Interlogix 5845-ID Installation

5845-ID
g
Description
The 5845-ID (Figure 1) is an addressable glassbreak device that interfaces with the PinPoint® system. The system provides flexible and reliable two-way communication between the device and the controller. This glassbreak device is based on ShatterPro® II technology and uses patented Pattern Recognition Technology.
Figure 1. Exploded view
Sensor module
Base
Range
The unit is omni-directional, providing 360° coverage. Coverage is measured from the unit to the most distant point on the glass (Figure 2).
Minimum 3.3 feet (1 m) from the glass Maximum 20 feet (6 m) for plate, tempered,
laminated, and wired glass; 12 feet (3.7 m) for armor-plated glass
Figure 2. Maximum range
20 ft. (6 m)
20 ft. (6 m)
installation instructions
For best detection, avoid installing in:
• Rooms with lined, insulating, or sound deadening drapes
• Rooms with closed, inside wooden window shutters
• Corners of a room
• Glass airlocks and glass vestibule areas
For best false alarm immunity:
• Install the unit as a perimeter zone which is armed only when the perimeter doors and windows are armed. Avoid installing the unit as a 24-hour zone, where the unit will be armed even when the room is in use.
• Do not install in humid rooms such as small utility and bathrooms. The unit is not hermetically sealed and excess moisture on the circuit board can eventually cause a short and a false alarm.
• Do not use where white noise, such as air compressor noise, is present. A blast of compressed air may cause a false alarm.
• A void rooms smaller than 10 by 10 feet (3 by 3 m) and rooms with multiple noise sources such as noisy kitchens, stairwells, residential garages, and other small accoustically live rooms.
Mounting location
For best false alarm immunity the unit should be located at least 4 feet (1.2 m) away from noise sources (televisions, speakers, sinks, doors, etc.). The unit must always be in direct line of sight of all windows to be protected. There is no front or back, up or down, orientation of the sensor required.
Wall mount
Since the sound of breaking glass travels directionally out from the broken window , the best location for mounting the unit is on the opposite wall, within the unit’s range and line of sight.
Recommended glass size
Minimum 1 by 2 feet (0.3 by 0.6 m) Glass thickness:
Plate 3/32 to 1/4 inch (2 to 6 mm) T empered 1/8 to 1/4 inch (3 to 6 mm) Wired 1/4 inch (6 mm) Laminated 1/8 to 1/4 inch (3 to 6 mm)
Ceiling mount
Mount the unit on any type of ceiling in a location which is in direct line of sight of the windows to be protected. However, since sound travels directionally out from the broken window , a position 6 to 10 feet (2 to 3 m) into the room provides optimal detection.
2 5845-ID
SON APEMS
Installation Instruction
Installation
See Figure 3 and do the following steps to install the unit. 1 . Run the PinPoint system wiring to the unit location.
2. Open the unit by gently inserting a screwdriver in the hidden opening notches that are located under the lid in the middle of the long side of the unit.
CAUTION You must be free of all static electricity
before handling sensor circuit boards. Touch a grounded, bare metal surface before touching ciruit boards or wear a
grounding strap.
3 . Set the PinPoint address DIP switches. Devices are
shipped with DIP switches set to 255. This is an invalid address. The device will not communicate with
the controller until a valid address has been set.
Refer to the controller's manual to determine the correct address setting for each unit.
4. Remove the appropriate wiring knockouts and use the mounting screws to remove the mounting knockouts.
5 . Pull the PinPoint wiring through the wiring knockout
holes.
6. Attach the base to the mounting surface with two screws through the mounting knockout holes. Use wall anchors if necessary .
7 . Strip 1/4 inch (6.4 mm) of insulation from each
PinPoint wire. Connect the wiring to the appropriate screw terminals and tighten the screws.
8 . Replace the lid on the unit.
