Ingersoll Rand System Automation VSD Box Instruction Manual

Ingersoll Rand
System Automation
Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and or the duties to be performed while operating and maintaining the unit. RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.
Instruction Manual
More Than Air. Answers.
Online answers: http://www.air.irco.com
C.C.N. : 80444128 REV. : B DATE : JULY 2008
SECTION 1  TABLE OF CONTENTS
Section 1 - tABLe oF contentS .............................3
Section 2 - intRoDUction ......................................4
Section 3 - SAFety ......................................................4
INSTALLATION .............................................................................4
OPERATION
MAINTENANCE AND REPAIR
..................................................................................4
.................................................4
Section 4 - coMPReSSoR connection AnD
contRoL .........................................................................5
COMPRESSOR CONNECTION AND CONTROL ................5
STANDARD CONTROL FEATURES AND FUNCTIONALITY
VSD BOX OPERATION
.........................................................................5
...............................................................6
Section 5 - inStALLAtion .........................................7
UNIT LOCATION ..........................................................................7
POWER SUPPLY
RS485 NETWORK
...........................................................................7
........................................................................7
Section 12 - PARtS LiSt .......................................... 25
IR VSD BOX .................................................................................25
Section 13 - tecHnicAL DAtA ............................... 25
VSD BOX ...................................................................................... 25
Section 14 - WiRinG DiAGRAM ............................. 26
Section 15 - coMMiSSioninG FoRM .................. 28
Refer to Section Indicated
Note
Important or Caution, Safety
PRESSURE SENSOR CONNECTIONS
VSD AND IRPCB COMPRESSOR CONNECTIVITY ..........9
IRPCB COMPRESSOR CONTROL ..........................................9
IRPCB COMPRESSOR STATUS MONITORING .................9
.............................................................................................9
READY
RUNNING
LOADED
.................................................................................... 10
......................................................................................10
....................................8
Section 6 - VSD BoX HARDWARe
conFiGURAtion ........................................................ 12
Section 7 - inGeRSoLL RAnD to VSD BoX
inteRconnect ........................................................... 13
Section 8 - coMMiSSioninG ................................. 15
Section 9 - DiSPLAy AnD MenU oPeRAtion .... 17
MENU NAVIGATION ...............................................................17
Section 10 - DiAGnoSticS ..................................... 22
Section 11 - oPeRAtion ......................................... 23
KEYPAD ........................................................................................23
DISPLAY .......................................................................................23
INDICATORS ..............................................................................23
USER MENU ITEMS.................................................................. 24
POWER FAILURE AUTORESTART ......................................24
3
SECTION 2  INTRODUCTION
The VSD Box is intended to provide a method of system integration for a VSD (Variable Speed Drive) air compressor that is not equipped with any accessible means of remote connectivity (such as the Ingersoll
SECTION 3  SAFETY
WARNING : Risk of Danger
WARNING : Risk of Electric Shock
WARNING : Risk of High Pressure
WARNING : Consult Manual
Before installing or operating the VSD BOX, take time
to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to
cause severe personal injury or property damage.
The operator should use common sense and good
working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed by adequately
qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a
competent person under qualified supervision.
A fused isolation switch must be fitted between the
main power supply and the VSD BOX.
The VSD BOX should be mounted in such a location
as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access to
the VSD BOX, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
OPERATION
The VSD BOX must only be operated by competent
personnel under qualified supervision.
Never remove or tamper with safety devices, guards
or insulation materials fitted to the VSD BOX.
Rand Nirvana). The VSD Box will provide the required functionality to enable system integration and efficient control using the X8I Automation System.
The VSD BOX must only be operated at the supply
voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are
present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical
components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment
connected to the unit should have a warning sign attached stating ‘THIS UNIT MAY START WITHOUT WARNING’ next to the display panel.
If an air compressor and/or other equipment
connected to the unit is to be started remotely, attach two warning signs to the equipment stating ‘THIS UNIT CAN BE STARTED REMOTELY’. Attach one sign in a prominent location, one on the outside of the equipment, and the other inside the equipment control compartment.
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must only be
carried out by competent personnel under qualified supervision.
If replacement parts are required use only genuine
parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening or
removing any access panels or carrying out any work on the VSD BOX:
Isolate the VSD BOX from the main electrical
i.
power supply. Lock the isolator in the ‘OFF’ position and remove the fuses.
Attach a label to the isolator switch and to the
ii.
unit stating ‘WORK IN PROGRESS - DO NOT APPLY VOLTAGE’. Do not switch on electrical power or attempt to start the VSD BOX if such a warning label is attached.
Make sure that all instructions concerning operation
and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
4
5
1
2
1
2
1
2
The accuracy of sensor devices must be checked
The VSD BOX must only be cleaned with a damp
on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any
indicators, controls, instructions or warnings.
SECTION 4  COMPRESSOR CONNECTION AND CONTROL
COMPRESSOR CONNECTION AND CONTROL
The VSD BOX is designed to connect to an X8I Automation System unit, using a 2-wire RS485 data cable.
The VSD Box is intended to provide a method of system integration for the Ingersoll Rand Bolt-On VSD’s as well as other 3rd party air compressors that are not equipped with any accessible means of remote connectivity.
Each air compressor in a system that requires VSD Box integration must be equipped with an individual VSD Box. Any number of VSD Boxes can be connected to the Automation System unit as long as the total number of compressors does not exceed the total number of compressors for the Automation System model.
In conjunction with a ‘speed monitoring kit’ (available separately) the VSD Box will provide all required functionality to maximize the ENER, energy control mode, in the X8I or X12I Automation System
3) 3rd party integrated VSD air compressors that are equipped with a single package discharge pressure sensor (1).
STANDARD CONTROL FEATURES AND FUNCTIONALITY
The Bolt-On VSD or the VSD equipped air compressor must be equipped with a 4-20mA pressure sensor or a
0.5V to 4.5VDC a pressure sensor that is used for variable speed drive regulation or compressor pressure regulation control. A VSD Box will accommodate a pressure sensor range of 1.0bar to 600bar.
Various Compressor Configurations and Characteristics Can Be Accommodated by the VSD Box. These include:
1) Bolt-On VSD air compressors that are equipped with two pressure sensors (1 and 2) that both monitor package discharge pressure. One sensor is dedicated to the compressor control system for load/unload regulation functions and the other pressure sensor is dedicated to the VSD for variable speed drive regulation.
2) Bolt-On VSD air compressors that are equipped with a package discharge pressure switch (1) dedicated to the compressor control system for load/unload regulation and a pressure sensor (2) dedicated to the VSD for variable speed drive regulation.
4) 3rd party integrated VSD air compressors that are equipped with a package discharge pressure sensor (1) and a second internal pressure sensor (2). The internal pressure sensor is generally used for internal air/oil filtration differential pressure monitoring and/ or internal pressure safety functions.
NOTE: There are VSD air compressors that are unable to maintain maximum speed operation for a prolonged period of time. In these instances, the compressor control system may automatically reduce speed regardless of demand. The VSD Box and Automation System will recognize this, and if necessary, utilize an additional compressor to meet demand.
NOTE: There are VSD air compressors that are unable to maintain minimum speed operation for a prolonged period of time. In these instances, the compressor control system may automatically stop the compressor regardless of demand. The VSD Box will recognize and accommodate this behavior. The Automation System will indicate and record the compressor status correctly without fault indication.
VSD BOX OPERATION
From VSD Box
To ir-PCB
To Intellisys Controller
From VSD Box
To ir-PCB
To 1PS Pressure Switch
From Pressure Transducer
To VSD Box
From VSD Box
To IR-5000 Pressure Transducer Input
From Pressure Transducer
To VSD Box
From VSD Box
To IR-5000 Pressure Transducer Input
All air compressors are equipped with a method of sensing pressure. An air compressor regulates using the compressor package discharge pressure as the control variable.
The VSD Box monitors the compressor pressure sensor as an input and simulates the pressure sensor signal as an output. The VSD Box uses this method to modify the pressure signal and manipulate the behavior of the air compressor. In other words, the VSD Box becomes the air compressor pressure sensor. This functionality enables the Automation System unit to utilize the compressor effectively and optimize total system efficiency and maintain air quality.
The VSD Box also monitors compressor status (Ready, Run, and Load/Unload) and continuously reports this information to the Automation System unit. This function enables the VSD Box to simulate all features of a standard X8I or X12I network compressor integration.
Actual System pressure and the Automation System ‘target’ pressure information is routinely transmitted from the X8I or X12I to the VSD Box. The VSD Box uses this information to calculate the difference between the compressor discharge pressure and the system ‘target’ pressure. The VSD Box utilizes pressure signal manipulation to continuously re-align compressor output with system requirements.
This functionality also enables the VSD Box to continuously compensate for any pressure differential that may occur across local air treatment, along air pipe work or between different locations in a compressed air network.
