Inovonics FA464DR User Manual

0 (0)

FA464DR

64 Transmitter / 16-Output Receiver

Installation Instructions

02039F

 

Document revision history / Notes

 

 

 

 

Rev. Level

Description

Date

B

Create F:\Eng\parts\02039\E02039B.doc from

6/01

 

P:\Master.dox\FA_dox\FA464.doc (pre-ECN)

 

 

 

 

C

Create F:\Eng\parts\02039\02039C.doc from

7/25/01

 

F:\Eng\parts\02039\E02039B.doc (ECN release version)

 

 

 

 

D

Replace ISO logo

7/25/01

 

 

 

E

Revise per ECN 2259

10/24/02

 

 

 

F

Add wire gauge p. 4; delete FA200/FA200W p.12

11/21/03

 

 

 

Important Notes

nThis product is designed to be installed and maintained by professional security technicians.

nUnless specifically noted, Inovonics products are intended for indoor use. This receiver is intended for use with indoor security systems. Use in outdoor applications may impair performance.

nTest system regularly.

© 1999 Inovonics Wireless Corporation 02039F.DOC LIT-FA464-INSTALL

1

hc:21-Nov-03

Inovonics FA464DR User Manual

FA464DR

64-Transmitter, 16-Relay Output Receiver

The FA464DR receiver has 16 Form C relay outputs, plus a global fault relay output.

Installers should note that alarm relay terminals are mounted so that normally open or normally closed terminal positions are side-by-side as shown in Figure 1.

TRANSMITTER PROGRAMMING PORT

REVIEW STATUS BUTTON

VALID DECODE LED

DECODE LED

OUTPUT LEDS 1-16

ADVANCE BUTTON

DELETE BUTTON

GLOBAL FAULT LED

FA104 PROGRAMMER PORT

RESET BUTTON

POWER LED

TRANSMITTER NUMBER DISPLAY

TAMPER SWITCH

TRANSMITTER STATUS LEDS

DECODE

 

 

TRANSMITTER

DC POWER ONLY

TAMPER

 

 

 

PROGRAMMING

 

VALID

 

 

 

 

 

 

 

 

 

 

TAMPER

12VDC TYPICAL 18VDC MAX

 

 

 

TRANSMITTER

RESET

+

 

OUTPUT

 

NUMBER

GND

 

1

 

ACTIVATED

 

 

DECODE

 

 

 

 

 

 

 

REVIEW

 

 

 

 

 

 

 

TAMPERED

 

 

 

 

 

2

STATUS

 

NC

NC

 

 

 

 

 

1

 

3

 

LOW BATTERY

16

COM

COM

 

 

 

 

NO

NO

 

 

 

 

INACTIVE

 

 

 

 

 

 

NO

NO

 

 

4

ADVANCE

DELETE

 

 

 

 

 

COM

COM

 

 

 

 

 

15

2

 

 

 

PROGRAMMED

 

NC

NC

 

 

 

 

 

 

 

 

5

 

NC

NC

 

6

14

COM

COM

3

 

NO NO

NO NO

 

7

 

 

 

COM

COM

 

8

13

4

 

NC

NC

 

 

 

 

 

NOTE:

 

 

 

 

NORMALLY OPEN TERMINALS

 

 

9

ARE SIDE-BY-SIDE

 

 

 

 

 

 

 

10

(8 PLACES)

 

 

 

 

NC

NC

 

 

12

5

11

COM

COM

 

 

 

 

12

 

NO

NO

 

 

NO

NO

 

 

 

 

 

11

COM

COM

6

13

 

NC

NC

 

 

10

NC

NC

7

14

COM

COM

15

 

NO

NO

 

 

NO

NO

 

 

9

8

16

COM

COM

 

FAULT

NC

NC

 

 

 

 

FA104

NC

PROGRAMMER

RESET

COM FAULT

POWER

NO

 

PROGRAMMER

FA464D

FA116

 

FA116 PROGRAMMER PORT

DATA LED

EXTERNAL TAMPER INPUT

POWER INPUT

RESET INPUT

ALARM OUTPUTS

1-4 and 13-16

WIRING HARNESS

TIE-DOWN HOLES (2 PLACES)

ALARM OUTPUTS

5-8 and 9-12

FAULT OUTPUT

Figure 1

Note: References in this manual to features shown in Figure 1 will be printed in bold italics.

