Inovonics EN4216MR User Manual

0 (0)
Inovonics EN4216MR User Manual

EN4216MR EchoStream® Receiver

Installation and Operation Manual - 05637D, April 4, 2011

1 Overview

The EN4216MR receiver allows you to add up to 16 transmitters and six outputs to any application. With diversity reception and advanced signal processing, Inovonics EchoStream technology is designed to minimize dead spots in transmission areas.

1.1 Installing an Inovonics Security System

An EchoStream survey kit must be used to establish a UL system. The EchoStream survey kit measures the signal strength of high-power repeater and sensor messages to help optimize your EchoStream system.

1.3 EN4216MR Front Panel

 

 

 

A

 

 

D

 

 

B

 

 

 

 

E

 

 

 

 

 

 

 

 

C

 

 

 

 

F

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

Figure 2 Receiver front panel

H

 

 

 

A Output LED

 

B Fault LED

C Power LED

D LCD display

 

E Up button

F Down button

G Back button

 

H Enter button

 

 

 

Output LED: Lights when any transmitter output is active.

Fault LED: Lights when any transmitter is sending a fault condition. Power LED: Lit when receiving power.

LCD Display: Shows status, event log and programming information. Decode LED: Flashes when any recognizable transmission is received. This LED is only visible when the cover is removed.

Up button: Scrolls the display up. Down button: Scrolls the display down.

Back button: Returns display to the previous menu, or when pressed in the main menu options, returns the unit to normal operating mode. When entering information in the display, returns to the last character entered.

Enter button: Selects the currently displayed menu item. If in normal operating mode, sets the unit to menu mode.

Reset button: Clears the current status for all points and resets all outputs and LEDs. Records a receiver reset entry in the event log and resets the supervision window timers. This button is only accessible when the cover is removed.

1.4 EN4216MR Internal Components

B A

Figure 1 Sample EchoStream System

The EchoStream survey kit provides you with two signal strength measurements: signal level and signal margin.

Signal level

The signal level is the measurement of the overall decibel level of the message.

Signal margin

The signal margin is the measurement of the decibel level of the message, minus the decibel level of any interfering signals. Inovonics Wireless equipment should be placed within a facility such that all end-devices produce signal margin readings of at least 4 decibels.

Both the signal level and signal margin are measured in decibels. Because signal strength and signal margin are measured on a logarithmic scale, the difference between a decibel level of 3 (Weak) and a decibel level of 4 (Good) is a much larger difference than it would be on a linear scale.

Note: For more information about the EchoStream survey kit, see the EN/ EE7016SK EchoStream® Survey Kit Installation and Operation Manual.

1.2 Inovonics Wireless Contact Information

If you have any problems with this procedure, contact Inovonics Wireless technical services:

E-mail: support@inovonics.com

Phone: (800) 782-2709; (303) 939-9336

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

K

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

J

G

 

 

 

 

 

 

 

H

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3 EN4216MR internal components

 

 

 

 

 

A Housing release

B Power

C Operation LEDs

 

tabs

 

 

connections

 

 

 

 

 

D Relay outputs

E Tamper output

F Receiver power loss output

G Jam output

 

 

H Reset input

I Frequency band selection

J Reset button

 

 

K Decode LED

 

 

pins

 

 

 

 

 

 

 

 

2 Power Cabling

Before beginning startup, you will need to connect power to the receiver. To connect power to the receiver:

1.Connect power cabling to the Vs (+) and GND (-) connections.

Power source should be 11-14 VDC. Power supply must be unswitched, uninterrupted, and regulated.

Use 14 - 22 gauge wire for all cabling, and ensure torque on the screw terminals does not exceed 7 inch-pounds.

For UL installations, wire lengths must not exceed 300 feet.

© Inovonics, 2011 - www.inovonics.com

3 Select the Frequency Band

EchoStream products use a range of radio frequencies, and must be configured for your geographic area. To configure the receiver:

1.Use a small screwdriver to press the housing release tabs on the top or bottom of the receiver; separate the housing.

2.Place a selection jumper on the appropriate frequency band selection pins.

Leave the jumper off the pins to set the frequency range to 902-928 MHz for North America.

