ShatterPro™ II Advanced Acoustic Sensor with Pattern Recognition Technology
Protected under U.S. Patent 5,192,931 and 5,510,767
Installation Instructions for Recessed and Surface Mount Models
Recessed ShatterPro™ II 5820A
SENTROL
Surface Mount ShatterPro™ II
Surface Mount ShatterPro™ II 5812A
WIRING
5812EZ
™
Strip back the outer jacket on your wiring cable. This will allow wires to flex in the case. Make sure the cable is slack in the wall to
avoid stressing the wires at their connections.
Cut for latching LED
N.C.
COM
TAMP
TAMP
+
–
spring clip for
latching LED
N.C.
COM
TAMP
TAMP
NO
+
–
Loop
+
−
spring clip for
latching LED
5820A-W and 5822A-W
NOTE: When wiring the
5812EZ-W
5812A-W
5815EZ-W
5815A-W
5822A, the tamper is in series
with the alarm loop. There is
insufficient room for a separate
set of terminals for the tamper.
ORDERING INFORMATION
DescriptionModel No.ColorListing
ShatterPro™ II EZ, tamper, latch or non-latch LED5812EZ-WWhiteUL
ShatterPro™ II EZ, tamper, Form C, latch or non-latch LED5815EZ-WWhiteULC
ShatterPro™ II, tamper, latch or non-latch LED5812A-WWhiteUL
ShatterPro™ II, tamper, Form C, latch or non-latch LED5815A-WWhiteULC
Recessed ShatterPro™ II, latch or non-latch LED5820A-WWhite
Recessed ShatterPro™ II, tamper, latch or non-latch LED5822A-WWhiteUL
Single Gang Box ShatterPro™ II5825A-WWhite
Single Gang Box Kit for Recessed ShatterPro™ II5829A-WWhite
Hand-held Tester, for testing effective range5709C-WWhite
RANGE OF COVERAGE
25' (7.5 m)
25' (7.5 m)
The ShatterPro sensors are omni-directional, providing 360°
coverage. Coverage is measured from the sensor to the point on
the glass farthest from the sensor. The sensor can be mounted as
close as 3.3' (1 m) from the glass.
1.Mounted on opposite wall or adjoining walls, range is 25 ft.
(7.5m) for plate, tempered, laminated and wired glass.
2.Mounted on the ceiling, maximum range is 25 ft. (7.5m) for
plate, tempered, laminated and wired glass.
3.For armor-coated glass, mount sensor no more than 12 ft.
(3.65m) from glass.
Recommended Glass Size:
Minimum 1' x 2' (0.3 m x 0.6 m) or larger
Glass thickness:
Plate: 3/32" to 1/4" (2.4 mm to 6.4 mm)
Tempered: 1/8" to 1/4" (3.2 mm to 6.4 mm)
Wired: 1/4" (6.4 mm)
Laminated: 1/8" to 1/4" (3.2 mm to 6.4 mm)
TESTING THE SENSOR
Put Sensor in Test Mode
1.Connect 9-volt battery to sensor for pre-testing.
2.Use double-stick tape provided to temporarily mount sensor
in desired location.
3.Use Sentrol 5709C Hand-Held Tester to put sensor into test
mode. Set tester to tempered glass and hold on top of
sensor. Activate tester this will trip sensor into test mode
for one minute. In test mode, LED will blink continuously.
To extend test time, activate tester at least once a minute.
Test the Sensor (sensor must be in test mode, blinking)
1.The 5709C tester has settings for different types of glass.
Use tempered setting if unsure of glass type.
2.Hold tester near surface of glass to be protected and aim at
sensor. Press test button.
If drapes or blinds are present, hold the tester behind the
closed drapes or blinds.
3.If LED stays on for four seconds, glass is within detection
range of sensor.
4.If LED does not stay on, reposition the sensor and retest.
(Verify adequate battery strength in tester.)
5.For latching LED: open the spring clip and provide a power
reset by removing power and resetting the LED.
For Best Detection, Avoid Installing In:
Rooms with lined, insulating, or sound deadening drapes.
Rooms with closed wooden window shutters inside.
SENTROL
ShatterSwitch
Shatterbox II
Shatterbox
ShatterPro
5709C
Use for testing:
Laminated •
Shatter Series Tester
stays on during test
Battery LED
Battery is OK if LED
Hold tester so that the speaker is
within 1 inch of sensor microphone
In test mode the sensor LED will light
solid for about 4 seconds,
then blink for about a minute
<1 inch
• Single
• Continuous
Plate •
Tempered •
How Test Mode Works:
Test Mode is activated by the hand-held tester when the tester is
held directly over the microphone and set off. The sensors LED
will blink continuously for 1 minute. During this time, the
installer can test the unit using the instructions above. When the
system is armed and the ShatterPro II trips to an alarm condition,
the LED will latch solid for 4 seconds and then revert back to a
1 minute test mode. At the end of one minute, the LED will
extinguish if in set up LED mode, or the LED will latch if set
for Latching LED. Open spring clip for Latching LED.
MOUNTING
D
DD
is distance from glass.
The optimum performance zone
is distance D in either direction
on the glass.
ShatterPro
D' ≤ 25'
Locate sensor at least 4' from noise sources (TVs, speakers, sinks,
doors, etc.), and at least 3.3' away from nearest point of glass to
be protected.
Sensor location should be in direct line of sight of glass to be
protected.
