Interlogix 560NSTR, 562NSR, 562NST, 570NR, 572NSTR Specsheet

FireworX Fire & Life Safety
Conventional Initiating Devices
Overview
GE wireless compatible photoelectric smoke detectors come in a variety of models for different OEM applications. The 560/570 Series is specifically designed and listed for use with OEM’s proprietary transmitters and systems. Additional submittals to a a Nationally Recognized Testing Laboratory will be required to complete the Listing process.
All GE wireless compatible photoelectric smoke alarms and detec­tors continually monitor operational status and provide a visual trouble condition if they drift out of the sensitivity range or fail internal diagnostics. The series meets NFPA 72 field sensitivity test­ing requirements without the need for external meters. The alarm sensitivity level can be determined at the unit. Another feature is built-in drift compensation that allows the alarm to adjust sensitivity automatically as it becomes dirty over time. The drift compensation feature dramatically increases the time between cleanings, as well as reducing the chance of a nuisance alarm.
Additional diagnostic information is activated by applying a magnet near the detector’s integral reed switch. This initiates a self-diag­nostic routine and provides visual indication of sensitivity level, or if service is required.
The 560/570 Series is powered by long life 3V Lithium batteries that can provide power to both the smoke alarm and OEM transmitter.
Standard Features
Long-life 3V lithium battery operated
Field-replaceable optical chamber
Integral 85dBA sounder
Automatic drift compensation
Optional integral heat detector
Smoke alarm test/hush feature
Low-profile design that blends into ceiling
Base tamper provides trouble condition if smoke alarm is re-
• moved
Wireless Compatible Smoke Alarms and Detectors
560N/570N
SKU guide: 562NSTR 5 = 500 Series 6 = UL 217 recognized 0 = No batteries included
2 = 2 - 3V Lithium batteries included
7 = UL 268 recognized S = Integral Sounder T = Dual fixed/ROR heat R = Plastic housing not assembled 20PKG = Bulk pack of 20 units
Engineering Specification
The GE 560N/570N Series wireless compatible smoke alarms and detectors monitor their own sensitivity and operational status by continuously verifying the integrity of the sensing chamber and internal electronics. The alarm meets the NFPA 72 field sensitivity requirements without the need for external meters. The 560N/570N series alarms and detectors' drift compensation feature automatically adjusts their sensitivity up to a maximum of 0.5%/ft., if they become dirty. This feature increases immunity to dust and dirt by 30-50%. Each of the UL 217 smoke alarm models in the GE 560N Series ship with a built-in 85dBa sounder that will sound the ANSI temporal 3 pat­tern until the smoke has cleared or the unit has been silenced.
Note: The wireless compatible 560N/570N Series includes CleanMe®. When a CleanMe condition occurs, the alarm transmits a trouble signal to the control, which in turn reports to the central station indicating the unit needs service.
Ordering Information
560NS Wireless compatible, Photoelectric
560NSR­20PKG
562NS Wireless compatible, Photoelectric
562NST Wireless compatible, Photoelectric
572NS Wireless compatible, Photoelectric
572NS Wireless compatible, Photoelectric
Accessories 401
SM200­12PKG
SM-EXT1 211-
10PKG
smoke alarm, Sounder, 3V, no batteries, UL 217
Wireless compatible, photoelectric Smoke alarm, sounder, heat, 3V, no Batteries, plastic housing not assembled, Package of 20 units, UL 217
smoke alarm, Sounder, 2- 3V lithium batteries included, UL 217
smoke alarm, Sounder, heat, 2- 3V lithium batteries included, UL 217
smoke detector, Sounder, 3V, 2 – 3V lithium batteries, UL 268 recognized
smoke detector, Sounder, 3V, 2 – 3V lithium batteries, plastic housing not assembled, Package of 20 Units, UL 268 recognized
Test magnet in a plastic shell for pole mounting
Smoke! in a Can® (aerosol spray) for functional testing of smoke detectors, pack of 12
Smoke! in a Can extension tube
Replacement optical chambers, pack of 10
Technical Specifications
Electrical
Voltage 3VDC Typical average
standby current Typical test current 2mA Typical alarm current 70mA Battery type
Low battery threshold 2.7V causes low battery
Sounder
Low battery beep rate 1 every 45 ± 2 sec
Signal Types
Outputs Alarm, restore, tamper, low
Environmental
Sensitivity 2.3% ± 0.890% Operating
temperature Operating humidity 0-95% non-condensing RF Immunity 20V/m min; 1-1000MHz
Physical
Color White Alarm dimensions 5.6 x 2.4” (142 x 61mm) Base dimensions 5.4 x 0.46” (137 x 11.7mm) Drift compensation
adjustment Heat alarm
specifications
Regulations
Approvals 560N UL 217 recognized;
Note 1: tested and approved for use with the 560/570 series.
Note 2: Some 570 models do not include integral sounder.
* Specifications only for 560N smoke alarm when listed with a transmitter and a 570N when listed with a UL 864 Commercial Fire Alarm System. Please call OEM sales at 800.547.2556 for more information regarding the process for fully listing the 560N/570N wireless compatible smoke alarm and detectors with an OEM transmitter.
1
2
These batteries are the ONLY brands that have been
35μA
3V Lithium, Duracell® 123, Sanyo® and Panasonic® CR123A
signal 85dBa at 10’, temporal
pattern
battery, trouble, 1 hour supervisory
40 °F to 100 °F (4.4 °C to 38 °C)
0.5%/ft. max
Rate-of-rise: 15°F/min >105°F (8.3°C/min > 40.6°C) Fixed: 135°F ± 5°F (57.2°C ± 2.8°C)
570N UL 268 recognized.*
Loading...