6
7
1
VOLTAGE SELECT
2 3 4
X04
1
VOLTAGE SELECT
2 3 4
X04
230Vac
115Vac
XPM-TAC24
L2 L1
X07
L2
L1
2
SECTION 5  INSTALLATION
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
UNIT LOCATION
The VSD Box is wall mounted using conventional screws/ bolts. The maximum distance between the X8I or X12I and the VSD Box is 4000ft (1219 meters) of cable length. The maximum distance between the VSD Box and each compressor is 330ft (100 meters) of cable length and within 330ft (100 meters) of cable length from any pressure sensor option (if applicable)..
POWER SUPPLY
A fused switching isolator must be installed to the main incoming power supply, external to the VSD Box. The isolator must be fitted with a properly sized fuse to provide adequate protection to the power supply cable used (in accordance with local electrical and safety regulations).
1 2 3 4
L
N
N L E
EE
X01
RS485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use earth shielded cables, securely bonded to a known good earth at one end. In addition, give careful consideration to cable routing during installation.
a.
Never route an RS485 data communications or low voltage signal cable alongside a high voltage or 3­phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.
b.
If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor X8I to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an earthed cable tray such that the cable tray forms an earthed electrical interference shield.
c.
Where possible, never route an RS485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).
Power Supply Terminals
Ensure that the voltage select input is properly jumpered for the incoming power. Default voltage configuration is 230Vac.
RS485 NETWORK
The VSD Box is equipped with an RS485 network communications capability using the ir485 protocol. The VSD Box is intended to operate as part of the X8I or X12I Automation System. Connection to the system management unit is two-wire, twisted pair, earth shielded, RS485 data link. Connect the RS485 data cable wires to terminal X07 located on the VSD Box ‘S1’ controller.
Note: Polarity is important.
The cable used between the X8I and the VSD Box is Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219 meters) in length.
PRESSURE SENSOR CONNECTIONS
Consult the X8I Interconnect and Application Guide prior to the installation of the VSD Box to the pressure sensor on the VSD and the compressor.
Pressure sensor connectivity is dependant on compressor and control system type.
Electrical Interference
0.5 to 4.5VDC Pressure Sensors
Voltage sensors and cables carrying low voltage analog signals are highly susceptible to interference.
4 to 20mA Pressure Sensors
Always use shielded, 18 gauge, 2-conductor cable no more than 330 feet (100 meters) in length. Ensure the shield wire is securely connected to earth ground at the VSD Box end only.
Always use shielded, braided, foil wrapped with a drain wire, 18 AWG maximum, 2-conductor cable no more than 330 feet (100 meters) in length. Ensure the braided steel wire is securely connected to a known good earth ground at both ends. Ensure the internal drain wire is securely connected to a known good earth ground at the VSD Box end only.
Failure to protect low voltage pressure signals between the compressor and VSD Box will result in unstable and/or erratic pressure readings; resulting in unstable and/or erratic compressor regulation behavior.
8
9
VSD AND IRPCB COMPRESSOR
ir-PCB
LED 1LED 2
C01 C02 C04
C03
2 4 61 3 5
X01
2 4 61 3 5
#1
V
C05
0V
+V
READY LAMP
RUN
READY
ALARM
C04
CONNECTIVITY
IRPCB COMPRESSOR STATUS MONITORING
An ir-PCB is a requirement for a VSD Box installation.
The ir-PCB is a DIN rail mountable unit designed to be installed within the compressor control or switchgear area and connected to the VSD Box using a six-wire cable.
The ir-PCB is used for compressor status monitoring and in some installations, for remote load/unload or pressure switch regulation control.
Consult the X8I Interconnect and Application Guide
prior to the installation of the VSD Box and the ir-PCB to the air compressor.
Consult the X8I Interconnect and Application Guide prior to the installation of the VSD Box and the ir-PCB to the air compressor.
The ir-PCB is fitted with a six-pin terminal C04 for compressor monitoring. The ir-PCB uses three inputs (Ready, Run and Loaded) to determine compressor status. All three status-monitoring input signals are required.
READY
The ‘Ready’ connection is intended to indicate that the compressor is in a ‘started’ state, has no operational inhibiting fault condition and is ready to respond to VSD Box regulation without manual intervention.
Ready Input
The ir-PCB uses a 12V to 250V ac/dc input voltage detection system and universal relay contact control outputs (250Vac/dc @ 5A maximum). Integrated directly into the circuits of an air compressor, the ir-PCB avoids the need for additional relays or remote inputs. The ir-PCB also acts as an electrical barrier between the compressor and the VSD Box providing protection and voltage isolation.
IRPCB COMPRESSOR CONTROL
Consult the X8I Interconnect and Application Guide prior to the installation of the VSD Box and the ir-PCB to the air compressor.
When connecting to an VSD, the VSD Box will control the ir-PCB load/unload relay outputs (terminals C01 and C02) in accordance with the VSD Box load and unload pressure set points. The ir-PCB load/unload relay contacts can be used for compressor that have pressure switch load/ unload regulation as well as those that have digital inputs for load/unload regulation.
The READY input will accept 12V to 250V ac (50/60Hz) or dc.
Caution: Do not connect a voltage greater than 250Vac/ dc to this input.
This input must be connected to the terminals of a ‘ready’ or ‘operational’ lamp, or other circuit of the compressor control system, that will be energized when the compressor is in started (standby or running) condition.
The voltage to this input must de-energize when the compressor is stopped and unavailable to produce air upon a load signal or the Emergency Stop button is pressed or when the compressor experiences a fault that prevents the compressor from running.
When the compressor ready lamp, or other control circuit, is energized the ir-PCB will detect the voltage and signal the VSD Box that the compressor is ready and available to load and produce air when a load request signal is given
Note: The ir-PCB input common terminal must always be connected to the neutral, common or 0V line of the applied input.
Ready Input, Alternative Connection Method:
F1
+Vac
0Vac
READY
0V
RUN
READY
ALARM
+V
MAIN (LINE) CONTACTOR
C04
0V
+V
MAIN (LINE) CONTACTOR
0V
+V
AUXILIARY SWITCH
RUN
READY
ALARM
C04
In instances where a convenient voltage signal for a
compressor ready condition is not available the ‘Ready’
input can be connected directly to a constant compressor
control system power supply voltage (12V to 250Vac or
dc). This will signal the VSD Box that the compressor is
ready and available at all times when power is applied
to the compressor. The VSD has a built-in function to
determine when a compressor is not responding, or is
in a shutdown condition, regardless of a constant ready
signal. If the VSD Box requests a compressor to run/load,
but fails to detect a RUN signal within 60 seconds, the
VSD Box will regard the compressor as ‘not ready’ and
indicate the compressor as not available. If a RUN signal is
detected at any time, the VSD Box will automatically reset
the compressor ‘not ready’ condition and re-establish
control.
For a fixed speed air compressor this input can be connected to the control terminals A1 and A2 (coil) of the main starter contactor of the compressor. When the compressor control system energizes the main contactor, the ir-PCB will detect the voltage across the contactor coil terminals and signal the VSD Box that the compressor is running
Alternatively, if the main contactor coil voltage is greater than 250Vac, a contactor auxiliary relay can be used to apply a suitable voltage to the ‘Run’ input terminals.
For a ‘Variable Speed’ air compressor alternative methods of determining a running condition may have to be established.
Safety: Never connect the READY input positive
connection directly to the output of a control system
transformer; always connect after a fuse or circuit breaker.
If a normally closed contact of an Emergency Stop button
is included in the compressor power supply circuit,
connect after the Emergency Stop button contacts. This
will instantly indicate a compressor ‘not ready’ condition if
the Emergency Stop button is activated
RUNNING
The majority of VSD compressors are fitted with a single main motor contactor but in most instances this contactor energizes at compressor initialization and remains energized regardless of motor running. The following alternative signals may be used to indicate motor running in most cases:-
1) The ‘Fan’ contactor – in instances where the cooling fan energizes and de-energizes in conjunction with the main motor.
2) The compressor controller ‘run’ signal to the ‘Inverter Drive Unit’; an interface relay may be required.
Note: The ir-PCB input common terminal must always be connected to the neutral, common or 0V line of the applied input voltage.
LOADED
ALARM = LOAD
The VSD Box uses the ir-PCB ALARM input to detect the load condition of the compressor. There is no Alarm input facility on the ir-PCB when used with a VSD Box. An auxiliary ‘Alarm’ input terminal within the VSD Box is available.
The RUN input will accept 12V to 250V ac (50/60Hz) only (DC can not be used).
Caution: Do not connect a voltage greater than 250V to this input.
12V to 250Vac must be applied to the ‘Run’ terminals when the compressor motor is running.
Note: A fault that stops the compressor, and/or prevents the compressor from running, is determined from the ‘Run’ and ‘Ready’ inputs; Alarm detection is optional and is not a requirement.
10
11
0V
+V
LOAD SOLENOID
RUN
READY
ALARM
C04
The LOAD input will accept 12V to 250V ac (50/60Hz) or dc.