© 1999 Inovonics Wireless Corporation 02039F.DOC LIT-FA464-INSTALL

2

hc:21-Nov-03

Features of the FA464DR include:

x Full supervision of up to 64 FA transmitters.

x The FA464DR has 16 Form C Alarm Output Relays, plus a global Fault Output Relay.

x Transmitter, receiver and output options are factory assigned. They may be changed with the FA116 Executive Programmer or with the FA104 (upgraded C104) programmer.

x Intelligent global fault output for tamper, low battery and inactive transmitters. For example, if one of the alarm outputs is assigned to monitor low battery faults, the fault output automatically becomes tamper and inactive only.

x Manual and/or electronic reset of the receiver.

x Factory default programming: "Alarm" and "Inactive" outputs are programmed to follow transmitter status; "Tamper" and "Low battery" outputs are latching. Latched outputs require the receiver to be reset.

x Simple restoral to factory defaults.

x Automatic exit from programming after 4 minutes of inactivity.

x Transmitter Status LEDs show transmitter activation, tamper, low battery and inactive.

x The Programming LED blinks when the point IS NOT programmed, is on steady when the point IS programmed.

© 1999 Inovonics Wireless Corporation 02039F.DOC LIT-FA464-INSTALL

3

hc:21-Nov-03

Technical Specifications:

Dimensions (housing):

11" x 8.5" x 1.75"

Weight:

34 oz

 

 

Environmental:

 

 

 

Operating temperature:

q

q

q q

32 -140 F (0 -60 C)

Relative Humidity:

90% (non-condensing)

Electrical:

 

 

 

Power Requirement:

12-17 VDC, 980mA

Minimum:

60 Ma

 

 

Output relay rating:

1A @ 28 VDC, 0.5A @ 30 VAC (resistive)

Wire gauge:

14-22 AWG

 

Receiver:

 

 

 

Type:

frequency-hopping spread spectrum

Operating frequency:

902-928 MHz

Installation:

Power: Supply power and ground to designated terminals on the Power Input terminals.

Note: To power the FA464DR directly from an AC power source, Inovonics recommends a power supply that is UL listed for use with “Burglar Alarm Systems.”

Mounting: Use supplied hardware to attach FA464DR housing to wall or surface.

RECEIVER COVER SCREW ACCESS

WALL MOUNT SCREW ACCESS

(2 PLACES)

(2 PLACES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

© 1999 Inovonics Wireless Corporation 02039F.DOC LIT-FA464-INSTALL

Figure 2

4

hc:21-Nov-03

Connecting to a panel: When the FA464DR will be used with a hardwire security panel, the panel will typically supply power and ground to the FA464DR (if the power supply provides the required current).

Typical connections between the FA464DR and a hardwire panel:

The installer wires the relay common terminal to the panel Zone Return, and wires either the Normally Open or the Normally Closed terminal of the relay to the panel Zone input terminal.

TRANSMITTER

PROGRAMMING

TRANSMITTER

NUMBER

REVIEW

STATUS

ADVANCE DELETE

 

FA464DR

 

DC POWER ONLY

TAMPER

 

 

TAMPER

12VDC TYPICAL 18VDC MAX

 

RESET

+

ACTIVATED

GND

 

TAMPERED

 

NC

NC

 

 

 

1

LOW BATTERY

16

COM

COM

INACTIVE

 

NO

NO

 

 

NO

NO

 

 

 

 

 

15

COM

COM

2

PROGRAMMED

 

NC

NC

 

 

NC

NC

 

 

 

 

 

14

COM

COM

3

 

 

NO NO

NO NO

 

 

13

COM

COM

4

 

 

NC

NC

 

13.6VDC GROUND

PANEL ZONE 1 ZONE 1 RETURN

PANEL ZONE 2

ZONE 2 RETURN

PANEL

NOTE: GROUND

AND RETURNS

ARE NOT COMMON

In this example, Panel Zones 1 and 2 are configured to be N/C.

Figure 3

© 1999 Inovonics Wireless Corporation 02039F.DOC LIT-FA464-INSTALL

5

hc:21-Nov-03

Programming transmitters:

Without the FA116 programmer:

1.Refer to Appendix A to determine available default parameters.

2.Select a point number which matches desired transmitter parameters.

3.Press the Advance Button on the FA464DR until the Transmitter Number Display shows the desired transmitter number. (Hold down the Advance Button for auto repeat.) The Programming LED will blink if the point has not been programmed. If a transmitter has already been programmed to that channel, the LED will be on steady.

4.Connect the programming cable to the transmitter and then to the Transmitter Programming Port on the FA464DR.

5.Press the transmitter reset button. (Refer to.) When the transmitter is successfully programmed, the receiver will emit a single "deedle" tone and the Programming LED will be on solid. (It may be necessary to press the transmitter reset button more than once, if the receiver is "busy" with signals from other transmitters.)

With the FA116 programmer: Up to 64 transmitters can be selected, programmed and deleted. The programmer allows installers to configure receiver parameters and output options. Point status and signal strength can be observed. Receiver outputs can be activated for testing and faults can be cleared.

Refer to FA116 programming documentation.

© 1999 Inovonics Wireless Corporation 02039F.DOC LIT-FA464-INSTALL

6

hc:21-Nov-03