Place the jumper on the top two pins, marked NZ, to set the frequency range to 921-928 MHz for New Zealand

Place the jumper on the bottom two pins, marked AUS, to set the frequency range to 915-928 MHz for Australia.

Note: North American is also selected when the jumper is only attached to one pin. This can prevent the jumper from being lost when selecting North America.

Note: Only devices set for use in North America are configured for UL installations.

3. Cycle power to reset.

4 Connect Input/Output Cabling

1.Connect cabling to the receiver power loss output. Must be configured for UL installations.

The receiver power loss output is a normally closed (N/C) output that opens when the receiver loses power.

2.Connect cabling to the tamper output. Must be configured for UL installations.

The tamper output is a normally open (N/O) output that reports receiver case tamper to an external device.

3.Connect cabling to the jam output. Must be configured for UL installations.

The jam output is a normally closed (N/C) output that opens when noise thresholds on all receive channels remain above a predetermined value for 10 seconds. The jam output is set to the follower output type.

4.Connect a momentary switch to the reset input and ground. Must be configured for UL installations.

The reset input circuit permits installation of a remote momentary normally open (N/O) switch to clear faults, unlatch outputs, and reset the receiver to a normal state.

5.Connect cabling to the output terminals. Must be configured for UL installations.

The EN4216MR provides six Form-C relays.

6.Close receiver housing.

Vs

Ground

NC

Caution:

 

COM

 

Incorrect

 

NO

 

connections

 

 

may cause

 

COM

damage to the

outputJam outputTamper inputReset Receiver losspower output

NC COM NO NC COM NO NC COM NO

NC

unit

 

COM

 

 

NO

 

 

NC

 

 

NO

 

 

Figure 4 EN4216MR Terminals

5 Mount the Receiver

Caution: Mount the receiver in a location removed from metal. Metal objects (duct work, wire mesh screens, boxes) will reduce RF range.

Note: For UL listed systems containing a UL hold-up switch, the EN4216MR must be located within three feet of a system keypad in a location out of sight from the protected premise.

Note: For UL installations, the EN4216MR must be in the same room as the control panel.

1. Use the provided anchors and screws to mount the receiver in a location accessible for future maintenance.

2.Perform a walk test, activating each transmitter assigned to the receiver and ensuring a good signal.

6 Factory Configuration Defaults

The EN4216MR arrives with the tamper, low battery, and inactive trouble conditions pre-programmed.

Default Trouble Condition Programming

Condition

Output

 

 

Tamper

6

 

 

Low Battery

5

 

 

Supervision Loss/Inactive

6

 

 

7 System Status

System status information displays alarm and fault information on the LCD display by default. Points in alarm are displayed as ALARM, with the point number following. If more than one point is in alarm, the display scrolls through each point. If a point has more than one alarm, the display scrolls through each alarm. Fault conditions are indicated by FAULT in the LCD display if there is no ALARM already displayed; point numbers are not displayed. If no point is in alarm and there are no fault conditions, READY displays.

8 Point Status

POINT STATUS allows you to view detailed alarm and fault information. Point status information is available without a password.

To access POINT STATUS:

1.From system status information, press the Enter button to access the receiver’s three main menus. POINT STATUS displays.

2.Press Enter to display point status details.

3.Use the Up/Down buttons to scroll through the points; press Enter again to view the outputs the displayed conditions are mapped to.

Point status flags are defined as follows: A = Alarm (transmitter only); T = Tamper; B = Low Battery; L = AC loss (repeater only); I = Inactive.

Note: If - - displays, the displayed condition has been mapped to a null output.

9 Install & Service

Note: The default password is 3446.

The INSTALL & SERVICE menu is used to reset factory configuration, change password, view signal strength, delete points, register transmitters, and setup points for any of the programmed points.

To access the INSTALL & SERVICE menu:

1.From the system status information, press the Enter button to access the receiver’s three main menu options.

2.Use the Up and Down buttons to navigate to the the INSTALL & SERVICE menu; press the Enter button.

3.Enter a password to access INSTALL & SERVICE menus.