RUN
READY
ALARM
C04
Running 0v
1
4
1
6
X04
1
3
1
5
Aux Alarm
Aux Trip
1
4
1
6
X04
1
3
1
5
X05
1
8
2
0
2
2
1
7
1
9
2
1
+
rpm
Auxiliary Trip Input (Option)
The VSD Box is equipped with an auxiliary ‘Trip’ input. The input can be used to detect a compressor shutdown trip condition. The input can also be used to monitor other auxiliary equipment associated with the compressor and initiate a compressor trip condition.
The Automation System unit will regard the trip as a compressor shutdown trip and will remove the compressor from sequence; the compressor will run-on for the compressor controller’s set run-on time and stop.
Caution: Do not connect a voltage greater than 250Vac/dc to this input.
Note: The Alarm input can not be directly connected to a Triac Output, as used on the IntelliSys controller. When connecting to an IntelliSys controller, an auxiliary relay must be used to apply a suitable voltage to the ‘Alarm’ input terminals.
The ‘Load’ input can be connected to the terminals of the compressor’s load solenoid; or other accessible part of the control circuit that is energized when the compressor is loaded.
Note: The ir-PCB input common terminal must always be connected to the neutral, common or 0V line of the applied input voltage.
For a compressor that is not equipped with a load solenoid (a compressor that is loaded at all times while running) the ‘Load’ input can be connected to the ‘Run’ input.
Auxiliary Alarm Input (Option)
The VSD Box is equipped with an auxiliary ‘Alarm (Warning)’ input. This input can be used to detect a compressor ‘Warning’ or ‘Alarm’ condition. The input can also be used to detect an ‘Alarm’ condition of auxiliary equipment associated with the compressor.
The Automation System unit will regard the alarm as a compressor alarm.
As default the auxiliary ‘Alarm’ input is normally open, Alarm on closed circuit condition. If required this can be reversed in the VSD Box setup menu to be normally closed, alarm on open circuit.
As default the auxiliary ‘Trip’ input is normally open, Trip on closed circuit condition. If required this can be reversed in the VSD Box setup menu to be normally closed, trip on open circuit.
Note: The maximum cable length for Auxiliary ‘Alarm’ or ‘Trip’ inputs is 330ft (100m).
Speed Monitoring Input (Option)
The VSD Box is equipped with a ‘speed detection’ input designed to function with a ‘VSD Speed Monitoring Kit’ (available separately). This optional feature will provide all required functionality to enable total synergy with the energy control, VSD compressor aware, functions of an X8I or X12I.
Remote Outputs
Compressor Running:
The VSD Box is equipped with a volt-free relay contact output (R5) to indicate when the compressor is detected as running. The output contacts will close when the compressor is running.
Group Alarm:
The VSD Box is equipped with a volt-free relay contact output (R6) to indicate Group Alarm. The Group Alarm relay contacts are normally closed and will open in the following conditions:-
1) VSD Box power failure
2) VSD Box internal fault condition
3) Input pressure sensor fault
4) Compressor ‘Not Ready’
3
1
3
2
3
3
3
4
X08
X09
R5
R6
Compressor Running
Group Alarm
SECTION 6  VSD BOX HARDWARE CONFIGURATION
J1
2 4 6
281027 26 25 24 23 22 21
20 19
9 8 7 6 5
4 3
2 1
18 17 16 15 14 13 12
11
KC-
KC-
8 10 12 14 16 18 20 22 24 26 282930
2725
23
21
19171513
119
7
53
1
31 32 33 34
R06
R05
X07X06X05
X04
X03
X02
X01
X08
X09
VSD/EX
+
2
4
V
D
C
0
V
X01
2 1
RS485
L
1
L
2
X04X05
L
E
D
1
123 3
s
c
r
e
e
n
X02
X03X06
-
A
N
A
1
+
A
N
A
1
VDC
4-20mA(2)
4-20mA(1)
Ao2
2 1
A
N
A
3
+
A
N
A
3
-
2 1
A
N
A
2
+
A
N
A
2
-
#1
#2
C03
C010
PASSIVE MODE
4-20mA(2)
4-20mA(1)
X06 X03
X02
VSD Box Terminal PCB Type Selector
VSD Box Terminal PCB has a jumper on it that determines the type of control box the PCB is being used in. Check to determine if jumper (J1), as shown below, is placed in the correct position for a VSD Box.
Relay contact rating:
CE: 250V @ 5A max
UL: 115V @ 5A max
XPM-Ao2 Module 4-20mA Output Mode Selectors
Remove the top cover of the XPM-Ao2 module and check the 4-20mA output mode selectors are in the ‘PASSIVE’ mode position. (The default position as shipped from the factory.)
12
13
VSD Box
XPM-Ao2
Pressure Transducer
Case Ground
IR-5000
Signal
Signal
+VDC
+VDC
COM
A1
13
60
55
39
+24
- ANA1
+ ANA1
X07
X02
SECTION 7  INGERSOLL RAND TO VSD BOX INTERCONNECT
The following drawing represents the correct method for wiring the VSD Box and Ingersoll Rand Bolt-On VSD’s.
INGERSOLL RAND INTELLISYS CONTROLLED VSD COMPRESSORS TO VSD BOX INTERCONNECT
IN
OUT
LED 4
READY
LED 3
RUN
SEQ CONT
LOAD UNL
LED 5 VFD LED 2 LOAD LED 1 SEQ
GND
D11
D12 +20V
ALARM
RUN
READY
IR-PCB
+VDC
COL
ON
HATR Contact
Restart TD Relay Contact
To TR Relay To M Contact
To 1SV To 3SV To 2CR
OFF
E-STOP
SSR UP6 20-30 FV
VFD/fixed
Load Enable Load/Unload
XCR
XCR
110VAC
110VAC
0 VAC
VSD BOX X01 TERMINAL
SG SSR
VSD BOX X01 TERMINAL
SEQ CONT
LOAD UNL
GND
D11
D12 +20V
LED 5 VFD LED 2 LOAD LED 1 SEQ
LED 4
READY
LED 3
RUN
VFD/fixed
Load Enable Load/Unload
IR-PCB
+VDC
OUT
IN
ALARM
RUN
READY
XCR
110VAC
0VAC
To Exixting Blowdown Solenoid 2CR Relay
E-STOP
1ATS
Remote Load Enable
Remote Load/Unload
Intellisys SG
INGERSOLL RAND PRESSURE SWITCH CONTROLLED VSD COMPRESSORS TO VSD INTERCONNECT
Consult the X8I Interconnect and Application Guide prior to the installation of the VSD Box and the ir-PCB to the air compressor.
14
15
COMPRESSOR
Pressure Set Points
COMPRESSOR
Pressure Set Points
I
m
m
e
d
i
a
t
e
S
t
o
p
P
r
e
s
s
u
r
e
7psi (0.5bar) min
Controlled Stop Pressure
7psi (0.5bar) min
7psi (0.5bar) min
7psi (0.5bar) min
Target Pressure
Unload Pressure
Excess or Alarm Pressure
Target Pressure
Load Pressure
Pressure
Pressure
SECTION 8  COMMISSIONING
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
Information regarding the compressor control system, method of operation and regulation settings, is required. Knowledge of VSD compressor regulation methods, experience working with compressor control systems and basic principle knowledge of compressed air systems, is also required to be able to successfully install and commission this product.
Physical Checks
Before applying power to the VSD Box ensure that the power supply connections are correct and secure and that the operating voltage selector is set correctly for the power supply voltage in use; 115Vac or 230Vac (+-10%), 50/60Hz; see ‘Installation’.
Check and ensure all pressure sensor, output pressure signal and ir-PCB connections are correctly installed and secure.
Compressor Pressure Set Points
Establish the following pressure set point values from the compressor control system.
NOTE: For fixed speed compressors the ‘target’ pressure can be set at the mid-point between the compressor ‘load’ and ‘unload’ pressure set points.
4) The maximum Discharge pressure level (and maximum Internal pressure level if used) set in the compressor controller. This value will be the Excess or High pressure Alarm safety level. On fully integrated VSD compressor controllers this value may be represented as the ‘Immediate Stop Pressure’ level.
Establishing the correct compressor pressure set
point values is critical to successful VSD Box operation.
1) Compressor ‘Load’ pressure set point: The pressure at which the compressor will start/load.
On 3rd party fully integrated VSD compressor
controllers this value may be represented as the ‘Target Pressure’ level.
2) Compressor ‘Unload’ pressure set point. The pressure at which the compressor will stop/unload.
On 3rd party fully integrated VSD compressor
controllers this value may be represented as the ‘Controlled Stop Pressure’ level.
3) Compressor ‘Target’ pressure set point.
For 3rd party integrated VSD type compressors this
is the pressure that the variable speed drive is set to maintain.
This value will generally be the same as the ‘load’ pressure set point for 3rd party variable speed compressors that have fully integrated VSD control systems. For Ingersoll Rand Bolt-On VSD compressors, this value will be the mid-point between the ‘load’ and ‘unload’ pressure set points.
