubleshooting
Table 3 below describes what to do if the touchpad does not operate correctly.
Table 3: Troubleshooting Problem Action/Solution
Touchpad doesn’t power up (no display and no beeps when buttons are pressed).
Touchpad display appears blank, but beeps sound when buttons are pressed.
Touchpad display shows a flashing *, indicating a trouble condition and system doesn’t respond to commands from touchpad.
Check for correct wiring connections at touchpad and panel terminals. Make sure panel battery is connected correctly and that the panel transformer is plugged in. Make sure panel transformer is not plugged into an electrical outlet controlled by a switch. Relocate transformer to an unswitched outlet location, if necessary.
Check the touchpad display contrast setting. It may be set to 0 (no display).
Check for correct bus wiring connections (green and white wires) at touchpad and panel terminals. Make sure touchpad unit number is set to a different number than all other bus devices. If necessary, change the touchpad unit number (see procedure on this page). (Concord panels with software versions 1.0-
1.6 only.)
4. Press Ç to exit from the configuration mode. Note: If the new touchpad unit number was previously
learned by the panel, communication between the touchpad and the panel begins immediately. However, if the new touchpad unit number has never been learned by the panel, continue with step five.
5. Force the panel to scan bus devices as follows:
For systems where this is the only installed touchpad,
remove panel AC and battery power, then re-apply power.
For systems with more than one touchpad, go to another
system touchpad and enter 8 + installer/dealer CODE + 0 + 1. The display shows SCANNING BUS DEVICES, then a time and date display.
The touchpad and all other bus devices should operate correctly and any bus failures should be cleared.
Note: If the panel still indicates a bus failure the panel may have previously learned a unit number that is no longer used by any bus device. See the specific panel Installation Instructions for more information on deleting unused unit numbers.
Specifications
Compatibility Concord, Concord Express, Concord Ultra
Panels
Power requirements 12 VDC nominal (see Table 1 on page 1 for
more information) Operating temperature 32 to 120°F (0 to 49°C) Humidity 70% relative, non-condensing Dimensions 5.0 x 4.5 x 0.75 in. (L x W x D) Installation Wall mount
Changing the Touchpad Unit Number (Concord Panels with Software Version 1.0-1.6 Only)
Use the following guidelines when changing device unit numbers to avoid communication conflicts between bus devices and the panel:
All bus devices with DIP switches (LED Touchpads, ESMs, HIMs, etc.) must be set to the desired unit number before applying power and entering program mode.
Whenever possible, assign touchpad unit numbers before all other panel programming.
To change the touchpad unit number:
At the touchpad, press and hold the D and 6 buttons
1. together for at least 2 seconds. The display should show DA n, where n is the touchpad current unit number (000 -
015).
Note: At this time, the touchpad is in configuration mode and no longer communicating to the panel. The system may immediately indicate a bus failure. Ignore the failure and continue with the procedure. The bus failure will clear after successfully changing the touchpad unit number.
2. Press É. The display shows ENTER _.
3. Enter the desired three digit unit number (000 - 015), then press É. The display shows DA n, where n is the new touchpad unit number.
Note: Do not use unit number 15 in Concord RF systems.
Regulatory information
Manufacturer UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943, USA
UL listings UL 985 Household Fire Warning System Units
UL 1023 Household Burglar-Alarm System Units UL1610 Central Station Burglar-Alarm Units (Commercial Burglary) Note: See specific panel Installation Instructions for complete UL installation requirements for the system you are installing
Contact information
For contact information, see www.utcfireandsecurity.com or www.interlogix.com.
For technical support, toll-free: 888.437.3287 in the US including Alaska, Hawaii, Puerto Rico, and Canada. Outside the tool-free area, contact your dealer.
Copyright © 2011 Interlogix, a UTC Fire & Security Company. All rights reserved.
4 SuperBus 2000 2X16 LCD Alphanumeric Touchpad Installation Instructions
Loading...