Surface Mount
Wall Mounting
The best location for mounting the sensor is on the opposite wall
assuming the glass to be protected is within the sensors range
and line of sight (see figure). The ceiling and adjoining (side)
walls are also good sensor locations.
Ceiling Mounting
Mount the sensor in any type of ceiling in a location which is in
direct line of sight of the windows to be protected. However,
since sound travels directionally out from the broken window, a
position 8' (2.4 m) into the room provides better detection (see
figure).
AVOIDING FALSE ALARMS
Areas to Avoid:
Glass airlocks and glass vestibule areas
Kitchens
Corner mounting
Residential car garages
Small utility rooms
Stairwells
Bathrooms
Other small acoustically live rooms
For glassbreak protection in such applications, use Sentrol
shock or ShatterPoint (model 5600, 5620) sensors on the
windows or window frames.
Do Not Install In Humid Rooms
No glassbreak sensor is hermetically sealed. Excess moisture
on the circuit board can eventually cause a short and a false
alarm.
For Best False Alarm Immunity:
Avoid 24-hour loop applications (perimeter loop OK).
Dont use where white noise, such as air compressor noise,
is present. (A blast of compressed air may cause a false
alarm.)
Avoid rooms smaller than 10' x 10' (3 m x 3 m) and rooms
with multiple noise sources such as kitchens, glass booths,
noisy areas, garages, bathrooms, etc.
In rooms less than 10' x 10', use a reduced-range ShatterPro
II, (models 5820A-W2, 5812A-W2), or ShatterPoint (model
5600, 5620).
Proper Testing
The ShatterPro II is designed to detect the breaking of framed
glass mounted in an outside wall. Testing the sensor with
unframed glass, broken bottles, etc., may not trip the sensor.
The ShatterPro II typically does not trip to glass breaking in
the middle of the room. No burglar breaks glass in the middle
of a room, so such breaks are false alarms.
Recessed
Wall or Ceiling Mount
Drill 1" (2.5 cm) hole. (Spade bit makes cleaner hole than
twist bit.) (Drill 1-1/16" (2.7 cm) hole for hard woods.)
Run wires through hole.
Connect wires to terminal as shown in wiring diagrams.
Do not install in rooms with ultrasonic sensors.
Pre-Wire Installation for the 5812EZ
Single Gang Box
1. Place the 5811EZ trim plate accessory over the single gang box.
2. Route wire through wire entry hole.
3. Mount the sensor to the single gang box using the screw holes
that align to the gang box.
4. Attach wires to terminal strip and snap front cover in place.
Optimum
Detection
Zone
Mounting location can affect the ShatterPro’s detection ability.
To ensure optimum performance, the ShatterPro’s coverage
zone width should be no greater than two times the distance
from the sensor to the closest point of glass. For instance, if
the ShatterPro is mounted 10 feet from the glass, its optimum
performance zone will be 10 feet in either direction of the “midpoint” (see illustration above). ShatterPro can be mounted
from 3.3' to 25' from the farthest point on the glass.
Avoid 24-Hour Loop Applications
The ShatterPro II is recommended for perimeter loops and is designed
to function in occupied areas. In 24-hour loop applications, where the
sensor is armed all day and all night, the false alarm technology will be
pushed to its limit. Some sounds can duplicate the points on the
glassbreak pattern the ShatterPro II detects.
Install the ShatterPro II on a perimeter loop which is armed
whenever the door and window contacts are armed.
Protecting Occupied Areas
The ShatterPro IIs false alarm immunity is best in rooms with only
moderate noise. For 24-hour occupied area protection, use Sentrol
shock sensors or the ShatterPro Plus 5885 or ShatterPoint (5600,
5620).
NOTE: ShatterPro II may not consistently detect cracks in glass,
or bullets which break through the glass. Glassbreak sensors
should always be complemented with interior protection.
Connection to Panel
The ShatterPro II should be connected to a UL Listed control
panel, or a power supply that provides at least four hours of
standby power.
SPECIFICATIONS
2.75"
(6.99 cm)
4.5"
(11.43 cm)
Electrical
Voltage ...................................................................... 9 to 16 VDC
Current ............................................... 12 mA typical, 25 mA max.
Relay output............ Normally closed, open 4 seconds upon alarm
On resistance ................................................ 10 Ohm 5 +10
Off resistance....................................................... > 1 MOhms
Maximum loop rating (relay or tamper loop) .........................
...................................................................... 16 VDC, 50 mA
Operating Temperature ............. 0° F to 120° F (-18° C to +50° C)
Humidity ............................................10% to 90% noncondensing
ACCESSORIES
5825A Single Gang Box
ShatterPro™ II
NOTE: This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. There is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment on and off, the user is encouraged to
try to correct the interference by one or more of the following measures:
Re-orient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Under FCC Rules, Part 15 for Class B digital devices, operation is subject to the
following two conditions:
1) This device may not cause harmful interference.
2) This device must accept any interference received, including interference
that may cause undesired operation.
(Back box
not included)
2.53" diameter (6.43 cm)
1" diameter hole (2.54 cm)
5829A Single Gang Box Plate
for 5820A.
(Back box
not included)
5812EZ Pre-Wire Installation with 5811EZ and Single Gang Box
SENTRO L
CORPORATE HEADQUARTERS
U.S. & Canada: 800.547.2556
Technical Service: 800.648.7424
FaxBack: 800.483.2495
G-3513-798
15651 Rev. A
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.