NOTE: If the variable speed ‘target’ pressure is set separately from the compressor controller (in the variable speed drive controller menu or using a potentiometer connected to the variable speed drive controller), then the compressor controller is not a fully integrated type. In this instance the ‘target’ pressure may have to be determined by observation and/or experiment.
NOTE: If the compressor pressure set points have been set with small differentials then the pressure set points of the compressor will require adjustment before proceeding.
NOTE: It is recommended that the pressure differential between the ‘load’ and ‘unload’ (or ‘target’ and ‘controlled stop’) pressures is a minimum of 7psi (0.5bar).
NOTE: It is recommended that the pressure differential between the ‘unload’ and ‘excess’ (or ‘controlled stop’ and ‘immediate stop’) pressures is a minimum of 7psi (0.5bar).
VSD Box Configuration
Output Pressure Signal Calibration
Apply power to the VSD Box.
If the VSD Box automatically starts (the green started indicator illuminates or flashes) press the STOP button.
Using the VSD Box menu routines, set the ‘IC’ (I/O Configuration - Type) in menu P03 to the correct setting for the pressure sensor input/output configuration.
VSD Box Network Address
Each VSD compressor connected to the Automation System unit must be assigned a unique compressor identification number (1 to the maximum number of compressors). This number will be the ‘network address’ number for the compressor. The number should be clearly marked on the compressor for identification purposes.
When connecting a compressor(s) to the VSD Box, always use the Automation System unit’s unique identification number as the compressor ‘network address’ number.
Using the VSD Box menu routines, set the ‘Ad’ (Network Address) in menu P03 to the Automation System unit’s compressor identification number.
Input Pressure Sensor(s)
The offset and range of the pressure sensor(s) used on the compressor must be established for VSD Box pressure sensor calibration. Generally this information is indicated on the pressure sensor label.
The correct ‘offset’ and ‘range’ values of each pressure sensor are required for VSD Box ‘input’ pressure sensor calibration.
Using the VSD Box menu navigation procedure, select menu page P05 (Output Pressure Calibration). The ‘items’ of this menu enable calibration of the pressure signal(s) transmitted to the compressor controller.
Pressure Set Points
Establishing and implementing the correct pressure
set points is critical for successful VSD Box operation.
Using VSD Box menu navigation, select menu page P03 (Configuration).
1) Set the ‘Dm’ (Discharge Pressure Maximum Limit) to the compressor’s ‘Excess Discharge Pressure Alarm’ or ‘Immediate Stop’ pressure setting.
2) If an ‘Internal’ pressure sensor is in use set the ‘Im’ (Internal Pressure Maximum Limit) to the compressor’s ‘Excess Internal Pressure Alarm’ pressure setting. Typically this value will be at least 12psi (0.8bar) above the excess or alarm ‘discharge’ pressure limit.
Using VSD Box menu navigation, select menu page P01 (Pressure Set Points).
1) Set the ‘Pu’ (Unload) pressure set point to the compressor’s ‘Unload’ or ‘Controlled Stop’ pressure set point value.
2) Set the ‘Pt’ (Target) pressure set point to the ‘target’ pressure setting established for the compressor.
3) Set the ‘PL’ (Load) pressure set point to the compressor’s ‘Load’ or ‘Target’ pressure set point value.
The main value display should show a pressure value; for example 0.0 bar. If the display shows dashes (- - - -) check the ‘Discharge‘ pressure sensor connections.
Note: Wire polarity is important.
If an ‘Internal’ pressure sensor is in use press DOWN to view the ‘P2’ pressure value in the User menu ‘items’ display. The ‘P2’ value display should show a pressure value; for example 0.0 bar. If the display shows dashes (- -
- -) check the ‘Internal‘ pressure sensor connections.
Note: Wire polarity is important.
At this stage the displayed pressure values will probably be incorrect; this is normal.
Calibrate the input ‘Discharge’ pressure sensor, and input ‘Internal’ pressure sensor if used, following the input ‘Pressure Sensor Calibration’ procedure below:
Input and Output pressure calibration is critical for
successful VSD Box operation. Input Pressure Sensor Calibration
Using the VSD Box menu navigation procedure, select menu page P04 (Input Pressure Calibration). The ‘items’ of this menu enable calibration of the pressure sensor(s) connected to the VSD Box.
16
17
SECTION 9  DISPLAY AND MENU OPERATION
MENU NAVIGATION
Display Item Structure:
All value, parameter or option selection displays are grouped into menu lists. Items are assigned to a list according to type and classification. Items that can be used to select options or modify functions are assigned to ‘menu mode’ lists. Items that a User may require to view during routine operation, detected pressure for example, are assigned to the normal operational mode list. Lists are identified by page number; the normal User display list is page ‘P00’. All parameters and options are assigned to menu mode pages ‘P01’ or higher. All Page ‘P00’ items are view only and cannot be adjusted.
Normal Operational Mode (Page P00):
At controller initialization, all display elements and LED indicators are switched on for three seconds, the display will then show the software version code for a further 3 seconds before initialization is complete and the normal operating display (Page P0) is shown. In page P00 ‘normal operational display mode’ the main display will continuously show the detected delivery pressure and the Item display will show the first item of the ‘User’ menu. User menu ‘Items’ can be selected using the Up or Down buttons at any time. Pressing the Enter button will lock any selected Item display and inhibit return to the default display. When an Item display is locked the lock key symbol will slow flash. To unlock an Item display press Up or Down to view an alternative Item display or press Reset or Escape. No Item values, options or parameters can be adjusted in page ‘P00’. If a fault condition occurs the fault code becomes the first list item and the display will automatically jump to display the fault code. More than one active fault code item can exist at any one time.
Access Code:
Access to page list displays higher than page ‘P00’ is restricted by access code. To access menu mode pages press MENU, an access code entry display is shown and the first code character will flash. Use PLUS or MINUS to adjust the value of the first code character then press ENTER. The next code character will flash; use UP or DOWN to adjust then press ENTER. Repeat for all four code characters.
Access Code Timeouts:
When in menu mode, if no key activity is detected for a period of time the display will automatically reset to the normal operational display; Page ‘P00’.
Menu Mode Navigation:
In menu mode the main value display will flash and show the Page number. To select a page press UP or DOWN. For each page the display will show the first Item of the page list. To view a page list press ENTER, the Page number will stop flashing and the Item display will flash. Press UP or DOWN to view the selected page list items. To select an Item value for modification, press ENTER. The Item display will stop flashing and the Value display will flash. The value or option can now be modified by pressing UP(Plus) or DOWN(Minus). To enter a modified value or option in memory press, ENTER. Alternatively, the modification can be abandoned and the original setting maintained by pressing ESCAPE.
Press ESCAPE at any time in menu mode to step backwards one stage in the navigation process. Pressing ESCAPE when the page number is flashing will exit menu mode and return the display to normal operational mode; page ‘P00’.
Press and hold RESET for two seconds at any time
to immediately exit menu mode and return to the normal operational mode display. Any value or option adjustment that has not been confirmed and entered into memory will be abandoned and the original setting maintained
A flashing Key symbol displayed with any Item
indicates the Item is locked and cannot be modified. This will occur if the Item is view only (non adjustable) or in instances where the item cannot be adjusted while the EX Box is in ‘Remote Mode’.
If the code number is less than 1000 then the first code character will be 0(zero). To return to a previous code character press ESCAPE. When all four code characters have been set to an authorized code number press ENTER. An invalid code will return the display to normal operational mode; page ‘P00’.
Menu Items and Settings
MENU P00 - User
1 P1 Discharge Pressure - Output (view only) 2 P2 Internal Pressure - Output (view only) 3 SP Percent Speed (view only)
MENU P01 - Pressure Set Points
1 Pu Unload Pressure 2 Pt Target Pressure 3 PL Load Pressure
MENU P02 – Error Log
1 Hr VSD Box Operating Hours 2 01 Error Log #1
to
16 15 Error Log #15
MENU P10 – Unit Configuration
1 D7 Aux Alarm Input Configuration 2 D8 Aux Trip Input Configuration 3 SQ ir-PCB Sequence control hold 4 Ao Analog Output Function (4-20mA) 5
Er Error Log Reset
6 Hr VSD Box Operating Hours Adjust
MENU P16 – Analog Output Diagnostic
See ‘Diagnostics’
Note: Menus P07, 9 and 11 to 15 are not used.
Access Code = 0021
MENU P01 - Pressure Set Points
MENU P03 - Configuration
1 P> Pressure Units Select 2 Ad Network Address (Compressor No.) 3 PA Pressure Averaging Factor 4
IC I/O Configuration (Type) 5 DM Discharge Pressure Maximum Level 6 Im Internal Pressure Maximum Level
MENU P04 – Input Pressure Calibration
1 Do Discharge Pressure ‘Offset’ 2 Dr Discharge Pressure ‘Range’ 3
Io Internal Pressure ‘Offset’ 4 Ir Internal Pressure ‘Range’
MENU P05 – Output Pressure Calibration
1 Do Discharge Pressure ‘Offset’ 2 Dr Discharge Pressure ‘Range’ 3
Io Internal Pressure ‘Offset’ 4 Ir Internal Pressure ‘Range’
MENU P06 / Diagnostics
See ‘Diagnostics’
Pu: Unload Pressure
Compressor ‘Unload’ pressure set point: The pressure at which the compressor will stop/unload. On fully integrated VSD compressor controllers this value may be represented as the ‘Controlled Stop Pressure’ level. Set the ‘Pu’ (Unload) pressure set point to the compressor’s ‘Unload’ or ‘Controlled Stop’ pressure set point value.