9. Test the unit when the PinPoint system is completely installed and the control panel is powered.
Figure 3. Base and circuit board
PinPoint wiring knockout
Opening notch
LED Tamper
switch
PinPoint wiring knockout
Mounting knockout
+ - + -
IN
OUT
ON APEM
Mounting knockout
1 2 3 4 5 6 7 8
PinPoint terminal block
Opening notch
DIP switches
3
Testing
The Pattern Recognition Technology of the unit ignores most false alarm sounds, including glassbreak testers. In order to test the unit, a test mode is used. With the unit in test mode, processing of the glassbreak pattern in the upper and lower frequencies is disabled. The unit is then listening only for the mid-range frequencies, which the 5709C tester reproduces. It’s the mid-range frequencies that determine unit range.
1 . Lift the unit's lid off and put it back on to activate the
LED for the walk test.
2. Use the 5709C hand-held tester to set the unit into test mode. The 5709C tester has a different setting for each type of glass. (The tester should always be set for tempered or laminated glass unless the installer is certain that all the glass to be protected is plate glass.) Hold the tester speaker directly on top of the unit and activate the tester. The unit will alarm then go into test mode for one minute. When in test mode, the LED on the unit will blink continuously . Extend the test mode time by firing the tester at the unit at least once a minute. In normal mode the LED does not blink unless it hears a loud sound and the unit will not trip to the tester, unless the tester is held next to the unit.
3. Holding the tester near the surface of the glass, aim the tester at the unit and hold down the test button (Figure 4). If drapes or blinds are present, test with the tester behind the closed drapes or blinds (do not use with heavy or lined drapes).
When the LED on the unit goes solid momentarily while the tester is triggered, the glass is within detection range.
4 . If the LED does not go solid, but simply continues
blinking, reposition the unit closer to the protected windows and retest. Additional units may be required to achieve adequate coverage. It is very rare that the unit will not activate within its stated range of coverage. Double check adequate battery strength in the tester. A new tester battery may be needed to restore range.
The unit will automatically change from test mode to normal mode approximately one minute after it last hears the tester. LED feedback will time out in three minutes.
Figure 4. Testing the unit
Do not exceed the rated range of the sensor , regardless of what the tester shows. Room acoustics can artificially
extend the range of a glassbreak sensor. The specified range of the unit has been established for worst-case conditions. While the unit will likely function at additional range, it may miss a minimum output break, or room acoustics may be changed at some future time, bringing the unit range back into normal 20 foot (6 m) conditions.
Proper testing
The unit is designed to detect the breaking of framed glass mounted in an outside wall. Testing the sensor with unframed glass, broken bottles, etc., may not trip the unit. The unit typically does not trip to glass breaking in the middle of the room and may not consistently detect cracks in glass, or bullets which break through the glass. Glassbreak sensors should always be backed up by
interior protection.
Hand clap test
To verify visually that there is power to the unit and that the microphone and circuit board are functioning, clap your hands loudly under the unit (in normal mode). The LED will blink twice, but the unit will not trip.
Maintenance
When installed and used properly, this unit provides years of service with minimal maintenance. You should test the unit annually to ensure proper operation.
Clean the cover with a damp (water) cloth as needed to keep it free of dust and dirt. Always test the unit after cleaning.
4 5845-ID
Installation Instruction
Specifications
Housing material Flame retardant ABS Operating voltage 8 to 27V, (as supplied by
the PinPoint bus)
Current draw 250µA typical average
3 mA with LED momentarily on Microphone Omni-directional electret Operating temperature 14 to 120°F (-10 to 50°C) Relative humidity 10 to 90% non-condensing Maximum line length 10,000 ft. (3 km) Dimensions:
Width 3.13 in. (8.0 cm) Depth 1.70 in. (4.3 cm)
Height 4.24 in. (10.8 cm) Color White Listing FCC, CE
FCC compliance
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
Product ordering
Product Description
5845-ID Addressable ShatterPro® II
glassbreak for use with the PinPoint bus.
5709C Glassbreak tester
12345 SW Leveton Drive
GE Security
Tualatin, OR 97062
503-692-4052
USA & Canada: 800-547-2556 Tech Support: 800-648-7424 www.ge-security.com 1036047C / September 2004
Loading...