FireworX Fire & Life Safety
Conventional Initiating Devices
Overview
GE wireless compatible photoelectric smoke detectors come in a
variety of models for different OEM applications. The 560/570 Series
is specifically designed and listed for use with OEM’s proprietary
transmitters and systems. Additional submittals to a a Nationally
Recognized Testing Laboratory will be required to complete the
Listing process.
All GE wireless compatible photoelectric smoke alarms and detectors continually monitor operational status and provide a visual
trouble condition if they drift out of the sensitivity range or fail
internal diagnostics. The series meets NFPA 72 field sensitivity testing requirements without the need for external meters. The alarm
sensitivity level can be determined at the unit. Another feature is
built-in drift compensation that allows the alarm to adjust sensitivity
automatically as it becomes dirty over time. The drift compensation
feature dramatically increases the time between cleanings, as well
as reducing the chance of a nuisance alarm.
Additional diagnostic information is activated by applying a magnet
near the detector’s integral reed switch. This initiates a self-diagnostic routine and provides visual indication of sensitivity level, or if
service is required.
The 560/570 Series is powered by long life 3V Lithium batteries that
can provide power to both the smoke alarm and OEM transmitter.
Standard Features
•
Long-life 3V lithium battery operated
Field-replaceable optical chamber
•
Integral 85dBA sounder
•
Automatic drift compensation
•
Optional integral heat detector
•
Smoke alarm test/hush feature
•
Low-profile design that blends into ceiling
•
Base tamper provides trouble condition if smoke alarm is re-
•
moved
Wireless Compatible
Smoke Alarms and
Detectors
560N/570N
SKU guide: 562NSTR
5 = 500 Series
6 = UL 217 recognized
0 = No batteries included
2 = 2 - 3V Lithium batteries included
7 = UL 268 recognized
S = Integral Sounder
T = Dual fixed/ROR heat
R = Plastic housing not assembled
20PKG = Bulk pack of 20 units
Engineering Specification
The GE 560N/570N Series wireless compatible
smoke alarms and detectors monitor their own
sensitivity and operational status by continuously
verifying the integrity of the sensing chamber
and internal electronics. The alarm meets the
NFPA 72 field sensitivity requirements without the
need for external meters. The 560N/570N series
alarms and detectors' drift compensation feature
automatically adjusts their sensitivity up to a
maximum of 0.5%/ft., if they become dirty. This
feature increases immunity to dust and dirt by
30-50%. Each of the UL 217 smoke alarm models
in the GE 560N Series ship with a built-in 85dBa
sounder that will sound the ANSI temporal 3 pattern until the smoke has cleared or the unit has
been silenced.
Note: The wireless compatible 560N/570N Series
includes CleanMe®. When a CleanMe condition
occurs, the alarm transmits a trouble signal to
the control, which in turn reports to the central
station indicating the unit needs service.
Ordering Information
560NS Wireless compatible, Photoelectric
560NSR20PKG
562NS Wireless compatible, Photoelectric
562NST Wireless compatible, Photoelectric
572NS Wireless compatible, Photoelectric
572NS Wireless compatible, Photoelectric
Accessories
401
SM20012PKG
SM-EXT1
211-
10PKG
smoke alarm, Sounder, 3V, no batteries,
UL 217
Wireless compatible, photoelectric
Smoke alarm, sounder, heat, 3V, no
Batteries, plastic housing not assembled,
Package of 20 units, UL 217
smoke alarm, Sounder, 2- 3V lithium
batteries included, UL 217
smoke alarm, Sounder, heat, 2- 3V
lithium batteries included, UL 217
smoke detector, Sounder, 3V, 2 – 3V
lithium batteries, UL 268 recognized
smoke detector, Sounder, 3V, 2 – 3V
lithium batteries, plastic housing not
assembled, Package of 20 Units, UL 268
recognized
Test magnet in a plastic shell for pole
mounting
Smoke! in a Can® (aerosol spray) for
functional testing of smoke detectors,
pack of 12
Smoke! in a Can extension tube
Replacement optical chambers, pack
of 10
Technical Specifications
Electrical
Voltage 3VDC
Typical average
standby current
Typical test current 2mA
Typical alarm current 70mA
Battery type
Low battery threshold 2.7V causes low battery
Sounder
Low battery beep rate 1 every 45 ± 2 sec
Signal Types
Outputs Alarm, restore, tamper, low
Environmental
Sensitivity 2.3% ± 0.890%
Operating
temperature
Operating humidity 0-95% non-condensing
RF Immunity 20V/m min; 1-1000MHz
Physical
Color White
Alarm dimensions 5.6 x 2.4” (142 x 61mm)
Base dimensions 5.4 x 0.46” (137 x 11.7mm)
Drift compensation
adjustment
Heat alarm
specifications
Regulations
Approvals 560N UL 217 recognized;
Note 1:
tested and approved for use with the 560/570 series.
Note 2: Some 570 models do not include integral sounder.
* Specifications only for 560N smoke alarm when listed with a
transmitter and a 570N when listed with a UL 864 Commercial
Fire Alarm System. Please call OEM sales at 800.547.2556 for
more information regarding the process for fully listing the
560N/570N wireless compatible smoke alarm and detectors
with an OEM transmitter.
1
2
These batteries are the ONLY brands that have been
35μA
3V Lithium, Duracell® 123,
Sanyo® and Panasonic®
CR123A
signal
85dBa at 10’, temporal
pattern
battery, trouble, 1 hour
supervisory
40 °F to 100 °F (4.4 °C to
38 °C)
0.5%/ft. max
Rate-of-rise: 15°F/min
>105°F (8.3°C/min > 40.6°C)
Fixed: 135°F ± 5°F (57.2°C
± 2.8°C)
570N UL 268 recognized.*