Pt: Target Pressure
Compressor ‘Target’ pressure set point. For VSD type compressors this is the pressure that the variable speed drive is set to maintain. Set the ‘Pt’ (Target) pressure set point to the ‘target’ pressure setting established for the compressor.
PL: Load Pressure
Compressor ‘Load’ pressure set point: The pressure at which the compressor will start/load. On fully integrated VSD compressor controllers this value may be represented as the ‘Target Pressure’ level. Set the ‘PL’ (Load) pressure set point to the compressor’s ‘Load’ or ‘Target’ pressure set point value.
Establishing and maintaining the correct pressure set point values (Pu, Pt and PL ) is critical to the successful operation of VSD Box control functions.
See ‘Commissioning - Pressure Set Points’
MENU P02 - Error Log
MENU P08 – Speed Monitoring
1 FL Frequency at Minimum Speed 2 FH Frequency at Maximum Speed 3
C< Control Percentage (view only)
The first item of the log error menu is the VSD Box operational hours (Hr). This is an indication of the accumulated hours the VSD Box has been operational and is used to time-stamp fault codes in the error log. The hours counter has no other function.
The VSD Box operating hours counter is NOT intended as a measure of compressor operation or running hours; the hours counter will differ from, and operate independently from, the compressor hours counter.
18
19
Each error log item will show the fault code alternating with the VSD Box operational hours when the fault occurred. The error log stores the last 15 faults in chronological order; item ‘01’ is the most recent fault.
MENU P03 – Configuration P>: Pressure Units Select
Selects the display pressure units (bar, psi or kPa)
Im: Internal Pressure Maximum Level
If the detected Internal pressure input exceeds this setting ‘Pressure Control’ is disabled and the detected Discharge and Internal pressure is transmitted directly to the compressor controller without alteration. This is intended as a safety feature that will allow the safety functions of the compressor controller to respond to excess pressure situations.
Ad: Network Address
Network address; must be set to the compressor identification number used by the Automation System unit for the compressor (1 to the maximum number of compressors). Each compressor in a system must have a unique identification number.
PA: Pressure Averaging Factor
Pressure corrections supplied by the Automation System unit are averaged to prevent abrupt changes and enable smooth and controlled pressure adjustments. The Automation System updates pressure information approximately every two seconds. The ‘Pressure Averaging Factor’ is the number of previous pressure corrections that are used for averaging. For example: a factor of ‘2’ will average the most recent pressure correction value received with the previous two values received.
If system volume is large and/or pressure variations are slow a higher ‘Pressure Averaging Factor’ can be used to dampen response and smooth control pressure changes. If system volume is small and/or pressure variations are fast a lower ‘Pressure Averaging Factor’ should be used to enable a faster response. In some instances pressure differential across air treatment and/or small diameter pipe work can result in sudden and abrupt changes in detected pressure.
A higher ‘Pressure Averaging Factor’ can be used to dampen this effect.
IC: I/O Configuration (Type)
Determines the pressure detection and pressure output signal configuration.
‘1’ – Discharge pressure 4-20mA input with associating discharge pressure 4-20mA output. Internal pressure is ignored.
‘2’ – Discharge pressure 4-20mA input and Internal pressure 4-20mA input with associating 4-20mA outputs.
‘3’ – 0.5V to 4.5V Discharge pressure input with associating 0.5V to 4.5V output.
Internal pressure is ignored.
Dm: Discharge Pressure Maximum Level
If the detected Discharge pressure input exceeds this setting ‘Pressure Control’ is disabled and the detected Discharge pressure (and Internal pressure if in use) is transmitted directly to the compressor controller without alteration. This is intended as a safety feature that will allow the safety functions of the compressor controller to respond to excess pressure situations.
Note: Internal compressor pressure will increase over time with an increase in air/oil separator element differential and will generally be 0.8bar (12psi) above discharge pressure.
MENU P04 – Input Pressure Calibration Do: Discharge Pressure Offset
This parameter will be the minimum value of the pressure transducer, 0 PSI, 0 BAR, or 0 kPA. It can also be used to create an ‘Offset’ if there is a difference in the zero value being displayed. The default setting for this parameter is 0 PSI. The values for this parameter are:
“0” when using the minimum value of the pressure transducer range
A value greater than or less than 0 if the display does not read 0 or when using an Offset pressure transducer (an example of an Offset pressure transducer would be one where the range was minus PSI (-25) to a positive PSI (200).
The pressure transducer must be vented to atmosphere when setting the 0 or offset.
Dr: Discharge Pressure Range
This parameter will be the maximum range of the pressure transducer, 232 PSI, 16 BAR, or 1600 kPA. It can also be used to create an ‘Offset’ if there is a difference in the range value being displayed. The default setting for this parameter is 232 PSI. The values for this parameter are:
“232” when using the maximum value of the pressure transducer range
A value greater than or less than 232 if the display does not read 232.
The pressure transducer must have a known, accurate pressure applied to it when changing this value to a value other than 232.
Calibration Checks
When the ‘Discharge’ pressure sensor offset and range menu items are selected the menu page display value will change to show the actual detected ‘Discharge’ pressure measurement. This value can be used to compare with a ‘known’ pressure applied to the ‘Discharge’ pressure sensor for accurate calibration purposes. An independent and accurate means of measuring the applied pressure is required.
1) Subject the ‘Discharge’ pressure sensor to atmosphere 0psi (0bar).
2) Adjust the ‘Do’ pressure ‘offset’ value until the ‘Discharge’ pressure displayed by the VSD Box shows 0psi ((0) bar.
3) Apply a known pressure to the ‘Discharge’ pressure sensor. It is recommended that the applied pressure is representative of normal working pressure levels. It is not important if the applied pressure is static or continuously fluctuating.
4) Adjust the ‘Dr’ pressure ‘range’ value until the ‘Discharge’ pressure displayed by the VSD Box shows the same as the ‘known’ applied pressure.
The detected pressure is displayed with the calibration menu item and will change to match the new calibration setting as the setting is adjusted.
1) Subject the input ‘Discharge’ pressure sensor to atmosphere 0psi (0bar).
2) Adjust the ‘Do’ pressure signal ‘offset’ value until the compressor controller’s discharge pressure display value shows 0psi (0) bar.
3) Apply a known pressure to the input ‘Discharge’ pressure sensor. It is recommended that the applied pressure is representative of normal working pressure levels. It is not important if the applied pressure is static or continuously fluctuating.
4) Adjust the ‘Dr’ pressure signal ‘range’ value until the compressor controller’s discharge pressure display value shows the same as the VSD Box discharge pressure.
Io: Internal Pressure Offset
Use the same procedure as described for Do: to set the Offset for Io:
Ir: Internal Pressure Range
There is no need for the applied pressure to be static; it can be dynamic and changing. This enables calibration to be carried out on a fully operational system where changing system pressure can be accurately verified from another source.
Correct pressure sensor set-up and calibration is critical for successful system operation. It is recommended that pressure sensor calibration is examined, and adjusted if necessary, annually or a pre­determined routine periodic basis.
Io: Internal Pressure Offset
Use the same procedure as described for Do: to set the Offset for Io:
Ir: Internal Pressure Range
Use the same procedure as described for Dr: to set the Offset for Ir:
Follow the same procedure described above for Do: and Dr: Calibration Checks for applying adjustments to the ‘Io’ (Internal offset) and ‘Ir’ (Internal range).
MENU P05 – Output Pressure Calibration Do: Discharge Pressure Offset
Enter the ‘OFFSET’ value for the ‘Discharge’ pressure signal in the ‘Do’ menu item. Set this value will to same as the initial ‘Discharge’ pressure sensor input ‘offset’.
Dr: Discharge Pressure Range
Enter the ‘RANGE’ value for the ‘Discharge’ pressure signal in the ‘Dr’ menu item. Set this value to the same as the initial ‘Discharge’ pressure sensor input ‘range’.
Calibration Checks
When the output ‘Discharge’ pressure signal offset and range menu items are selected the menu page display value will change to show the actual detected input ‘Discharge’ pressure measurement. This value represents the pressure the VSD Box is attempting to transmit to the compressor controller and can be used to compare with the compressor controller’s displayed pressure value.
Use the same procedure as described for Dr: to set the Offset for Ir:
Follow the same procedure described above for Do: and Dr: Calibration Checks for applying adjustments to the ‘Io’ (Internal offset) and ‘Ir’ (Internal range).