9.1 Setup Point

1.From the INSTALL & SERVICE menu, press Enter at the SETUP POINT prompt.

2.Use the Up/Down buttons to scroll through point numbers; press the Enter button to select a point.

TX REGISTR’D displays if a transmitter or repeater is currently registered to this point; TX NOT REGSTR’D displays if no transmitter is registered to this point.

3.Press Enter to continue.

Supervision Time: Sets a time limit on missing transmitters.

The valid range is 0 to 99 hours. The default is 60 minutes. Selecting 0 turns off supervision.

Caution: Turning off supervision can jeopardize the integrity of your system. Inovonics does not recommend turning off supervision. For supervision to function correctly, the supervision time must be set for an interval greater than the transmitter check-in time.

a.Use the Up and Down buttons to adjust the supervision time; press the Enter button to select.

b.Use the Up and Down buttons to toggle between Hrs (hours) and Min

(minutes); press the Enter button to select.

Select Security/Repeater: Configures point’s alarm and alert messages as either a repeater or a security transmitter.

a. Use the Up and Down buttons to choose SELECT SECURITY for a security transmitter or SELECT REPEATER for a repeater; press the Enter button to select.

© Inovonics, 2011 - www.inovonics.com

2

1-4 Alarm Inputs: Allows security transmitters with multiple alarm conditions to be assigned a separate output type for each individual condition.

a. Use the Up and Down buttons to navigate the number of alarm inputs for the transmitter; press the Enter to select.

Alarm Out: Maps the security transmitter’s alarm condition(s) to alarm outputs.

a.Use the Up/Down buttons to scroll through the output numbers. Choosing - - will disable alarm output.

b.Press Enter to select the output to use for the alarm condition. Alarm Output Type: Selects the output type for the alarm condition.

a.Use the Up/Down buttons to scroll through the following options:

Follower: The output reflects the transmitter’s alarm status. Press the Enter button to select.

Latching: The output turns on when activated and remains on until the receiver is reset. Press the Enter button to select.

Toggle: The output changes state each time the device sends a new activation. Press the Enter button to select.

INACTIVE displays when selected. Inactive time prevents output chatter. The valid range is 2.0 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Momentary: The output turns on for the programmed duration, then turns off, regardless of the device status. Press the Enter button to select.

MOMENT displays when selected. This sets the time that the output will stay activated. The valid range is 0.5 to 99.5 seconds, in 0.5 second

increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Inactive Out: Maps transmitter/repeater inactivity fault output.

a.Use the Up/Down buttons to scroll through the output numbers. Choosing - - will disable inactivity reporting.

b.Press Enter to select the output to use for this transmitter/repeater.

Inactive Output Type: Selects the output type for the inactive condition. a. Use the Up/Down buttons to scroll through the following options:

Follower: The output reflects the transmitter’s inactive status. Press the Enter button to select.

Latching: The output turns on when a inactive condition is sent and remains on until the receiver is reset. Press the Enter button to select.

Toggle: The output changes state each time the device becomes inactive. Press the Enter button to select.

INACTIVE displays when selected. Inactive time prevents output chatter. The valid range is 2.0 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Momentary: The output turns on for the programmed duration, then turns off, regardless of the device status. Press the Enter button to select.

MOMENT displays when selected. This sets the time that the output will stay activated. The valid range is 0.5 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the

Enter button to select.

Tamper Out: Maps transmitter/repeater tamper fault output.

a.Use the Up/Down buttons to scroll through the output numbers. Choosing - - will disable tamper output.

b.Press Enter to select the output to use for this transmitter/repeater's

tamper transmission.

Tamper Output Type: Selects the output type for the tamper condition. a. Use the Up/Down buttons to scroll through the following options:

Follower: The output reflects the transmitter’s tamper status. Press the Enter button to select.

Latching: The output turns on when a tamper condition is sent and remains on until the receiver is reset. Press the Enter button to select.

Toggle: The output changes state each time the device sends a new tamper condition. Press the Enter button to select.

Inactive displays when selected. Inactive time prevents output chatter. The valid range is 2.0 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Momentary: The output turns on for the programmed duration, then turns off, regardless of the device status. Press the Enter button to select.