Input and Output pressure calibration is critical to the successful operation of VSD Box functions and must be examined, and adjusted if necessary, periodically on a routine basis.
MENU P08 – Speed Monitoring FL: Frequency at Minimum Speed
Used for optional ‘Speed Monitoring Kit’ if fitted. Must be set to 0(zero) if speed detection is not in use.
Note: Intended for inverter drive variable speed type compressors.
The inverter drive output frequency at the compressor’s minimum operating speed.
When this menu item is selected the menu page number display will change to show the actual detected frequency. By restricting the output air from the compressor the compressor inverter drive can be forced to minimum speed. Set the value to the lowest frequency detected.
The frequency setting must represent the lowest inverter drive output frequency that will occur in normal operation.
FH: Frequency at Maximum Speed
Used for optional ‘Speed Monitoring Kit’ if fitted. Must be set to 0(zero) if speed detection is not in use. Intended for inverter drive variable speed type compressors.
The inverter drive output frequency at the compressor’s maximum operating speed.
20
21
When this menu item is selected the menu page number display will change to show the actual detected frequency. By creating a demand for air the compressor inverter drive can be forced to maximum speed. Set the value to the highest frequency detected.
The frequency setting must represent the maximum (100%) inverter drive output frequency that will occur in normal operation.
C>: Control Percentage
This menu item value is view only and cannot be adjusted. The value represents the variation in inverter drive output frequency; where 0% is minimum speed and 100% is maximum speed.
Note: The ‘Control Percentage’ value represents the percentage of speed variation from minimum speed to maximum speed and differs from the ‘User’ menu percent motor speed value. This value is used internally by the VSD Box for Automation System unit functions and is only active when an optional ‘Speed Monitoring Kit’ is installed.
MENU P10 – Unit Configuration D7: Auxiliary Alarm Input Configuration
‘0’ – Disabled
‘9’ – Detected Discharge pressure
‘10’ – Detected Internal pressure
Er: Error Log Reset
Adjust to ‘RST’ and press ENTER to clear and reset the ‘Error Log’ menu.
Hr: VSD Box Operating Hours Adjust
Allows adjustment of the VSD Box operating hours counter. The accumulated hours counter is used for ‘Error Log’ time-stamp only and has no other function.
Determines the input configuration for the auxiliary Alarm input:
‘0’ – Normally open, Alarm when closed
‘1’ – Normally closed, Alarm when open
D8: Auxiliary Trip Input Configuration
Determines the input configuration for the auxiliary Trip input:
‘0’ – Normally open, Trip when closed
‘1’ – Normally closed, Trip when open
SQ: ir-PCB Sequence Control Hold
If using the ir-PCB load relay output on a remote digital input pressure control, or pressure switch, type compressor controller, it may be desirable to maintain VSD Box load/unload control of the compressor when the VSD Box is stopped.
If this item is set to ‘1’ the VSD Box will continue to load and unload the compressor, in accordance with the set VSD Box ‘load’ and ‘unload’ pressure set points, at all times.
If set to ‘0’ (Default) the VSD Box will deactivate remote pressure control (SEQ) and/or re-introduce the pressure switch, when the VSD Box is stopped. The compressor will operate in ‘local’ pressure control mode.
Ao: Analog Output Function
The VSD Box controller is equipped with a 4-20mA auxiliary output. The output can be used to remotely signal the selected analog value.
SECTION 10  DIAGNOSTICS
The VSD Box controller is equipped with comprehensive diagnostic functions. Each input can be examined individually and each output can be manually activated or manipulated individually.
Controller Diagnostics:
Menu P06 - Diagnostics
D1 Digital Input 1 D2 Digital Input 2 ON D3 Digital Input 3 D4 Digital Input 4 D5 Digital Input 5 D6 Digital Input 6 D7 Digital Input 7 D8 Digital Input 8
---------------------------------------------------------------------------
R1 Relay Output 1
R3 Relay Output 3 R4 Relay Output 4
R6 Relay Output 6
---------------------------------------------------------------------------
A1 Analog Input 1 bar <> mA A2 Analog Input 2 bar <> mA A3 Analog Input 3 bar <> +VDC
---------------------------------------------------------------------------
Ao Analog Output 1 4.0 to 20.0mA
Digital Inputs:
D2 and D6 (connected to the ir-PCB) are the only digital inputs that will detect a pulsing signal.
D2: ir-PCB Compressor Ready/Run Status
OFF Not Ready
OFF
Pulsing
OFFR2 Relay Output 2
ONR5 Relay Output 5
Relay Outputs:
Each relay output can be energised and de-energised manually by selecting the item. Use PLUS and MINUS to adjust and ENTER.
Analog Inputs:
The item will alternate between the detected value and the electrical measurement on the input terminals. An independent measuring device can be used to check the displayed electrical measurement.
A1: Discharge Pressure 4-20mA
A2: Internal Pressure 4-20mA
A3: Discharge Pressure 0.5-4.5VDC
Analog Output:
The output can be manually adjusted by selecting the item. Use PLUS and MINUS to adjust and ENTER. The output will return to normal operational value upon menu exit.
XPM-Ao2 Module Diagnostics:
MENU P16 / XPM-Ao2 Diagnostics
A1 Analog Output 1 4-20mA #1 A2 Analog Output 2 4-20mA #2 A3 Analog Output 3 0.5-4.5VDC
Analog Outputs:
Each output can be manually adjusted by selecting the item. Use PLUS and MINUS to adjust and ENTER. The output will return to normal operational value upon menu exit.
A1: Discharge Pressure 4-20mA
A2: Internal Pressure 4-20mA
A3: Discharge Pressure 0.5-4.5VDC
ON Ready
Pulsing Running
D3: ir-PCB Compressor Load/Maintenance
OFF Alarm (unless reversed in menu)
ON OK (unless reversed in menu)
Pulsing Service Maintenance
The pulse signal is 24VDC at 50/60Hz. A DC voltage meter will detect this as 12VDC +-4V.
22
23
SECTION 11  OPERATION
a
b
c
d
f
g
h
e
psi
A
C
B
KEYPAD
Start
a.
Reset
b.
Stop
c.
Menu
d.
Enter
e.
Escape (Cancel)
f.
Up (Plus)
g.
Down (Minus)
h.
DISPLAY
Flashing - Not Responding, Compressor Not Running When Required
Flashing - Not Responding, Compressor Not Loading When Required
Service Maintenance function active
Discharge Pressure or Internal Pressure has exceeded the maximum set limit
Compressor Not Ready
Fault, Auxiliary Input Alarm/Trip
Pressure Control OFF or inhibited
Load Request to compressor
Unload Request to compressor
Pressure Control Active
INDICATORS
Run Indicator (Green LED)
OFF - Pressure Control Off, Stopped Flashing - Pressure Control ON, waiting for
compressor to respond ON - Pressure Control On, Started
Fault Indicator (Red LED)
OFF – No fault Flashing – VSD Box Fault Condition (see Fault
Codes)
The primary display value (A) will continuously show the detected ‘Discharge’ pressure. The pressure is derived from the compressor ‘Discharge’ pressure sensor and the displayed value is not manipulated or adjusted.
The compressor controller ‘Pressure Display’ may not represent the actual true local pressure(s) when VSD Box ‘Pressure Control’ is active. Use the VSD Box ‘Input’ pressure display(s) for local pressure reference.
The ‘User Menu’ item display (B) will show the selected user menu item. Press UP or DOWN to scroll through the display ‘items’ list.
Status Symbols
The Status display will continuously show the current state of the VSD Box (C) by using the following icons.
Power Failure Auto Restart (always on)
Communicating with System Management Controller
Flashing - No Communications with System Management Controller
Compressor Running
Compressor Loaded
The VSD Box will report that the compressor is ‘Not Available’ to the Automation System controller when the VSD Box is in a stopped or fault condition.
Start
Press START to activate VSD Box pressure control. The run indicator (9) will illuminate or flash.
The compressor must be in a started state (running or
in standby) before VSD Box pressure control will function.
When started the VSD Box will begin to manipulate the pressure signal(s) to the compressor controller – ‘Pressure Control’ is active.
Pressure Control will de-activate automatically if communications with the system management unit is disrupted or not connected; the detected pressure from the pressure sensor(s) is re-transmitted to the compressor control directly
VSD Box will automatically re-activate ‘Pressure Control’.
When communications are re-established the
Stop
Percentage Motor Speed:
Press STOP to de-activate VSD Box pressure control. The run indicator (9) will extinguish.
When stopped the VSD Box will not manipulate or adjust the pressure signal(s) to the compressor controller; the detected pressure from the pressure sensor(s) is re­transmitted to the compressor control directly.
The VSD Box will report that the compressor is ‘Not Available’ to the system management unit when the VSD Box is in a stopped condition.
Note: During compressor service or routine maintenance the VSD Box can be stopped to return the compressor to normal local pressure regulation.
Compressor Status
The detected status of the compressor is indicated by the VSD Box display status symbols (see Status Symbols)
VSD Box Status
VSD Box operation is indicated by the ‘Run’ LED indicator (see Indicators). Pressure Control status is indicated by the ‘pressure’ status symbols (see Status Symbols).
USER MENU ITEMS
To view the ‘User Menu Items’ press UP or DOWN. The ‘Item’ display value will scroll through the available items.
P1 ‘Discharge’ output pressure transmitted to the compressor controller.
The percentage of detected motor speed compared to maximum motor speed. This value provides a direct indication of variable speed compressor output regulation.
VSD Box Status:
The central ‘item’ display value (B) is the compressor system identification number (network address number). This is the same as the compressor system identification number shown on the system management unit.
The ‘right hand’ display value indicates the VSD Box status condition (see Status Block Diagram).
POWER FAILURE AUTORESTART
Power failure auto restart is always active and cannot be de-activated.
The VSD Box will re-start if the VSD Box was in an operational started status before the break or failure of the main power supply occurred.
The VSD Box will not re-start if it was not in an operational started status before the break or failure of the main power supply occurred.
Fault Codes
If a VSD Box fault, or auxiliary input fault, occurs the ‘Item’ display will show a fault code:
0080E Auxiliary Input Shutdown Trip
P2* ‘Internal’ output pressure transmitted to the compressor controller.
SP** Percent motor speed
C> VSD Box Status
(*) The ‘Internal’ output pressure item is only shown if the ‘Internal’ pressure control function is activated (IC = 2).
(**) The percentage motor speed item is only shown if a ‘Speed Monitoring Kit’ is fitted and the function is activated (Menu P08).
Discharge Output Pressure:
The discharge output pressure is manipulated during ‘Pressure Control’ and will differ from the actual ‘Input Discharge’ pressure displayed as the main display value. Pressure control function can be observed by comparing the ‘Output’ discharge pressure with the actual detected ‘Input’ discharge pressure. The two pressures will be identical when ‘Pressure Control’ is not active.
Internal Output Pressure:
The internal output pressure is manipulated during ‘Pressure Control’ to simulate and maintain the actual detected differential between the ‘Input’ discharge pressure and the ‘Input’ Internal pressure. This functionality allows compressor controller differential pressure monitoring functions to be maintained regardless of VSD Box output pressure signal manipulation.
0115E 4-20mA Discharge P. Sensor Fault 0125E 4-20mA Internal P. Sensor Fault 0135E 4.5VDC Discharge .P. Sensor Fault 0821E Short Circuit Condition Detected
Check all inputs and outputs. 0845E S1 Controller Communications with XPM-Ao2
unit disrupted 2070A Auxiliary Input Alarm
Press RESET to reset the fault code display when the fault condition is resolved.
24
25
SECTION 12  PARTS LIST
20mm
5mm
IEC
3 2 1
24mm
238mm
24mm
188mm
8mm Ø
236mm
286mm
Item Part No. Description
- 42659417 Kit, VSD Box
- 23242225 Unit, VSD Box
- 80444086 Manual, User CD
1 42659490 Controller, VSD 2 42659284 Unit, XPM-PSU24 3 23242282 Unit, XPM-Ao2 4 39265913 Unit, XPM-TAC24 5 23242993 PCB, Terminal VSD 6 38036703 Gland, Set - Pg13.5 7 39265921 Unit, ir-PCB
6
XPM-Ao2
XPM-PSU24
4
5
Optional Accessories:
Item Part No. Description
8 39265939 Sensor, Pressure
4-20mA, 0-16.0bar
Qty Part No. Description
10 39265962 IEC Fuse T1.0A 10 39265970 IEC Fuse T1.6A 10 39265988 IEC Fuse T3.15A
SECTION 13  TECHNICAL DATA
Dimensions 11.45” x 9.45” x 6.0”
291mm x 241mm x 152mm Weight 14Ib (6.5kg) Mounting wall, 4 x screw fixings Enclosure IP54, NEMA 12 Supply 230Vac +/- 10%
115Vac +/- 10% Power 50VA Temperature 0°C to 46°C (32°F to 115°F) Humidity 95% RH non-condensing
7
ir-PCB
8
SECTION 14  WIRING DIAGRAM
x
o B
D S V
r lle
o
r
t n o
C 1
S
2
0 X
+VDC
5 R
6 R
Ai1
5
+VDC
0 X
Ai2
A-GND
Ai3
A-GND
6
o
0
A
k
r
m
o
e
t
tw
s
e
y S
N
1
2
L
L
5 8
7
i4
0
lt u
X
M
1
#
1
5
L
8
4
2 L
S
R
X
+ C
1 2 3
4
4
0 X
5 6 7 8
C023
C035
C036 C037 C038 C039 C040
C034
C033
C032 C031 C030 C029 C028 C027 C026 C025 C024
1
2
3
4
4
3 3
3 2
3 1
3
0
3
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
9
1
8
1
7
1
9
0 X
8
0
7
0 X
6
0 X
5
0 X
R6
R6 R5
R5
+
Ai3
-
-
Ai2
+
-
Ai1
+
+
Ao
-
A-GND
Di5 +C
Speed Signal
Di4 +C Di3 +C
Group Alarm
Compressor Running
0.5 to 4.5VDC Delivery P. < IN
4-20mA Internal P. < IN
4-20mA Delivery P. < IN
8
0 X
5 8 4
M P X
1 0 X
1
1
N
L
N
L
230Vac 10% 115Vac 10%
+C
Di7
4
0 X
+C Di8
R2
3
0 X
GND
R1 R3
2
0 X
GND GND
+
Di2
1 X
Di6
0 X
-
R4
R1
1
J
-
6
0.5-4.5VDC
0 X
Delivery P. > OUT
+
-
3
4-20mA
0 X
Internal P. > OUT
+
-
2
4-20mA
0 X
Delivery P. > OUT
+
Aux Alarm
Aux Trip
SEQ
+20VDC Ready/Run
Load/Service GND
LOAD SEQ
B C P
i-
Ao3
Ao2 +
Ao1 +
6
1
5
1
4
1
3
1
2
1
1
1
0
1
9
8
7
6
5
4
3
2
1
2 1
2 1
2 1
3
0
2
#
1
5
L
8
4
2 L
S
R
c a V 4 2
2
2 0 X
2
E
E
E
X
1 R
2 R
3 R
4 R
C041
4
2
3
C
0
2
A
X
T
­M
P X
1
3
c
2
1
a
0
V
X
4
1
2 C
2
2
D
0
V
X
1
4 2
1 0 X
4
2 U S P
­M
P X
c a V 4 2
c a V 0
C044
C045
C046
C047
C048
C049
C042
C043
10k
A-GND
2
C
2
-
D V 4
1
+
2
1
1
L 2
2
L
3
M
o
P
1 0 X
5 0 X
A
X
0
E
1
V
0
I
C
S
&
S
3
A
0
P
C
26
27
XPM-TAC24
XPM-Ao2 (Analog Output)
XPM-PSU24 (24Vac to 24VDC)
+
2
4
V
D
C
0
V
X01
2 1
RS485
L
1
L
2
X04
X05
L
E
D
1
123 3
s
c
r
e
e
n
X02
X03X06
-
A
N
A
1
+
A
N
A
1
VDC
4-20mA(2)
4-20mA(1)
Ao2
2 1
A
N
A
3
+
A
N
A
3
-
2 1
A
N
A
2
+
A
N
A
2
-
#1
#2
C010
ACTIVE
PASSIVE
X03
4-20mA(2)
C03
ACTIVE
PASSIVE
X02
4-20mA(1)
-
+
-
PASSIVE MODE
0VDC
­+
+
-
+12-30VDC
ACTIVE MODE
XPM-Ao2
500R
max
+
-
+
-
+24VDC
0VDC
500R max
+24VDC
LED 1
LED 2
PSU24
3
2
2
4
V
a
c
0
V
a
c
X01
1
1
2
+
2
4
V
D
C
X02
1
2
X03
1
2
0
V
D
C
X04
+ - + - + -
1
2
X05
L
E
D
1
+-
L
E
D
2
+
8
V
D
C
0
V
D
C
230V 115V
24Vac/1 isolated
24Vac/2
earthed
EE
L
N
N L E
BLUE
BROWN
RED
GREEN
VIOLET
WHITE
ORANGE
BLACK
FH1
FH2
FH3FH4
FH5
1
VOLTAGE SELECT
2 3 4
X04
2 1 2
X03
X02
X01
T3.15A
T1.6A
T1.6A
T1.0A
T1.0A
1 2 3 4
115V +-10%
230V +-10%
1 2 3 4
IEC
5x20mm
SECTION 15  COMMISSIONING FORM
psi cfm Kpa
VA
Hz
kW
COMMISSIONING FORM
Customer Contact Customer Ref:
Phone Internal Ref:
Installation/Site Commission Date Software Ser No. Commission Engineer
Manufacturer Model/Type
Working Pressure psi/bar/Kpa Full Load Capacity cfm
Minimum Load Capacity** cfm Full Load Power Minimum Load Power** kW Voltage V
** variable speed/regulation
Full Load Current (FLC) A Frequency Hz
P01 Pu Unload Pressure Set Point psi/bar/Kpa P01 Pt Load Pressure Set Point psi/bar/Kpa P01 PL Load Pressure psi/bar/Kpa
P03 P> Pressure Units P03 Ad Network Address (Compressor No.) P03 PA Pressure Averaging Factor P03 IC I/O Configuration (Type) P03 Dm Delivery Pressure Maximum Limit psi/bar/Kpa P03 Im Internal Pressure Maximum Limit psi/bar/Kpa
P04 Do Delivery Pressure ‘Offset’ psi/bar/Kpa P04 Dr Delivery Pressure ‘Range’ psi/bar/Kpa P04 Io Internal Pressure ‘Offset’ psi/bar/Kpa P04 Ir Internal Pressure ‘Range’ psi/bar/Kpa
P08 FL Frequency at Minimum Speed Hz P08 FH Frequency at Maximum Speed Hz
P10 D7 Auxiliary Alarm Input Configuration P10 D8 Auxiliary Trip Input Configuration P10 SQ ‘i-PCB’ Sequence Control Hold P10 Ao Analogue Output Function (4-20mA)
bar psi kpa
1 2 3
NO NC NO NC 0 1 0 9 10
28
Ingersoll Rand
Instruktionsmanual
System Automatisering
VSD boks
Inden enheden installeret eller opstartes første gang, bør denne manual gennemgås nøje med henblik på at forstå hvordan enheden fungerer og/eller hvilke opgaver, der skal udføres under drift og vedligeholdelse af enheden. OPBEVAR DENNE MANUAL SAMMEN MED ENHEDEN. Denne tekniske manual indeholder VIGTIGE SIKKERHEDS­DATA og bør altid opbevares sammen med enheden.