MOMENT displays when selected. This sets the time that the output will stay activated. The valid range is 0.5 to 99.5 seconds, in 0.5 second

increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Low Batt Out: Maps transmitter/repeater low battery fault output.

a.Use the Up/Down buttons to scroll through the output numbers. Choosing - - will disable low battery output.

b.Press Enter to select the output to use for this transmitter/repeater's

low battery transmission.

Low Battery Output Type: Selects the output type for the low battery condition.

a. Use the Up/Down buttons to scroll through the following options:

Follower: The output reflects the transmitter’s low battery status. Press the Enter button to select.

Latching: The output turns on when a low battery condition is sent and remains on until the receiver is reset. Press the Enter button to select.

Toggle: The output changes state each time the device sends a new low battery condition. Press the Enter button to select.

INACTIVE displays when selected. Inactive time prevents output chatter. The valid range is 2.0 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Momentary: The output turns on for the programmed duration, then turns off, regardless of the device status. Press the Enter button to select.

MOMENT displays when selected. This sets the time that the output will stay activated. The valid range is 0.5 to 99.5 seconds, in 0.5 second

increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Line Power Loss Out: Maps repeater line power loss fault output.

a.Use the Up/Down buttons to scroll through the output numbers. Choosing - - will disable line power loss output.

b.Press Enter to select the output to use for this repeater's line power

loss transmission.

Line Power Loss Output Type: Selects the output type for the line power loss condition.

a. Use the Up/Down buttons to scroll through the following options:

Follower: The output reflects the repeater’s line power loss status. Press the Enter button to select.

Latching: The output turns on when a condition is sent and remains on until the receiver is reset. Press the Enter button to select.

Toggle: The output changes state each time the device sends a new line power loss condition. Press the Enter button to select. INACTIVE displays when selected. Inactive time prevents output chatter. The valid range is 2.0 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the Enter button to select.

Momentary: The output turns on for the programmed duration, then turns off, regardless of the device status. Press the Enter button to select.

MOMENT displays when selected. This sets the time that the output will stay activated. The valid range is 0.5 to 99.5 seconds, in 0.5 second increments. Use the Up and Down buttons to navigate; press the

Enter button to select.

Text: Enter eight-character descriptive text for the transmitter/repeater

a. Use Up/Down buttons to scroll through the alphanumeric characters; press Enter to select and advance to the next character. To select a space, press Enter without selecting a digit.

Note: If you do not use all eight characters, you must enter spaces to the end of the line.

b. When finished, press Enter again to complete selection.

Register Transmitter: The REGISTER TRANSMITTER option allows you to register a transmitter or repeater to the programmed point.

a. Use the Up and Down buttons to toggle between N for no and Y for yes to choose whether or not you wish to register a transmitter/repeater to the point; press Enter to select.

b.Press the transmitter/repeater’s Reset button at the RESET XMITTER prompt.

c.When TX REGD displays, press Enter to finish and advance to the next point.

d.When all transmitters have been registered, press Reset on the

receiver to clear faults.

Note: A transmitter/repeater can be registered to the point at a later time using the REGISTER XMITTER prompt in the INSTALL & SERVICE menu.

9.2 Factory Config

The FACTORY CONFIG option is used to restore the EN4216MR to its factory defaults.

Caution: Choosing FACTORY CONFIG will erase all programmed point and output information, as well as the password.

To restore the factory configuration defaults to the EN4216MR:

1. From the INSTALL & SERVICE menu, use the Up and Down buttons to navigate to the FACTORY CONFIG prompt; press the Enter button.

2. The RESET CONFIG prompt displays. Use the Up and Down buttons to choose Y for yes; press Enter to select.

3. The CONFIG RESET prompt displays; press the Enter button to return to the INSTALL & SERVICE menu.

The receiver can also be brought back to the factory default configuration through a hardware initiated sequence.

1.Connect a wire between the reset terminal and the ground terminal

2.While pressing the Back button, cycle the power to the unit

3.Release the Back button and remove the wire between the reset terminal and ground

© Inovonics, 2011 - www.inovonics.com

3

Loading...
+ 7 hidden pages