Mere end luft. Svar.
Onlinesvar: http://www.air.irco.com
C.C.N. : 80444128 REV. : B DATO : JULY 2008
AFSNIT 1  INDHOLDSFORTEGNELSE
Afsnit 1 - inDHOLDsfORtEGnELsE ........................3
Afsnit 2 - intRODuktiOn .........................................3
Afsnit 3 - sikkERHED .................................................3
MONTERING .................................................................................3
DRIFT ..............................................................................................3
VEDLIGEHOLDELSE OG REPARATION ................................3
Afsnit 4 - kOMPREssORtiLsLutninG OG
kOntROL .........................................................................4
KOMPRESSORTILSLUTNING OG KONTROL......................4
NORMALE KONTROLFUNKTIONER OG
FUNKTIONALITET .......................................................................4
ANVENDELSE AF VSDBOKSEN ............................................5
Afsnit 5 - MOntERinG ................................................5
ENHEDSPLACERING ..................................................................5
STRØMFORSYNING ...................................................................5
RS485 NETVÆRK .........................................................................5
Afsnit 12 - DELE ........................................................ 24
IR VSD BOX .................................................................................24
Afsnit 13 - tEkniskE DAtA ..................................... 24
VSDBOKS ...................................................................................24
Afsnit 14 - kAbELføRinGsDiAGRAM .................. 25
Afsnit 15 - AnVEnDELsEsfORM ........................... 27
Refer to Section Indicated
Note
Important or Caution, Safety
TRYKSENSORENS TILSLUTNINGER ......................................6
VSD OG IRPCB KOMPRESSORTILSLUTNING ..................7
KONTROL AF IRPCB KOMPRESSOR ...................................7
STATUSOVERVÅGNING AF IRPCB KOMPRESSOREN ...7
KLAR ................................................................................................7
KØRER .............................................................................................8
BELASTET ......................................................................................8
Afsnit 6 - VsD-bOksEns
HARDwAREkOnfiGuRAtiOn .................................. 11
Afsnit 7 -inGERsOLL RAnD tiL VsD-bOks
sAMMEnkObLinG ...................................................... 12
Afsnit 8 - ibRuGtAGninG ....................................... 14
sEktiOn 9 - skæRMbiLLEDE OG MEnu ................ 16
MENUNAVIGATION ...............................................................16
Afsnit 10 - DiAGnOstikkER ................................... 21
Afsnit 11 - DRift ....................................................... 22
TASTATUR ................................................................................... 22
DISPLAY .......................................................................................22
INDIKATORER ............................................................................ 22
BRUGERMENUENS PUNKTER .............................................23
STRØMSVIGT AUTOMATISK GENSTART .........................23
3
!
!
AFSNIT 2  INTRODUKTION
VSD-boksen er beregnet til at give en metode til systemintegration hos en VSD-kompressor (Variable Speed Drive), som ikke er udstyret med nogen tilgængelige former for erntilslutning
(såsom Ingersoll Rand Nirvana). VSD-boksen giver den nødvendige funktionalitet som behøves til systemintegration og effektiv kontrol med automationssystemet X8I .
AFSNIT 3  SIKKERHED
ADVARSEL : Risiko for fare
ADVARSEL : Risiko for elektrisk stød
ADVARSEL : Risiko for højt tryk
ADVARSEL : Se i manualen
Inden du installerer eller anvender VSD-boksen, skal
du tage dig tid til at læse alle instruktionerne i denne manual, alle kompressormanualer og alle manualer der er tilknyttet perifere enheder, som kan installeres i eller sluttes til dette produkt.
Elektricitet og trykluft har potentiale til at forårsage
alvorlig person- eller tingsskade.
Operatøren bør brug sin sunde fornuft samt gode
arbejdsmetoder i tilslutning med anvendels og vedligeholdelse af systemet. Alle relevante koder bør overholdes nøje.
Vedligeholdelsesarbejde skal udføres af kvalificeret
personale, som er udstyret med rette værktøj.
VSD-boksen må kun anvendes med den tiltænkte
forsyningsspænding og -frekvens.
Når strømmen er slået til, er der dødbringende
spænding tilstede i de elektriske kredsløb, hvilket betyder, at der skal udvises ekstrem forsigtighed, når der skal udføres arbejde på enheden.
Åben ikke adgangspanelerne og rør ikke ved de
elektriske komponenter, når der er aktiv spænding, medmindre det er nødvendigt for at kunne foretage målinger, tests eller justeringer. Sådant arbejde bør kun udføres af en kvalificeret elektriker, som er i besiddelse af det korrekte værktøj, og som har den nødvendige beskyttelse mod elektriske faremomenter.
Alle luftkompressorer og/eller andet udstyr, der er
forbundet med enheden, bør være udstyret med et advarselsskilt ved siden af displaypanelet som siger at “DENNE ENHED KAN STARTE UDEN VARSEL”.
Hvis en luftkompressor og/eller andet udstyr som er
sluttet til enheden skal ernstartes, skal der påsættes to skilte på udstyret med følgende besked: ‘DENNE ENHED KAN FJERNSTARTES’. Påsæt et skilt et på en synlig placering, et på ydersiden af udstyret og det andet inde i udstyrets kontrolskab.
MONTERING
Monteringsarbejdet må kun udføres af en kompetent
person under kvalificeret opsyn.
Der skal anbringes en sammensmeltet
isoleringsafbryder mellem hovedstrømforsyningen og VSD-boksen.
VSD-boksen skal monteres på et sted, hvor
der er drifts- og vedligeholdelsesadgang uden forhindringer eller fare, og indikatorerne skal altid forblive synlige.
Hvis der er brug for forhøjede platforme til at give
adgang til VSD-boksen, må de ikke forstyrre den normale drift eller adgang. Platforme og trapper skal være rist- eller pladekonstruerede med sikkerhedsrælinger til alle åbne sider.
DRIFT
VSD-boksen må kun anvendes af kompetent
personale under kvalificeret opsyn.
Fjern eller rod aldrig med de sikkerhedsaggregater,
afskærmninger og isoleringsmaterialer som er monteret på VSD-boksen.
VEDLIGEHOLDELSE OG REPARATION
Vedligeholdelse, reparation og ændringer må kun
udføres af kompetent personale under kvalificeret opsyn.
Hvis der kræves reservedele, må der kun anvendes
originale dele fra den oprindelige fabrikant, eller fra en anden godkendt kilde.
Udfør følgende trin, inden der åbnes eller ernes
adgangspaneler, samt før der udføresarbejde på VSD-boksen:
Isoler VSD-boksen fra
i.
hovedstrømforsyningen. Fastlås isolatoren i OFF-positionen og ern sikringerne.
Påsæt en etiket på isolatorkafbryderen og
ii.
på enheden´med teksten “ARBEJDE PÅGÅR
- TILFØR IKKE SPÆNDING”. Der må ikke sluttes elektrisk strøm eller forsøges at starte VSD­boksen, hvis et sådant advarselsskilt er påsat.
Vær sikker på, at alle instruktioner vedrørende drift
og vedligeholdelse følges nøje samt at enheden, såvel som alt tilbehør og sikkerhedsanordninger, holdes i god tilstand.
3
Loading...
+ 225 hidden pages